Plan Review Details - Permit 07090496
Plan Review Stops For Permit 07090496
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2007-10-30 Cont ID  
Sent By lursu Date 2007-10-30 Time 15:13 Rev Time 0.00
Received By lursu Date 2007-10-30 Time 15:13 Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2007-09-26 Cont ID  
Sent By dpalmer Date 2007-10-15 Time 11:42 Rev Time 0.00
Received By lursu Date 2007-09-26 Time 13:25 Sent To  
Notes
2007-09-26 13:38:37BASED ON THE SITE PLANS THE LIFT STATION IS LOCATED ON
 PCN = 74434320060010000 AND THE OWNER OF THIS PROPERTY
 IS COURTNEY LAKES APARTMENTS LLC ;HOWEVER THE OWNER ON
 THE PERMIT APPLICATIONIS DR PALM BEACH INC. PLEASE
 CLARIFYTHE OWNER OF NEW LIFT STATION AND ALSO CLARIFY
 THE NEW LIFT STATION ENTRANCE IF ISFROM N CONGRESS
 AVE OR COURTNEY LAKES CIR .
  
 NOTE: BASED ON THE INITIAL SITE PLANS SUBMITTED THE
 SITE ADDRESS ASSIGNED TO THE LIFT STATION WAS 311
 COURTNEY LAKES CIR .THE INITAL SITE ADDRESS WILL BE
 CHANGED IF THE ENTRANCE IS FROM
 N CONGRESS AVE .
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 1 Status P Date 2007-09-24 Cont ID  
Sent By lursu Date 2007-09-24 Time 09:37 Rev Time 0.00
Received By lursu Date 2007-09-24 Time 09:37 Sent To  
Notes
2007-09-24 09:39:28NEW SITE ADDRESS HAS BEEN ASSIGNED TO THE NEW LIFT
 STATION AS 311 COURTNEY LAKES CIR .THE CORRECT PARCEL
 CONTROL NUMBER TO USE IS : 74434320060010000 .PLEASE
 FILL OUT THE CORRECT OWNER INFORMATION ON THE PERMIT
 APPLICATION .
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-10-31 Cont ID  
Sent By dpalmer Date 2007-10-31 Time 12:50 Rev Time 0.00
Received By dpalmer Date 2007-10-31 Time 12:30 Sent To PC
Notes
2007-10-31 12:51:48REDLINED 250.20,250.30,250.50 FOR GROUNDING OF
 TRANSFORMER.
  
  
  
 GENERATOR IS NTO INCLUDED IN SCOPE OF WORK. THIS IS
 FUTURE AND WILL BE UNDER SEPARATE PERMIT.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-10-26 Cont ID  
Sent By dpalmer Date 2007-10-26 Time 12:32 Rev Time 0.00
Received By dpalmer Date 2007-10-26 Time 12:32 Sent To AD
Notes
2007-10-26 12:33:52TEMP FAILED, AS ADDRESSING NEEDS TO REVIEW.
 WILL RED-LINE PLANS FOR SD SYSTEM 250.20,250.30,250.50,
 AND 250.66

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-10-15 Cont ID  
Sent By dpalmer Date 2007-10-15 Time 11:42 Rev Time  
Received By dpalmer Date 2007-10-05 Time 11:15 Sent To PC
Notes
2007-10-15 11:42:36**** DENIED 2ND REVIEW****
  
 ** PLANS RECEIVED FROM ADDRESSING 10/11
  
 1) NOTE: PLEASE SEE THE ADDRESSING COMMENTS ARE THE
 SAME AS PREVIOUS REVIEW. ELECTRICAL SIGN OFF CAN NOT BE
 ACHIEVED UNTIL ADDRESSING HAS BEEN CORRECTED AND
 COORDINATED WITH PLANS.
 PLEASE SEE THE PLANS/TITLE BLOCKS DO NOT INDICATE THE
 CORRECT LOCATION, STILL INDICATES HAWTHORNE SUITES.
 FA C61G15-23.002
  
 2) NOTE: PLEASE SEE RISER IS STILL INDICATING AN
 *EQUIPMENT GROUNDING CONDUCTOR* BEFORE THE FIRST MEANS
 OF DISCONNECT WHICH IS NOT PERMITTED. THIS IS SHOWN
 FROM BOTH THE FPL TRANSFORMER AND FROM METER TO MAIN.
 250.6, 250.24B.
 ** EQUIPMENT GROUNDING CONDUCTORS ARE ONLY INSTALLED
 AFTER THE FIRST MEANS OF DISCONNECT.
  
 3) NOTE: PLEASE SEE THE RISER IS INDICATING NOTE #6 AS
 *FUTURE*, YET THERE ARE SEVERAL LOCATIONS WHICH THIS #6
 WOULD NEED TO BE INSTALLED AT THIS TIME.
 PLEASE SEE FOR EXAMPLE THE #6 FROM MAIN, TO ATS, ATS TO
 PANEL ETC.
  
 4) NOTE: PLEASE VERIFY GROUNDING ELECTRODE FOR
 SEPARATELY DERIVED SYSTEM PER 250.50, 250.20, AND
 250.30.
 COULD NOT LOCATE THIS SYSTEM.
  
 5) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE ATS WHICH IS BEING INSTALLED AT THIS
 TIME.
 THE GENERATOR IS THE ITEM THAT WILL BE FUTURE.
 90.7, 110.3
 FBC 106.1.2
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW, IF
 THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-10-05 11:19:49SENT TO ADDRESSING. NEEDS ADDRESSING BEFORE
 ELECTRICAL.
 PERMIT APPLICATION NOT CORRECTED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-09-27 Cont ID  
Sent By dpalmer Date 2007-09-27 Time 14:00 Rev Time 0.00
Received By dpalmer Date 2007-09-27 Time 13:59 Sent To PC
Notes
2007-09-27 14:04:29** DENIED**
  
 1) NOTE: PLEASE VERIFY OWNER, PROPOERTY INFORMATION AS
 PERMIT WAS APPLIED FOR UNDER 301 LAMBERTON WHICH IS A
 SEPARATE PCN.
 PLEASE VERIFY LOCATION OF LEFT STATION AND WHETHER OR
 NOT THIS IS ON PRIVATE PROPERTY ?
 PLEASE SEE ANY COMMENTS FROM ADDRESSING.
  
 2) NOTE: PLEASE SEE THIS IS BEING APPLIED AS AN
 ELECTRICLA PERMIT ALTHOUGH PLANS ARE FOR A GENERATOR
 ALSO.
 IF A GENERATOR IS BEING PROPOSED, A PERMIT APPLICATION
 FOR THIS UNIT WHICH WOULD INCLUDE ALL ITEMS GIVEN TO
 THE WEITZ COMPANY AT MEETING DATED 9/27 WOULD BE NEEDED
 FOR SUBMISSION.
  
 ** PLEASE DETERMINE SCOPE AND APPLY ACCORDINLY.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-01-14 Cont ID  
Sent By adarroug Date 2008-01-14 Time 10:02 Rev Time 0.00
Received By adarroug Date 2008-01-14 Time 10:02 Sent To E
Notes
2008-01-14 10:02:48TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-10-24 Cont ID  
Sent By adarroug Date 2007-10-24 Time 10:50 Rev Time 0.00
Received By adarroug Date 2007-10-24 Time 10:50 Sent To E
Notes
2007-10-24 10:51:07TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-03 Cont ID  
Sent By adarroug Date 2007-10-03 Time 17:57 Rev Time 0.00
Received By adarroug Date 2007-10-03 Time 17:57 Sent To E
Notes
2007-10-03 17:57:47TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-09-27 Time   Rev Time 0.00
Received By adarroug Date 2007-09-17 Time 16:14 Sent To  
Notes
2007-09-17 16:14:38TO "E" BOX