| 2007-10-05 12:06:37 | |
| | *** DENIED 2ND REVIEW *** |
| | |
| | ** PLEASE SEE THAT THE PREVIOUS REVIEW NOTES REQUESTED |
| | TO GO OVER ELECTRICAL PLANS FOR COORDINATION BEFORE |
| | RESUBMITTING AS THERE WERE SEVERAL ITEMS WHICH NEEDED |
| | TO MEET 2005 NEC> |
| | AT THAT TIME A FULL REVIEW WAS NOT DONE AND IT WAS |
| | STATED AS SUCH. |
| | PLEASE SEE COMMENTS BELOW. |
| | |
| | |
| | 1) NOTE:PLEASE SEE THE CONDUIT ON THE RISER FOR THE |
| | SERVICE ENTRANCE CONDUCTORS IS BEING SHOWN AS A 4INCH |
| | CONDUIT. HOW IS THIS POSSIBLE WHEN THE METER-CAN WILL |
| | NOT BE LARGE ENOUGH TO ACCOMMODATE THIS SIZE CONDUIT? |
| | PLEASE ALSO SEE THE RISER UP TO METER-CAN ALSO |
| | INDICATES CONDUIT AS SCHEDULE 40, THIS WOULD BE |
| | REQUIRED TO BE SCHEDULE 80 AS THIS IS A LOCATION |
| | SUBJECT TOPHYSICAL DAMAGE. 352.10F |
| | PLEASE ADJUST. |
| | FBC 106.1.2 FOR COORDINATION. |
| | |
| | 2) NOTE: PLEASE INDICATE AMPERAGE OF METER-CAN. |
| | FBC 106.3.5.1.2 |
| | |
| | 3) NOTE: PLEASE CLARIFY THE LOAD SHOWN ON PANEL *N* FOR |
| | LIGHT POLES. THE PLANS INDICATE 3-POLES, EACH WITH 250W |
| | FIXTURES. WHERE DOES THE LOAD AS SHOWN COME FROM? |
| | PLEASE SHOW ALL CONTINUOUS LOADS AT 125% INCLUDING |
| | PUMPS AND OTHER LIGHTING WHICH IS EXPECTED TO RUN FOR 3 |
| | OR MORE HOURS AS DEFINED IN ART 100 OF THE NEC. |
| | PLEASE SEE 215.3, 230.42 ETC FOR LOADS. |
| | PLEASE REVISE CALCULATIONS INCLUDING LOADS ON THE |
| | AQUAGENIX PANEL. |
| | |
| | 4) NOTE: PLEASE SEE THE RISER IS SHOWING *EQUIPMENT |
| | GROUNDING CONDUCTOR* BEING INSTALLED ON THE LINE SIDE |
| | OF THE METER FROM FPL TRANSFORMER. PLEASE ALSO SEE THE |
| | RISER ALSO INDICATES THIS SAME EQUIPMENT GROUND FROM |
| | THE METER TO THE MAIN (FIRST MEANS OF DISCONNECT) WHICH |
| | IS NOT PERMITTED. |
| | PLEASE SEE 250.24B, AND 250.6. AS THE GROUNDED/NEUTRAL |
| | CONDUCTOR IS REQUIRED TO BE BONDED AT THIS FIRST MEANS |
| | OF DISCONNECT, IF AN EQUIPMENT GROUNDING CONDUCTOR WAS |
| | INSTALLED AHEAD OF THIS MAIN, THIS WOULD CREATE |
| | OBJECTIONABLE CURRENTS. |
| | PLEASE ADJUST RISER AND NOTES AND REMOVE. |
| | |
| | 5) NOTE: PLEASE KNOW THAT NO ELECTRICAL LIGHTING |
| | FIXTURES/EQUIPMENT OF ANY KIND WILL BE PERMITTED TO BE |
| | IN POOL AREA AND ELECTRICAL WHICH IS BEING FED FROM THE |
| | MAIN HOTEL WHICH IS A SEPARATE ELECTRICAL SERVICE. |
| | POOL AREA ELECTRICAL SHOULD BE SEPARATED. |
| | PLEASE BE SURE TO ADJUST ANY LOCATIONS IN WHICH THIS |
| | MAY THE SITUATION. |
| | THIS IS ONLY BEING NOTED FOR INFORMATION. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS AS STATED ON PREVIOUS |
| | REVIEW |
| | |