Plan Review Details - Permit 07090490
Plan Review Stops For Permit 07090490
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-08-20 Cont ID  
Sent By shill Date 2008-08-20 Time 13:57 Rev Time 0.00
Received By shill Date 2008-08-20 Time 13:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-06-13 Cont ID  
Sent By shill Date 2008-06-13 Time 08:44 Rev Time 0.00
Received By shill Date 2008-06-13 Time 08:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-04-02 Cont ID  
Sent By shill Date 2008-04-02 Time 17:44 Rev Time 0.00
Received By shill Date 2008-04-02 Time 17:44 Sent To  
Notes
2008-04-02 17:47:01****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.SHEET 1216F-SC-001, DESIGN CRITERIA, NOTE THE
 FOLLOWING:
  
 A.THE CORRECT ASCE REFERENCE IS 7-02, FBC CHAPTER 35
 (ASCE7-05 SHOWN ON THE PLAN).
  
 B.FROM THE SURVEY, THIS APPEARS TO BE EXPOSURE C.
 EITHER REVISE THE EXPOSURE CLASSIFICATION AND ANCHORING
 IF REQUIRED OR CLARIFY EXPOSURE B CLASSIFICATION.
 PLEASE NOTE THAT THE DEFINITION FOR EXPOSURE C HAS
 CHANGED EFFECTIVE DECEMBER 8, 2006 FBC1609.4.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-16 Cont ID  
Sent By jwitmer Date 2007-10-16 Time 13:29 Rev Time 0.77
Received By jwitmer Date 2007-10-16 Time 13:28 Sent To  
Notes
2007-10-16 13:32:08BUILDING PLAN REVIEW
 PERMIT: 07090490
 ADD: 7501 N JOG RD
 CONT: DALE ROSSMAN
 TEL: (561)262-9566
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2007 REVISIONS.
  
 2) 2004 FL. BLD CODE 1603.1.4 THE FOLLOWING INFORMATION
 RELATED TO WIND SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-09-30 Cont ID  
Sent By dpalmer Date 2008-09-30 Time 16:39 Rev Time 0.00
Received By dpalmer Date 2008-09-30 Time 16:39 Sent To FUEL
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-07-29 Cont ID  
Sent By dpalmer Date 2008-07-29 Time 13:04 Rev Time 0.00
Received By dpalmer Date 2008-07-29 Time 13:04 Sent To  
Notes
2008-07-29 13:05:28** TEMPORARY DENIEDREVIEW **
  
  
 1) NOTE:PLANS WERE PLACED INTO TWO COMPLETE SETS WITH
 SHEETS ATTACHED AS REQUESTED ON PREVIOUS REVIEW BY THIS
 REVIEWER.
 PLEASE KNOW THE SPEC/CUT SHEETS FOR THE GENERATOR WERE
 NOT IN PACKAGE RESUBMITTED ONLY THE BILLING SHEET.
 PLEASE SUBMIT.
 THIS CAN BE COORDINATED TO BE BROUGHT IN AS SOON AS
 POSSIBLE. CALLED AND SPOKE TO JOHN BELL. WILL CALL
 BACK.
  
 ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 561-805-6717

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-06-13 Cont ID  
Sent By dpalmer Date 2008-06-13 Time 16:16 Rev Time 0.00
Received By dpalmer Date 2008-06-13 Time 16:16 Sent To  
Notes
2008-06-13 16:16:52** DENIED **
  
 1) NOTE: PLEASE SEE COMMENT WITH RESPECT TO GROUND
 FAULT ON ELECTRICAL SERVICE ALONG WITH GROUND FAULT
 SENSING IS STILL A COMMENT. AS STATED ON PREVIOUS
 REVIEWS ALL MANUFACTURES WHITE PAPERS AND DOCUMENTS
 READ BY THIS REVIEWER INDICATE A COORDINATION LOSS
 BETWEEN THE MAIN, ATS AND SYSTEM WHEN A FOUR POLE UNIT
 IS NOT INSTALLED.
 PLEASE PROVIDE DOCUMENTATION FROM THE PROPOSED
 MANUFACTURE ASCO WHICH SHOWS AND STATES THIS IS NO
 LONGER AN ISSUE OR IS NOT AN ISSUE FOR THE GROUND FAULT
 PROTECTION ON PRIMARY AND GROUND FAULT SENSING ON THE
 GENERATOR AND SECONDARY SIDE OF EQUIPMENT.
 110.3, 90.7, 240.13, 230.95, 700.26, 700.7D, 701.17,
 NFPA-110 6.2.15.
 THE RESPONSE LETTER MENTIONS THIS SYSTEM DOES NOT
 AFFECT OTHER EMERGENCY POWER IN THE BUILDING. WHAT ARE
 THE OTHER EMERGENCY POWER SOURCES FOR BACK UP OF
 EMERGENCY AND LEGALLY REQUIRED SYSTEM?
 THE RESPONSE MENTIONS THAT THE NEUTRAL AND GROUND BOND
 TO BE REMOVED AT THE GENERATOR AS WELL AS THIS WAS
 NOTED ON PLANS.
 THIS WAS NOT MY PREVIOUS COMMENT. IF A FOUR POLE
 TRANSFER SWITCH IS REQUIRED TO PROVIDE COORDINATION,
 THEN THE GENERATOR WOULD BE REQUIRED TO BE SEPARATELY
 DERIVED.
  
 2) NOTE: PLEASE BE SURE TO PLACE ALL PLANS INTO AN
 ATTACHED ORDERLY FASHION. NEW SHEETS SHOULD BE SEPARATE
 INTO TWO SETS WITH OLD SHEETS ATTACHED TO EACH OTHER
 SEPARATELY.
  
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-03-05 Cont ID  
Sent By dpalmer Date 2008-03-05 Time 12:54 Rev Time 0.00
Received By dpalmer Date 2008-03-05 Time 12:54 Sent To  
Notes
2008-03-05 12:54:17** DENIED2ND REVIEW **
  
 ** IMPORTANT: AS NOTED ON PREVIOUS REVIEW THERE WERE
 SEVERAL ITEMS NOT SUBMITTED FOR INITIAL REVIEW AND THAT
 THAT MANY OF THESE ITEMS ARE ONLY NOW BEING SUBMITTED
 FOR THE FIRST TIME THERE ARE SEVERAL NEW COMMENTS.
 ** PLEASE ALSO BE AWARE AS THERE ARE STILL SOME ITEMS
 NOT SUBMITTED OR WILL BE CHANGING BASED ON COMMENTS
 BELOW A FULL REVIEW FOR CODE COMPLIANCE MAY NOT BE DONE
 AT THIS TIME.
  
 1) NOTE: PLEASE SEE FBC CHAPTER 27 WHICH STATES ALL
 BACK POWER GENERATOR POWER TO BE DONE PER NFPA-110.
 THIS DOES NOT STATE WITH THE EXCEPTION TO OPTIONAL
 STAND-BY SYSTEMS.
  
 2) NOTE: PLEASE SEE THE RISER NOW SHOWS GROUND FAULT
 PROTECTION ON THE GENERATOR. PLEASE SEE THE PREVIOUS
 REVIEW COMMENT WAS WITH RESPECT TO THE REQUIRED GFP ON
 THE PRIMARY SIDE THE SERVICE. PLEASE SEE 230.95 AND
 240.13 WHICH DOES NOT REQUIRE THIS GFP ON THE SECONDARY
 EMERGENCY SIDE. PLEASE SEE 700 AND 701 DOES REFLECT THE
 DESIRE FOR GROUND FAULT SENSING. PLEASE SEE WHITE
 PAPERS FOR SEVERAL MANUFACTURES WITH RESPECT TO
 COORDINATION OF THE GFP OF SYSTEMS. THIS OFFICE HAS
 FOUND FROM ALL MANUFACTURES REVIEWED TO DATE SPEAK OF
 COORDINATION LOSS WHEN THE USE OF A 4-POLEIS NOT
 INSTALLED.
 ** PLEASE BE AWARE USING THE 4-POLE UNIT WOULD REQUIRE
 A SEPARATELY DERIVED GENERATOR SYSTEM.
  
 A) PLEASE SEE THE PLANS CLEARLY SHOW THE NEW PROPOSED
 ATS LOCATED OUTSIDE YET THE BILLING AND ORDER FORMS
 CLEARLY SHOW THE ATS AS NEMA 1 RATED WHICH IS ONLY FOR
 INDOOR INSTALLATIONS.110.9, 90.7
 PLEASE SEE THAT NO INFORMATION COULD BE LOCATED TO SHOW
 THE ATS IS *SERVICE ENTRANCE RATED*. RATING OF SERVICE
 EQUIPMENT AND WHETHER OR NOT IT CONTAINS A *MANUAL
 MEANS OF DISCONNECT, RATED FOR THE LOAD SERVED*
 (230.76, 230.79).
  
 B) PLEASE SEE THE PLANS INDICATE THE ATS AS 1600AMPS
 AND RISER INDICATES THE ATS AS 2000AMPS, AND YET THE
 BILLING ORDER SHEETS INDICATE 1200AMPS?
 PLEASE COORDINATE.
  
 110.3, 90.7 ETC
 FBC 106.1.2, 106.3.5.1.2
  
 2) NOTE: PLEASE SEE THE CONDUIT DUCT BANK DETAILS WHICH
 DOES NOT INDICATE ALL CONDUITS IN FACT THE DETAIL
 MENTIONS TYPICAL OF THREE YETBASED ON THE RISER THE
 THERE ARE DUCK BANKS WITH 6 AND 4 SETS.
 PLEASE COORDINATE AND CLARIFY THESE.
 FBC 106.1.2 FOR COORDINATION.
  
 3) NOTE: PLEASE CLARIFY WHAT THE 1/C IS IN EACH OF THE
 CONDUIT/CONDUCTORS NOTES.
 FBC 106.1.2 ADDITIONAL INFORMATION.
  
 4) NOTE: PLEASE SUBMIT LOAD CALCULATIONS AND INTENDED
 LOADS FOR THE SERVICE. PLEASE SEE 702.5 AS THE
 EQUIPMENT NEEDS TO BE RATED FOR THE LOADS TO BE SERVED.
 AS THE SERVICE IS 2000AMPS AND THE BREAKER ON THE
 GENERATOR IS ONLY 1000AMPS.
 PLEASE SUBMIT LOADS.
 220.87
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-10-14 Cont ID  
Sent By dpalmer Date 2007-10-14 Time 13:49 Rev Time 0.00
Received By dpalmer Date 2007-10-14 Time 12:59 Sent To  
Notes
2007-10-14 13:49:27** DENIED**
  
 1) NOTE: PLEASE SUBMIT TWO SETS OF PLANS. PLEASE DO NOT
 SUBMIT INDIVIDUAL LOOSE SHEETS NOT IN SETS FOR REVIEW.
 ONE SET WAS MADE FOR REVIEW OF PLANS BY THIS REVIEWER.
 PLEASE BE SURE TO DO THIS UPON THE NEXT RE-SUBMITTAL OF
 PLANS.
 FBC ADMIN SECTION 106.1
  
 2) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-110 ( FBC CHAPTER 27 REFERENCED.
  
 3) NOTE: PLEASE SEE COLOR CODING IS REQUIRED TO BE
 BROWN, PURPLE AND YELLOW.
 THE NEC DOES NOT PROVIDE COLOR CODING AND *ORANGE* IS
 BASED ON A HIGH-LEG SYSTEM WHICH THIS IS NOT. THE
 CURRENT COLOR CODING IN THIS JURISDICTION FOR THE PAST
 20+ YEARS IS THAT AS BR/PURP/YELL.
 90.4
  
 4) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR BOTH THE GENERATOR AND ATS BEING PROPOSED.
 PLEASE SEE COMMENTS BELOW AS THERE ARE SEVERAL ITEMS TO
 BE REVIEWED FOR CODE COMPLIANCE WHICH CAN NOT BE DONE
 AT THIS TIME.
 PLEASE BE SURE THE SPECS/CUT SHEETS FOR ANY FUEL TANK
 FOR PRIME-MOVER ARE SUBMITTED ALSO. THIS WILL BE
 REVIEWED BY OTHER TRADES SUCH AS MECHANICAL, FIRE
 MARSHAL ETC.
 NEC 90.7, 110.3 ETC
  
 5) NOTE: PLEASE SEE 240.13 AND 230.95 AS GF PROTECTION
 COULD NOT BE LOCATED.
 PLEASE ALSO SEE SPECIFICATIONS FROM MANUFACTURES AS
 THIS MAY REQUIRE THIS TO BE A 4-POLE DEVICE WHICH THE
 GENERATOR WOULD THEN BECOME AND SEPARATELY DERIVED
 SYSTEM.
 PLEASE SUBMIT.
  
 6) NOTE: PLEASE SEE MISSING DISCONNECT FOR FEEDERS FROM
 THE GENERATOR TO MEET 225.31-225.39.
 PLEASE KNOW AS ZONING WILL REQUIRE AN ENCLOSURE AROUND
 THE UNIT AND THE GENERATOR BREAKER MAY NOT BE USED TO
 MEET 702.11AS THIS WILL BE ENCLOSED, ETC, PLEASE
 PROVIDE DISCONNECT.
 PLEASE SEE COMMENT ABOVE WITH RESPECT TO THE TYPE OF
 ATS. THIS NEED ONLY BE A DISCONNECTING MEANS AND DOES
 NOT REQUIRE OVER CURRENT PROTECTION.
  
 7) NOTE: PLEASE SEE NOTE ON SHEET EE-001WHICH MENTIONS
 OWNER MAY CHOOSE LOADS MANUALLY PER 702.5, HOWEVER THE
 SYSTEM AS SUBMITTED IS AN AUTOMATED SYSTEM.
 PLEASE CLARIFY.
  
 THE LIFE SAFETY CODE ALONG WITH STATUTES ETC REQUIRED
 EMERGENCY AND LEGALLY REQUIRED SYSTEMS. IT IS WITH
 RESPECT TO SECTION 702 FOR OPTIONAL STAND-BY SYSTEMS,
 THE CODES ETC DO NOT REQUIRE ANY SUCH SPECIFIC LOADS
 AND THE LOADS FOR AN OSS MAY BE CHOSEN BY OWNER. AS THE
 PLANS SHOW A COMPLETE AUTOMATED SYSTEM, THIS UNIT SHALL
 MEET ALL LOADS AS DETERMINED BY LOAD CALCULATIONS OR
 BUILDING READINGS AS STATED. NO MANUAL SYSTEM WAS SHOWN
 ON PLANS.
 PLEASE PROVIDE MORE DETAILS ON LOADS WHICH WERE
 GENERATED BY READINGS.
  
 8) NOTE: PLEASE CLARIFY THE 60AMP CIRCUIT WHICH IS
 SHOWN ON RISER BEING FED FROM A *OWNER APPROVED
 PANEL*???
 THIS FEED ON THE SHEET E4-002 APPEARS THIS IS COMING
 FROM ANOTHER SERVICE/LOCATION.
 AS SYSTEM TO SINGLE UNIT EQUIPMENT MAY NOT BE MIXED
 FROM DIFFERENT SERVICES, UNTIL CLARIFICATION IS MADE NO
 REVIEW FOR THIS ITEM CAN BE CONFIRMED.
 PLEASE ALSO INDICATE WHAT THIS CIRCUIT IS FOR?
 PLEASE PROVIDE LOADS, ETC.
 FBC 106.1.2
  
 ** PLEASE KNOW AS NOT ALL INFORMATION WAS SUBMITTED FOR
 REVIEW AND DUE TO COMMENTS ABOVE, THERE MAY VERY WELL
 BE NEW COMMENTS ON THE FOLLOWING REVIEW.
 NOTES CAN ONLY BE GIVEN BASED ON PLANS/DOCUMENTS
 SUBMITTED.
  
  
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-08-14 Cont ID  
Sent By mawillia Date 2008-08-14 Time 14:58 Rev Time 0.00
Received By mawillia Date 2008-08-14 Time 14:49 Sent To  
Notes
2008-08-14 14:48:29*****APPROVED*****
  
 PLAN SHEET 1216F-E4-002 (PREVIOUSLY APPROVED ON
 6/16/08) WAS STAMPED, INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-06-16 Cont ID  
Sent By mawillia Date 2008-06-16 Time 14:31 Rev Time 0.00
Received By mawillia Date 2008-06-16 Time 13:20 Sent To  
Notes
2008-06-16 14:01:55*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED;PLAN SHEET 1216F-E4-002 STAMPED,
 INITIALED, AND DATED.
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-04-04 Cont ID  
Sent By mawillia Date 2008-04-04 Time 12:14 Rev Time 0.00
Received By mawillia Date 2008-04-04 Time 09:54 Sent To  
Notes
2008-04-04 12:14:23*****DENIED*****
  
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE ADDRESSED:
  
 1. OK
  
 2.OK
  
 3.WHAT SIZE AND WHAT LISTINGS ARE PRESENT FOR THE
 DIESEL TANK?
  
 4.PLEASE INDICATE WHAT EQUIPMENT THE NEW GENERATOR
 WILL SUPPLY.IS ANY EMERGENCY EQUIPMENTBEING
 SUPPLIED POWER FROM THIS EQUIPMENT.
  
 5.OK
  
 6.NO INFORMATION PROVIDED REGARDING ANY WARNING
 LABELS OR SIGNAGE RELATING TO THE DIESEL TANK
 INSTALLATION.
  
 7.NO INFORMATION PROVIDED WITH REGARDS TO THE VENTING
 OF THE DIESEL TANK.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-10-22 Cont ID  
Sent By mcarsill Date 2007-10-22 Time 10:21 Rev Time 0.00
Received By mcarsill Date 2007-10-22 Time 10:03 Sent To  
Notes
2007-10-22 10:21:251. THE ENTIRE INSTALLATION TO COMPLY WITH NFPA 70, THE
 NATIONAL ELECTRICAL CODE.
  
 2. NO CUT SHEETS OR PRODUCT APPROVALS PROVIDED WITH
 PERMIT APPLICATION.
  
 3. SEVERAL PLANS DECLARES THAT A DIESEL TANK IS
 PROPOSED. WHAT SIZE AND WHAT LISTINGS ARE PRESENT FOR
 THE TANK.
  
 4. PLEASE INDICATE WHAT EQUIPMENT THE NEW GENERATOR
 WILL SUPPLY. IS ANY EMERGENCY EQUIPMENT BEING SUPPLIED
 POWER FROM THIS EQUIPMENT.
  
 5. IS ANY DEVICES PLANNED TO PREVENT THE GENERATOR FROM
 RECEIVING ANY MECHANICAL DAMAGE FROM PASSING VEHICLES.
  
 6. NO INFORMATION PROVIDED REGARDING ANY WARNING LABELS
 OR SIGNAGE RELATING TO THE DIESEL TANK INSTALLATION.
  
 7. NO INFORMATION PROVIDED WITH REGARDS TO THE VENTING
 OF THE DEIESEL TANK.
  
 8. MORE DETAILS NEEDED TO PROVIDE A COMPLETE FIRE PLAN
 REVIEW.
  
 MIKE CARSILLO, BATTALION CHIEF
 804-4709 PHONE
 804-4774 FAX

Review Stop FUEL DIESEL GENERATOR
Rev No 2 Status P Date 2008-10-18 Cont ID  
Sent By rregueir Date 2008-10-18 Time 11:04 Rev Time 0.00
Received By rregueir Date 2008-10-18 Time 11:04 Sent To PC
Notes
***NONE***

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status F Date 2007-11-05 Cont ID  
Sent By rregueir Date 2007-11-05 Time 13:22 Rev Time 0.00
Received By rregueir Date 2007-11-05 Time 13:22 Sent To  
Notes
2007-11-05 13:22:54REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC
 CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 NO INFORMATION WAS PROVIDED FOR THE PROPOSED GENERATOR
 OR MEANS OF FUEL STORAGE. PROVIDE MANUFACTURER'S SPECS
 AND CUT SHEETS FOR THE GENERATOR AND THE FUEL TANK.
 THIS APPLICATION CAN NOT BE REVIEWED AT THIS TIME.
  
 NOTE: UNDERGROUND FUEL TANKS >110 GALLONS AND ABOVE
 GROUND FUEL TANKS >550 GALLONS REQUIRE PRIOR APPROVAL
 BY PALM BEACH COUNTY DEPARTMENT OF ENVIRONMENTAL
 RESOURCE MANAGEMENT. FOR ADDITIONAL INFORMATION PLEASE
 CONTACT PBC DERM AT 561-233-2400 OR VISIT THEM AT:
 HTTP://WWW.CO.PALM-BEACH.FL.US/ERM/INDEX.ASP
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-09-26 Cont ID  
Sent By adarroug Date 2008-09-26 Time 10:46 Rev Time 0.00
Received By adarroug Date 2008-09-26 Time 10:46 Sent To E
Notes
2008-09-26 10:47:15TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-07-18 Cont ID  
Sent By adarroug Date 2008-07-18 Time 11:19 Rev Time 0.00
Received By adarroug Date 2008-07-18 Time 11:19 Sent To  
Notes
2008-07-18 11:24:04TO "COMM" BD#46

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-05-20 Cont ID  
Sent By adarroug Date 2008-05-20 Time 14:57 Rev Time 0.00
Received By adarroug Date 2008-05-20 Time 14:57 Sent To  
Notes
2008-05-22 13:25:07TO "COMM" BD#63
2008-05-20 14:57:56WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-02-29 Cont ID  
Sent By adarroug Date 2008-02-29 Time 08:26 Rev Time 0.00
Received By adarroug Date 2008-02-29 Time 08:26 Sent To  
Notes
2008-02-29 08:29:49TO "COMM" BD#42

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-02-29 Cont ID  
Sent By adarroug Date 2007-11-05 Time 08:25 Rev Time 0.00
Received By adarroug Date 2007-09-17 Time 14:56 Sent To  
Notes
2007-10-09 15:20:08TO "COMM" BD#27
2007-09-17 14:56:14WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2008-10-18 Cont ID  
Sent By rregueir Date 2008-10-18 Time 11:04 Rev Time 0.00
Received By rregueir Date 2008-10-18 Time 11:04 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-08-11 Cont ID  
Sent By rregueir Date 2008-08-11 Time 09:40 Rev Time 0.00
Received By rregueir Date 2008-08-11 Time 09:36 Sent To  
Notes
2008-08-11 09:40:00SAME AS PREVIOUS REVIEW. PLANS WILL BE STAMPED AND FUEL
 STOP WILL BE PASSED ONCE PLANS ARE STAMPED BY
 ELECTRICAL REVIEWER.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-06-16 Cont ID  
Sent By rregueir Date 2008-06-16 Time 11:04 Rev Time 0.00
Received By rregueir Date 2008-06-16 Time 11:03 Sent To  
Notes
2008-06-16 11:04:29SAME AS PREVIOUS REVIEW. PLANS WILL BE STAMPED FOR CODE
 COMPLIANCE ONCE ELECTRICAL REVIEW IS PASSED SINCE THE
 SAME PAGES ARE AFFECTED FOR BOTH REVIEWS.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-03-17 Cont ID  
Sent By rregueir Date 2008-03-17 Time 16:37 Rev Time 0.00
Received By rregueir Date 2008-03-17 Time 16:37 Sent To  
Notes
2008-03-17 16:42:19REVIEW #: 2ND
 ACTION: FAILED PENDING.
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 MECHANICAL REVIEW PASSED. PLANS WILL NOT BE STAMPED AT
 THIS TIME PENDING SUCCESSFUL ELECTRICAL REVIEW AS
 SEVERAL PAGES ARE LIKELY TO BE REPLACED DURING THIS
 PROCESS. REVIEW WILL REMIAN IN FAIL STATUS UNTIL THAT
 PART OF THE REVIEW PROCESS IS COMPLETE. NEW SHEETS MAY
 REQUIRE AN ADDITIONAL MECHANICAL REVIEW.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-11-05 Cont ID  
Sent By rregueir Date 2007-11-05 Time 13:22 Rev Time 0.00
Received By rregueir Date 2007-11-05 Time 13:15 Sent To  
Notes
2007-11-05 13:22:03REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC
 CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 NO INFORMATION WAS PROVIDED FOR THE PROPOSED GENERATOR
 OR MEANS OF FUEL STORAGE. PROVIDE MANUFACTURER'S SPECS
 AND CUT SHEETS FOR THE GENERATOR AND THE FUEL TANK.
 THIS APPLICATION CAN NOT BE REVIEWED AT THIS TIME.
  
 NOTE: UNDERGROUND FUEL TANKS >110 GALLONS AND ABOVE
 GROUND FUEL TANKS >550 GALLONS REQUIRE PRIOR APPROVAL
 BY PALM BEACH COUNTY DEPARTMENT OF ENVIRONMENTAL
 RESOURCE MANAGEMENT. FOR ADDITIONAL INFORMATION PLEASE
 CONTACT PBC DERM AT 561-233-2400 OR VISIT THEM AT:
 HTTP://WWW.CO.PALM-BEACH.FL.US/ERM/INDEX.ASP
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date 2008-07-28 Cont ID  
Sent By eschneid Date 2008-07-28 Time 16:06 Rev Time 0.00
Received By eschneid Date 2008-07-28 Time 16:05 Sent To  
Notes
2008-07-28 16:07:21PASSED W/PROVISO
  
 LANDSCAPE SHALL BE INSTALLED PER THE ATTACHED DIAGRAM.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.

Review Stop Z ZONING
Rev No 3 Status P Date 2008-06-02 Cont ID  
Sent By eschneid Date 2008-06-02 Time 15:12 Rev Time 0.00
Received By eschneid Date 2008-06-02 Time 15:12 Sent To  
Notes
2008-06-02 15:13:04PASSED W/PROVISO
  
 NEW LANDSCAPE SHALL BE INSTALLED PER THE DIAGRAM
 ATTACHED TOTHE PLANS.

Review Stop Z ZONING
Rev No 2 Status P Date 2008-03-03 Cont ID  
Sent By eschneid Date 2008-03-03 Time 16:34 Rev Time 0.00
Received By eschneid Date 2008-03-03 Time 16:34 Sent To  
Notes
2008-03-03 16:35:28PASSED W/PROVISO
  
 REFER TO THE ATTACHED PLANTING DIAGRAM FOR LANDSCAPE
 INSTALLATION.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-10-12 Cont ID  
Sent By eschneid Date 2007-10-12 Time 15:22 Rev Time 0.00
Received By eschneid Date 2007-10-12 Time 15:22 Sent To  
Notes
2007-10-12 15:26:38FAILED
  
 1) PROVIDE PHOTOS OF THE PROPOSED LOCATION.
  
 2) PROVIDE THE HEIGHT OF THE PROPOSED GENERATOR.
  
 3) AN OPAQUE FENCE/WALL AND LANDSCAPE HEDGE SHALL BE
 PROVIDED AROUND THE GENERATOR PAD AS SCREENING.A
 SEPARATE PERMIT WILL BE REQUIRED FOR THE FENCE/WALL.
 LANDSCAPE MAY BE SHOWN WITH THESE PLANS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.