Plan Review Details - Permit 07090452
Plan Review Stops For Permit 07090452
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-04-01 Cont ID  
Sent By shill Date 2008-04-01 Time 10:04 Rev Time  
Received By shill Date 2008-03-31 Time 08:42 Sent To  
Notes
2008-04-01 10:05:42****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1A. WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION AND REMOVE AND REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOU
 PERMIT.THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2ND REVIEW, SEE A3, PRESSURES WERE ADDED BUT NOT
 CLOUDED.IT APPEARS THAT POSSIBLY OTHER CHANGES WERE
 MADE TO THE PLANS BUT NOT CLOUDED AND NUMBERED.PLEASE
 CLEARLY INDICATE ALL CHANGES TO THE PLAN TO EXPEDITE
 THE PLAN REVIEW PROCESS.OTHERWISE A COMPLETELY NEW
 REVIEW IS REQUIRED, RATHER THAN CHECKING ONLY THINGS
 WHICH HAVE CHANGED FROM THE PREVIOUS REVIEW.SEE ITEM
 16 AND SHEET S10.FAILURE TO CLOUD ALL CHANGES
 REQUIRES A COMPLETELY NEW REVIEW FOR EACH PAGE, EVERY
 DETAIL, EVERY NOTE.NOTE THAT A COMPLETE REVIEW WAS
 NOT DONE AS CHANGES WERE NOT CLOUDED.PLEASE CLOUD ALL
 CHANGES ON THE PLAN WHICH WERE DONE AFTER THE FIRST
 SUBMITTAL AND THOSE CHANGES WILL BE REVIEWED IN THE
 NEXT REVIEW.
  
 OLD SHEETS WERE NOT SUBMITTED.THIS IS REQUIRED FOR
 REFERENCE.
  
 1B. ADDRESSED.
  
 1C. FBC*106.1.1, DRAWINGS AND SPECIFICATIONS TO BE
 SPECIFIC AND CANNOT REFER TO CODE SECTIONS IN LIEU OF
 DESIGN CRITERIA.
  
 2.THIS REVIEW IS A PLAN REVIEW, OR MAJOR WORKING
 DRAWING REVIEW.THIS PROJECT WILL REMAIN IN FAILED
 STATUS UNTIL APPLICATION FOR PERMIT BY A CONTRACTOR
 LICENSED TO PERFORM OR SUPERVISE THE WORK.IF THE
 PERMIT IS NOT APPLIED FOR PRIOR TO OCTOBER 1, 2008,
 GOVERNING CODE WILL BE FBC2007 RATHER THAN FBC2004 WITH
 2007 REVISIONS/SUPPLEMENTS AS CURRENTLY DESIGNED.
  
 3-8C. ADDRESSED.
  
 8D. ENGINEER STATES THAT THIS IS AN UNOCCUPIED
 BUILDING.SEE FBC1004.1, ALL BUILDINGS ARE TO COMPLY
 WITH EGRESS REQUIREMENTS BASED ON THE GREATER OF EITHER
 DESIGN LOAD (IN THIS CASE, ZERO FOR UNOCCUPIED) OR THE
 OCCUPANT LOAD BASED ON FBC TABLE 1004.1.DESIGNER
 CANNOT DECLARE AN OCCUPANT LOAD LESS THAN REQUIRED IN
 FBC TABLE 1004.1, SEE FBC1004.1. PLEASE DECLARE
 OCCUPANT LOAD.
  
 PLEASE NOTE FBC1001.1, SCOPE; THE BUILDING IS REQUIRED
 TO HAVE AN OCCUPANT LOAD DECLARED BUT THE STORAGE TANK
 WOULD NOT BE CONSIDERED A BUILDING.
  
 8E-G.ADDRESSED.
  
 8H. SQUARE FOOT AREA FOR THE BUILDING WAS PROVIDED.
 PLEASE ALSO PROVIDE SQUARE FOOT AREA FOOTPRINT OF THE
 TANK.
  
 9-11. PRODUCT APPROVALS, ADDRESSED.
  
 12.ENGINEER'S RESPONSE LETTER STATES THAT PRODUCT
 APPROVALS ARE ATTACHED.SEE THE PREVIOUS LIST
 REGARDING INFORMATION REQUIRED FOR ROOF PERMITS.THIS
 INFORMATION MAY BE PROVIDED AT THE TIME OF ROOF PERMIT
 APPLICATION.ROOF DESIGN PRESSURES ON S2 ARE -40.5,
 -67.9, -102.2.
  
 13-14. I WAS ABLE TO LOCATE THE IMPORTANCE FACTOR OF
 1.15 ON S1 BUT THIS WAS NOT CLOUDED.ALL WIND DESIGN
 CRITERIA (INCLUDING IMPORTANCE FACTOR) IS REQUIRED ON
 THE PLANS, FBC1603.ALL CHANGES SHOULD BE CLEARLY
 INDICATED AND THE OLD SHEETS SHOULD BE SUBMITTED FOR
 REFERENCE.
  
 15. ADDRESSED.
  
 16. ENGINEER'S RESPONSE LETTER STATES THAT THE STAIR
 RISER AND TREAD DIMENSIONS HAVE BEEN ADDED TO SHEET
 S10.I WAS ABLE TO LOCATE THE DIMENSIONS BUT PLEASE
 NOTE THAT THIS CHANGE WAS NOT CLOUDED.SEE OTHER
 COMMENTS REGARDING CHANGES TO THE PLAN.
 17-18. ADDRESSED.
  
 19. ENGINEER?S RESPONSE WAS THAT THE TANK MANUFACTURER
 IS RESPONSIBLE FOR THE DESIGN.THIS PERMIT WILL BE
 ISSUED WITH A PROVISO THAT STRUCTURAL INFORMATION BE
 PROVIDED FOR REVIEW PRIOR TO INSTALLATION.
  
 20. ADDRESSED.
  
 NEW COMMENTS:
  
 21.ROOF PLAN A2, NORTH AND EAST ELEVATIONS A3, SHOW
 HANDRAILS.GUARDS ARE TO COMPLY WITH FBC 1012.5 AND
 1607.PLEASE REVISE PLAN TO INCLUDE DESIGN CRITERIA. A
 NOTE ON S9 STATES THAT THE RAIL WILL COMPLY WITH
 "APPLICABLE CODE REQUIREMENTS".SEE COMMENT 1C, DESIGN
 CRITERIA IS TO BE SPECIFIC AND CANNOT REFER TO "CODE"
 EITHER GENERALLY OR BY CODE NUMBER. NEW DETAIL ADDED TO
 PLAN.
  
 22.S10, THE HANDRAIL HEIGHT IS SHOWN GRAPHICALLY AS
 SHORTER THAN THE GUARDRAIL.42INCH MINIMUM IS REQUIRED
 AS THE HANDRAIL ALSO ACTS AS A GUARDRAIL.PLEASE
 CLARIFY (ADD REQUIRED DIMENSION) OR REVISE. SEE
 FBC1009.NEW DETAIL ADDED TO PLAN.
  
 23. CLARIFY S1 DESIGN DATA, N.3.C., EXPOSURE B
 DECLARED.SEE FBC1609.4.3, THIS APPEARS TO BE EXPOSURE
 C.NOTE THAT THE DEFINITION FOR EXPOSURE C CHANGED
 EFFECTIVE DECEMBER 8, 2006.
  
 24.WHEN RESUBMITTING, PLEASE INCLUDE A RESPONSE
 LETTER INDICATING HOW EACH ITEM WAS ADDRESSED.ALSO
 PLEASE CLOUD AND NUMBER ALL CHANGES AND SUBMIT OLD
 SHEETS FOR REFERENCE (FIRST AND SECOND REVIEWS).IT
 APPEARS THAT THIS WAS NOT DONE AS SEVERAL REVISIONS
 WERE NOT CLOUDED BASED ON ENGINEER?S RESPONSE (STATING
 THAT THESE ITEMS WERE ADDED OR REVISED) AND FIRST
 REVIEW.TO EXPEDITE THE PLAN REVIEW PROCESS, ALL
 CHANGES ARE TO BE CLEARLY INDICATED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-22 Cont ID  
Sent By jwitmer Date 2007-10-22 Time 16:19 Rev Time 4.44
Received By jwitmer Date 2007-10-22 Time 16:19 Sent To  
Notes
2007-10-22 16:52:316800 ROEBUCK RD
 WAST WATER TREATMENT PLANT
 REPUMP STATION & 3MG PRE-STRESSED CONCRETE STORAGE
 TANK
 OCT.22/ 2007
  
  
 BUILDING PLAN REVIEW
 PERMIT: 07090452
 ADD: 6800 ROEBUCK RD
 CONT: GLOBALTECH**PLAN
 REVIEW**
 TEL: (954)818-5205
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 2)THIS REVIEW IS BEING DONE AS A PLAN REVIEW OR MAJOR
 WORKING DRAWING REVIEW, PLANS SUBMITTED FOR PERMIT
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2007 REVISIONS.
  
 3) GLOBALTECH, INC IS MISSING THEIR CERTIFICATE OF
 AUTHORIZATION NUMBER ON THE PLANS.471.023 F.S.
 CERTIFICATE OF AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ENGINEER
 PRACTICING UNDER A FICTITIOUS NAME, A CORPORATION, OR A
 PARTNERSHIP, OFFERING ENGINEERING SERVICES, SHALL
 INCLUDE THE CERTIFICATE OF AUTHORIZATION NUMBER. ADD
 THE NUMBER TO EACH SHEET.THIS MAY
 BE ADDED BY HAND.
  
 4)WORCESTER ENGINEERING, INC. IS MISSING THEIR
 CERTIFICATE OF AUTHORIZATION.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY SHEET BEARING
 THE NAME OF AN ENGINEER
 PRACTICING UNDER A FICTITIOUS NAME, A CORPORATION, OR A
 PARTNERSHIP, OFFERING ENGINEERING SERVICES, SHALL
 INCLUDE THE CERTIFICATE OF AUTHORIZATION NUMBER. ADD
 THE NUMBER TO EACH SHEET.THIS MAY
 BE ADDED BY HAND.
  
 5)HILLERS ELECTRICAL ENGINEERING, INC. IS MISSING
 THEIR CERTIFICATE OF AUTHORIZATION NUMBER. CERTIFICATE
 OF AUTHORIZATION.THE TITLE BLOCK FOR ANY SHEET
 BEARING THE NAME OF AN ENGINEER
 PRACTICING UNDER A FICTITIOUS NAME, A CORPORATION, OR A
 PARTNERSHIP, OFFERING ENGINEERING SERVICES, SHALL
 INCLUDE THE CERTIFICATE OF AUTHORIZATION NUMBER. ADD
 THE NUMBER TO EACH SHEET.THIS MAY
 BE ADDED BY HAND.
  
 6)PROVIDE (3) ORIGINAL SOILS REPORTS THAT WERE
 PREPARED BY DUNKLEBURGER ENGINEERING & TESTING, PROJECT
 NO. 05-21-6014, ORIGINAL SIGNATURE AND SEALED. FBC
 1802.2.1 QUESTIONABLE SOIL.
 WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN
 DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT
 SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION
 BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE
 PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 .
  
 7) ALSO, PLEASE ARRANGE WITH HAROLD PISKURA (INSPECTION
 SERVICES MANAGER - TEL: 561 805 6711), A MEETING
 INVOLVING THE OWNER, SPECIALINSPECTOR, JOB INSPECTOR,
 CONTRACTOR AND ENGINEER.
  
 8 ) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
 A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT
 IS DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 5,
 TABLE 503.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM ISPROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
 H ) SQ. FT. FOOTPRINT
  
 9)PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72.
  
 10) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 11) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR)
 OF PRODUCT TESTING REPORTS ,MISSING REPORTS ARE AS
 FOLLOWS:
 10A) EXTERIOR HOLLOW METAL DOORS, SINGLE AND PAIRS
 10B) WALL LOUVERS
 10C) OVERHEAD METAL COIL DOOR
 10D) ROOFING ASSEMBLIES, FLAT ROOF
  
 12)) THIS ROOF IS MISSING OR NOT IN COMPLIANCE WITH
 THE FOLLOW ITEMS:
 _XX__ CONTRACTOR DID NOT PROVIDE THE MEAN ROOF HEIGHT.
 _XX__ CONTRACTOR FAILED TO INDICATE WHICH SUB-SYSTEM TO
 BE USED.
 _XX__ THE SYSTEM PROVIDED HAS A LOW PRESSURE FOR ZONE
 _2&3__ .
 _XX_ THE SYSTEM PROVIDED STATES LIMITATION# 7, SHOULD
 THE FASTENER RESISTANCE BE LESS THAN THAT EQUIRED, AS
 DETERMINED BY THE BUILDING OFFICIAL, A REVISED FASTENER
 SPACING, PREPARED , SIGNED
 AND SEALED BY A FLORIDA REGISTERED PROFESSIONAL
 ENGINEER, REGISTEREDARCHITECT OR REGISTERED ROOF
 CONSULTANT MAY BE SUBMITTED.
 __XX_CHECK THE SUBMITTAL THE SUB-SYSTEM CHOSEN MAY
 INDICATE LIMITATION# 9, NO ENHANCED FASTENING ALLOWED.
  
 13)PLANS DO NOT PROVIDE THE POSITIVE & NEGATIVE
 PRESSURES FOR DOORS AND WINDOWS NOTE IMPORTANCE FACTOR
 OF 1.15 FOR THE 150 MPH WIND ZONE. ALSO INDICATE END
 ZONES AND INTERIOR ZONES.
 COMPONENTS AND CLADDING 1609.6.1.2.
  
 14) THE PLANS DO NOT PROVIDE THE PRESSURES FOR THE ROOF
 IN ZONES 1,2 OR 3 PLEASE PROVIDE THE POSITIVE AND
 NEGATIVE PRESSURES FOR THE ROOF ZONES. 1609.6.1.2.
  
 15) SHEETS-10 INDICATES A GENERATOR PAD BUT NO
 INFORMATION ON THE ANCHORING OF THE GENERATOR TO THE
 SLAB PLEASE PROVIDETHE QUANTITY OF ANCHORS, SIZE,
 SPACING OF ANCHORS.
 1609.1.3 ANCHORAGE AGAINST OVERTURNING, UPLIFT &
 SLIDING.
  
 16) SHEET S-10 DOES NOT INDICATE THE RIS OR RUN FOR THE
 STAIRS SHOWN ON THIS SHEET, PLEASE PROVIDE COMPLIANCE
 WITH 1009.3.
  
 17) AT THIS TIME THERE IS NO INFORMATION SUPPLIED FOR
 THE GENERATOR, FUEL STORAGE VAULT, PLEASE SUPPLY CUT
 SHEETS ADDITIONAL COMMENTS MAY APPEAR ONCE THESE
 DOCUMENTS HAVE BEEN EXAMINED.
 106.1.2, ADDITIONAL INFORMATION REQUIRED,
  
 18)NOTE: OUTDOOR STORAGE, DISPENSING AND USE. THE
 OUTDOOR STORAGE, DISPENSING AND USE OF HAZARDOUS
 MATERIALS SHALL BE IN ACCORDANCE WITH THE FLORIDA FIRE
 PREVENTION CODE.
  
 19)PLEASE PROVIDE ADDITIONAL INFORMATION FOR THE 3 MG
 PRE-STRESSED CONCRETE STORAGE TANK, THERE ARE NO PLANS
 FOR THIS PORTION OF WORK.106.1.2 ADDITIONAL INFORMATION
 REQUIRED.
 106.3.5 MINIMUM CRITERIA FOR PLAN REVIEW.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-02-16 Cont ID  
Sent By dpalmer Date 2008-02-16 Time 14:09 Rev Time 0.00
Received By dpalmer Date 2008-02-16 Time 14:09 Sent To  
Notes
2008-02-16 14:09:11** DENIED 2ND REVIEW **
  
 1) NOTE: PLEASE SEE AS NOTED ON PREVIOUS REVIEW. AS
 PLANS HAVE ONLY BEEN SUBMITTED FOR PLAN REVIEW ONLY,
 EVEN ONCE ALL ITEMS ON PLANS ARE OK, REVIEW WILL STILL
 REMAIN IN FAILED STATUS.
 AS PLAN REVIEW, ALL ITEMS EVEN MINOR IN NATURE ARE TO
 BE COMMENTED ON.
  
 2) NOTE: THE RESPONSE LETTER MENTIONS THE GENERATOR IS
 NOW PORTABLE AND THE MANUFACTURES SPECS/CUT SHEET NOW
 INDICATE THIS HOWEVER THE ELECTRICAL PLANS ONLY SHOWS
 *GENERATOR*. THERE IS NO REFERENCE TO THIS UNIT AS
 PORTABLE.
 THE PREVIOUS PLAN REVIEW COMMENT WITH RESPECT TO
 225-31.225.9 AND WHETHER OR NOT THE EXCEPTION IN 702.11
 COULD BE USED. THE RESPONSE MENTIONS 700.12B6 WHICH IS
 FOR EMERGENCY LIFE SAFETY SYSTEMS. PLEASE CLARIFY THIS
 AS THIS OFFICE IS NOT AWARE OF THIS BEING A LEGALLY
 REQUIRED OR LIFE SAFETY GENERATOR FALLING UNDER
 NFPA-110 LEVEL 1 OR LEVEL 2 SYSTEMS.
 IF THERE IS ANY TYPE REQUIREMENT THEN A PERMANENT UNIT
 WOULD BE REQUIRED AND A PORTABLE UNIT WOULD NOT BE
 PERMITTED.
 IF THIS IS INDEED AN OPTIONAL STAND-BY AS 702.1 SCOPE
 SPEAKS OF THEN ONLY SECTIONS OF 702 APPLY.
 PLEASE KNOW UNDER A PORTABLE UNIT AND THE UNIT MEETS
 BOTH EXCEPTIONS AS STATED ON PREVIOUS REVIEW THEN A
 DISCONNECTING MEANS WOULD NOT BE REQUIRED AT BUILDING.
 THIS REVIEW IS NOT REQUIRING AN ITEM WHICH IS ABOVE THE
 MINIMUM CODE.
  
 3) NOTE: SPECIFICATION SHEETS FOR DIVISION SPECS
 REDLINED FOR COLOR CODING FOR ANY 277/480V SYSTEMS TO
 BE BROWN, PURPLE, YELLOW.
  
 ** ONCE REVIEW NOTE #2 IS CLARIFIED, IT DOES NOT APPEAR
 ANY REVISIONS WILL BE NEEDED TO PLANS. COMMENT #1
 REMAINS UNTIL PERMIT IS APPLIED FOR. NEW BUILDING
 CODES, LICENSING ETC WILL BE VERIFIED ONCE PERMIT HAS
 BEEN APPLIED.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-10-11 Cont ID  
Sent By dpalmer Date 2007-10-11 Time 11:42 Rev Time 0.00
Received By dpalmer Date 2007-10-07 Time 14:19 Sent To  
Notes
2007-10-11 11:42:36** DENIED **
  
 1) NOTE: PLEASE KNOW THAT PLANS HAVE ONLY BEEN
 SUBMITTED FOR *PLAN REVIEW* AND HAVE NOT BEEN SUBMITTED
 UNDER PERMIT APPLICATION. WHEN ALL COMMENTS HAVE BEEN
 ADDRESSED AND PERMIT APPLICATION HAS NOT BEEN MADE,
 PLANS WILL STILL REMAIN IN *FAILED* STATUS.
 THERE ARE SEVERAL ITEMS CONFIRMED ONCE APPLICATION HAS
 BEEN MADE.
 **THIS IS FOR INFORMATIONAL PURPOSES ONLY.
  
 2) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
 2002 NFPA-110
  
 ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED
 FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS
 NOT MADE BY OTHER TRADE(S).
  
 3) NOTE: PLEASE CLARIFY THE MEANS OF DISCONNECT
 REQUIRED FOR FEEDERS FROM GENERATOR ON THE LOAD SIDE OR
 LINE SIDE OF THE ATS TO MEET 225.31-225.39.
 BASED ON THE SYMBOLS SHOWN ON THE DP CAN NOT COORDINATE
 THESE WITH THE SYMBOLS ON E-1 SO CAN NOT CONFIRM THIS.
  
 4) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE GENERATOR, ATS AND FUEL TANK. PLEASE
 KNOW THE FUEL TANK WILL BE REVIEWED BY OTHER TRADES
 110.3, 90.7.
 FBC 106.1.2
  
 5) NOTE: PLEASE CLARIFY THE *FUTURE-LOAD* BEING SHOWN
 ON THE GENERATOR WHICH SHOWS THE LOAD EXCEEDING THE
 RATING OF THE UNIT.
 702.5, 220.
 THIS FUTURE SCOPE OF WORK IS NOT BEING SHOWN HOWEVER
 PLEASE BE AWARE THAT THE RATING OF THE GENERATOR IS
 REQUIRED TO RATED FOR THE LOADS BEING SERVED UNLESS
 LOAD SHEDDING DEVICES/EQUIPMENT IS GOING TO BE
 INSTALLED.
 FBC 10
  
 6) NOTE: PLEASE KNOW THAT THE LOW VOLTAGE AS SHOWN ON
 PLANS WILL BE REQUIRED TO BE UNDER SEPARATE PERMITS.
 THE BASE PLANS MAY BE REFERENCED FOR TURN AROUND
 PERMITS.
 THIS IS FOR INFORMATION ONLY.
  
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
2007-10-07 14:19:402007-1007 14:19:40
  
 IN ELECTRIC FOR REVIEW.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2008-02-28 Cont ID  
Sent By rchokshi Date 2008-02-28 Time 11:33 Rev Time 0.00
Received By rchokshi Date 2008-02-28 Time 11:23 Sent To  
Notes
2008-02-28 11:33:48***FAILED**** PLEASE PROVIDE THE FOLLOWING:
  
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
  
 OUR RESPONSE: WE COULD NOT FIND A COPY OF NOI IN YOUR
 PACKAGE.
  
 2.PLEASE PROVIDE A COPY OF STORM WATER QUALITY
 CALCULATIONS TO 100045TH STREET ENGINEERING FOR THEIR
 REVIEW. THESE WATER QUALITY CALS MUST BE APPROVED FROM
 ENGINEERING BEFORE WE APPROVED.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2007-10-17 Cont ID  
Sent By rchokshi Date 2007-10-17 Time 11:38 Rev Time 0.00
Received By rchokshi Date 2007-10-17 Time 11:32 Sent To  
Notes
2007-10-17 11:38:15***FAILED**** PLEASE PROVIDE THE FOLLOWING:
  
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
 2. PLEASE SHOW ON DRAWING ALL CITY STANDARDS NOTES FOR
 SIDEWALK, DRIVEWAY, APPROACH, PARKINGS, HANDICAP
 PARKINGS, DUMPSTER ENCLOSURE, YOU CAN GET A C D FROM
 1000, 45 STREET FOR ALL THESE CITY STANDARDS NOTES.
 PHONE# 494-1040
 3. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
 4. PLEASE SHOW ON CALCULATION THAT YOU HAVE CONSIDERED
 FLOOD ZONE AREA, & 5,10, 25, 100 YEAR FLOOD CRITERIA TO
 DETERMINE THE FIRST FLOOR ELEVATION, PARKING LOT
 ELEVATION, CROWN OF THE ROAD ELEVATION, SIDEWALK ETC.
 5. PLEASE SHOW ON DRAINAGE DRAWINGTHE SITE AREA,
 GREEN, LAKE,PARKING AREA, IMPERVIOUS,PERVIOUS AREAYOU
 ARE DEVELOPING FOR THIS PROJECT . PLEASEMAKE SURE
 THESE AREAS SHOWN ON DRAINAGE DRAWINGS MUST MATCH WITH
 AND USED IN STORM WATER QUALITY CALCULATIONS.
 6. PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE
 SO, WE CANSEE THE LAYOUT OF STORM WATER PIPES FROM
 ALL OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF THE
 CONTROL STRUCTURESWITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC ON DRAWINGS, CALCULATION FOR
 EXFILTRATION TRENCHES, PLEASE SHOW DRY DETENTION/WET
 DETENTION AREAS IN STORM WATER CALS.
 7. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN.
 8. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, &STORM
 WATER QUALITY CALCULATIONS. STORM WATER CALS MUST BE
 APPROVED FROM 100045TH STREET ENGINEERING SERVICES.
 9.POLLUTION PREVENTION DETAILS:HEIGHT OF FENCE SHOULD
 BE HIGH ENOUGH PER FDEP TO STOP FLYING DUST PARTICLES.
 10. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-03-24 Cont ID  
Sent By mawillia Date 2008-03-24 Time 16:43 Rev Time 0.00
Received By mawillia Date 2008-03-24 Time 16:03 Sent To  
Notes
2008-03-24 16:40:52*****APPROVED*****
  
 ALL THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW
 (WHICH WAS CONDUCTED BY FIRE MARSHAL MIKE CARSILLO)
 HAVE BEEN ADDRESSED AND/OR ACKNOWLEDGED;HOWEVER THE
 APPROPIATE PLAN SHEET(S) TO BE FIRE STAMPED WHEN THE
 OTHER REVIEWERS HAVE BEEN SATISFIED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-10-23 Cont ID  
Sent By mcarsill Date 2007-10-23 Time 10:54 Rev Time 0.00
Received By mcarsill Date 2007-10-23 Time 10:16 Sent To  
Notes
2007-10-23 10:54:431. A KNOX-BOX WILL BE REQUIRED TO ALLOW FOR FIRE AND
 PARAMEDICAL ACCESS THRU THE SWING GATES.
  
 2. SUITABLE ACCESS SHALL BE PROVIDED FOR FIRE AND
 PARAMEDICAL EQUIPMENT TO THE SITE AND APPURTENANT
 EQUIPMENT.
  
 3. PORTABLE FIRE EXTINGUISHERS DISPLAYED ON THE PLANS
 SHALL BE CURRENTLY SERVICE TAGGED BY A LICENSED FIRE
 EQUIPMENT COMPANY.
  
 4. A SIGN SHALL BE AFFIXED TO DIRECT PERSONS TO THE
 APPLICABLE LOCATION AND PROPOSED ADDRESS TO AID IN
 EMERGENCY RESPONSE.
  
 5. PLEASE PROVIDE PRODUCT APPROVALS AND APPROPRIATE
 LISTINGS FOR THE FUEL TANK. TANK WILL MOST LIKELY HAVE
 TO BE REGISTERED WITH PBC DERM BASED ON ITS SIZE.
  
 6. PLEASE PROVIDE ALL PRODUCT LABELS AND WARNINGS SIGNS
 THAT WILL BE PROVIDED FOR THE FUEL TANK.
  
 7. PLEASE PROVIDE ALL DETAILS REGARDING VENTING OF THE
 FUEL TANK.
  
 8. ALL ELECTRICAL INSTALLATIONS TO COMPLY WITH NFPA 70,
 THE NATIONAL ELECTICAL CODE.
  
 9. ALL CHEMICALS SHALL BE STORED, USED, AND HANDLED IN
 ACOCRDANCE WITH NATIONAL, STATE, COUNTY, AND LOCAL
 REQUIREMENTS.
  
 10. PROPOSED FIRE HYDRANT TO MEET UTILITY AND FIRE
 RESCUE STANDARDS.
  
 11. THE ACTIVATION OF ANY DUCT SMOKE DETECTORS SHALL
 CAUSE THE AIR CONDITIONING UNIT TO SHUT DOWN.
  
 12. ALL HANDRAILS AND GUARDRAILS SHALL COMPLY WITH THE
 APPLICABLE CODE REQUIREMENTS REGARDING PRESCRIPTIVE
 STRENGTH REQUIREMENTS.
  
 13. APPROPRIATE WARNING SIGNS AND LABELS SHALL BE
 PROVIDED FOR CHEMICAL STORAGE VESSELS AND EQUIPMENT.
  
 14. HOW WILL EMERGENCIES BE REPORTED AT THE SITE DURING
 OCCUPIED AND UNOCCUPIED TIMES.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 804-4709 PHONE
 804-4774 FAX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-02-15 Cont ID  
Sent By adarroug Date 2008-02-15 Time 14:26 Rev Time 0.00
Received By adarroug Date 2008-02-15 Time 14:26 Sent To  
Notes
2008-02-15 14:33:34TO "COMM" BD#50/PLANS ON RACK--2 ROLLS/1 BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-25 Cont ID  
Sent By kstevens Date 2007-10-25 Time 12:59 Rev Time 0.00
Received By kstevens Date 2007-09-17 Time 09:47 Sent To  
Notes
2007-10-05 17:18:57TO "COMM" BD#43
2007-09-17 09:47:26WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-03-16 Cont ID  
Sent By rregueir Date 2008-03-16 Time 15:19 Rev Time 0.00
Received By rregueir Date 2008-03-16 Time 15:00 Sent To  
Notes
2008-03-16 15:19:41REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 RESPONSE LETTER FROM GLOBALTECH INDICATES THAT TWO
 COPIES FO DERM APPROVED PLANS HAVE BEEN INCLUDED WITH
 THIS SUBMITTAL. THOS PLANS COULD NOT BE LOCATED IN THE
 SUBMITTAL. PLEASE PROVIDE TWO COPIES OF PBC DERM
 APPROVED PLANS PRIOR TO PERMIT ISSUANCE.
  
 ALL OTHER OUTSTANDING REVIEW COMMENTS HAVE BEEN
 ADEQUATELY ADDRESSED. PLANS WILL BE STAMPED UPON
 RECEIPT OF MISSING PLANS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-10-19 Cont ID  
Sent By rregueir Date 2007-10-19 Time 15:38 Rev Time 0.00
Received By rregueir Date 2007-10-19 Time 14:03 Sent To  
Notes
2007-10-19 15:24:32REVIEW #: 1
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC
 CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PG M-5 SHOWS AN ELECTRIC GENERATOR WITH SUB BASE AND
 SECONDARY FUEL STORAGE TANKS. PROVIDE LISTING,
 SUBMITTALS AND INSTALLATION INSTRUCTIONS FOR THE
 GENERATOR AND FUEL TANKS. WHAT TYPE OF FUEL IS TO BE
 USED? NFPA 37-02 AND FBC 106.1.2
  
 2. ABOVE GROUND FUEL STORAGE TANKS GREATER THAN 550
 GALLONS REQUIRE APPROVAL BY THE PALM BEACH COUNTY DEPT.
 OF ENVIRONMENTAL RESOURCE MANAGEMENT IN ACCORDANCE WITH
 F.S. 376.303. PROVIDE TWO SETS OF PLANS WITH PBC DERM
 APPROVAL FOR PROPOSED FUEL STORAGE SYSTEMS. FOR MORE
 INFORMATION PLEASE CONTACT PBC DERM AT
 WWW.CO.PALM-BEACH.FL.US/ERM/CONTACT.ASP OR
 561-233-2400.
  
 3. SHOW GENERATOR TO BE IN COMPLIANCE WITH NFPA 37-02
 IN ACCORDANCE WITH FBC,M 915.1 AND FUEL STORAGE TANKS
 TO BE IN COMPLIANCE WITH NFPA 30-00 IN ACCORDANCE WITH
 NFPA37-02 SEC. 6.3.3. PLANS CAN NOT BE REVIEWED BY
 THESE STANDARDS AT THIS TIME DUE TO INSUFFICIENT DETAIL
 AND INFORMATION. SEE COMMENT #1. ADDITIONAL COMMENTS
 ARE POSSIBLE ONCE ALL REQUIRED INFORMATION IS
 PROVIDED.
  
 4. SHOW SIZE AND TYPE OF MATERIAL OF FUEL PIPING ALONG
 WITH SUBMITTAL AND INSTALLATION INSTRUCTIONS FOR FUEL
 TRANSFER PUMP TO SHOW COMPLIANCE WITH THE ABOVE STATED
 CODES. FBC 106.1.2
  
 5. PG A-5: EXTERIOR WALL LOUVERS ARE SUBJECT TO FAC
 RULE 9B-72 AND AS SUCH ARE REQUIRED TO HAVE PRODUCT
 APPROVAL. PROVIDE PRODUCT APPROVAL DOCUMENTATION FOR
 ALL EXTERIOR WALL LOUVERS. FOR MORE INFORMATION ON THE
 FLORIDA PRODUCT APPROVAL SYSTEM PLEASE VISIT:
 WWW.FLORIDABUILDING.ORG
  
 6. PG A-2: EF-1 ON ROOF APPEARS TO BE WITHIN 10 FEET OF
 THE ROOF EDGE. GUARDS SHALL BE PROVIDED WHERE
 APPLIANCES, EQUIPMENT, FANS OR OTHER COMPONENTS THAT
 REQUIRE SERVICE ARE LOCATED WITHIN 10 FEET OF A ROOF
 EDGE AND SUCH EDGE OR OPEN SIDE IS LOCATED MORE THAN 30
 INCHESABOVE THE FLOOR OR GRADE BELOW. THE GUARD SHALL
 EXTEND NOT LESS THAN 30 INCHES BEYOND EACH END OF SUCH
 APPLIANCE, EQUIPMENT, FAN OR COMPONENT AND THE TOP OF
 THE GUARD SHALL BE LOCATED NOT LESS THAN 42 INCHES
 ABOVE THE ELEVATED SURFACE ADJACENT TO THE GUARD. THE
 GUARD SHALL BE CONSTRUCTED SO AS TO PREVENT THE PASSAGE
 OF A 21-INCH-DIAMETER SPHERE AND SHALL COMPLY WITH THE
 LOADING REQUIREMENTS FOR GUARDS SPECIFIED IN THE
 FLORIDA BUILDING CODE, BUILDING.FBC,M 304.10.
  
 7. ON PG A-2 EF-1 IS SHOWN OVER THE CHLORINE ROOM, BUT
 ON PG BS-2 EF-1 IS SHOWN IN THE TOILET ROOM. PLEASE
 COORDINATE EQUIPMENT SCHEDULES AND PLANS, UNIQUELY
 IDENTIFYING EACH PIECE OF EQUIPMENT. FBC,M 304.11
  
 8. PG M-10: ROOF EXHAUST FAN DETAIL #121, THERE IS NO
 DETAIL OR SUBMITTAL DATA SHOWING ROOFTOP EXHAUST FANS
 AND SUPPORTS DESIGNED TO MEET WIND LOAD REQUIREMENTS.
 PROVIDE DETAILS AND DATA SHOWING FANS, CURBS AND ALL
 RELATED ATTACHMENTS ARE DESIGNED FOR THIS WIND ZONE
 (140 MPH) IN ACCORDANCE WITH FBC,M 301.13 AND FBC
 CH.16. NOTE: THIS FACILITY WILL BE CONSIDERED TO HAVE A
 WIND IMPORTANCE FACTOROF 1.15 IN ACCORDANCE WITH FBC
 TABLE 1604.5.
  
 9. PG BS-1: HVAC UNIT DETAIL SHOWS AHU-1 BEING FED BY
 CHILLED WATER PIPES, BUT THE EQUIPMENT SCHEDULE AND
 FLOOR PLAN ON BS-2 SHOW A SPLIT SYSTEM WITH REFRIGERANT
 LINES. WHICH IS CORRECT? EQUIPMENT SHALL BE ACCURATELT
 IDENTIFIED ON PLANS IN ACCORDANCE WITH FBC
 106.3.5.1.4.
  
 10. PG BS-1 SHOWS REFRIGERANT LINES ABOVE GROUND AND
 BS-2 SHOWS REFRIGERANT LINES UNDERGROUND. IF
 REFRIGERANT LINES ARE UNDER ANY PORTION OF THE SLAB,
 THEY SHALL BE ENCASED IN A SLEEVE OR PIPE DUCT IN
 ACCORDANCE WITH FBC,M 1107.2.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-03-17 Cont ID  
Sent By kstevens Date 2008-03-17 Time 08:28 Rev Time 0.00
Received By kstevens Date 2008-03-15 Time 15:34 Sent To  
Notes
2008-03-17 08:43:13DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
  
 2. THE CERTIFICATE OF AUTHORIZTION NUMBER IS REQUIRED
 ON ALL SHEETS WITH THE WORCESTER ENGINEERING INC. TITLE
 BLOCK ON IT. FAC 61G15-23.002(2) & FS 471.025.
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
  
 3. OK
  
 4. SUBMIT A DETAIL/ELEVATION SHOWING COMPLIANCE WITH
 THE FOLLOWING:
 ___FOR THE W/C:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED
 B. 11-4.16.3 HEIGHT
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
 C. 11-4.16.4 GRAB BARS
 D. OK
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
 E. OK
 ___FOR THE LAV:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
 B. 11-4.19.3 CLEAR FLOOR SPACE
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
 C. 11-4.19.4 EXPOSED PIPES & SURFACES
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
 D. 11-4.19.5 FAUCETS
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
 E. OK
 ___FOR THE TOILET ROOM:
 A. OK
 ___FOR THE DRINKING FOUNTAIN:
 A. 11-4.15.2 SPOUT HEIGHT
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
 B. 11-4.15.3 CLEARANCES & CLEAR FLOOR SPACE & SECTION
 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING, (IF NOT A HIGH/LOW
 D/F).
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
  
 5. OK
 6. OK
 7. OK
 8. OK
 9. OK
 10. OK
  
 **********NEW COMMENT**********
  
 1B. SHT BS-3 FLOOR PLAN AND SANITARY RISER DIAGRAM. THE
 SERVICE SINK AND DRINKING FOUNTAIN SHALL DISCHARGE
 DOWNSTREAM OF THE HORIZONTAL WET-VENT FOR THE BATHROOM
 FIXTURES. SECTION 909.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 ****RESPONSE NOTED, BUT VOIDED SHEETS NOT RESUBMITTED
 SEPARATELY FOR COMPARISON.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-10-25 Cont ID  
Sent By kstevens Date 2007-10-25 Time 12:01 Rev Time 0.00
Received By kstevens Date 2007-10-24 Time 12:01 Sent To  
Notes
2007-10-25 12:57:23DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. PLEASE INDICATE THE OCCUPANCY GROUP & THE SQUARE
 FOOTAGE OF THE BUILDING. SECTIONS 106.1.2, 106.3.5.1(2)
 & 302.1.
  
 2. THE CERTIFICATE OF AUTHORIZTION NUMBER IS REQUIRED
 ON ALL SHEETS WITH THE WORCESTER ENGINEERING INC. TITLE
 BLOCK ON IT. FAC 61G15-23.002(2) & FS 471.025.
  
 3. PER TABLE 403.1 A DRINKING FOUNTAIN AND A SERVICE
 SINK ARE REQUIRED. PLEASE INDICATE THE LOCATION OF EACH
 ON THE FLOOR PLAN.
  
 4. SUBMIT A DETAIL/ELEVATION SHOWING COMPLIANCE WITH
 THE FOLLOWING:
 ___FOR THE W/C:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.3 HEIGHT
 C. 11-4.16.4 GRAB BARS
 D. 11-4.16.5 FLUSH CONTROLS
 E. 11-4.16.6 DISPENSERS
 ___FOR THE LAV:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 B. 11-4.19.3 CLEAR FLOOR SPACE
 C. 11-4.19.4 EXPOSED PIPES & SURFACES
 D. 11-4.19.5 FAUCETS
 E. 11-4.19 6 MIRRORS
 ___FOR THE TOILET ROOM:
 A. 11-4.22.3 TURNING CIRCLE
 ___FOR THE DRINKING FOUNTAIN:
 A. 11-4.15.2 SPOUT HEIGHT
 B. 11-4.15.3 CLEARANCES & CLEAR FLOOR SPACE & SECTION
 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING, (IF NOT A HIGH/LOW
 D/F).
  
 5. SHTS A-2 & A-3. SUBMIT CALCULATIONS FOR THE ROOF
 DRAINAGE PER SECTION 1106 & TABLES 1106.3 & 1106.6.
 INDICATE THE SQUARE FOOTAGE OF THE ROOF AND INDICATE
 1/2 AREA OF ALL VERTICAL WALLS INCLUDING PARAPETS. SHOW
 THE SIZE OF THE GUTTERS AND SHOW THE SIZE OF THE
 DOWNSPOUTS. INDICATE THE SLOPE OF THE GUTTER AND SHOW
 THE HIGH POINTS OF THE GUTTER PER TABLE 1106.6.
  
 6. SHT A-5. PER SECTION 1210.2 THE WALLS WITHIN 2FT OF
 THE WATER CLOSET SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT SURFACE. PLEASE INDICATE HOW PAINT WILL BE
 A NONABSORBENT SURFACE.
  
 7. SHTS M-3 & M-10 SHOWS 3 FLOOR DRAINS, A HOSE REEL,
 AN EXTERIOR HOSE VALVE AND AN EMERGENCY SHOWER/EYE WASH
 NOT INDICATED ON SHT BS-3. PLEASE CORRELATE PLUMBING
 INFORMATION AND SHOW ON THE PLUMBING SHEET. SECTION
 106.1.1.--NO VENTING IS SHOWN FOR THE FLOOR DRAINS
 AS REQUIRED IN SECTION 901.2.1.--THE RISER DIAGRAMS
 SHALL REFLECT ALL PIPING FOR THE SANITARY AND WATER. --
 PLEASE SHOW THE HOSE REEL, THE EXTERIOR HOSE VALVE AND
 EMERGENCY SHOWER/EYE WASH ON THE FLOOR PLANS. SECTION
 106.1.1
  
 8. SHT M-3SHOWS PVC PIPE FOR THE DISTRIBUTION WATER
 TO THE TOILET ROOM.DISTRIBUTION PIPING SHALL COMPLY
 WITH TABLE 605.4. ALSO SEE PLUMBING NOTE #10 ON SHT
 BS-3. PLEASE CORRELATE PIPING INFORMATION.
  
 9. SHTS BS-1, BS-2 & BS-3 THE ADDRESS FOR KAM
 CONSULTING DOES NOT REFLECT THE ADDRESS OF RECORD ON
 THE STATE OF FLORIDA DBPR WEBSITE. (SEE ATTACHED
 SHEET). PLEASE UPDATE THE TITLE BLOCKS OR THE DBPR
 WEBSITE PRIOR TO RESUBMITTING FOR REVIEW. FAC
 61G15-23.002(2) & FS 471.025.
  
 10. SHT BS-3 WATER RISER DIAGRAM. THE WATER HAMMERS
 SHALL BE LOCATED NEAR THE FIXTURES IN AN "EFFECTIVE
 RANGE" NOT IN THE CEILING AS SHOWN. PDI-WH 201, MANUF.
 INSTALLATION INSTRUCTIONS & SEE PLUMBING NOTE 13 THIS
 SHEET.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2008-03-04 Cont ID  
Sent By bpowell Date 2008-03-04 Time 08:14 Rev Time 0.00
Received By bpowell Date 2008-03-04 Time 08:14 Sent To  
Notes
2008-03-04 08:22:211. PLEASE PROVIDE AN UP TO DATE SURVEY OF THE PROPERTY
 SHOWING THE CURRENT CONDITIONS.
  
 2. PER SECTION 94-205 OF THE ZLDRS THE MAXIMUM BUILDING
 HEIGHT IS 35 FEET.PLEASE PROVIDE AN ELEVATION OF THE
 3MG STORAGE TANK.IF THE TANK IS PROPOSED TO BE TALLER
 THAN 35 FEET A VARIANCE WILL BE REQUIRED.
  
 3. THE ADA ACCESSIBLE SPACE SHALL MEET THE STANDARDS
 SET FORTH BY THE ADA. THE BACK OF THE WHEEL STOP
 SHALL BE A MINIMUM OF TWO (2) FEET FROM THE THE BACK OF
 THE PARKING SPACE.THE DISABLED LOGO SHALL BE TWO (2)
 FROM THE BOTTOM OF THE PARKING SPACE, THE LOGO SHALL BE
 PAINTED WHITE AND EITHER THREE (3) OR FIVE (5) FEET.
  
 FOR QUESTIONS OR COMMENTS PLEASE CONTACT BOBBY POWELL
 JR., PLANNER, (561) 822-1401, [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2007-10-19 Cont ID  
Sent By bpowell Date 2007-10-19 Time 16:12 Rev Time 0.00
Received By bpowell Date 2007-10-19 Time 16:11 Sent To  
Notes
2007-10-19 16:18:421.PLEASE PROVIDE AN UP TO DATE SURVEY OF THE PROPERTY
 SHOWING CURRENT CONDITIONS.
  
 2.ALL PARKING SPACES SHALL BE DOUBLE STRIPPED, PER
 SECTION 94-485 IN THE STALL PAINTING DETAIL. THE
 CURRENT DETAIL DOES NOT SHOW PARKING BEING DOUBLE
 STRIPPED.
  
 3.PER SECTION 94-205 OF THE ZLDRS THE MAXIMUM
 BUILDING HEIGHT IS 35 FEET. PLEASE PROVIDE AN ELEVATION
 OF THE 3MG STORAGE TANK, IF IT IS PROPOSED TO BE TALLER
 THAN 35FT A VARIANCE WILL BE REQUIRED.
 4.WHEN SHOWING PARCEL LINES PLEASE ONLY SHOW THE
 LINES THAT ACTUALLY EXIST.THE LINE SHOWN EAST OF THE
 PUMP ROOM AND THE LINE LEFT OF THE STORAGE TANK SHOULD
 BE REMOVED FROM THE PLANS.
  
 FOR QUESTIONS OR COMMENTS PLEASE CONTACT; BOBBY POWELL
 JR., PLANNER, [email protected], (561) 822-1435


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved