| Plan Review Stops For Permit 07090435 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2007-12-11 |
|
|
Cont ID |
|
| Sent By |
amorse |
Date |
2007-12-11 |
Time |
16:46 |
Rev Time |
0.00 |
| Received By |
amorse |
Date |
2007-12-11 |
Time |
16:46 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-11-10 |
|
|
Cont ID |
|
| Sent By |
amorse |
Date |
2007-11-10 |
Time |
09:38 |
Rev Time |
0.00 |
| Received By |
amorse |
Date |
2007-11-10 |
Time |
09:38 |
Sent To |
PC |
|
| Notes |
| 2007-11-10 09:50:45 | | | | | | | DENIED | | | | | | THE FOLLOWING COMMENTS WERE NOT ADDRESSED ON 1ST | | | REVIEW | | | | | | 2)IN AN EXISTING BUILDING WHERE ALTERATIONS ARE BEING | | | MADE A DESIGN PROFESSIONAL MUST ELECT THE LEVEL OF | | | ALTERATION PER 301.5 OF EXISTING BUILDING CODE AND | | | STATE ALONG WITH THE TYPE OF CONSTRUCTION ON THE | | | DRAWINGS | | | *******ALTERATION LEVEL SHALL BE PRESENT ON THE | | | DRAWINGS******* | | | | | | 6)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA | | | STATE PRODUCT APPROVAL COVER | | | SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON | | | WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT | | | SUBMITTED APPLICATIONS WILL BE DENIED | | | *******NOTE THAT SHINGLES AND LINTELS DO NOT HAVE THE | | | STATE PRODUCT APPROVAL SHEETS ATTACHED****** | | | | | | 7)NO PRODUCT APPROVALS WERE SUBMITTED FORCONNECTORS | | | AND STRAPS.INSTEAD THEY MAY ALL BE LISTED IN THE | | | SCHEDULE COMPLETE WITH FLORIDA PRODUCT APPROVAL | | | NUMBERS | | | *******SCHEDULE DOES NOT CONTAIN FLORIDA PRODUCT | | | APPROVAL NUMBERS******* | | | | | | NEW REVIEW COMMENTS | | | | | | 1)NEW DRAWINGS REQUIRE HISTORIC STAMP TO BE ADDED | | | | | | 2)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SETS OF PLANS MUST BE STAMPED BY THAT OFFICE, | | | AND A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561) 233-5025 FOR MORE | | | INFORMATION. THIS STAMP IS TO BE PRESENT EVEN IF FEES | | | ARE NOT REQUIRED, PLEASE MAKE ALL CORRECTIONS PRIOR TO | | | COUNTY IMPACT FEE APPROVAL | | | | | | 3)PLEASE NOTE THAT WHEN PULLING UP THE FLORIDA STATE | | | PRODUCT APPROVALS THAT THERE IS A LINK TO THE CORRECT | | | NOA TO BE USED WITH THAT APPROVAL. THE MIAMI-DADE NOA'S | | | FOR THE SHINGLES, FIXED WINDOWS AND DOORS ARE OLD AND | | | HAVE BEEN REVISED. SEE PAGE 2 OF THE STATE COVER SHEET, | | | FIND THE PRODUCT THAT YOU WILL BE USING AND CLICK ON | | | THE LINK TO BRING UP THE NOA THAT WAS USED TO CERTIFY | | | THE STATE APPROVAL | | | | | | 4)PROVIDE THE RIDGE BEAM CONNECTOR THAT WILL AT | | | DOUBLE GIRDER AND RAKE BEAM ALSO THE SADDLES FOR THE | | | RAFTER ATTACHMENT TO THE RIDGE BEAM, SEE SHEETS #2 AND | | | #5 | | | | | | 5)REVISION FOR RAFTER ATTACHMENT SHOULD BE TWIST | | | STRAP MTSM 16 THE H 10-2 WAS FOR GIRDER ONLY ? | | | | | | 6)PLEASE NOTE THAT THE C25 CASEMENT WINDOWS WILL NOT | | | MEET THE -47PSF PRESSURE UNLESS THE GLAZING USED IS | | | TYPE B OR E. PLEASE SPECIFY TYPE OF GLAZING ON WINDOW | | | SCHEDULE. ***NOTE MIN GLAZING TYPE A WORKS ON ALL OTHER | | | CASEMENTS*** | | | | | | 7)PLEASE NOTE THAT PER 713.13(2) F.S. IF THE | | | IMPROVEMENT DESCRIBED IN THE NOC HAS NOT COMMENCED | | | WITHIN 90 DAYS OF RECORDING, THE NOTICE IS VOID AND | | | WILL NEED TO BE RERECORDED | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-10-08 |
|
|
Cont ID |
|
| Sent By |
amorse |
Date |
2007-10-08 |
Time |
14:34 |
Rev Time |
0.00 |
| Received By |
amorse |
Date |
2007-10-08 |
Time |
14:34 |
Sent To |
|
|
| Notes |
| 2007-10-08 15:51:04 | | | | | | | DENIED | | | | | | 1)PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL | | | COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006 | | | AMENDMENTS PER 106.1.1 FBC* | | | | | | 2)IN AN EXISTING BUILDING WHERE ALTERATIONS ARE BEING | | | MADE A DESIGN PROFESSIONAL MUST ELECT THE LEVEL OF | | | ALTERATION PER 301.5 OF EXISTING BUILDING CODE AND | | | STATE ALONG WITH THE TYPE OF CONSTRUCTION ON THE | | | DRAWINGS | | | | | | 3)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON | | | SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER | | | ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE | | | ADDED TO THE PERMIT APPLICATION FEES | | | | | | NOTE: FEES ARE DUE IN THE AMOUNT OF $ FOR STATE | | | RADON FEES THIS AMOUNT IS REQUIRED TO BE PAID PRIOR TO | | | FURTHER PLAN REVIEW | | | | | | 4)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF | | | EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. THESE | | | SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER PAGES. | | | ALL CAN BE FOUND ON WWW.FLORIDABUILDING.ORG | | | | | | 5)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE | | | 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND | | | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO | | | SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC* | | | | | | 6)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA | | | STATE PRODUCT APPROVAL COVER | | | SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON | | | WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT | | | SUBMITTED APPLICATIONS WILL BE DENIED | | | *****PLEASE SEE TOP OF PRODUCT APPROVALS FOR THE | | | CORRECT FLORIDA STATEWIDE APPROVAL NUMBERS**** | | | | | | 7)NO PRODUCT APPROVALS WERE SUBMITTED FOR CASTCRETE | | | LINTELS AND CONNECTORS AND STRAPS OR THEY MUST ALL BE | | | LISTED IN THE SCHEDULE COMPLETE WITH FLORIDA PRODUCT | | | APPROVAL NUMBERS | | | | | | 8)SUBMIT ENERGY CALC'S PER 13-101.2.2 FBC. BE SURE | | | THAT THEY ARE SIGNED AND DATED BY PREPARER AND | | | OWNER/AGENT PRIOR TO SUBMITTAL | | | ***** PLEASE NOTE THAT THE ENERGY CALC'S ARE NOT | | | MATCHING R-VALUES PROVIDED ON THE PERMIT DRAWINGS | | | (RAISED FLOOR IS R19 IN PLANS AND R-11 IN THE ENERGY | | | CALC'S) ALSO CALC'S SHALL BE SIGNED AND DATED BUY | | | OWNER/AGENT***** | | | | | | 9)PROVIDE WINDOW SCHEDULE THAT STATES SIZE (REPLACED | | | EXISTING) AND TYPE OF WINDOW (FIXED,CASEMENT,ETC) AND | | | THEIR LOCATION (MARK) | | | | | | 10)PROVIDE DETAIL OF CONNECTION FOR 2X4 INFILL RAFTER | | | TO 2X10 RAFTER AT NEW PEAK AND TO EXISTING ROOF | | | | | | 11)NOTE S-3 TYPE CONNECTOR (H10) WILL NEED TO BE | | | (H10-2) FOR DOUBLE GIRDER APPLICATION OVER TERRACE | | | AREA | | | | | | 12)NOTE THAT MBHA THAT IS SPECIFIED FOR RIDGE | | | LOCATION AT RIDGE BEAM HAVE A MIN WIDTH OF 3 1/8" | | | | | | 13)SHOW AREA TO BE VAULTED, DOES IT BEGIN AT NEW | | | GIRDER TRUSS? AND WHAT IS THE MAKE UP OF THE GIRDER IS | | | IT ENGINEERED OR A BUILT UP GIRDER? | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B1 |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
N |
Date |
2007-12-11 |
|
|
Cont ID |
|
| Sent By |
amorse |
Date |
|
Time |
16:44 |
Rev Time |
0.00 |
| Received By |
amorse |
Date |
|
Time |
16:44 |
Sent To |
|
|
| Notes |
| 2007-12-11 16:48:05 | | | | | | | B1 STOP ENTERED BY MISTAKE | | | | | | ADRIAN |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2007-12-03 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-12-03 |
Time |
07:22 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-12-03 |
Time |
06:58 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2007-10-25 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-10-25 |
Time |
09:23 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-10-25 |
Time |
07:28 |
Sent To |
M |
|
| Notes |
| 2007-10-25 08:18:20 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} THE CODES REFERENCED IN THE ELECTRICAL NOTES, SHEET | | | #1, ARE NOT CURRENT. CHANGE THE NOTES TO INDICATE THE | | | CODES THIS PROJECT WAS DESIGNED UNDER. 106.1.3 FBC AS | | | AMENDED.* THE CHANGES ON SHEET 4A ARE NOTED BUT SHEET | | | #1, NOTE #7,IS STILL INCORRECT. | | | | | | 2} PLEASE PROVIDE A PANEL SCHEDULE SO THAT | | | BRANCH/FEEDER CIRCUIT CONDUCTOR AND OVERCURRENT | | | PROTECTION COMPLIANCE MAY BE REVIEWED PER 106.3.5.4 FBC | | | AS AMENDED. SEE 408.4 2005 NEC. * THE JACCUZZI AND | | | WATER HEATER IN THE LOAD CALCULATIONS ARE NOT ON THE | | | LOAD CALCULATIONS. CORRELATE SAME. | | | | | | 3} INDICATE IF THE A/C SYSTEM IS NEW OR EXISTING. IF | | | NEW LOCATE THE AHU ON THE PLAN.* STILL NOT ON THE | | | ELECTRICAL PLAN. | | | | | | 4} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH | | | 210.52(A), 210.52(C), AND 210.8(A)(6) GFI.* NOT ALL ARE | | | INDICATED AS GFI. | | | | | | 5} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. WHEN | | | INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A | | | PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE | | | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL | | | DWELLING UNIT SHALL BE PROVIDED WITH SMOKE ALARMS | | | LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE ALARMS | | | SHALL BE INTERCONNECTED AND HARD WIRED. PLEASE INDICATE | | | SAME ON PLANS. *OK, SO NOTED. | | | | | | 6} THE NOTE ON SHEET #4 "FOR REFERENCE ONLY" SEEMS TO | | | IMPLY THAT THE ENGINEER THAT SIGNED AND SEALED THIS | | | SHEET IS NOT TAKING RESPONSIBILITY FOR THE DESIGN. PER | | | 106.1.3, 106.3.4.3 FBC AS AMENDED, THE PERSON TAKING | | | RESPONSIBILITY MUST COMPLY WITH THE STATUTES. REMOVE | | | THE NOTE OR REMOVE THE SEAL AND SIGNATURE AND HAVE THE | | | PERSON TAKING RESPONSIBILITY COMPLY. *OK, CONTRACTOR | | | MAY PRINT AND SIGN AS DESIGNER PER 471.OO3(H) | | | EXEMPTION. | | | | | | NEW COMMENTS : | | | | | | 7} THE RISER DIAGRAM HAS CHANGED TO A DUPLEX METER WITH | | | ONE 125 AMP MAIN BREAKER PANEL. THIS PANEL NEEDS TO BE | | | LOCATED ON THE FLOOR PLAN SO THAT COMPLIANCE WITH | | | ARTICLE 230.70(A) MAY BE REVIEWED. | | | | | | 8} THE PLAN INDICATES A 200 AMP EXISTING PANEL ON THE | | | EXTERIOR OF THE ADDITION. THIS IS OBVIOUSLY RELOCATED, | | | NOT EXISTING. THE METER AT THIS SAME LOCATION IS NOT | | | SHOWN AS A DUPLEX. CORRELATE THE RISER AND THE DRAWING, | | | INDICATE THE AIC RATING OF ALL SERVICE EQUIPMENT NEW OR | | | RELOCATED. | | | | | | 9} THE HEAT LOAD IN THE ELECTRICAL CALCULATIONS IS | | | LISTED AS 500 VA. SHEET #6 LISTS THAT LOAD AS 9.6KW. | | | CORRELATE SAME. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-09-18 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-09-18 |
Time |
10:50 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-09-18 |
Time |
10:21 |
Sent To |
M |
|
| Notes |
| 2007-09-18 10:50:50 | | | | | | | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} THE CODES REFERENCED IN THE ELECTRICAL NOTES, SHEET | | | #1, ARE NOT CURRENT. CHANGE THE NOTES TO INDICATE THE | | | CODES THIS PROJECT WAS DESIGNED UNDER. 106.1.3 FBC AS | | | AMENDED. | | | | | | 2} PLEASE PROVIDE A PANEL SCHEDULE SO THAT | | | BRANCH/FEEDER CIRCUIT CONDUCTOR AND OVERCURRENT | | | PROTECTION COMPLIANCE MAY BE REVIEWED PER 106.3.5.4 FBC | | | AS AMENDED. SEE 408.4 2005 NEC. | | | | | | 3} INDICATE IF THE A/C SYSTEM IS NEW OR EXISTING. IF | | | NEW LOCATE THE AHU ON THE PLAN. | | | | | | 4} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH | | | 210.52(A), 210.52(C), AND 210.8(A)(6) GFI. | | | | | | 5} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. WHEN | | | INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A | | | PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE | | | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL | | | DWELLING UNIT SHALL BE PROVIDED WITH SMOKE ALARMS | | | LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE ALARMS | | | SHALL BE INTERCONNECTED AND HARD WIRED. PLEASE INDICATE | | | SAME ON PLANS. | | | | | | 6} THE NOTE ON SHEET #4 ?FOR REFERENCE ONLY? SEEMS TO | | | IMPLY THAT THE ENGINEER THAT SIGNED AND SEALED THIS | | | SHEET IS NOT TAKING RESPONSIBILITY FOR THE DESIGN. PER | | | 106.1.3, 106.3.4.3 FBC AS AMENDED, THE PERSON TAKING | | | RESPONSIBILITY MUST COMPLY WITH THE STATUTES. REMOVE | | | THE NOTE OR REMOVE THE SEAL AND SIGNATURE AND HAVE THE | | | PERSON TAKING RESPONSIBILITY COMPLY. | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2007-09-14 |
|
|
Cont ID |
|
| Sent By |
ssherman |
Date |
2007-09-14 |
Time |
11:25 |
Rev Time |
0.00 |
| Received By |
ssherman |
Date |
2007-09-14 |
Time |
11:24 |
Sent To |
|
|
| Notes |
| 2007-09-14 11:25:34 | HISTORICAL APPROVAL PER GALINAJUDGE NO FEE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2008-02-12 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-02-12 |
Time |
16:10 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-02-12 |
Time |
16:10 |
Sent To |
M |
|
| Notes |
| 2008-02-12 16:11:17 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2008-01-30 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-01-30 |
Time |
16:13 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-01-30 |
Time |
16:13 |
Sent To |
P |
|
| Notes |
| 2008-01-30 16:14:09 | TO "P" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-11-27 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-11-27 |
Time |
09:03 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-11-27 |
Time |
09:03 |
Sent To |
Z |
|
| Notes |
| 2007-11-27 09:04:02 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-10-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-10-18 |
Time |
09:29 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-10-18 |
Time |
09:29 |
Sent To |
Z |
|
| Notes |
| 2007-10-18 09:30:14 | TO "Z" BOX/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2007-10-08 |
Time |
|
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-09-14 |
Time |
14:32 |
Sent To |
|
|
| Notes |
| 2007-09-14 14:32:37 | TO "SFR" "Z" |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2008-02-13 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-02-13 |
Time |
10:04 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2008-02-13 |
Time |
10:04 |
Sent To |
|
|
| Notes |
| 2008-02-13 10:04:37 | REVISION TO MECH. PLAN. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2007-10-26 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-10-26 |
Time |
08:52 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2007-10-26 |
Time |
08:52 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2007-09-18 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-09-18 |
Time |
12:12 |
Rev Time |
0.25 |
| Received By |
tgordon |
Date |
2007-09-18 |
Time |
12:12 |
Sent To |
P |
|
| Notes |
| 2007-09-18 12:26:34 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) MECHANICAL PERMIT #07090442 HAS BEEN APPLIED FOR BUT | | | NO MECHANICAL PLANS WERE SUBMITTED FOR REVIEW. PLEASE | | | SUBMIT MECHANICAL PLANS FOR REVIEW, PER 2004 FBC CITY | | | OF WPB AMEND. 106.3.5.4 (10). | | | | | | 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT | | | ALSO, PER 2004 FBC 13-600.3.ABC.2. | | | | | | 3) CLOTHES DRYER VENT MAY NOT TERMINATE NEAR THE A/C | | | CONDENSER UNIT, PER 2004 FBC/M 501.2 . PLEASE CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2008-02-12 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-02-12 |
Time |
12:26 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-02-12 |
Time |
11:03 |
Sent To |
|
|
| Notes |
| 2008-02-12 12:26:53 | REVISION OK--SANT. RISER DIAGRAM ADDED W/M BRANCH | | | LINE, STACK & VENT |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2007-11-10 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-11-10 |
Time |
05:09 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-11-10 |
Time |
05:09 |
Sent To |
B1 |
|
| Notes |
| 2007-11-10 05:10:05 | PASSED PROVISO:--SANITARY PIPE SIZE PER TABLE | | | 709.1. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2007-09-19 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-09-19 |
Time |
12:05 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-09-19 |
Time |
12:04 |
Sent To |
B1 |
|
| Notes |
| 2007-09-19 12:05:48 | PASSED PROVISO:--SANITARY PIPE SIZE PER TABLE | | | 709.1. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2007-11-29 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-11-29 |
Time |
09:29 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-11-29 |
Time |
09:29 |
Sent To |
E |
|
| Notes |
| 2007-11-29 09:35:19 | ***APPROVED - RESUB #2*** | | | | | | | | | | | | SENT TO "E" - BT |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2007-10-22 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-10-22 |
Time |
15:44 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-10-22 |
Time |
15:44 |
Sent To |
E |
|
| Notes |
| 2007-10-22 15:49:25 | ***FAILED - RESUB #1*** | | | | | | | | | REPEATCOMMENT: | | | | | | 1)AS THE VALUE OF THE PROPOSED WORK EXCEEDS 50% OF | | | THE VALUE OF THE HOME: THE LANDSCAPE PLAN SHALL SHOW | | | COMPLIANCE WITH THE CITY OF WEST PALM BEACH ZONING AND | | | LAND DEVELOPMENT REGULATIONS, SECTION 94-442: | | | | | | FOR SINGLE-FAMILY DWELLING UNITS, AT LEAST ONE SHADE, | | | FLOWERING OR FRUIT TREE SHALL BE PLANTED FOR EACH 1,200 | | | SQUARE FEET OF OPEN SPACE OR PORTION THEREOF. FOR | | | SINGLE-FAMILY DWELLING UNITS, AT LEAST ONE SHRUB SHALL | | | BE PLANTED FOR EACH 500 SQUARE FEET OF OPEN SPACE OR | | | PORTION THEREOF.(PALM TREES DO NOT COUNT AS SHADE | | | TREES, REQUIRED TREES SHALL BE A MINIMUM OF 8' IN | | | HEIGHT, ETC...REFER TO CODE. | | | | | | LANDSCAPE PLAN SHALL SHOW COMPLIANCE WITH | | | AFOREMENTIONED CODE SECTION, AND SHOW A DATA TABLE | | | WITH: OPEN SPACE, REQUIRED LANDSCAPING, PROVIDED | | | LANDSCAPING, ETC. | | | | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING | | | TECHNICIAN | | | (561)805-6720 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2007-09-14 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-09-14 |
Time |
17:51 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-09-14 |
Time |
17:51 |
Sent To |
E |
|
| Notes |
| 2007-09-14 18:00:10 | ***FAILED*** | | | | | | | | | 1)INDICATE SEPARATION DISTANCE BETWEEN PROPOSED | | | ADDITION AND THE EXISTING ACCESSORY BUILDING, ALSO | | | PROVIDE SAME DISTANCE FROM OUTERMOST EDGE OF PROPOSED | | | STAIRS TO THE EXISTING ACCESSORY BUILDING. | | | | | | 2)IF MOVING OR ADDING ANY A/C EQUIPMENT, INDICATE | | | SETBACK DIMENSIONS FROM THE EDGE OF EQUIPMENT TO THE | | | PROPERTY LINES. | | | | | | 3)LANDSCAPE PLAN REFERENCES "SEE ENCLOSED PHOTOS", | | | THERE ARE NO PHOTOS PROVIDED.AS THE VALUE OF THE | | | PROPOSED WORK EXCEEDS 50% OF THE VALUE OF THE HOME: THE | | | LANDSCAPE PLAN SHALL SHOW COMPLIANCE WITH THE CITY OF | | | WEST PALM BEACH ZONING AND LAND DEVELOPMENT | | | REGULATIONS, SECTION 94-442: | | | | | | FOR SINGLE-FAMILY DWELLING UNITS, AT LEAST ONE SHADE, | | | FLOWERING OR FRUIT TREE SHALL BE PLANTED FOR EACH 1,200 | | | SQUARE FEET OF OPEN SPACE OR PORTION THEREOF. FOR | | | SINGLE-FAMILY DWELLING UNITS, AT LEAST ONE SHRUB SHALL | | | BE PLANTED FOR EACH 500 SQUARE FEET OF OPEN SPACE OR | | | PORTION THEREOF.(PALM TREES DO NOT COUNT AS SHADE | | | TREES, REQUIRED TREES SHALL BE A MINIMUM OF 8' IN | | | HEIGHT, ETC...REFER TO CODE. | | | | | | 4)INDICATE PROPOSED REAR DECK HEIGHT, AND INDIVIDUAL | | | STAIR HEIGHTS. | | | | | | | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING | | | TECHNICIAN | | | (561)805-6720 |
|
|