Plan Review Details - Permit 07090435
Plan Review Stops For Permit 07090435
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-12-11 Cont ID  
Sent By amorse Date 2007-12-11 Time 16:46 Rev Time 0.00
Received By amorse Date 2007-12-11 Time 16:46 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-11-10 Cont ID  
Sent By amorse Date 2007-11-10 Time 09:38 Rev Time 0.00
Received By amorse Date 2007-11-10 Time 09:38 Sent To PC
Notes
2007-11-10 09:50:45 
  
 DENIED
  
 THE FOLLOWING COMMENTS WERE NOT ADDRESSED ON 1ST
 REVIEW
  
 2)IN AN EXISTING BUILDING WHERE ALTERATIONS ARE BEING
 MADE A DESIGN PROFESSIONAL MUST ELECT THE LEVEL OF
 ALTERATION PER 301.5 OF EXISTING BUILDING CODE AND
 STATE ALONG WITH THE TYPE OF CONSTRUCTION ON THE
 DRAWINGS
 *******ALTERATION LEVEL SHALL BE PRESENT ON THE
 DRAWINGS*******
  
 6)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER
 SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON
 WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT
 SUBMITTED APPLICATIONS WILL BE DENIED
 *******NOTE THAT SHINGLES AND LINTELS DO NOT HAVE THE
 STATE PRODUCT APPROVAL SHEETS ATTACHED******
  
 7)NO PRODUCT APPROVALS WERE SUBMITTED FORCONNECTORS
 AND STRAPS.INSTEAD THEY MAY ALL BE LISTED IN THE
 SCHEDULE COMPLETE WITH FLORIDA PRODUCT APPROVAL
 NUMBERS
 *******SCHEDULE DOES NOT CONTAIN FLORIDA PRODUCT
 APPROVAL NUMBERS*******
  
 NEW REVIEW COMMENTS
  
 1)NEW DRAWINGS REQUIRE HISTORIC STAMP TO BE ADDED
  
 2)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SETS OF PLANS MUST BE STAMPED BY THAT OFFICE,
 AND A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION. THIS STAMP IS TO BE PRESENT EVEN IF FEES
 ARE NOT REQUIRED, PLEASE MAKE ALL CORRECTIONS PRIOR TO
 COUNTY IMPACT FEE APPROVAL
  
 3)PLEASE NOTE THAT WHEN PULLING UP THE FLORIDA STATE
 PRODUCT APPROVALS THAT THERE IS A LINK TO THE CORRECT
 NOA TO BE USED WITH THAT APPROVAL. THE MIAMI-DADE NOA'S
 FOR THE SHINGLES, FIXED WINDOWS AND DOORS ARE OLD AND
 HAVE BEEN REVISED. SEE PAGE 2 OF THE STATE COVER SHEET,
 FIND THE PRODUCT THAT YOU WILL BE USING AND CLICK ON
 THE LINK TO BRING UP THE NOA THAT WAS USED TO CERTIFY
 THE STATE APPROVAL
  
 4)PROVIDE THE RIDGE BEAM CONNECTOR THAT WILL AT
 DOUBLE GIRDER AND RAKE BEAM ALSO THE SADDLES FOR THE
 RAFTER ATTACHMENT TO THE RIDGE BEAM, SEE SHEETS #2 AND
 #5
  
 5)REVISION FOR RAFTER ATTACHMENT SHOULD BE TWIST
 STRAP MTSM 16 THE H 10-2 WAS FOR GIRDER ONLY ?
  
 6)PLEASE NOTE THAT THE C25 CASEMENT WINDOWS WILL NOT
 MEET THE -47PSF PRESSURE UNLESS THE GLAZING USED IS
 TYPE B OR E. PLEASE SPECIFY TYPE OF GLAZING ON WINDOW
 SCHEDULE. ***NOTE MIN GLAZING TYPE A WORKS ON ALL OTHER
 CASEMENTS***
  
 7)PLEASE NOTE THAT PER 713.13(2) F.S. IF THE
 IMPROVEMENT DESCRIBED IN THE NOC HAS NOT COMMENCED
 WITHIN 90 DAYS OF RECORDING, THE NOTICE IS VOID AND
 WILL NEED TO BE RERECORDED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-08 Cont ID  
Sent By amorse Date 2007-10-08 Time 14:34 Rev Time 0.00
Received By amorse Date 2007-10-08 Time 14:34 Sent To  
Notes
2007-10-08 15:51:04 
  
 DENIED
  
 1)PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL
 COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006
 AMENDMENTS PER 106.1.1 FBC*
  
 2)IN AN EXISTING BUILDING WHERE ALTERATIONS ARE BEING
 MADE A DESIGN PROFESSIONAL MUST ELECT THE LEVEL OF
 ALTERATION PER 301.5 OF EXISTING BUILDING CODE AND
 STATE ALONG WITH THE TYPE OF CONSTRUCTION ON THE
 DRAWINGS
  
 3)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON
 SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER
 ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE
 ADDED TO THE PERMIT APPLICATION FEES
  
 NOTE: FEES ARE DUE IN THE AMOUNT OF $ FOR STATE
 RADON FEES THIS AMOUNT IS REQUIRED TO BE PAID PRIOR TO
 FURTHER PLAN REVIEW
  
 4)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF
 EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. THESE
 SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER PAGES.
 ALL CAN BE FOUND ON WWW.FLORIDABUILDING.ORG
  
 5)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 6)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER
 SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON
 WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT
 SUBMITTED APPLICATIONS WILL BE DENIED
 *****PLEASE SEE TOP OF PRODUCT APPROVALS FOR THE
 CORRECT FLORIDA STATEWIDE APPROVAL NUMBERS****
  
 7)NO PRODUCT APPROVALS WERE SUBMITTED FOR CASTCRETE
 LINTELS AND CONNECTORS AND STRAPS OR THEY MUST ALL BE
 LISTED IN THE SCHEDULE COMPLETE WITH FLORIDA PRODUCT
 APPROVAL NUMBERS
  
 8)SUBMIT ENERGY CALC'S PER 13-101.2.2 FBC. BE SURE
 THAT THEY ARE SIGNED AND DATED BY PREPARER AND
 OWNER/AGENT PRIOR TO SUBMITTAL
 ***** PLEASE NOTE THAT THE ENERGY CALC'S ARE NOT
 MATCHING R-VALUES PROVIDED ON THE PERMIT DRAWINGS
 (RAISED FLOOR IS R19 IN PLANS AND R-11 IN THE ENERGY
 CALC'S) ALSO CALC'S SHALL BE SIGNED AND DATED BUY
 OWNER/AGENT*****
  
 9)PROVIDE WINDOW SCHEDULE THAT STATES SIZE (REPLACED
 EXISTING) AND TYPE OF WINDOW (FIXED,CASEMENT,ETC) AND
 THEIR LOCATION (MARK)
  
 10)PROVIDE DETAIL OF CONNECTION FOR 2X4 INFILL RAFTER
 TO 2X10 RAFTER AT NEW PEAK AND TO EXISTING ROOF
  
 11)NOTE S-3 TYPE CONNECTOR (H10) WILL NEED TO BE
 (H10-2) FOR DOUBLE GIRDER APPLICATION OVER TERRACE
 AREA
  
 12)NOTE THAT MBHA THAT IS SPECIFIED FOR RIDGE
 LOCATION AT RIDGE BEAM HAVE A MIN WIDTH OF 3 1/8"
  
 13)SHOW AREA TO BE VAULTED, DOES IT BEGIN AT NEW
 GIRDER TRUSS? AND WHAT IS THE MAKE UP OF THE GIRDER IS
 IT ENGINEERED OR A BUILT UP GIRDER?
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2007-12-11 Cont ID  
Sent By amorse Date   Time 16:44 Rev Time 0.00
Received By amorse Date   Time 16:44 Sent To  
Notes
2007-12-11 16:48:05 
  
 B1 STOP ENTERED BY MISTAKE
  
 ADRIAN

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-12-03 Cont ID  
Sent By btrobaug Date 2007-12-03 Time 07:22 Rev Time 0.00
Received By btrobaug Date 2007-12-03 Time 06:58 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-10-25 Cont ID  
Sent By btrobaug Date 2007-10-25 Time 09:23 Rev Time 0.00
Received By btrobaug Date 2007-10-25 Time 07:28 Sent To M
Notes
2007-10-25 08:18:20 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE CODES REFERENCED IN THE ELECTRICAL NOTES, SHEET
 #1, ARE NOT CURRENT. CHANGE THE NOTES TO INDICATE THE
 CODES THIS PROJECT WAS DESIGNED UNDER. 106.1.3 FBC AS
 AMENDED.* THE CHANGES ON SHEET 4A ARE NOTED BUT SHEET
 #1, NOTE #7,IS STILL INCORRECT.
  
 2} PLEASE PROVIDE A PANEL SCHEDULE SO THAT
 BRANCH/FEEDER CIRCUIT CONDUCTOR AND OVERCURRENT
 PROTECTION COMPLIANCE MAY BE REVIEWED PER 106.3.5.4 FBC
 AS AMENDED. SEE 408.4 2005 NEC. * THE JACCUZZI AND
 WATER HEATER IN THE LOAD CALCULATIONS ARE NOT ON THE
 LOAD CALCULATIONS. CORRELATE SAME.
  
 3} INDICATE IF THE A/C SYSTEM IS NEW OR EXISTING. IF
 NEW LOCATE THE AHU ON THE PLAN.* STILL NOT ON THE
 ELECTRICAL PLAN.
  
 4} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A), 210.52(C), AND 210.8(A)(6) GFI.* NOT ALL ARE
 INDICATED AS GFI.
  
 5} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. WHEN
 INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE PROVIDED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE ALARMS
 SHALL BE INTERCONNECTED AND HARD WIRED. PLEASE INDICATE
 SAME ON PLANS. *OK, SO NOTED.
  
 6} THE NOTE ON SHEET #4 "FOR REFERENCE ONLY" SEEMS TO
 IMPLY THAT THE ENGINEER THAT SIGNED AND SEALED THIS
 SHEET IS NOT TAKING RESPONSIBILITY FOR THE DESIGN. PER
 106.1.3, 106.3.4.3 FBC AS AMENDED, THE PERSON TAKING
 RESPONSIBILITY MUST COMPLY WITH THE STATUTES. REMOVE
 THE NOTE OR REMOVE THE SEAL AND SIGNATURE AND HAVE THE
 PERSON TAKING RESPONSIBILITY COMPLY. *OK, CONTRACTOR
 MAY PRINT AND SIGN AS DESIGNER PER 471.OO3(H)
 EXEMPTION.
  
 NEW COMMENTS :
  
 7} THE RISER DIAGRAM HAS CHANGED TO A DUPLEX METER WITH
 ONE 125 AMP MAIN BREAKER PANEL. THIS PANEL NEEDS TO BE
 LOCATED ON THE FLOOR PLAN SO THAT COMPLIANCE WITH
 ARTICLE 230.70(A) MAY BE REVIEWED.
  
 8} THE PLAN INDICATES A 200 AMP EXISTING PANEL ON THE
 EXTERIOR OF THE ADDITION. THIS IS OBVIOUSLY RELOCATED,
 NOT EXISTING. THE METER AT THIS SAME LOCATION IS NOT
 SHOWN AS A DUPLEX. CORRELATE THE RISER AND THE DRAWING,
 INDICATE THE AIC RATING OF ALL SERVICE EQUIPMENT NEW OR
 RELOCATED.
  
 9} THE HEAT LOAD IN THE ELECTRICAL CALCULATIONS IS
 LISTED AS 500 VA. SHEET #6 LISTS THAT LOAD AS 9.6KW.
 CORRELATE SAME.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-09-18 Cont ID  
Sent By btrobaug Date 2007-09-18 Time 10:50 Rev Time 0.00
Received By btrobaug Date 2007-09-18 Time 10:21 Sent To M
Notes
2007-09-18 10:50:50 
  
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE CODES REFERENCED IN THE ELECTRICAL NOTES, SHEET
 #1, ARE NOT CURRENT. CHANGE THE NOTES TO INDICATE THE
 CODES THIS PROJECT WAS DESIGNED UNDER. 106.1.3 FBC AS
 AMENDED.
  
 2} PLEASE PROVIDE A PANEL SCHEDULE SO THAT
 BRANCH/FEEDER CIRCUIT CONDUCTOR AND OVERCURRENT
 PROTECTION COMPLIANCE MAY BE REVIEWED PER 106.3.5.4 FBC
 AS AMENDED. SEE 408.4 2005 NEC.
  
 3} INDICATE IF THE A/C SYSTEM IS NEW OR EXISTING. IF
 NEW LOCATE THE AHU ON THE PLAN.
  
 4} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A), 210.52(C), AND 210.8(A)(6) GFI.
  
 5} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. WHEN
 INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE PROVIDED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE ALARMS
 SHALL BE INTERCONNECTED AND HARD WIRED. PLEASE INDICATE
 SAME ON PLANS.
  
 6} THE NOTE ON SHEET #4 ?FOR REFERENCE ONLY? SEEMS TO
 IMPLY THAT THE ENGINEER THAT SIGNED AND SEALED THIS
 SHEET IS NOT TAKING RESPONSIBILITY FOR THE DESIGN. PER
 106.1.3, 106.3.4.3 FBC AS AMENDED, THE PERSON TAKING
 RESPONSIBILITY MUST COMPLY WITH THE STATUTES. REMOVE
 THE NOTE OR REMOVE THE SEAL AND SIGNATURE AND HAVE THE
 PERSON TAKING RESPONSIBILITY COMPLY.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2007-09-14 Cont ID  
Sent By ssherman Date 2007-09-14 Time 11:25 Rev Time 0.00
Received By ssherman Date 2007-09-14 Time 11:24 Sent To  
Notes
2007-09-14 11:25:34HISTORICAL APPROVAL PER GALINAJUDGE NO FEE

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-02-12 Cont ID  
Sent By adarroug Date 2008-02-12 Time 16:10 Rev Time 0.00
Received By adarroug Date 2008-02-12 Time 16:10 Sent To M
Notes
2008-02-12 16:11:17TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-01-30 Cont ID  
Sent By adarroug Date 2008-01-30 Time 16:13 Rev Time 0.00
Received By adarroug Date 2008-01-30 Time 16:13 Sent To P
Notes
2008-01-30 16:14:09TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-11-27 Cont ID  
Sent By adarroug Date 2007-11-27 Time 09:03 Rev Time 0.00
Received By adarroug Date 2007-11-27 Time 09:03 Sent To Z
Notes
2007-11-27 09:04:02TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-18 Cont ID  
Sent By adarroug Date 2007-10-18 Time 09:29 Rev Time 0.00
Received By adarroug Date 2007-10-18 Time 09:29 Sent To Z
Notes
2007-10-18 09:30:14TO "Z" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-10-08 Time   Rev Time 0.00
Received By adarroug Date 2007-09-14 Time 14:32 Sent To  
Notes
2007-09-14 14:32:37TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-02-13 Cont ID  
Sent By tgordon Date 2008-02-13 Time 10:04 Rev Time 0.30
Received By tgordon Date 2008-02-13 Time 10:04 Sent To  
Notes
2008-02-13 10:04:37REVISION TO MECH. PLAN.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-10-26 Cont ID  
Sent By tgordon Date 2007-10-26 Time 08:52 Rev Time 0.30
Received By tgordon Date 2007-10-26 Time 08:52 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-09-18 Cont ID  
Sent By tgordon Date 2007-09-18 Time 12:12 Rev Time 0.25
Received By tgordon Date 2007-09-18 Time 12:12 Sent To P
Notes
2007-09-18 12:26:34PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) MECHANICAL PERMIT #07090442 HAS BEEN APPLIED FOR BUT
 NO MECHANICAL PLANS WERE SUBMITTED FOR REVIEW. PLEASE
 SUBMIT MECHANICAL PLANS FOR REVIEW, PER 2004 FBC CITY
 OF WPB AMEND. 106.3.5.4 (10).
  
 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 3) CLOTHES DRYER VENT MAY NOT TERMINATE NEAR THE A/C
 CONDENSER UNIT, PER 2004 FBC/M 501.2 . PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-02-12 Cont ID  
Sent By kstevens Date 2008-02-12 Time 12:26 Rev Time 0.00
Received By kstevens Date 2008-02-12 Time 11:03 Sent To  
Notes
2008-02-12 12:26:53REVISION OK--SANT. RISER DIAGRAM ADDED W/M BRANCH
 LINE, STACK & VENT

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-11-10 Cont ID  
Sent By kstevens Date 2007-11-10 Time 05:09 Rev Time 0.00
Received By kstevens Date 2007-11-10 Time 05:09 Sent To B1
Notes
2007-11-10 05:10:05PASSED PROVISO:--SANITARY PIPE SIZE PER TABLE
 709.1.

Review Stop P PLUMBING
Rev No 1 Status P Date 2007-09-19 Cont ID  
Sent By kstevens Date 2007-09-19 Time 12:05 Rev Time 0.00
Received By kstevens Date 2007-09-19 Time 12:04 Sent To B1
Notes
2007-09-19 12:05:48PASSED PROVISO:--SANITARY PIPE SIZE PER TABLE
 709.1.

Review Stop Z ZONING
Rev No 3 Status P Date 2007-11-29 Cont ID  
Sent By choops Date 2007-11-29 Time 09:29 Rev Time 0.00
Received By choops Date 2007-11-29 Time 09:29 Sent To E
Notes
2007-11-29 09:35:19***APPROVED - RESUB #2***
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 2 Status F Date 2007-10-22 Cont ID  
Sent By choops Date 2007-10-22 Time 15:44 Rev Time 0.00
Received By choops Date 2007-10-22 Time 15:44 Sent To E
Notes
2007-10-22 15:49:25***FAILED - RESUB #1***
  
  
 REPEATCOMMENT:
  
 1)AS THE VALUE OF THE PROPOSED WORK EXCEEDS 50% OF
 THE VALUE OF THE HOME: THE LANDSCAPE PLAN SHALL SHOW
 COMPLIANCE WITH THE CITY OF WEST PALM BEACH ZONING AND
 LAND DEVELOPMENT REGULATIONS, SECTION 94-442:
  
 FOR SINGLE-FAMILY DWELLING UNITS, AT LEAST ONE SHADE,
 FLOWERING OR FRUIT TREE SHALL BE PLANTED FOR EACH 1,200
 SQUARE FEET OF OPEN SPACE OR PORTION THEREOF. FOR
 SINGLE-FAMILY DWELLING UNITS, AT LEAST ONE SHRUB SHALL
 BE PLANTED FOR EACH 500 SQUARE FEET OF OPEN SPACE OR
 PORTION THEREOF.(PALM TREES DO NOT COUNT AS SHADE
 TREES, REQUIRED TREES SHALL BE A MINIMUM OF 8' IN
 HEIGHT, ETC...REFER TO CODE.
  
 LANDSCAPE PLAN SHALL SHOW COMPLIANCE WITH
 AFOREMENTIONED CODE SECTION, AND SHOW A DATA TABLE
 WITH: OPEN SPACE, REQUIRED LANDSCAPING, PROVIDED
 LANDSCAPING, ETC.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2007-09-14 Cont ID  
Sent By choops Date 2007-09-14 Time 17:51 Rev Time 0.00
Received By choops Date 2007-09-14 Time 17:51 Sent To E
Notes
2007-09-14 18:00:10***FAILED***
  
  
 1)INDICATE SEPARATION DISTANCE BETWEEN PROPOSED
 ADDITION AND THE EXISTING ACCESSORY BUILDING, ALSO
 PROVIDE SAME DISTANCE FROM OUTERMOST EDGE OF PROPOSED
 STAIRS TO THE EXISTING ACCESSORY BUILDING.
  
 2)IF MOVING OR ADDING ANY A/C EQUIPMENT, INDICATE
 SETBACK DIMENSIONS FROM THE EDGE OF EQUIPMENT TO THE
 PROPERTY LINES.
  
 3)LANDSCAPE PLAN REFERENCES "SEE ENCLOSED PHOTOS",
 THERE ARE NO PHOTOS PROVIDED.AS THE VALUE OF THE
 PROPOSED WORK EXCEEDS 50% OF THE VALUE OF THE HOME: THE
 LANDSCAPE PLAN SHALL SHOW COMPLIANCE WITH THE CITY OF
 WEST PALM BEACH ZONING AND LAND DEVELOPMENT
 REGULATIONS, SECTION 94-442:
  
 FOR SINGLE-FAMILY DWELLING UNITS, AT LEAST ONE SHADE,
 FLOWERING OR FRUIT TREE SHALL BE PLANTED FOR EACH 1,200
 SQUARE FEET OF OPEN SPACE OR PORTION THEREOF. FOR
 SINGLE-FAMILY DWELLING UNITS, AT LEAST ONE SHRUB SHALL
 BE PLANTED FOR EACH 500 SQUARE FEET OF OPEN SPACE OR
 PORTION THEREOF.(PALM TREES DO NOT COUNT AS SHADE
 TREES, REQUIRED TREES SHALL BE A MINIMUM OF 8' IN
 HEIGHT, ETC...REFER TO CODE.
  
 4)INDICATE PROPOSED REAR DECK HEIGHT, AND INDIVIDUAL
 STAIR HEIGHTS.
  
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved