Plan Review Details - Permit 07090432
Plan Review Stops For Permit 07090432
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2007-10-18 Cont ID  
Sent By mperson Date 2007-10-18 Time 09:30 Rev Time 0.00
Received By mperson Date 2007-10-18 Time 09:30 Sent To PC
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-10-01 Cont ID  
Sent By mperson Date 2007-10-01 Time 13:48 Rev Time 0.00
Received By mperson Date 2007-10-01 Time 13:48 Sent To PC
Notes
2007-10-01 14:05:49DENIED
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: THE SUBMITTED DRAWING IS NOT AN ISOMETRIC AND
 DOES NOT CLEARLY INDICATE ALL CORRESPONDING LENGTHS.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL.
 TUBING FOR EACH PIPE SIZE BEING USED.
 NOTE: PLEASE INDICATE THIS ON THE RESUBMITTED ISOMETRIC
 DRAWING.
  
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER OR TANK), TO THE MOST REMOTE OUTLET IN
 THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: PLEASE INDICATE THIS ON THE RESUBMITTED ISOMETRIC
 DRAWING.
  
 5. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 NOTE: PLEASE INDICATE THE DISTANCE OF THE PROPOSED 250
 GAL UG/LP TANK ON A RESUBMITTED SITE PLAN FROM ALL
 ADJACENT PROPERTY LINES AND BUILDINGS.
  
 6. FBC-2004 CHAPTER 1,SECTION 106.3.4.3:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-03 Cont ID  
Sent By adarroug Date 2007-10-03 Time 12:28 Rev Time 0.00
Received By adarroug Date 2007-10-03 Time 12:28 Sent To G
Notes
2007-10-03 12:29:05TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-01 Cont ID  
Sent By mperson Date 2007-10-01 Time 14:05 Rev Time 0.00
Received By mperson Date 2007-09-17 Time 13:22 Sent To  
Notes
2007-09-17 13:22:39TO "G" BOX