| 2007-10-06 17:36:14 | |
| | *** DENIED*** |
| | |
| | 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS |
| | WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES |
| | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | |
| | ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED |
| | FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS |
| | NOT MADE BY OTHER TRADE(S). |
| | |
| | 2) NOTE: PLEASE SEE THE PROPOSED LOCATIONS OF EQUIPMENT |
| | AND ELECTRICAL CONDUITS IN ANY STAIRWAYS ARE STRICTLY |
| | PROHIBITED. PLEASE SEE FBC CHAPTER 10 AND BUILDING |
| | REVIEW AND FIRE MARSHAL REVIEW NOTES. |
| | THIS IS BEING NOTED AT THIS TIME FOR INFORMATION. |
| | |
| | 3) NOTE: PLEASE KNOW THE ADDITIONAL SERVICE AS SHOWN |
| | AND PROPOSED IS NOT GRANTED AT THIS TIME PER 230.2. |
| | PLEASE SEE THE LOCATION OF ALL DISCONNECTING MEANS FOR |
| | POWER SHALL BE GROUPED. 230.72 |
| | PLEASE CLARIFY WHY THERE ARE TWO 200AMP RECEPTACLE |
| | SOURCES?SEEMS TO SHOW ONE AT ROOF AND ONE AT GROUND |
| | LEVELS? |
| | THERE ARE NO NOTES FOR SIGNAGE ETC. |
| | PLEASE KNOW AT THIS TIME DUE TO THE SERVICE EQUIPMENT |
| | BEING CHANGED ETC, THERE MAY BE NEW NOTES ON THE |
| | FOLLOWING REVIEW. |
| | |
| | 4) NOTE: PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS |
| | FOR WHAT APPEARS TO BE A MANUAL TRANSFER SWITCH/ |
| | *WALKING BEAM* BREAKER. |
| | PLEASE SUBMIT A COMPLETE PACKAGE FOR PROPOSED EQUIPMENT |
| | AND PLEASE BE SURE ALL EQUIPMENT CONTAINS THE REQUIRED |
| | LISTINGS PER A NATIONALLY RECOGNIZED TESTING LABORATORY |
| | (NRTL)> |
| | 110.3, 90.3. |
| | FBC 106.1.2 |
| | |
| | 5) NOTE: PLEASE ADJUST INFORMATION ON TITLE BLOCKS FOR |
| | KCI AS THE ADDRESS INFORMATION AS LISTED WITH THE |
| | DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION IS |
| | NOT THAT AS LISTED ON PLANS. |
| | FAC 61G11-16.004 |
| | PLEASE ALSO SEE THE REQUIRED MISSING COMPLETE |
| | INFORMATION FOR THE ENGINEER OF RECORD AS SHOWN PER |
| | 61G15-23.002. |
| | PLEASE SEE THE INFORMATION FOR THE ENGINEER OF RECORD |
| | IS NOT COMPLETE AT THIS TIME. |
| | |
| | 6) NOTE: PLEASE SEE THE APPLIED VALUE FOR THE COMPLETE |
| | SCOPE OF WORK WHICH IS SHOWN ON PLANS IS LOW. PLEASE |
| | SEE FBC 108.3 AS THE VALUE IS TO INCLUDE ALL LABOR, |
| | MATERIALS, EQUIPMENT, AND DESIGN COST ETC EVEN IF ANY |
| | EQUIPMENT IS OWNER SUPPLIED. |
| | |
| | 7) NOTE: PLEASE SEE THE GROUNDING ELECTRODE SYSTEM AS |
| | SHOWN DOES NOT MEET 250.50. |
| | |
| | 8) NOTE: PLEASE PROVIDE WALL/FLOOR PENETRATION DETAIL |
| | SHEET WITH ALL LISTED DETAILS AS REQUIRED. |
| | THIS WILL ALSO MOST LIKELY BE A COMMENT FROM |
| | FIRE/BUILDING. |
| | PLEASE SEE NEC 300.21. |
| | ANSI, ASTM, NFPA, UL ETC. |
| | |
| | 9) NOTE: PLEASE SEE THAT THE ACTUAL ADDRESS OF THE |
| | SCOPE OF WORK IS PLACED ON TEH TITLE BLOCKS. WP1097 |
| | DOES NOT GIVE THE ACURATE RECORD AS NEEDED PER FAC |
| | 61G1-16.004, 61G15-23.002, FBC 110.1.2, 106.1.2 |
| | |
| | ** AS THERE WILL BE SEVERAL CHANGES, PLEASE BE SURE TO |
| | GO OVER COMMENTS FROM ALL TRADES WHICH MAY AFFECT THE |
| | SCOPE OF WORK ALONG WITH OTHER TRADE REVIEWED SHEETS. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |