Plan Review Details - Permit 07090403
Plan Review Stops For Permit 07090403
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-02-04 Cont ID  
Sent By jwitmer Date 2008-02-04 Time 16:03 Rev Time 2.22
Received By jwitmer Date 2008-02-04 Time 16:03 Sent To  
Notes
2008-02-04 16:57:55 
  
  
  
  
 BUILDING PLAN REVIEW
 PERMIT: 07090403
 ADD: 4920 LORING DRIVE
 CONT: REGENCY COMMUNICATIONS
 TEL: (561)633-5250
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
  
 BUILDING PROVISO:
 BUILDINGS 4 STORIES AND MORE FALL UNDER THE FLORIDA
 STATE STATUTE 553.73 THAT PERTAINS TO THRESHOLD
 BUILDINGS, REQUIRING A THRESHOLD INSPECTION PLAN. THE
 BUILDING DEPARTMENT WILL REQUIRE THIS TRESHOLD
 INSPECTION PLAN BEFORE THE FIRST INSPECTION,2
 ORIGINAL SIGNED AND SEALED DOCUMENTS.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-12-14 Cont ID  
Sent By jwitmer Date 2007-12-14 Time 09:30 Rev Time 1.22
Received By jwitmer Date 2007-12-14 Time 09:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-16 Cont ID  
Sent By jwitmer Date 2007-10-16 Time 16:16 Rev Time 1.33
Received By jwitmer Date 2007-10-16 Time 16:16 Sent To  
Notes
2007-10-16 16:30:02BUILDING PLAN REVIEW
 PERMIT: 07090403
 ADD: 4920 LORING DRIVE
 CONT: REGENCY COMMUNICATIONS
 TEL: (561)633-5250
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2007 REVISIONS.
  
 2) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR)
 OF PRODUCT TESTING REPORTS ,MISSING REPORTS ARE AS
 FOLLOWS:
 A) LOUVERED DOOR
 B) WALL LOUVER
  
 3)PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72.
  
 4) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-01-12 Cont ID  
Sent By dpalmer Date 2008-01-12 Time 16:37 Rev Time 0.00
Received By dpalmer Date 2008-01-12 Time 16:37 Sent To  
Notes
2008-01-12 16:37:22NEEDS BLDG REVIEW, ALL NEW SHEETS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-12-03 Cont ID  
Sent By dpalmer Date 2007-12-03 Time 16:13 Rev Time 0.00
Received By dpalmer Date 2007-12-03 Time 16:13 Sent To  
Notes
2007-12-03 16:13:50 
  
 ** DENIED REVIEW **
  
 ** PLEASE SEE THERE ARE NOTES FROM PREVIOUS REVIEW
 WHICH ARE STILL IN NEED OF ADDRESSING ALONG WITH NEW
 NOTES.
  
  
  
 1) NOTE:PLEASE SEE THE MANUFACTURES SPECS/CUT SHEETS
 HAVE NOT BEEN SUBMITTED FOR EQUIPMENT INCLUDING
 TRANSFER SWITCH(S) AS REQUESTED ON PREVIOUS REVIEW.
 AS EACH SITE IS *SITE SPECIFIC* EACH SET OF PLANS AND
 RECORD DOCUMENTS ARE REQUIRED TO BE SITE SPECIFIC TO
 EACH LOCATION.
 110.3, 90.7
 FBC 106.1.2
  
 2) NOTE: PLEASE SEE FS 365.172. PLEASE PROVIDE
 DOCUMENTATION AS TO WHETHER OR NOT THE BACK UP SYSTEM
 IS PART OF A E-911 SYSTEM.
 PLEASE SEE NFPA-1221 CHAPTER 4 AS THIS WOULD REQUIRE
 BACK UP POWER FOR ANY LEGALLY REQUIRED SYSTEM.
 IF THE BACK UP SYSTEM IS REQUIRED BY LAW PLEASE PROVIDE
 DOCUMENTS AND PLANS ACCORDINGLY.
 PLEASE ALSO SEE TITLE 47 OF THE FEDERAL US CODE.
 THIS IS A NEW NOTE AND CLARIFICATION OF SYSTEM IS
 NEEDED.
  
 3) NOTE: PLEASE PROVIDE THE MAIN HEADQUARTERS ADDRESS
 ON PLANS/TITLE BLOCKS FOR COORDINATION WITH STATE
 SITE.
 IF SHEETS DO NOT NEED TO BE REVISED FOR OTHER COMMENTS
 THEN PLEASE KNOW THIS CAN BE ADDED TO TITLE BLOCKS BY
 HAND.
 FAC 61G15-23.002
  
 4) NOTE: PLEASE SEE VALUE FOR SCOPE OF WORK WAS NOT
 ADJUSTED.
 PLEASE SEE THAT ALL LABOR, ALL MATERIALS, ALL
 EQUIPMENT; DESIGN COST ETC EVEN IF ANY OF THESE ARE
 OWNER SUPPLIED IS TO BE INCLUDED IN PERMIT
 APPLICATION.
 FBC 108.3
  
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-10-06 Cont ID  
Sent By dpalmer Date 2007-10-06 Time 17:35 Rev Time 0.00
Received By dpalmer Date 2007-10-06 Time 17:01 Sent To  
Notes
2007-10-06 17:36:14 
 *** DENIED***
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2003 NFPA-101
  
 ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED
 FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS
 NOT MADE BY OTHER TRADE(S).
  
 2) NOTE: PLEASE SEE THE PROPOSED LOCATIONS OF EQUIPMENT
 AND ELECTRICAL CONDUITS IN ANY STAIRWAYS ARE STRICTLY
 PROHIBITED. PLEASE SEE FBC CHAPTER 10 AND BUILDING
 REVIEW AND FIRE MARSHAL REVIEW NOTES.
 THIS IS BEING NOTED AT THIS TIME FOR INFORMATION.
  
 3) NOTE: PLEASE KNOW THE ADDITIONAL SERVICE AS SHOWN
 AND PROPOSED IS NOT GRANTED AT THIS TIME PER 230.2.
 PLEASE SEE THE LOCATION OF ALL DISCONNECTING MEANS FOR
 POWER SHALL BE GROUPED. 230.72
 PLEASE CLARIFY WHY THERE ARE TWO 200AMP RECEPTACLE
 SOURCES?SEEMS TO SHOW ONE AT ROOF AND ONE AT GROUND
 LEVELS?
 THERE ARE NO NOTES FOR SIGNAGE ETC.
 PLEASE KNOW AT THIS TIME DUE TO THE SERVICE EQUIPMENT
 BEING CHANGED ETC, THERE MAY BE NEW NOTES ON THE
 FOLLOWING REVIEW.
  
 4) NOTE: PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS
 FOR WHAT APPEARS TO BE A MANUAL TRANSFER SWITCH/
 *WALKING BEAM* BREAKER.
 PLEASE SUBMIT A COMPLETE PACKAGE FOR PROPOSED EQUIPMENT
 AND PLEASE BE SURE ALL EQUIPMENT CONTAINS THE REQUIRED
 LISTINGS PER A NATIONALLY RECOGNIZED TESTING LABORATORY
 (NRTL)>
 110.3, 90.3.
 FBC 106.1.2
  
 5) NOTE: PLEASE ADJUST INFORMATION ON TITLE BLOCKS FOR
 KCI AS THE ADDRESS INFORMATION AS LISTED WITH THE
 DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION IS
 NOT THAT AS LISTED ON PLANS.
 FAC 61G11-16.004
 PLEASE ALSO SEE THE REQUIRED MISSING COMPLETE
 INFORMATION FOR THE ENGINEER OF RECORD AS SHOWN PER
 61G15-23.002.
 PLEASE SEE THE INFORMATION FOR THE ENGINEER OF RECORD
 IS NOT COMPLETE AT THIS TIME.
  
 6) NOTE: PLEASE SEE THE APPLIED VALUE FOR THE COMPLETE
 SCOPE OF WORK WHICH IS SHOWN ON PLANS IS LOW. PLEASE
 SEE FBC 108.3 AS THE VALUE IS TO INCLUDE ALL LABOR,
 MATERIALS, EQUIPMENT, AND DESIGN COST ETC EVEN IF ANY
 EQUIPMENT IS OWNER SUPPLIED.
  
 7) NOTE: PLEASE SEE THE GROUNDING ELECTRODE SYSTEM AS
 SHOWN DOES NOT MEET 250.50.
  
 8) NOTE: PLEASE PROVIDE WALL/FLOOR PENETRATION DETAIL
 SHEET WITH ALL LISTED DETAILS AS REQUIRED.
 THIS WILL ALSO MOST LIKELY BE A COMMENT FROM
 FIRE/BUILDING.
 PLEASE SEE NEC 300.21.
 ANSI, ASTM, NFPA, UL ETC.
  
 9) NOTE: PLEASE SEE THAT THE ACTUAL ADDRESS OF THE
 SCOPE OF WORK IS PLACED ON TEH TITLE BLOCKS. WP1097
 DOES NOT GIVE THE ACURATE RECORD AS NEEDED PER FAC
 61G1-16.004, 61G15-23.002, FBC 110.1.2, 106.1.2
  
 ** AS THERE WILL BE SEVERAL CHANGES, PLEASE BE SURE TO
 GO OVER COMMENTS FROM ALL TRADES WHICH MAY AFFECT THE
 SCOPE OF WORK ALONG WITH OTHER TRADE REVIEWED SHEETS.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-02-04 Cont ID  
Sent By mawillia Date 2008-02-04 Time 12:33 Rev Time 0.00
Received By mawillia Date 2008-02-04 Time 12:15 Sent To  
Notes
2008-02-04 12:30:45*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED;PLAN SHEETS A-1 AND E-1 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-12-26 Cont ID  
Sent By mawillia Date 2007-12-26 Time 15:18 Rev Time 0.00
Received By mawillia Date 2007-12-26 Time 14:44 Sent To  
Notes
2007-12-26 15:03:02*****DENIED******
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW STILL
 NEED TO BE ADDRESSED;SEE ATTACHED COPY OF BATTALLION
 CHIEF/FIRE MARSHAL MIKE CARSILLO'S COMMENTS OF
 10/22/07.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-10-22 Cont ID  
Sent By mcarsill Date 2007-10-22 Time 16:16 Rev Time 0.00
Received By mcarsill Date 2007-10-22 Time 15:56 Sent To  
Notes
2007-10-22 16:16:121. NO ELECTRICAL CONDUITS SHALL ENTER ANY OF THE
 REQUIRED EXIT STAIRTOWERS. PLEASE PROVIDE A NOTE ON THE
 PLANS THAT NO CONDUITS SHALL BE CHASED THROUGH ANY EXIT
 STAIRTOWER EITHER VERTICALLY OR HORIZONTALLY.
  
 2. ANY PROPOSED INSTALLATION OF EQUIPMENT SHALL NOT
 INTERFERE WITH ANY EXISTING FIRE PROTECTION SYSTEMS OR
 DEVICES.
  
 3. ANY EQUIPMENT INSTALLED ON THE ROOF SHALL NOT
 INTERFERE WITH ANY STANDPIPE ROOF MANIFOLDS.
  
 4. ALL CONSTRUCTION, DEMOLITION, AND RENOVATION WORK TO
 COMPLY WITH NFPA 241.
  
 5. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY.
  
 6. EXITS SHALL REMAIN CLEAR AND UNOBSTRUCTED DURING
 WORK ACTIVITIES.
  
 7. ANY PENETRATIONS EITHER VERTICALLY OR HORIZONTALLY
 WITHIN RATED FIRE RATED ASSEMBLIES SHALL BE PROPERLY
 SEALED TO PREVENT FIRE, SMOKE OR HEATED FIRE GASES FROM
 SPREADING.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 804-4709 PHONE
 804-4774 FAX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-01-10 Cont ID  
Sent By mmiller Date 2008-01-10 Time 15:42 Rev Time 0.00
Received By mmiller Date 2008-01-10 Time 15:42 Sent To  
Notes
2008-01-10 15:43:33SENT TO COMM BOARD # 23

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-15 Cont ID  
Sent By adarroug Date 2007-11-15 Time 13:51 Rev Time 0.00
Received By adarroug Date 2007-11-15 Time 13:51 Sent To  
Notes
2007-11-30 13:24:47TO "COMM" BD#6
2007-11-15 13:52:10WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-23 Cont ID  
Sent By adarroug Date 2007-10-22 Time 08:37 Rev Time 0.00
Received By adarroug Date 2007-09-13 Time 16:51 Sent To  
Notes
2007-10-05 17:19:52TO "COMM" BD#21

Review Stop Z ZONING
Rev No 1 Status P Date 2007-09-25 Cont ID  
Sent By kdfreema Date 2007-09-25 Time 09:15 Rev Time 0.00
Received By kdfreema Date 2007-09-25 Time 09:15 Sent To  
Notes
***NONE***