Plan Review Details - Permit 07090360
Plan Review Stops For Permit 07090360
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2007-10-18 Cont ID  
Sent By shill Date 2007-10-18 Time 17:05 Rev Time 0.00
Received By shill Date 2007-10-18 Time 17:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-05-23 Cont ID  
Sent By btrobaug Date 2008-05-23 Time 14:04 Rev Time 0.00
Received By btrobaug Date 2008-05-23 Time 13:48 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-12-03 Cont ID  
Sent By btrobaug Date 2007-12-03 Time 06:49 Rev Time 0.00
Received By btrobaug Date 2007-12-03 Time 06:35 Sent To G
Notes
2007-12-03 06:49:17 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1}THE LOAD BEING SERVED BY THE GENERATOR, (86.33
 AMPS) IS LARGER THAN THE GENERATOR OUTPUT (75 AMPS).
 SEE 702.5 CAPACITY AND RATING
 AN OPTIONAL STANDBY SYSTEM SHALL HAVE ADEQUATE CAPACITY
 AND RATING FOR THE SUPPLY OF ALL EQUIPMENT INTENDED TO
 BE OPERATED AT ONE TIME. OPTIONAL STANDBY SYSTEM
 EQUIPMENT SHALL BE SUITABLE FOR THE MAXIMUM AVAILABLE
 FAULT CURRENT AT ITS TERMINALS. THE USER OF THE
 OPTIONAL STANDBY SYSTEM SHALL BE PERMITTED TO SELECT
 THE LOAD CONNECTED TO THE SYSTEM.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-09-27 Cont ID  
Sent By btrobaug Date 2007-09-27 Time 07:44 Rev Time 0.00
Received By btrobaug Date 2007-09-27 Time 06:42 Sent To P
Notes
2007-09-27 07:44:33 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} PROVIDE A RISER DIAGRAM PER 215.5
 INCLUDING GENERATOR AND RELATED
 EQUIPMENT.
  
 2} PROVIDE A LOAD CALCULATION FOR THE
 LOAD INTENDED TO BE SERVED. 215.5. 702.5, 2005NEC
  
 3} PROVIDE A PANEL SCHEDULE FOR THE
 GENERATOR PANEL. 106.3.5.4 FBC AS
 AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2007-12-07 Cont ID  
Sent By mperson Date 2007-12-07 Time 09:28 Rev Time 0.00
Received By mperson Date 2007-12-07 Time 09:28 Sent To PC
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-10-01 Cont ID  
Sent By mperson Date 2007-10-01 Time 15:17 Rev Time 0.00
Received By mperson Date 2007-10-01 Time 15:17 Sent To B
Notes
2007-10-01 16:38:52DENIED
 REFERENCE:
 ** FBC-2004 WITH 05 &O6 REVISONS, FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTION/INFORMATION IS REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. PER FBC-2004 W/O5 & 06 REV, TABLE 402.4(2) THE
 ABOVE GROUND SCH 40 METALLIC PIPING NEEDS TO BE 1 INCH
 (1"). PLEASE PROVIDE MANUFACTURER'S SPECIFICATIONS OF A
 1 INCH SCH 40 METALLIC TO 3/4 INCH PE TRANSITION OR
 CHANGE ALL PIPE SIZES TO BE 1 INCH ON THE RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-05-20 Cont ID  
Sent By adarroug Date 2008-05-20 Time 11:58 Rev Time 0.00
Received By adarroug Date 2008-05-20 Time 11:58 Sent To E
Notes
2008-05-20 11:58:49TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-27 Cont ID  
Sent By adarroug Date 2007-11-27 Time 14:22 Rev Time 0.00
Received By adarroug Date 2007-11-27 Time 14:22 Sent To E
Notes
2007-11-27 14:22:40TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-18 Cont ID  
Sent By shill Date 2007-10-18 Time 17:05 Rev Time 0.00
Received By shill Date 2007-09-13 Time 10:21 Sent To  
Notes
2007-09-13 10:21:36TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-09-21 Cont ID  
Sent By tgordon Date 2007-09-21 Time 08:27 Rev Time 0.20
Received By tgordon Date 2007-09-21 Time 08:27 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2007-09-18 Cont ID  
Sent By choops Date 2007-09-18 Time 09:25 Rev Time 0.00
Received By choops Date 2007-09-18 Time 09:25 Sent To E
Notes
2007-09-18 09:26:07APPROVED GENERATOR LOCATION