Plan Review Details - Permit 07090355
Plan Review Stops For Permit 07090355
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-11-11 Cont ID  
Sent By shill Date 2007-11-11 Time 15:24 Rev Time 0.00
Received By shill Date 2007-11-11 Time 15:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-18 Cont ID  
Sent By shill Date 2007-10-18 Time 16:30 Rev Time 0.00
Received By shill Date 2007-10-18 Time 16:30 Sent To E
Notes
2007-10-18 16:32:23****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.PER FBPE AND FAC61G15-23.002, CALCULATIONS ARE TO
 BE SIGNED, SEALED, AND DATED ON EACH SHEET OR AN INDEX
 SHEET USED.
  
 2.THE PRINTED NAME OF THE PERSON SEALING THE DOCUMENT
 IS TO BE ON EACH SHEET, FAC61G15-23.002.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-10-23 Cont ID  
Sent By btrobaug Date 2007-09-27 Time 10:35 Rev Time 0.00
Received By btrobaug Date 2007-09-27 Time 07:49 Sent To I
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2007-11-07 Cont ID  
Sent By mperson Date 2007-11-07 Time 16:29 Rev Time 0.00
Received By mperson Date 2007-11-07 Time 16:29 Sent To B
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-10-01 Cont ID  
Sent By mperson Date 2007-10-01 Time 14:55 Rev Time 0.00
Received By mperson Date 2007-10-01 Time 14:55 Sent To B
Notes
2007-10-01 15:05:15DENIED
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 ******IMPORTANT INFORMATION******
 AS OF 8/25/06 GENERATOR (GEN/RES AND
 GEN/COM) PERMIT APPLICATIONS SHALL NOT
 BE ACCEPTED UNLESS THE ELECTRICAL INFOR-
 MATION AND GAS (OR DIESEL) INFORMATION
 IS ALL SUBMITTED AT THE SAME TIME. THE
 GENERATOR, ELECTRICAL AND GAS/DIESEL IN-
 FORMATION WILL BE ROUTED TOGETHER. THIS
 WILL ENSURE THAT ALL OF THE INFORMATION (PARTICULARLY
 THE MANUFACTURER'S SPECI-
 FICATIONS AND INSTALLATION INSTRUCTIONS)
 ARE AVAILABLE TO ALL PLAN REVIEWERS.
  
 CONTRACTOR INFORMATION
 NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL GEN/RES INSPECTION.
  
 **PLEASE SUBMIT THE FOLLOWING INFORMATION FOR A GAS
 PERMIT
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
  
 3. TYPE OF GAS, (LP OR NATURAL)
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 6. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 7. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
  
 8. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 9. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 10. FBC-2004 CHAPTER 1,SECTION 106.3.4.3:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-31 Cont ID  
Sent By adarroug Date 2007-10-31 Time 09:24 Rev Time 0.00
Received By adarroug Date 2007-10-31 Time 09:24 Sent To Z
Notes
2007-10-31 09:24:54TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-23 Cont ID  
Sent By btrobaug Date 2007-09-27 Time 07:57 Rev Time 0.00
Received By btrobaug Date 2007-09-13 Time 09:25 Sent To P
Notes
2007-09-13 09:26:07TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-11-02 Cont ID  
Sent By tgordon Date 2007-11-02 Time 16:04 Rev Time 0.20
Received By tgordon Date 2007-11-02 Time 16:04 Sent To G
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-09-21 Cont ID  
Sent By tgordon Date 2007-09-21 Time 08:30 Rev Time 0.20
Received By tgordon Date 2007-09-21 Time 08:30 Sent To E
Notes
2007-09-21 08:32:00PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) SEE ZONING REVIEW NOTES, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2007-11-02 Cont ID  
Sent By choops Date 2007-11-02 Time 11:00 Rev Time 0.00
Received By choops Date 2007-11-02 Time 11:00 Sent To M
Notes
2007-11-02 11:01:21***APPROVED - RESUB #1***
  
  
 SENT TO "M" - TG

Review Stop Z ZONING
Rev No 1 Status F Date 2007-09-17 Cont ID  
Sent By choops Date 2007-09-17 Time 17:51 Rev Time 0.00
Received By choops Date 2007-09-17 Time 17:51 Sent To E
Notes
2007-09-17 17:56:48***FAILED***
  
  
 1)PROPOSED GENERATOR LOCATION DOES NOT MEET REAR
 SETBACK REQUIREMENT OF 8.5' TO THE SOUTHERN PROPERTY
 LINE.AS THE SOUTHERN PROPERTY LINE IS CONSIDERED THE
 REAR OF THE PROPERTY FOR SETBACK PURPOSES IT'S REQUIRED
 SETBACK IS 12.5'.MECHANICAL EQUIPMENT IS ALLOWED TO
 ENCROACH 4' INTO A REQUIRED SETBACK, YIELDING A SETBACK
 REQUIREMENT OF 8.5' TO THE SOUTHERN PROPERTY LINE.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720