Plan Review Details - Permit 07090349
Plan Review Stops For Permit 07090349
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-11-19 Cont ID  
Sent By shill Date 2007-11-19 Time 18:07 Rev Time 0.00
Received By shill Date 2007-11-19 Time 18:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-18 Cont ID  
Sent By shill Date 2007-10-18 Time 09:24 Rev Time 0.00
Received By shill Date 2007-10-18 Time 09:24 Sent To  
Notes
2007-10-18 09:32:29****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)SEE FBC106.3.PROVIDE A SITE PLAN, DRAWN TO
 SCALE, WITH DIMENSIONS, CLEARLY SHOWING WORK LOCATION
 AND SCOPE.THE SITE PLAN IS TO BE LEGIBLE.
  
 2.)REVISE THE PERMIT APPLICATION."POSSIBLE REMOVE
 AND REPLACE DRIVEWAY."EITHER REMOVE THE WORD
 "POSSIBLE" OR REMOVE THE ENTIRE SENTENCE.YOU MAY
 APPLY FOR REMOVAL/REPLACEMENT OF THE DRIVEWAY AND
 SUBMIT A REVISION AT A FUTURE DATE IF YOU CHANGE THE
 SCOPE OF WORK.
  
 3.)INCLUDE TOTAL SQUARE FOOT AREA OF DEMO, TOTAL
 SQUARE FOOT OF NEW CONCRETE ON THE PERMIT APPLICATION.
  
 4.)SEE FBC R CHAPTER 4 AND FBC R CHAPTER 5.PROVIDE
 A DETAIL AND/OR SPECIFICATION FOR THE DRIVEWAY AND FOR
 THE FLOOR.
  
 5.)DECLARE GOVERNING CODE, FS553.
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-01-25 Cont ID  
Sent By shill Date 2008-01-25 Time 12:45 Rev Time 0.00
Received By shill Date 2008-01-25 Time 12:45 Sent To P
Notes
2008-01-25 12:45:42TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-01-23 Cont ID  
Sent By adarroug Date 2008-01-23 Time 10:23 Rev Time 0.00
Received By adarroug Date 2008-01-23 Time 10:23 Sent To P
Notes
2008-01-23 10:24:15TO "MPERSON" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-06 Cont ID  
Sent By adarroug Date 2007-11-06 Time 10:39 Rev Time 0.00
Received By adarroug Date 2007-11-06 Time 10:39 Sent To Z
Notes
2007-11-06 10:39:23TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-18 Cont ID  
Sent By shill Date 2007-10-18 Time 09:32 Rev Time 0.00
Received By shill Date 2007-09-12 Time 16:11 Sent To  
Notes
2007-09-12 16:11:56TO "Z' BOX

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-01-29 Cont ID  
Sent By mperson Date 2008-01-29 Time 16:01 Rev Time 0.00
Received By mperson Date 2008-01-29 Time 16:01 Sent To PC
Notes
2008-01-29 16:03:57REVISION #1: "OK" REPLACE EXISTING INTERIOR SANITARY
 PLUMBING BUILDING DRAIN LINES WITH NEW.

Review Stop P PLUMBING
Rev No 3 Status F Date 2008-01-24 Cont ID  
Sent By mperson Date 2008-01-24 Time 13:34 Rev Time 0.00
Received By mperson Date 2008-01-24 Time 13:34 Sent To PC
Notes
2008-01-24 13:49:28PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 REVISION DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1.PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4
 RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A
 PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING
 ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT
 LOCATIONS FOR THE BATHROOM AND WASHING MACHINE.
 **THE SUBMITTED DRAWING FOR THE PLUMBING REVISION IS
 NOT AN ISOMETRIC AND IS NOT COMPLIANT. PLEASE REFERENCE
 THE EXAMPLE ISOMETRIC THAT IS CODE COMPLIANT AND
 REFLECTS THE FLOOR PLAN ATTACHED TO THESE COMMENTS.
  
 2. THE FOLLOWING IS REQUIRED FOR THE WASHING MACHINE.
  
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
  
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING.
 **INDICATE WASHING MACHINE STANDPIPE.
  
 (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM)
 **WASHING MACHINE CLEANOUT SHALL BE 3".
  
 (D) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 **CLEANOUT FOR WASHING MACHINE SHALL BE LOCATED A 4'
 A.F.F.
  
 (E) 901.2.1 VENTING REQUIRED. WASHING MACHINE REQUIRES
 A VENT.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-11-13 Cont ID  
Sent By mperson Date 2007-11-13 Time 08:53 Rev Time 0.00
Received By mperson Date 2007-11-13 Time 08:53 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-09-27 Cont ID  
Sent By mperson Date 2007-09-27 Time 14:49 Rev Time 0.00
Received By mperson Date 2007-09-27 Time 14:48 Sent To B
Notes
2007-09-27 15:42:29DENIED
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 1. PERMIT APPLICATION AT A MINIMUM MUST PROVIDE A
 CLEAR SCOPE OF THE WORK BEING DONE ON PROJECT.
 NOTE: PERMIT APPLICATION INDICATES "POSSIBLE REMOVE AND
 REPLACE DRIVEWAY, REMOVE AND REPLACE CONCRETE FLOOR".
 THE SUBMITTED PLANS ARE INDICATING "RUN NEW SEWER"
 PLEASE CLARIFY IF THIS IS A NEW SEWER REPLACEMENT OF AN
 EXISTING SEWER OR AS THE PLANS INDICATE NEW SEWER.
 PLANS ARE ALSO INDICATING "RUN NEW LINE INTO AN
 EXISTING BATHROOM". PLEASE CLARIFY IF THE EXISTING
 BATHROOM PLUMBING IS OR IS NOT BEING REPLACED. IF THE
 BATHROOM PLUMBING IS BEING REPLACED PLEASE PROVIDE THE
 FOLLOWING INFORMATION.
  
 2. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4
 RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A
 PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING
 ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT
 LOCATIONS OF ALL INTERIOR PLUMBING WORK BEING
 REPLACED.
  
 3. PROVIDE A NOTICE OF COMMENCEMENT- PALM BEACH COUNTY
 COURTHOUSE-4TH FLOOR RECORDING DEPT., 205 N. DIXIE
 HWY.,WEST PALM BEACH FL., 33401, (561) 355-2991 BEFORE
 A PERMIT CAN BE ISSUED.
  
 4. FBC-2004 CHAPTER 1,SECTION 106.3.4.3:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2007-11-09 Cont ID  
Sent By choops Date 2007-11-09 Time 16:31 Rev Time 0.00
Received By choops Date 2007-11-09 Time 16:31 Sent To P
Notes
2007-11-09 16:32:34***APPROVED - RESUB #1***
  
  
 SENT TO "P" - MP

Review Stop Z ZONING
Rev No 1 Status F Date 2007-09-17 Cont ID  
Sent By choops Date 2007-09-17 Time 13:26 Rev Time 0.00
Received By choops Date 2007-09-17 Time 13:26 Sent To P
Notes
2007-09-17 13:29:06***FAILED***
  
  
 1)PLEASE PROVIDE A CLEAR SCOPE OF WORK.WHAT
 MATERIAL IS DRIVEWAY TO BE REPLACE WITH?PROVIDE ALL
 DIMENSIONS OF THE PROPOSED DRIVEWAY, INCLUDING THE
 SQUARE FOOTAGE OF THE PROPOSED DRIVEWAY AND ANY
 WALKWAYS WITHIN THE FRONT YARD (FROM FRONT PROPERTY
 LINE TO THE FRONT OF THE HOUSE).
  
 2)SURVEY SHOWS A LINE DRAWN AT REAR WITH "NEW" IN
 IT.CLARIFY.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720