Plan Review Details - Permit 07090338
Plan Review Stops For Permit 07090338
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2007-10-16 Cont ID  
Sent By rmcdouga Date 2007-10-16 Time 07:50 Rev Time 0.00
Received By rmcdouga Date 2007-10-16 Time 07:50 Sent To  
Notes
2007-10-16 07:55:322004 FBC W/2007 REVISIONS
 INSTALL POOL WITH GAS HEATER
  
 BUILDING PROVISO:
 TO BE IN PLACE AT C.O.:
  
 1) 424.2.17.1 OUTDOOR SWIMMING POOLS.
 OUTDOOR SWIMMING POOLS SHALL BE PROVIDED
 WITH A BARRIER COMPLYING WITH
 424.2.17.1.1 THROUGH 424.2.17.1.14.
  
 424.2.17.1.5 CHILD SAFETY BARRIER
 ASTM D5034 100 LB TENSILE STRNGTH
 ASTM D3787 150 LB BALL BURST
 STRENGTH
  
 2) 13-612.1.ABC.2.3.2 COVERS REQUIRED.
 SPAS AND HEATED SWIMMING POOLS SHALL BE
 EQUIPPED WITH A COVER DESIGNED TO
 MINIMIZE HEAT LOSS.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-09-18 Cont ID  
Sent By btrobaug Date 2007-09-18 Time 16:58 Rev Time 0.00
Received By btrobaug Date 2007-09-18 Time 16:51 Sent To P
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2007-10-30 Cont ID  
Sent By mperson Date 2007-10-30 Time 14:31 Rev Time 0.00
Received By mperson Date 2007-10-30 Time 14:31 Sent To PC
Notes
2007-10-30 14:33:16CONTRACTOR INFORMATION
 NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL POOL INSPECTION.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2007-09-27 Cont ID  
Sent By mperson Date 2007-09-27 Time 14:15 Rev Time 0.00
Received By mperson Date 2007-09-27 Time 14:15 Sent To B
Notes
2007-09-27 14:18:54CONTRACTOR INFORMATION
 NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL POOL INSPECTION.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-18 Cont ID  
Sent By adarroug Date 2007-10-18 Time 10:17 Rev Time 0.00
Received By adarroug Date 2007-10-18 Time 10:17 Sent To P
Notes
2007-10-18 10:17:23TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-16 Cont ID  
Sent By rmcdouga Date 2007-10-16 Time 07:56 Rev Time 0.00
Received By rmcdouga Date 2007-09-12 Time 16:33 Sent To  
Notes
2007-09-12 16:33:43TO "Z" BOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-10-30 Cont ID  
Sent By mperson Date 2007-10-30 Time 14:30 Rev Time 0.00
Received By mperson Date 2007-10-30 Time 14:30 Sent To G
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-09-27 Cont ID  
Sent By mperson Date 2007-09-27 Time 13:49 Rev Time 0.00
Received By mperson Date 2007-09-27 Time 13:49 Sent To G
Notes
2007-09-27 14:14:52DENIED
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS SECTIONS 424.2 AND
 R4101 SWIMMING POOLS.
 ** FBC-2004 WITH 05 & 06 REVISIONS, PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SHEET 1 POOL DATA & EQUIPMENT INDICATES THE
 FOLLOWING "HEATER: EXISTING GAS HEATER". PLEASE CLARIFY
 ON THE RESUBMITTAL HOW A NEW POOL AND SPA HAS AN
 EXISTING GAS HEATER.
  
 2. FBC-2004 SEC. 424.2.14.1, OR
 FBCR-2004 SEC. R4101.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. (MANUFACTURE
 SHEETS REQUIRED, PLEASE SUBMIT)
  
 3. FBC-2004 SEC. 424.2.14.2, OR
 FBCR-2004 SEC. R4101.14.2 WATER
 RETENTION, PROVIDE A POSITIVE MEANS OF
 RETAINING WATER IN THE HEATER WHEN PUMP
 IS SHUT OFF.(MANUFACTURE SHEETS
 REQUIRED, PLEASE SUBMIT)
  
 4. FBC-2004 SEC. 424.2.14, OR FBCR-2004
 SEC. R4101.15 GAS PIPING SHALL COMPLY
 WITH FBC FUEL GAS. SEPARATE PLANS AND
 PERMIT REQUIRED.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2007-09-17 Cont ID  
Sent By choops Date 2007-09-17 Time 13:38 Rev Time 0.00
Received By choops Date 2007-09-17 Time 13:38 Sent To E
Notes
2007-09-17 13:39:11PROVISO:POOL EQUIPMENT SHALL NOT BE CLOSER THAN 3.5'
 TO THE EAST SIDE PROPERTY LINE.