Plan Review Details - Permit 07090326
Plan Review Stops For Permit 07090326
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-01-11 Cont ID  
Sent By mjacobs Date 2008-01-11 Time 09:59 Rev Time 0.00
Received By mjacobs Date 2008-01-11 Time 07:44 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-12-12 Cont ID  
Sent By mjacobs Date 2007-12-12 Time 06:38 Rev Time 0.00
Received By mjacobs Date 2007-12-11 Time 17:29 Sent To  
Notes
2007-12-12 06:38:10BUILDING PLAN REVIEW
 PERMIT: 07090326
 ADD: 525 S. FLAGLER DR. #1501
 CONT: DESIGN CONTRACTING INC.
  
 TEL: (561)514-3004
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 3RD 12/12/07
 ACTION: DENIED
  
 1) OK
  
 2)2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE. **THE HAND
 WRITTEN CHANGES ON THE PLANS ARE NOT ACCEPTABLE.**
  
 3)OK
 4)OK
 5)OK
  
 6) 106.1.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING A) THE EDITION OF
 THE CODE UNDER WHICH THE PROJECT IS DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 D) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED
 -------------------------------------
 **NEW** THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. NO HANDWRITING, WHITE-OUT,
 CHANGES IN PENCIL OR PEN IS ALLOWED ON THE PLANS. THIS
 POLICY IS ENFORCE DUE TO THE FACT THAT OTHER CHANGES
 MAY BE MAKE TO THE PLANS OUT IN THE FIELD WITHOUT THE
 APPROVAL OF THE BUILDING OFFICIAL.WPB AMENDMENTS
 SECTION 106.1.3 SEE SHEETSAB#1 AND AP#2.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-11-02 Cont ID  
Sent By mjacobs Date 2007-11-02 Time 08:16 Rev Time 0.00
Received By mjacobs Date 2007-11-02 Time 06:07 Sent To  
Notes
2007-11-02 08:16:13 
  
  
  
  
  
 BUILDING PLAN REVIEW
 PERMIT: 07090326
 ADD: 525 S. FLAGLER DR. #1501
 CONT: DESIGN CONTRACTING INC.
  
 TEL: (561)514-3004
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 2ND 11/2/07
 ACTION: DENIED
  
 1) --- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
 **NO RESPONSE NOT ADDRESSED**
 2)2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 3)OK
  
 **NO RESPONSE NOT ADDRESSED**
 4)THE CLAIMED VALUATION OF THE BUILDING ALTERATION IS
 TO LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, INTERIOR
 FINISH, ARCHITECTURAL AND DESIGN FEES ETC EXCLUDING
 LAND. FBC.108.3*.
  
 **NO RESPONSE NOT ADDRESSED**
 5)SHOW THE FRAMING DETAIL OF THE NEW DROP CEILING
 INDICATING THE MATERIALS TO BE USED.
  
 **NO RESPONSE NOT ADDRESSED**
 6) 106.1.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING A) THE EDITION OF
 THE CODE UNDER WHICH THE PROJECT IS DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 D) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED
 -------------------------------------
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-20 Cont ID  
Sent By mjacobs Date 2007-09-20 Time 10:31 Rev Time 0.00
Received By mjacobs Date 2007-09-20 Time 06:48 Sent To  
Notes
2007-09-20 10:31:07 
 BUILDING PLAN REVIEW
 PERMIT: 07090326
 ADD: 525 S. FLAGLER DR. #1501
 CONT: DESIGN CONTRACTING INC.
 TEL: (561)514-3004
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1) --- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 3)THE DRAWINGS SHALL BE PREPARED BY A DESIGN
 PROFESSIONAL.DUE TO THE WORK AND OCCUPANCY OF THE
 BUILDING (GROUP R-2), THE DRAWINGS SHALL BE PREPARED BY
 A DESIGN PROFESSIONAL WHO SHALL AFFIX HIS OR HER
 OFFICIAL SEAL, SIGNATURE AND DATE ON SAID PLANS PER
 FLORIDA STATUTES 481.229 (1) (B) AND (C).
  
 4)THE CLAIMED VALUATION OF THE BUILDING ALTERATION IS
 TO LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, INTERIOR
 FINISH, ARCHITECTURAL AND DESIGN FEES ETC EXCLUDING
 LAND. FBC.108.3*.
  
 5)SHOW THE FRAMING DETAIL OF THE NEW DROP CEILING
 INDICATING THE MATERIALS TO BE USED.
  
 6) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
 A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 -------------------------------------
 ) NUMBER OF UNITS
 ) NUMBER OF FLOORS
 ) NUMBER OF ROOMS
 ) NUMBER OF BEDROOMS
 ) SQ. FT. LIV SPACE/ FL
 ) SQ. FT. FOOTPRINT
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-01-09 Cont ID  
Sent By dpalmer Date 2008-01-09 Time 13:23 Rev Time 0.00
Received By dpalmer Date 2008-01-09 Time 13:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-12-04 Cont ID  
Sent By dpalmer Date 2007-12-04 Time 11:01 Rev Time 0.00
Received By dpalmer Date 2007-12-04 Time 11:00 Sent To  
Notes
2007-12-04 11:01:11** DENIED 3RD REVIEW **
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING ALONG WITH SOME NEW
 COMMENTS BASED ON REVISED PLANS/INFORMATION ETC.
 SOME INFORMATION NOW SHOWN WAS NOT ON PREVIOUS PLANS
 THEREFORE A REVIEW OF SOME OF THESE ITEMS COULD NOT
 HAVE BEEN DONE.
  
 ** SOME OF THESE COMMENTS BELOW COULD HAVE BEEN
 REDLINED HOWEVER NOT ALL.
  
 1) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS; PLEASE
 SEE MISSING CIRCUITING FOR SMOKE ALARMS AND ARC FAULT
 REQUIRED.
 PLEASE ALSO SEE MISSING CIRCUIT ON MASTER BEDROOM
 RECEPTACLE.
 210.12, 408.4, 240.4
 FBC 106.3.5.1.2
 REQUESTED ON TWO PREVIOUS REVIEWS IN NOTES #3, #4 AND
 #5.
  
 2) NOTE: PLEASE SEE BEDROOM #2 AS STATED ON PREVIOUS
 REVIEW NOTE # 7 WILL REQUIRE A LIGHT FIXTURE. THE
 RESPONSE MENTIONS TO SEE NOT AT THE TOP OF PLAN PAGE.
 THE NOTE ON PLANS IS FOR THE BALCONY LIGHTS. THE
 BALCONY ON A MULTI-STORY BUILDING IS NOT REQUIRED TO
 HAVE LIGHTING UNDER THE CURRENT CODE AS THERE IS NO
 GROUND LEVEL ACCESS. THIS NOTE WAS ONLY FOR A FIXTURE
 OF SOME TYPE IN BEDROOM #2. THIS COULD HAVE BEEN
 REDLINED HOWEVER OTHER COMMENTS NEED TO BE ADDRESSED.
  
 3) NOTE: PLEASE SEE THE CODE REFERENCED ON THE LOAD
 CALCULATIONS IS NOT FROM THE 2005 NEC. THE CALCULATIONS
 FOR EXISTING IS FROM 220.87
 THIS ALSO COULD HAVE BEEN REDLINED AS NOT SHOWING THE
 CORRECT CODE HOWEVER SEE THE FOLLOWING COMMENT.
  
 4) NOTE: PLEASE SEE THE LOAD CALCULATIONS STATE AND
 SHOW A NEW STEAM UNIT HOWEVER NO INFORMATION IS SHOWN
 ON PLANS, NO LOCATION, NO LISTING ON PANEL SCHEDULE, NO
 OVER CURRENT PROTECTION, NO CONDUCTORS ETC.
 PLEASE PROVIDE CUT SHEETS ON UNIT WHICH CONTAIN A
 LISTING FROM A NATIONALLY RECOGNIZED TESTING
 LABORATORY.
 THIS UNIT WAS NOT ON PREVIOUS PLANS OR LOAD
 CALCULATIONS.
 110.3, 90.7, 408.4, 310.16, 240.4 ETC
 FBC 106.1.2, 106.3.5.1.2
  
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-10-31 Cont ID  
Sent By dpalmer Date 2007-10-31 Time 12:26 Rev Time 0.00
Received By dpalmer Date 2007-10-31 Time 11:55 Sent To  
Notes
2007-10-31 12:26:39 
 ** DENIED 2ND REVIEW**
  
 ** PLEASE SEE NOTES FROM PREVIOUS REVIEW WHICH IS STILL
 IN NEED OF ADDRESSING.
 PLEASE SEE MOST OF THE NOTES BELOW WERE TAKEN FROM
 PREVIOUS REVIEW.
  
  
 1) NOTE:THIS IS THE SAME NOTE:
 PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH ARE
 SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE. PLEASE SEE
 THAT THIS SHALL INCLUDE 2006 REVISIONS TO THE 2004 FBC
 FOR ALL TRADES AND THE 2005 NFPA-70. PLEASE KNOW THERE
 ARE CHANGES IN THE FBC WHICH MAY AFFECT DESIGNS FOR ALL
 TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 2) NOTE:THIS IS THE SAME NOTE: IN FACT PLEASE SEE
 ELECTRICAL PLANS NOW CONTAIN A NOTE FROM THE ENGINEER
 WHICH SPECIFICALLY STATES THE ELECTRICAL IS DONE BY
 OTHER YET THIS SAME ENGINEER HAS SIGNED, DATED AND
 SEALED PLANS. IF THE ELECTRICAL DESIGN IS NOT DONE BY
 THIS ENGINEER, THEN ARE STATED IN THE FLORIDA STATUTES,
 HE MAY NOT SIGN, DATE AND SEAL SAID PLANS.
 PLEASE SEE THE *DESIGNER* AS LISTED ON PLANS* MUST MEET
 THE EXCEPTIONSAS SPECIFIED IN THE FLORIDA STATUTES.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE NO DESIGN PROFESSIONAL IS PRINTED, SIGNED,
 OR SIGNED, DATED AND SEALED ON PLANS. PLEASE SEE
 MISSING INFORMATION FOR TITLE BLOCKS IF DONE BY A
 DESIGN PROFESSIONAL UNDER FS 481, 471 PER FAC
 61G15-23.002, 61G1-16.004.
 PLEASE KNOW EVEN WHEN MEETING ANY EXCEPTIONS UNDER FS
 471.003, OR 481.229 A DESIGNER OF RECORD IS STILL
 REQUIRED TO PRINT NAME AND SIGN PLANS.
 FBC 106.1.2, 106.3, 106.5
  
 3) NOTE:THIS IS THE SAME NOTE:IN FACT PLEASE SEE
 THE PANEL SCHEDULE SUBMITTED IS NOT COMPLETE WITH THE
 OVER CURRENT PROTECTION OR MINIMUM CONDUCTOR SIZES.
 THIS WILL ALSO BE NOTED IN COMMENTS BELOW.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE COMPLETE ALL CIRCUITING ON PLANS FOR NEW AND
 CORRELATE WITH A NEW REVISED PANEL SCHEDULE TO BE
 SUBMITTED. THE EXISTING CIRCUITS ONLY NEED BE SHOWN
 WITH AN *E*.
 PLEASE SEE THE PANEL SCHEDULE IS TO INDICATE ALL NEW
 DEDICATED CIRCUITS AS NOTED BELOW.
 FBC 106.3.5.4
 408.4,240.4,310.16,408.4 ETC
  
 4) NOTE: PLEASE SEE THE SMOKE DEVICES WHICH ARE SHOWN
 ARE BEING INDICATED AS *SD* FOR SMOKE DETECTORS. IF
 THESE ARE TRUE SMOKE DETECTORS BY DEFINITION, PLEASE
 INCLUDE THE FIRE ALARM PANEL, HORN DEVICES ETC.
 IF SMOKE ALARMS, PLEASE CHANGE.
  
 ** PREVIOUS REVIEW NOTE **PLEASE SEE MISSING SMOKE
 DETECTION DEVICES AS REQUIRED UNDER FBC R313, AND
 NFPA-72 11.5.1.1, 11.8.3. THE PLANS NEED TO SHOW NEW OR
 EXISTING SMOKE ALARM DEVICES.
 5) NOTE:ARC FAULT INDICATED ON PANEL SCHEDULE HOWEVER
 AS CIRCUITING IS NOT ON PLANS FOR NEW ITEMS, THIS CAN
 NOT BE VERIFIED.
 PLEASE SEE 210.12 AND LIST.
  
 6) NOTE:THIS NOTE REMAINS AS WIRE SIZE AND OVER
 CURRENT PROTECTION ARE NOT SHOWN ON PANEL SCHEDULE.
 PLEASE ALSO SEE CIRCUITING ON PLANS.
 PLEASE BE SURE TO LIST THE REQUIRED DEDICATED
 CIRCUIT(S) FOR BATH RECEPTACLE(S) PER 210.52D,
 210.11C3.
 (MUST BE 20AMP AND #12)
  
 7) NOTE:THIS WAS NOTE #8 ON PREVIOUS REVIEW.
 PLEASE KNOW BEDRM #2 WILL REQUIRE SOME SORT OF LIGHT
 FIXTURE FOR EGRESS INTO THIS ROOM PER 210.70, LS 101
 7.8
  
 8) NOTE: THIS WAS NOTE #10 ON PREVIOUS REVIEW.
 PLEASE SEE MISSING DEDICATED LOAD FOR NEW REFRIGERATOR
 ON LOAD CALCULATIONS.
 220.
 (LIST ON PANEL SCHEDULE).
  
 9) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE.
 THIS IS ONLY A NOTICE GIVEN AT THIS TIME.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-09-15 Cont ID  
Sent By dpalmer Date 2007-09-15 Time 11:55 Rev Time 0.00
Received By dpalmer Date 2007-09-15 Time 11:35 Sent To  
Notes
2007-09-15 11:55:502007-09-15 11:55:50
  
 ** DENIED **
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 2) NOTE: PLEASE SEE NO DESIGN PROFESSIONAL IS PRINTED,
 SIGNED, OR SIGNED, DATED AND SEALED ON PLANS. PLEASE
 SEE MISSING INFORMATION FOR TITLE BLOCKS IF DONE BY A
 DESIGN PROFESSIONAL UNDER FS 481, 471 PER FAC
 61G15-23.002, 61G1-16.004.
 PLEASE KNOW EVEN WHEN MEETING ANY EXCEPTIONS UNDER FS
 471.003, OR 481.229 A DESIGNER OF RECORD IS STILL
 REQUIRED TO PRINT NAME AND SIGN PLANS.
 FBC 106.1.2, 106.3, 106.5
  
 3) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS FOR
 NEW AND CORRELATE WITH A NEW REVISED PANEL SCHEDULE TO
 BE SUBMITTED. THE EXISTING CIRCUITS ONLY NEED BE SHOWN
 WITH AN *E*.
 PLEASE SEE THE PANEL SCHEDULE IS TO INDICATE ALL NEW
 DEDICATED CIRCUITS AS NOTED BELOW.
 FBC 106.3.5.4
 408.4,240.4,310.16,408.4 ETC
  
 4) NOTE: PLEASE SEE MISSING SMOKE DETECTION DEVICES AS
 REQUIRED UNDER FBC R313, AND NFPA-72 11.5.1.1, 11.8.3.
 THE PLANS NEED TO SHOW NEW OR EXISTING SMOKE ALARM
 DEVICES.
 **210.12 IN NEXT COMMENT APPLIES **
  
 5) NOTE: PLEASE BE SURE TO LIST THE REQUIRED ARC FAULT
 PROTECTED CIRCUITS PER 210.12 OF THE 2005 NEC.
  
 6) NOTE: PLEASE BE SURE TO LIST THE REQUIRED DEDICATED
 CIRCUIT(S) FOR BATH RECEPTACLE(S) PER 210.52D,
 210.11C3.
 (MUST BE 20AMP AND #12)
  
 7) NOTE: PLEASE SEE MISSING GFI PROTECTION FOR SPA
 TUB/JACUZZI TUB PER 680.71
 (LIST ON PANEL SCHEDULE)
  
 8) NOTE: PLEASE KNOW BEDRM #2 WILL REQUIRE SOME SORT OF
 LIGHT FIXTURE FOR EGRESS INTO THIS ROOM PER 210.70, LS
 101 7.8
  
 9) NOTE: PLEASE KNOW THESE PLANS MAY BE REFERENCE FOR
 LOW VOLTAGE PERMITS; HOWEVER PLEASE KNOW THE LV PERMIT
 IS SEPARATE FROM THE ELECTRICAL PERMIT. (SPKRS, TV, AND
 PHONE MAY BE ON ONE LV PERMIT)
 THIS IS ONLY NOTED AT THIS TIME FOR INFORMATION SO THIS
 DOES NOT LEAD TO ANY CONFUSION AT A LATER DATE AT
 INSPECTION(S) TIME.
  
 10) NOTE: PLEASE SEE MISSING DEDICATED LOAD FOR NEW
 REFRIGERATOR ON LOAD CALCULATIONS.
 220.
 (LIST ON PANEL SCHEDULE).
  
 11) NOTE: PLEASE REVISE UNIT/SUITE # ON PLANS TO
 CORRELATE WITH SUITE/UNIT # IN OUR SYSTEM AS SSIGNED
 ADDRESS. (UNIT 1501).
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-01-10 Cont ID  
Sent By mawillia Date 2008-01-10 Time 13:42 Rev Time 0.00
Received By mawillia Date 2008-01-10 Time 13:27 Sent To  
Notes
2008-01-10 13:42:22*****APPROVED*****
  
 THE COMMENTS TAKEN FROM THE PREVIOUS FIRE PLAN REVIEW
 HAVE BEEN ADDRESSED;PLAN SHEETS AB 1 OF 4 AND EL 3 OF
 4 WERE STAMPED, INITIALED, AND DATED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2007-12-17 Cont ID  
Sent By mawillia Date 2007-12-17 Time 11:27 Rev Time 0.00
Received By mawillia Date 2007-12-17 Time 11:10 Sent To  
Notes
2007-12-17 11:26:23*****DENIED*****
  
 THE FOLLOWINGS COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE ADDRESSED:
  
 2.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 4.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE DAILY OR MORE FREQUENTLY AS
 NECESSARY FOR SAFE OPERATION.
  
 5.THE REMOVAL OF OLD AND/OR THE STOCKING OF NEW
 BUILDING MATERIALS & SUPPLIES SHALL NOT HINDER OR
 INTERFERE WITH ACCESS TO OR EGRESS FROM THE OTHER
 TENANT SPACES ON THE 15TH FLOOR OR THE BUILDING.
  
 7.SPECIFY THE NEW INTERIOR WALL AND CEILING FINISH
 MATERIAL IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 8.PLEASE INDICATE IF THE BUILDING IS SPRINKLERED AND
 IF SO, WILL THE SCOPE WORK CAUSE ANY SPRINKLER
 MODIFICATIONS.BE ADVISED THAT SEPARATE PLANS AND
 PERMIT WILL BE REQUIRED FOR SPRINKLER SYSTEM REMODEL.
  
 9.PLEASE INDICATE IF THE BUILDING/RESIDENCE HAS A
 FIRE ALARM SYSTEM AND IF SO, WILL THE SCOPE OF WORK
 CAUSE ANY FIRE ALARM DEVICE(S) MODIFICATIONS.BE
 ADVISED THAT SEPARATE PLANS AND PERMIT WILL BE REQUIRED
 FOR THE FIRE ALARM REMODEL.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS
 ADDRESSED.PLEASE BE ADVISED THAT THE HAND WRITTEN
 RESPONSES ON THE PLANS ARE NOT ACCEPTABLE!!!!!
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-11-03 Cont ID  
Sent By mawillia Date 2007-11-03 Time 17:18 Rev Time 0.00
Received By mawillia Date 2007-11-03 Time 17:00 Sent To  
Notes
2007-11-03 17:17:58*****DENIED*****
  
 THE FOLLOWINGS COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE ADDRESSED:
  
 2.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 4.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE DAILY OR MORE FREQUENTLY AS
 NECESSARY FOR SAFE OPERATION.
  
 5.THE REMOVAL OF OLD AND/OR THE STOCKING OF NEW
 BUILDING MATERIALS & SUPPLIES SHALL NOT HINDER OR
 INTERFERE WITH ACCESS TO OR EGRESS FROM THE OTHER
 TENANT SPACES ON THE 15TH FLOOR OR THE BUILDING.
  
 6.PLEASE SHOW THE LOCATION OF THE SMOKE ALARMS (SA)
 IN THIS RESIDENCE.PLEASE BE ADVISED THAT SMOKE ALARMS
 (SA)SOUND ONLY WITHIN AN INDIVIDUAL DWELLING UNIT,
 WHEREAS SMOKE DETECTORS (SD) ARE TIED INTO THE
 BUILDING'S FIRE ALARM SYSTEM.
  
 7.SPECIFY THE NEW INTERIOR WALL AND CEILING FINISH
 MATERIAL IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 8.PLEASE INDICATE IF THE BUILDING IS SPRINKLERED AND
 IF SO, WILL THE SCOPE WORK CAUSE ANY SPRINKLER
 MODIFICATIONS.BE ADVISED THAT SEPARATE PLANS AND
 PERMIT WILL BE REQUIRED FOR SPRINKLER SYSTEM REMODEL.
  
 9.PLEASE INDICATE IF THE BUILDING/RESIDENCE HAS A
 FIRE ALARM SYSTEM AND IF SO, WILL THE SCOPE OF WORK
 CAUSE ANY FIRE ALARM DEVICE(S) MODIFICATIONS.BE
 ADVISED THAT SEPARATE PLANS AND PERMIT WILL BE REQUIRED
 FOR THE FIRE ALARM REMODEL.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-10-04 Cont ID  
Sent By mawillia Date 2007-10-04 Time 15:51 Rev Time 0.00
Received By mawillia Date 2007-10-04 Time 15:37 Sent To  
Notes
2007-10-04 15:44:33*****DENIED*****
  
  
 1.THE ACTUAL ADDRESS OF THE PROJECT SITE SHALL BE IN
 THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.BE
 ADVISED THAT THIS RESIDENCE IS IN THE JURISDICTION OF
 WEST PALM BEACH, FLORIDA 33401.THE SUITE NUMBER SHOWN
 ON THE PLAN AS 15A DO NOT CORRELATE WITH WHAT IS
 INDICATED IN THE CITY'S PERMITTING SYSTEM WHICH IS
 1501.PLEASE CLARIFY OR AMEND.
  
 2.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 4.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE DAILY OR MORE FREQUENTLY AS
 NECESSARY FOR SAFE OPERATION.
  
 5.THE REMOVAL OF OLD AND/OR THE STOCKING OF NEW
 BUILDING MATERIALS & SUPPLIES SHALL NOT HINDER OR
 INTERFERE WITH ACCESS TO OR EGRESS FROM THE OTHER
 TENANT SPACES ON THE 15TH FLOOR OR THE BUILDING.
  
 6.PLEASE SHOW THE LOCATION OF THE SMOKE ALARMS (SA)
 IN THIS RESIDNCE.
  
 7.SPECIFY THE NEW INTERIOR WALL AND CEILING FINISH
 MATERIAL IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 8.PLEASE INDICATE IF THE BUILDING IS SPRINKLERED AND
 IF SO, WILL THE SCOPE WORK CAUSE ANY SPRINKLER
 MODIFICATIONS.BE ADVISED THAT SEPARATE PLANS AND
 PERMIT WILL BE REQUIRED FOR SPRINKLER SYSTEM REMODEL.
  
 9.PLEASE INDICATE IF THE BUILDING/RESIDENCE HAS A
 FIRE ALARM SYSTEM AND IF SO, WILL THE SCOPE OF WORK
 CAUSE ANY FIRE ALARM DEVICE(S) MODIFICATIONS.BE
 ADVISED THAT SEPARATE PLANS AND PERMIT WILL BE REQUIRED
 FOR THE FIRE ALARM REMODEL.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-01-09 Cont ID  
Sent By adarroug Date 2008-01-09 Time 08:44 Rev Time 0.00
Received By adarroug Date 2008-01-09 Time 08:44 Sent To  
Notes
2008-01-09 08:48:40TO "BOB"#14

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-11-29 Cont ID  
Sent By adarroug Date 2007-11-29 Time 11:47 Rev Time 0.00
Received By adarroug Date 2007-11-29 Time 11:47 Sent To  
Notes
2007-12-03 16:48:06TO "BOB"#12
2007-11-29 11:56:29WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-23 Cont ID  
Sent By adarroug Date 2007-10-23 Time 12:34 Rev Time 0.00
Received By adarroug Date 2007-10-23 Time 12:34 Sent To  
Notes
2007-10-30 14:41:43TO "BOB"#2
2007-10-23 12:34:16WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-04 Cont ID  
Sent By mawillia Date 2007-10-04 Time 15:37 Rev Time 0.00
Received By mawillia Date 2007-09-12 Time 15:06 Sent To  
Notes
2007-09-15 11:35:47TO BOB SPACE #14, DVP.
2007-09-12 15:07:19WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-01-09 Cont ID  
Sent By tgordon Date 2008-01-09 Time 13:51 Rev Time 0.20
Received By tgordon Date 2008-01-09 Time 13:51 Sent To  
Notes
2008-01-09 13:51:43TWO BATHROOM EXHAUST FANS ONLY.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-12-05 Cont ID  
Sent By tgordon Date 2007-12-05 Time 10:49 Rev Time 0.25
Received By tgordon Date 2007-12-05 Time 10:49 Sent To  
Notes
2007-12-05 10:50:38TWO BATHROOM EXHAUST FANS ONLY.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-10-31 Cont ID  
Sent By tgordon Date 2007-10-31 Time 14:16 Rev Time 0.25
Received By tgordon Date 2007-10-31 Time 14:15 Sent To  
Notes
2007-10-31 14:16:43TWO BATHROOM EXHAUST FAN ONLY.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-09-17 Cont ID  
Sent By tgordon Date 2007-09-17 Time 10:39 Rev Time 0.20
Received By tgordon Date 2007-09-17 Time 10:39 Sent To  
Notes
2007-09-17 10:40:40PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) SEE ELECTRICAL REVIEW NOTES 1 AND 2, PLEASE
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-01-10 Cont ID  
Sent By jleech Date 2008-01-10 Time 08:14 Rev Time 0.00
Received By jleech Date 2008-01-10 Time 08:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-12-15 Cont ID  
Sent By jleech Date 2007-12-15 Time 06:35 Rev Time 0.00
Received By jleech Date 2007-12-15 Time 06:35 Sent To  
Notes
2007-12-15 07:04:57DENIED;
 1. HAND WRITEN NOTES ON PLANS NOT EXCEPTABLE.
 2. EXISTING CHASES CAN NOT BE USED FOR FLOOR SPACE IN
 APARTMENT. MASTER SHOWER AREA, AND BATH 2 NEXT TO THE
 LAVATORY. THESE CHASES ARE USED FOR PLUMBING
 ,ELECTRICAL, AND MECHANICAL . THIS IS COMMON AREA NOT
 FOR UNIT USE.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-11-09 Cont ID  
Sent By jleech Date 2007-11-09 Time 09:17 Rev Time 0.00
Received By jleech Date 2007-11-09 Time 09:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-10-02 Cont ID  
Sent By jleech Date 2007-10-02 Time 09:40 Rev Time 0.00
Received By jleech Date 2007-10-02 Time 09:40 Sent To  
Notes
2007-10-02 09:45:36DENIED;
 SEE ELECTRICAL NOTES 1 AND 2.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status N Date 2007-11-09 Cont ID  
Sent By choops Date 2007-09-21 Time 14:24 Rev Time 0.00
Received By choops Date 2007-09-21 Time 14:24 Sent To  
Notes
2007-09-21 14:24:56*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.