| Plan Review Stops For Permit 07090326 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2008-01-11 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-01-11 |
Time |
09:59 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-01-11 |
Time |
07:44 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2007-12-12 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-12-12 |
Time |
06:38 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-12-11 |
Time |
17:29 |
Sent To |
|
|
| Notes |
| 2007-12-12 06:38:10 | BUILDING PLAN REVIEW | | | PERMIT: 07090326 | | | ADD: 525 S. FLAGLER DR. #1501 | | | CONT: DESIGN CONTRACTING INC. | | | | | | TEL: (561)514-3004 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: 3RD 12/12/07 | | | ACTION: DENIED | | | | | | 1) OK | | | | | | 2)2004 FBC EXISTING | | | 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE | | | OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO | | | SECTIONS 303, 304 AND 305 OF THIS CODE. **THE HAND | | | WRITTEN CHANGES ON THE PLANS ARE NOT ACCEPTABLE.** | | | | | | 3)OK | | | 4)OK | | | 5)OK | | | | | | 6) 106.1.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION | | | THAT IS REQUIRED FOR RECORD KEEPING A) THE EDITION OF | | | THE CODE UNDER WHICH THE PROJECT IS DESIGNED. | | | B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE | | | PROVISIONS OF CHAPTER 3. | | | C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6, | | | TABLE 601. | | | D) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED | | | ------------------------------------- | | | **NEW** THE BUILDING OFFICIAL MAY ESTABLISH THROUGH | | | DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND | | | SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS | | | RECORD RETENTION PROGRAM. NO HANDWRITING, WHITE-OUT, | | | CHANGES IN PENCIL OR PEN IS ALLOWED ON THE PLANS. THIS | | | POLICY IS ENFORCE DUE TO THE FACT THAT OTHER CHANGES | | | MAY BE MAKE TO THE PLANS OUT IN THE FIELD WITHOUT THE | | | APPROVAL OF THE BUILDING OFFICIAL.WPB AMENDMENTS | | | SECTION 106.1.3 SEE SHEETSAB#1 AND AP#2. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-11-02 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-11-02 |
Time |
08:16 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-11-02 |
Time |
06:07 |
Sent To |
|
|
| Notes |
| 2007-11-02 08:16:13 | | | | | | | | | | | | | | | | | | | BUILDING PLAN REVIEW | | | PERMIT: 07090326 | | | ADD: 525 S. FLAGLER DR. #1501 | | | CONT: DESIGN CONTRACTING INC. | | | | | | TEL: (561)514-3004 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: 2ND 11/2/07 | | | ACTION: DENIED | | | | | | 1) --- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | **NO RESPONSE NOT ADDRESSED** | | | 2)2004 FBC EXISTING | | | 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE | | | OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO | | | SECTIONS 303, 304 AND 305 OF THIS CODE. | | | | | | 3)OK | | | | | | **NO RESPONSE NOT ADDRESSED** | | | 4)THE CLAIMED VALUATION OF THE BUILDING ALTERATION IS | | | TO LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS | | | AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE | | | STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, INTERIOR | | | FINISH, ARCHITECTURAL AND DESIGN FEES ETC EXCLUDING | | | LAND. FBC.108.3*. | | | | | | **NO RESPONSE NOT ADDRESSED** | | | 5)SHOW THE FRAMING DETAIL OF THE NEW DROP CEILING | | | INDICATING THE MATERIALS TO BE USED. | | | | | | **NO RESPONSE NOT ADDRESSED** | | | 6) 106.1.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION | | | THAT IS REQUIRED FOR RECORD KEEPING A) THE EDITION OF | | | THE CODE UNDER WHICH THE PROJECT IS DESIGNED. | | | B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE | | | PROVISIONS OF CHAPTER 3. | | | C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6, | | | TABLE 601. | | | D) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED | | | ------------------------------------- | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-09-20 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-09-20 |
Time |
10:31 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-09-20 |
Time |
06:48 |
Sent To |
|
|
| Notes |
| 2007-09-20 10:31:07 | | | | BUILDING PLAN REVIEW | | | PERMIT: 07090326 | | | ADD: 525 S. FLAGLER DR. #1501 | | | CONT: DESIGN CONTRACTING INC. | | | TEL: (561)514-3004 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: 1ST | | | ACTION: DENIED | | | | | | 1) --- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | 2)2004 FBC EXISTING | | | 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE | | | OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO | | | SECTIONS 303, 304 AND 305 OF THIS CODE. | | | | | | 3)THE DRAWINGS SHALL BE PREPARED BY A DESIGN | | | PROFESSIONAL.DUE TO THE WORK AND OCCUPANCY OF THE | | | BUILDING (GROUP R-2), THE DRAWINGS SHALL BE PREPARED BY | | | A DESIGN PROFESSIONAL WHO SHALL AFFIX HIS OR HER | | | OFFICIAL SEAL, SIGNATURE AND DATE ON SAID PLANS PER | | | FLORIDA STATUTES 481.229 (1) (B) AND (C). | | | | | | 4)THE CLAIMED VALUATION OF THE BUILDING ALTERATION IS | | | TO LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS | | | AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE | | | STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, INTERIOR | | | FINISH, ARCHITECTURAL AND DESIGN FEES ETC EXCLUDING | | | LAND. FBC.108.3*. | | | | | | 5)SHOW THE FRAMING DETAIL OF THE NEW DROP CEILING | | | INDICATING THE MATERIALS TO BE USED. | | | | | | 6) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION | | | THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE | | | OF OCCUPANCY: | | | A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT IS | | | DESIGNED. | | | B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE | | | PROVISIONS OF CHAPTER 3. | | | C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6, | | | TABLE 601. | | | D) THE OCCUPANT LOAD, SEE 1004. | | | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED | | | F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED. | | | ------------------------------------- | | | ) NUMBER OF UNITS | | | ) NUMBER OF FLOORS | | | ) NUMBER OF ROOMS | | | ) NUMBER OF BEDROOMS | | | ) SQ. FT. LIV SPACE/ FL | | | ) SQ. FT. FOOTPRINT | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2008-01-09 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-01-09 |
Time |
13:23 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-01-09 |
Time |
13:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2007-12-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-12-04 |
Time |
11:01 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-12-04 |
Time |
11:00 |
Sent To |
|
|
| Notes |
| 2007-12-04 11:01:11 | ** DENIED 3RD REVIEW ** | | | | | | ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE | | | STILL IN NEED OF ADDRESSING ALONG WITH SOME NEW | | | COMMENTS BASED ON REVISED PLANS/INFORMATION ETC. | | | SOME INFORMATION NOW SHOWN WAS NOT ON PREVIOUS PLANS | | | THEREFORE A REVIEW OF SOME OF THESE ITEMS COULD NOT | | | HAVE BEEN DONE. | | | | | | ** SOME OF THESE COMMENTS BELOW COULD HAVE BEEN | | | REDLINED HOWEVER NOT ALL. | | | | | | 1) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS; PLEASE | | | SEE MISSING CIRCUITING FOR SMOKE ALARMS AND ARC FAULT | | | REQUIRED. | | | PLEASE ALSO SEE MISSING CIRCUIT ON MASTER BEDROOM | | | RECEPTACLE. | | | 210.12, 408.4, 240.4 | | | FBC 106.3.5.1.2 | | | REQUESTED ON TWO PREVIOUS REVIEWS IN NOTES #3, #4 AND | | | #5. | | | | | | 2) NOTE: PLEASE SEE BEDROOM #2 AS STATED ON PREVIOUS | | | REVIEW NOTE # 7 WILL REQUIRE A LIGHT FIXTURE. THE | | | RESPONSE MENTIONS TO SEE NOT AT THE TOP OF PLAN PAGE. | | | THE NOTE ON PLANS IS FOR THE BALCONY LIGHTS. THE | | | BALCONY ON A MULTI-STORY BUILDING IS NOT REQUIRED TO | | | HAVE LIGHTING UNDER THE CURRENT CODE AS THERE IS NO | | | GROUND LEVEL ACCESS. THIS NOTE WAS ONLY FOR A FIXTURE | | | OF SOME TYPE IN BEDROOM #2. THIS COULD HAVE BEEN | | | REDLINED HOWEVER OTHER COMMENTS NEED TO BE ADDRESSED. | | | | | | 3) NOTE: PLEASE SEE THE CODE REFERENCED ON THE LOAD | | | CALCULATIONS IS NOT FROM THE 2005 NEC. THE CALCULATIONS | | | FOR EXISTING IS FROM 220.87 | | | THIS ALSO COULD HAVE BEEN REDLINED AS NOT SHOWING THE | | | CORRECT CODE HOWEVER SEE THE FOLLOWING COMMENT. | | | | | | 4) NOTE: PLEASE SEE THE LOAD CALCULATIONS STATE AND | | | SHOW A NEW STEAM UNIT HOWEVER NO INFORMATION IS SHOWN | | | ON PLANS, NO LOCATION, NO LISTING ON PANEL SCHEDULE, NO | | | OVER CURRENT PROTECTION, NO CONDUCTORS ETC. | | | PLEASE PROVIDE CUT SHEETS ON UNIT WHICH CONTAIN A | | | LISTING FROM A NATIONALLY RECOGNIZED TESTING | | | LABORATORY. | | | THIS UNIT WAS NOT ON PREVIOUS PLANS OR LOAD | | | CALCULATIONS. | | | 110.3, 90.7, 408.4, 310.16, 240.4 ETC | | | FBC 106.1.2, 106.3.5.1.2 | | | | | | | | | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2007-10-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-10-31 |
Time |
12:26 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-10-31 |
Time |
11:55 |
Sent To |
|
|
| Notes |
| 2007-10-31 12:26:39 | | | | ** DENIED 2ND REVIEW** | | | | | | ** PLEASE SEE NOTES FROM PREVIOUS REVIEW WHICH IS STILL | | | IN NEED OF ADDRESSING. | | | PLEASE SEE MOST OF THE NOTES BELOW WERE TAKEN FROM | | | PREVIOUS REVIEW. | | | | | | | | | 1) NOTE:THIS IS THE SAME NOTE: | | | PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH ARE | | | SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS | | | UNDER THE NEW CODES ADOPTED BY THE STATE. PLEASE SEE | | | THAT THIS SHALL INCLUDE 2006 REVISIONS TO THE 2004 FBC | | | FOR ALL TRADES AND THE 2005 NFPA-70. PLEASE KNOW THERE | | | ARE CHANGES IN THE FBC WHICH MAY AFFECT DESIGNS FOR ALL | | | TRADES. | | | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS | | | REVIEWER AT A MINIMUM. | | | 2004 FBC W/ 2006 REVISIONS | | | 2005 NFPA-70 | | | 2002 NFPA-72 | | | 2003 NFPA-101 | | | | | | 2) NOTE:THIS IS THE SAME NOTE: IN FACT PLEASE SEE | | | ELECTRICAL PLANS NOW CONTAIN A NOTE FROM THE ENGINEER | | | WHICH SPECIFICALLY STATES THE ELECTRICAL IS DONE BY | | | OTHER YET THIS SAME ENGINEER HAS SIGNED, DATED AND | | | SEALED PLANS. IF THE ELECTRICAL DESIGN IS NOT DONE BY | | | THIS ENGINEER, THEN ARE STATED IN THE FLORIDA STATUTES, | | | HE MAY NOT SIGN, DATE AND SEAL SAID PLANS. | | | PLEASE SEE THE *DESIGNER* AS LISTED ON PLANS* MUST MEET | | | THE EXCEPTIONSAS SPECIFIED IN THE FLORIDA STATUTES. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SEE NO DESIGN PROFESSIONAL IS PRINTED, SIGNED, | | | OR SIGNED, DATED AND SEALED ON PLANS. PLEASE SEE | | | MISSING INFORMATION FOR TITLE BLOCKS IF DONE BY A | | | DESIGN PROFESSIONAL UNDER FS 481, 471 PER FAC | | | 61G15-23.002, 61G1-16.004. | | | PLEASE KNOW EVEN WHEN MEETING ANY EXCEPTIONS UNDER FS | | | 471.003, OR 481.229 A DESIGNER OF RECORD IS STILL | | | REQUIRED TO PRINT NAME AND SIGN PLANS. | | | FBC 106.1.2, 106.3, 106.5 | | | | | | 3) NOTE:THIS IS THE SAME NOTE:IN FACT PLEASE SEE | | | THE PANEL SCHEDULE SUBMITTED IS NOT COMPLETE WITH THE | | | OVER CURRENT PROTECTION OR MINIMUM CONDUCTOR SIZES. | | | THIS WILL ALSO BE NOTED IN COMMENTS BELOW. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE COMPLETE ALL CIRCUITING ON PLANS FOR NEW AND | | | CORRELATE WITH A NEW REVISED PANEL SCHEDULE TO BE | | | SUBMITTED. THE EXISTING CIRCUITS ONLY NEED BE SHOWN | | | WITH AN *E*. | | | PLEASE SEE THE PANEL SCHEDULE IS TO INDICATE ALL NEW | | | DEDICATED CIRCUITS AS NOTED BELOW. | | | FBC 106.3.5.4 | | | 408.4,240.4,310.16,408.4 ETC | | | | | | 4) NOTE: PLEASE SEE THE SMOKE DEVICES WHICH ARE SHOWN | | | ARE BEING INDICATED AS *SD* FOR SMOKE DETECTORS. IF | | | THESE ARE TRUE SMOKE DETECTORS BY DEFINITION, PLEASE | | | INCLUDE THE FIRE ALARM PANEL, HORN DEVICES ETC. | | | IF SMOKE ALARMS, PLEASE CHANGE. | | | | | | ** PREVIOUS REVIEW NOTE **PLEASE SEE MISSING SMOKE | | | DETECTION DEVICES AS REQUIRED UNDER FBC R313, AND | | | NFPA-72 11.5.1.1, 11.8.3. THE PLANS NEED TO SHOW NEW OR | | | EXISTING SMOKE ALARM DEVICES. | | | 5) NOTE:ARC FAULT INDICATED ON PANEL SCHEDULE HOWEVER | | | AS CIRCUITING IS NOT ON PLANS FOR NEW ITEMS, THIS CAN | | | NOT BE VERIFIED. | | | PLEASE SEE 210.12 AND LIST. | | | | | | 6) NOTE:THIS NOTE REMAINS AS WIRE SIZE AND OVER | | | CURRENT PROTECTION ARE NOT SHOWN ON PANEL SCHEDULE. | | | PLEASE ALSO SEE CIRCUITING ON PLANS. | | | PLEASE BE SURE TO LIST THE REQUIRED DEDICATED | | | CIRCUIT(S) FOR BATH RECEPTACLE(S) PER 210.52D, | | | 210.11C3. | | | (MUST BE 20AMP AND #12) | | | | | | 7) NOTE:THIS WAS NOTE #8 ON PREVIOUS REVIEW. | | | PLEASE KNOW BEDRM #2 WILL REQUIRE SOME SORT OF LIGHT | | | FIXTURE FOR EGRESS INTO THIS ROOM PER 210.70, LS 101 | | | 7.8 | | | | | | 8) NOTE: THIS WAS NOTE #10 ON PREVIOUS REVIEW. | | | PLEASE SEE MISSING DEDICATED LOAD FOR NEW REFRIGERATOR | | | ON LOAD CALCULATIONS. | | | 220. | | | (LIST ON PANEL SCHEDULE). | | | | | | 9) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO | | | REPEAT COMMENTS FOR CODE COMPLIANCE. | | | THIS IS ONLY A NOTICE GIVEN AT THIS TIME. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | | DELAYS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-09-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-09-15 |
Time |
11:55 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-09-15 |
Time |
11:35 |
Sent To |
|
|
| Notes |
| 2007-09-15 11:55:50 | 2007-09-15 11:55:50 | | | | | | ** DENIED ** | | | | | | 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS | | | WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES | | | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. | | | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO | | | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. | | | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY | | | AFFECT DESIGNS FOR ALL TRADES. | | | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS | | | REVIEWER AT A MINIMUM. | | | 2004 FBC W/ 2006 REVISIONS | | | 2005 NFPA-70 | | | 2002 NFPA-72 | | | 2003 NFPA-101 | | | | | | 2) NOTE: PLEASE SEE NO DESIGN PROFESSIONAL IS PRINTED, | | | SIGNED, OR SIGNED, DATED AND SEALED ON PLANS. PLEASE | | | SEE MISSING INFORMATION FOR TITLE BLOCKS IF DONE BY A | | | DESIGN PROFESSIONAL UNDER FS 481, 471 PER FAC | | | 61G15-23.002, 61G1-16.004. | | | PLEASE KNOW EVEN WHEN MEETING ANY EXCEPTIONS UNDER FS | | | 471.003, OR 481.229 A DESIGNER OF RECORD IS STILL | | | REQUIRED TO PRINT NAME AND SIGN PLANS. | | | FBC 106.1.2, 106.3, 106.5 | | | | | | 3) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS FOR | | | NEW AND CORRELATE WITH A NEW REVISED PANEL SCHEDULE TO | | | BE SUBMITTED. THE EXISTING CIRCUITS ONLY NEED BE SHOWN | | | WITH AN *E*. | | | PLEASE SEE THE PANEL SCHEDULE IS TO INDICATE ALL NEW | | | DEDICATED CIRCUITS AS NOTED BELOW. | | | FBC 106.3.5.4 | | | 408.4,240.4,310.16,408.4 ETC | | | | | | 4) NOTE: PLEASE SEE MISSING SMOKE DETECTION DEVICES AS | | | REQUIRED UNDER FBC R313, AND NFPA-72 11.5.1.1, 11.8.3. | | | THE PLANS NEED TO SHOW NEW OR EXISTING SMOKE ALARM | | | DEVICES. | | | **210.12 IN NEXT COMMENT APPLIES ** | | | | | | 5) NOTE: PLEASE BE SURE TO LIST THE REQUIRED ARC FAULT | | | PROTECTED CIRCUITS PER 210.12 OF THE 2005 NEC. | | | | | | 6) NOTE: PLEASE BE SURE TO LIST THE REQUIRED DEDICATED | | | CIRCUIT(S) FOR BATH RECEPTACLE(S) PER 210.52D, | | | 210.11C3. | | | (MUST BE 20AMP AND #12) | | | | | | 7) NOTE: PLEASE SEE MISSING GFI PROTECTION FOR SPA | | | TUB/JACUZZI TUB PER 680.71 | | | (LIST ON PANEL SCHEDULE) | | | | | | 8) NOTE: PLEASE KNOW BEDRM #2 WILL REQUIRE SOME SORT OF | | | LIGHT FIXTURE FOR EGRESS INTO THIS ROOM PER 210.70, LS | | | 101 7.8 | | | | | | 9) NOTE: PLEASE KNOW THESE PLANS MAY BE REFERENCE FOR | | | LOW VOLTAGE PERMITS; HOWEVER PLEASE KNOW THE LV PERMIT | | | IS SEPARATE FROM THE ELECTRICAL PERMIT. (SPKRS, TV, AND | | | PHONE MAY BE ON ONE LV PERMIT) | | | THIS IS ONLY NOTED AT THIS TIME FOR INFORMATION SO THIS | | | DOES NOT LEAD TO ANY CONFUSION AT A LATER DATE AT | | | INSPECTION(S) TIME. | | | | | | 10) NOTE: PLEASE SEE MISSING DEDICATED LOAD FOR NEW | | | REFRIGERATOR ON LOAD CALCULATIONS. | | | 220. | | | (LIST ON PANEL SCHEDULE). | | | | | | 11) NOTE: PLEASE REVISE UNIT/SUITE # ON PLANS TO | | | CORRELATE WITH SUITE/UNIT # IN OUR SYSTEM AS SSIGNED | | | ADDRESS. (UNIT 1501). | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2008-01-10 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-01-10 |
Time |
13:42 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-01-10 |
Time |
13:27 |
Sent To |
|
|
| Notes |
| 2008-01-10 13:42:22 | *****APPROVED***** | | | | | | THE COMMENTS TAKEN FROM THE PREVIOUS FIRE PLAN REVIEW | | | HAVE BEEN ADDRESSED;PLAN SHEETS AB 1 OF 4 AND EL 3 OF | | | 4 WERE STAMPED, INITIALED, AND DATED. | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2007-12-17 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-12-17 |
Time |
11:27 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-12-17 |
Time |
11:10 |
Sent To |
|
|
| Notes |
| 2007-12-17 11:26:23 | *****DENIED***** | | | | | | THE FOLLOWINGS COMMENTS TAKEN FROM THE PREVIOUS FIRE | | | PLAN REVIEW STILL NEED TO BE ADDRESSED: | | | | | | 2.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED. | | | | | | 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 4.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL | | | BE REMOVED FROM THE SITE DAILY OR MORE FREQUENTLY AS | | | NECESSARY FOR SAFE OPERATION. | | | | | | 5.THE REMOVAL OF OLD AND/OR THE STOCKING OF NEW | | | BUILDING MATERIALS & SUPPLIES SHALL NOT HINDER OR | | | INTERFERE WITH ACCESS TO OR EGRESS FROM THE OTHER | | | TENANT SPACES ON THE 15TH FLOOR OR THE BUILDING. | | | | | | 7.SPECIFY THE NEW INTERIOR WALL AND CEILING FINISH | | | MATERIAL IN TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | | | 8.PLEASE INDICATE IF THE BUILDING IS SPRINKLERED AND | | | IF SO, WILL THE SCOPE WORK CAUSE ANY SPRINKLER | | | MODIFICATIONS.BE ADVISED THAT SEPARATE PLANS AND | | | PERMIT WILL BE REQUIRED FOR SPRINKLER SYSTEM REMODEL. | | | | | | 9.PLEASE INDICATE IF THE BUILDING/RESIDENCE HAS A | | | FIRE ALARM SYSTEM AND IF SO, WILL THE SCOPE OF WORK | | | CAUSE ANY FIRE ALARM DEVICE(S) MODIFICATIONS.BE | | | ADVISED THAT SEPARATE PLANS AND PERMIT WILL BE REQUIRED | | | FOR THE FIRE ALARM REMODEL. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS | | | ADDRESSED.PLEASE BE ADVISED THAT THE HAND WRITTEN | | | RESPONSES ON THE PLANS ARE NOT ACCEPTABLE!!!!! | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2007-11-03 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-11-03 |
Time |
17:18 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-11-03 |
Time |
17:00 |
Sent To |
|
|
| Notes |
| 2007-11-03 17:17:58 | *****DENIED***** | | | | | | THE FOLLOWINGS COMMENTS TAKEN FROM THE PREVIOUS FIRE | | | PLAN REVIEW STILL NEED TO BE ADDRESSED: | | | | | | 2.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED. | | | | | | 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 4.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL | | | BE REMOVED FROM THE SITE DAILY OR MORE FREQUENTLY AS | | | NECESSARY FOR SAFE OPERATION. | | | | | | 5.THE REMOVAL OF OLD AND/OR THE STOCKING OF NEW | | | BUILDING MATERIALS & SUPPLIES SHALL NOT HINDER OR | | | INTERFERE WITH ACCESS TO OR EGRESS FROM THE OTHER | | | TENANT SPACES ON THE 15TH FLOOR OR THE BUILDING. | | | | | | 6.PLEASE SHOW THE LOCATION OF THE SMOKE ALARMS (SA) | | | IN THIS RESIDENCE.PLEASE BE ADVISED THAT SMOKE ALARMS | | | (SA)SOUND ONLY WITHIN AN INDIVIDUAL DWELLING UNIT, | | | WHEREAS SMOKE DETECTORS (SD) ARE TIED INTO THE | | | BUILDING'S FIRE ALARM SYSTEM. | | | | | | 7.SPECIFY THE NEW INTERIOR WALL AND CEILING FINISH | | | MATERIAL IN TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | | | 8.PLEASE INDICATE IF THE BUILDING IS SPRINKLERED AND | | | IF SO, WILL THE SCOPE WORK CAUSE ANY SPRINKLER | | | MODIFICATIONS.BE ADVISED THAT SEPARATE PLANS AND | | | PERMIT WILL BE REQUIRED FOR SPRINKLER SYSTEM REMODEL. | | | | | | 9.PLEASE INDICATE IF THE BUILDING/RESIDENCE HAS A | | | FIRE ALARM SYSTEM AND IF SO, WILL THE SCOPE OF WORK | | | CAUSE ANY FIRE ALARM DEVICE(S) MODIFICATIONS.BE | | | ADVISED THAT SEPARATE PLANS AND PERMIT WILL BE REQUIRED | | | FOR THE FIRE ALARM REMODEL. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS | | | ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2007-10-04 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-10-04 |
Time |
15:51 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-10-04 |
Time |
15:37 |
Sent To |
|
|
| Notes |
| 2007-10-04 15:44:33 | *****DENIED***** | | | | | | | | | 1.THE ACTUAL ADDRESS OF THE PROJECT SITE SHALL BE IN | | | THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.BE | | | ADVISED THAT THIS RESIDENCE IS IN THE JURISDICTION OF | | | WEST PALM BEACH, FLORIDA 33401.THE SUITE NUMBER SHOWN | | | ON THE PLAN AS 15A DO NOT CORRELATE WITH WHAT IS | | | INDICATED IN THE CITY'S PERMITTING SYSTEM WHICH IS | | | 1501.PLEASE CLARIFY OR AMEND. | | | | | | 2.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED. | | | | | | 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 4.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL | | | BE REMOVED FROM THE SITE DAILY OR MORE FREQUENTLY AS | | | NECESSARY FOR SAFE OPERATION. | | | | | | 5.THE REMOVAL OF OLD AND/OR THE STOCKING OF NEW | | | BUILDING MATERIALS & SUPPLIES SHALL NOT HINDER OR | | | INTERFERE WITH ACCESS TO OR EGRESS FROM THE OTHER | | | TENANT SPACES ON THE 15TH FLOOR OR THE BUILDING. | | | | | | 6.PLEASE SHOW THE LOCATION OF THE SMOKE ALARMS (SA) | | | IN THIS RESIDNCE. | | | | | | 7.SPECIFY THE NEW INTERIOR WALL AND CEILING FINISH | | | MATERIAL IN TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | | | 8.PLEASE INDICATE IF THE BUILDING IS SPRINKLERED AND | | | IF SO, WILL THE SCOPE WORK CAUSE ANY SPRINKLER | | | MODIFICATIONS.BE ADVISED THAT SEPARATE PLANS AND | | | PERMIT WILL BE REQUIRED FOR SPRINKLER SYSTEM REMODEL. | | | | | | 9.PLEASE INDICATE IF THE BUILDING/RESIDENCE HAS A | | | FIRE ALARM SYSTEM AND IF SO, WILL THE SCOPE OF WORK | | | CAUSE ANY FIRE ALARM DEVICE(S) MODIFICATIONS.BE | | | ADVISED THAT SEPARATE PLANS AND PERMIT WILL BE REQUIRED | | | FOR THE FIRE ALARM REMODEL. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS | | | ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2008-01-09 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-01-09 |
Time |
08:44 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-01-09 |
Time |
08:44 |
Sent To |
|
|
| Notes |
| 2008-01-09 08:48:40 | TO "BOB"#14 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-11-29 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-11-29 |
Time |
11:47 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-11-29 |
Time |
11:47 |
Sent To |
|
|
| Notes |
| 2007-12-03 16:48:06 | TO "BOB"#12 | | 2007-11-29 11:56:29 | WAITING FOR "BOB" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-10-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-10-23 |
Time |
12:34 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-10-23 |
Time |
12:34 |
Sent To |
|
|
| Notes |
| 2007-10-30 14:41:43 | TO "BOB"#2 | | 2007-10-23 12:34:16 | WAITING FOR "BOB" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-10-04 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-10-04 |
Time |
15:37 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-09-12 |
Time |
15:06 |
Sent To |
|
|
| Notes |
| 2007-09-15 11:35:47 | TO BOB SPACE #14, DVP. | | 2007-09-12 15:07:19 | WAITING FOR "BOB" |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2008-01-09 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-01-09 |
Time |
13:51 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2008-01-09 |
Time |
13:51 |
Sent To |
|
|
| Notes |
| 2008-01-09 13:51:43 | TWO BATHROOM EXHAUST FANS ONLY. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2007-12-05 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-12-05 |
Time |
10:49 |
Rev Time |
0.25 |
| Received By |
tgordon |
Date |
2007-12-05 |
Time |
10:49 |
Sent To |
|
|
| Notes |
| 2007-12-05 10:50:38 | TWO BATHROOM EXHAUST FANS ONLY. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2007-10-31 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-10-31 |
Time |
14:16 |
Rev Time |
0.25 |
| Received By |
tgordon |
Date |
2007-10-31 |
Time |
14:15 |
Sent To |
|
|
| Notes |
| 2007-10-31 14:16:43 | TWO BATHROOM EXHAUST FAN ONLY. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2007-09-17 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-09-17 |
Time |
10:39 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2007-09-17 |
Time |
10:39 |
Sent To |
|
|
| Notes |
| 2007-09-17 10:40:40 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) SEE ELECTRICAL REVIEW NOTES 1 AND 2, PLEASE | | | CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2008-01-10 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2008-01-10 |
Time |
08:14 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2008-01-10 |
Time |
08:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2007-12-15 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-12-15 |
Time |
06:35 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-12-15 |
Time |
06:35 |
Sent To |
|
|
| Notes |
| 2007-12-15 07:04:57 | DENIED; | | | 1. HAND WRITEN NOTES ON PLANS NOT EXCEPTABLE. | | | 2. EXISTING CHASES CAN NOT BE USED FOR FLOOR SPACE IN | | | APARTMENT. MASTER SHOWER AREA, AND BATH 2 NEXT TO THE | | | LAVATORY. THESE CHASES ARE USED FOR PLUMBING | | | ,ELECTRICAL, AND MECHANICAL . THIS IS COMMON AREA NOT | | | FOR UNIT USE. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2007-11-09 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-11-09 |
Time |
09:17 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-11-09 |
Time |
09:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-10-02 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-10-02 |
Time |
09:40 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-10-02 |
Time |
09:40 |
Sent To |
|
|
| Notes |
| 2007-10-02 09:45:36 | DENIED; | | | SEE ELECTRICAL NOTES 1 AND 2. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2007-11-09 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-09-21 |
Time |
14:24 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-09-21 |
Time |
14:24 |
Sent To |
|
|
| Notes |
| 2007-09-21 14:24:56 | *ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK | | | DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE. |
|
|