Plan Review Details - Permit 07090320
Plan Review Stops For Permit 07090320
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-10-31 Cont ID  
Sent By mjacobs Date 2007-10-31 Time 15:45 Rev Time 0.00
Received By mjacobs Date 2007-10-31 Time 13:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-21 Cont ID  
Sent By mjacobs Date 2007-09-21 Time 05:45 Rev Time 0.00
Received By mjacobs Date 2007-09-20 Time 11:33 Sent To  
Notes
2007-09-20 14:05:30BUILDING PLAN REVIEW
 PERMIT: 07090320
 ADD: 1649 FORUM PLACE
 CONT: LONGMIRE BUILDING CORP.
 TEL: (561)753-3533
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1) - VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
 A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
 . -------------------------------------
 ) NUMBER OF UNITS
 ) NUMBER OF FLOORS
 ) NUMBER OF ROOMS
 ) SQ. FT. FOOTPRINT
  
 3)TABLE 803.5 MINIMUM INTERIOR FINISH CLASSIFICATION;
 PROVIDE INFORMATION BASED ON INTERIOR FINISH
 REQUIREMENTS BASED ON OCCUPANCY.
  
  
  
 4)SINKS:
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL BE MOUNTED WITH
 THE COUNTER NO HIGHER THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH
 30" WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH
 SINKS.
 11-4.24.5 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES
 (760 MM BY 1219 MM) COMPLYING WITH SECTION 11-4.2.4
 SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW FORWARD
 APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN
 ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF 19
 INCHES (485 MM) UNDERNEATH THE SINK. THE DOORS IN FRONT
 OF THE SINK SHALL BE REMOVED TO PROVIDE THE FORWARD
 APPROACH.
  
 5)2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 6)SHEET 3.1. THE DRESSING ROOM SHALL HAVE A CLEAR
 FLOOR SPACE ALLOWING A PERSON USING A WHEELCHAIR TO
 MAKE A 180-DEGREE TURN.
  
 7) SHEET 3.1. THE DRESSING ROOM SHALL HAVE 24 INCHES BY
 48 INCHES BENCH FIXED TO THE WALL ALONG THE LONGER
 DIMENSION. THE BENCH SHALL BE MOUNTED 17 INCHES TO 19
 INCHES ABOVE THE FINISH FLOOR. FBC 11-4.35.4. THE BENCH
 SHALL NOT PROJECT INTO THE CLEAR FLOOR SPACE.
  
 8)THE RECEPTIONIST DESK SHALL MEET THE REQUIREMENTS
 OF FBC 11-7.2(2) (I). SHOW COMPLIANCE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-11-14 Cont ID  
Sent By jleahy Date 2007-11-14 Time 16:30 Rev Time 0.45
Received By jleahy Date 2007-11-14 Time 16:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-10-26 Cont ID  
Sent By dpalmer Date 2007-10-26 Time 09:06 Rev Time 0.00
Received By dpalmer Date 2007-10-26 Time 08:27 Sent To  
Notes
2007-10-26 09:06:23 
  
  
  
 *** DENIED 2ND REVIEW ***
  
 1) NOTE: PLEASE SEE THE LIGHTING ENERGY CALCULATIONS
 SUBMITTED ATTACHED TO PLANS INDICATE A METHOD *C* AND
 METHOD AS SHOWN ON PLANS IS SPACE BY SPACE BY SPACE
 METHOD *B*.
 THIS SPACE IS BEING SHOWN AS *RETAIL* IN THE
 CALCULATIONS, HOWEVER BY DEFINITIONS IN THE FBC FOR
 OCCUPANCIES, THE AREA IS BASED AS A BUSINESS OCCUPANCY.
 THE CLOSEST SPACE WOULD BE OFFICE. THERE ARE ADDITIONAL
 WATTAGES PERMITTED FOR SOME ITEM AS LISTED IN
 13-415.2.B.1, HOWEVER THE WATTAGE AS SHOWN ON PLANS
 EXCEEDS THAT AS PERMITTED.
 PLEASE ADJUST FIXTURES/CALCULATIONS. PLEASE PROVIDE A
 MORE DETAIL BREAKDOWN FOR ANY ADDITIONAL WATTAGE AS
 PERMITTED. BASED ON THE WATTAGES SHOWN THESE DO NOT
 MEET 13-415.2, TABLES *B* OR *C*.
 PLEASE CALL TO GO OVER.
  
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-09-15 Cont ID  
Sent By dpalmer Date 2007-09-15 Time 11:25 Rev Time 0.00
Received By dpalmer Date 2007-09-15 Time 10:34 Sent To  
Notes
2007-09-15 11:26:152007-09-15 11:26:15
  
 ** DENIED **
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 2) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS AS
 THERE ARE SOME LIGHTING FIXTURES WHICH DO NOT SHOW
 CIRCUITING OR CONTROLS.
 FBC 106.3.5.4
 240.4,310.16,408.4 ETC
  
 3) NOTE: PLEASE SUBMIT A FIXTURE LEGEND, INCLUDING
 INFORMATION FOR NEW AND EXISTING FIXTURES.
 PLEASE SEE 13-415.2, 13-415.1.C.
 PLEASE SEE THE LIGHTING LEVELS FOR TRACK LIGHTING IS
 REQUIRED TO MEET 13-415.2.ABC.1.1, 13-415.2.ABC.1.2.
 (SEE PARAGRAPH (3) FOR LINE VOLTAGE TRACK).
 THIS IS REQUIRED TO BE THE LARGER OF THE LOADS BASED ON
 LINEAR FEET OF TRACK OR FIXTURE WATTAGE WHICH EVER IS
 GREATER.
 THE WATTAGE ON TRACK FIXTURES SEEM LOW, HOWEVER IN
 EITHER CASE THE LINEAR WATTAGE IS GREATER.
 PLEASE SE METHOD C AS SUBMITTED IS EXCEEDED FOR
 INTERIOR LIGHTING ALLOWANCES BASED ON PLANS AND
 LIGHTING AS SUBMITTED.
  
 4) NOTE: PLEASE SEE NO LIGHTING CONTROLS AS REQUIRED
 PER 13-415.1.ABC.1.1, .1.2 AND .1.3 IS SUBMITTED. THE
 PLANS INDICATE SOME SORT OF LIGHTING CONTACTOR LOCATED
 BY THE PANEL HOWEVER DEVICES, OVER RIDES, TIMES, OVER
 RIDE TIMES, ANY OCCUPANCY SENSORS OR TIMER INFORMATION
 WERE SUBMITTED FOR REVIEW. 13-101.
  
 5) NOTE: PLEASE SEE MISSING WINDOW RECEPTACLES WHICH
 WILL BE REQUIRED PER 210.62, 90.4 AND LOADS PER
 220.43.
  
 6) NOTE: PLEASE SEE TRACK LIGHTING CALCULATIONS ON LOAD
 CALCULATIONS NEED TO BE SHOWN PER 220.43.
  
 7) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING
 CONDUCTOR FROM MAIN DISCONNECT TO THE NEW SUB PANEL *B*
 AND FROM *B* TO *C*.
 250.110, 250.24, 250.122, ETC
  
 8) NOTE: RISER INDICATES NEW 300AMP SERVICE, WHAT IS
 THE SIZE OF THE EXISTING SERVICE FOR THIS SPACE? WHAT
 IS THE LOAD ON THE EXISTING SERVICE GUTTER CONDUCTORS
 WITH NEW LOAD NOW ADDED?
 NOT ENOUGH INFORMATION WAS GIVEN FOR NEW AND EXISTING
 LOADS.
 220, 240, 310.16, 215.5,
 FBC 106.3.5.1.2
  
 9) NOTE: PLEASE SEE 422.13 AS THE LOAD FOR WATER HEATER
 IS NOW CONSIDERED A CONTINUOUS LOAD UNDER THE 2005 NEC
 WHICH REQUIRES THIS LOAD TO BE SHOWN AT 125%.
  
 10) NOTE: PLEASE SEE 220.54 AND VERIFY LOAD FOR THE
 DRYER AS SHOWN. PLEASE SEE THIS IS BEING SHOWN ON A
 20AMP CIRCUIT WITH LOAD AT 19AMPS?
  
 11) NOTE: PLEASE SEE CIRCUITING ON PLANS NEEDS TO
 COORDINATE WITH THE PANEL SCHEDULES.
 PLEASE SEE THE DISPOSAL IS SHOWN TO CIRCUIT B-36,
 HOWEVER THIS IS THE SIGN CIRCUIT?
 FBC 106.1.2, 106.3.5.1.2,
 NEC 408.4
  
 12) NOTE: PLEASE SEE COMMENTS FROM BUILDING AND FIRE
 FOR ANY POSSIBLE HAZARDOUS CHEMICAL STORAGE/MIXING
 AREAS WHICH MAY BE OF CONCERN FOR LIFE SAFETY, ETC.
 THIS MAY AFFECT ELECTRICAL PLANS AND DESIGN IN
 GENERAL.
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-11-02 Cont ID  
Sent By mwennerg Date 2007-11-02 Time 10:31 Rev Time 0.00
Received By mwennerg Date 2007-11-02 Time 10:31 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-10-04 Cont ID  
Sent By mawillia Date 2007-10-04 Time 15:10 Rev Time 0.00
Received By mawillia Date 2007-10-04 Time 14:38 Sent To  
Notes
2007-10-04 15:10:03*****DENIED*****
  
  
 1.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 2.PLEASE INDICATE THE PREVIOUS OCCUPANCY TYPE AS WELL
 AS THE PROJECTED OCCUPANCY TYPE.
  
 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 4.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE DAILY OR MORE FREQUENTLY AS
 NECESSARY FOR SAFE OPERATION.
  
 5.THE REMOVAL OF OLD AND/OR THE STOCKING OF NEW
 BUILDING MATERIALS & SUPPLIES SHALL NOT HINDER OR
 INTERFERE WITH ACCESS TO OR EGRESS FROM THE OTHER
 TENANT SPACES ON THE 12TH FLOOR OR THE BUILDING.
  
 6.PLEASE SHOW THE LOCATION OF THE EXIT LIGHTS,
 EMERGENCY LIGHTS, AND LOCATION OF THE 2A:10BC RATED
 FIRE EXTINGUISHER FOR THIS TENANT SPACE.
  
 7.SPECIFY THE NEW INTERIOR WALL AND CEILING FINISH
 MATERIAL IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 8.PLEASE INDICATE IF THE BUILDING IS SPRINKLERED AND
 IF SO, WILL THE SCOPE WORK CAUSE ANY SPRINKLER
 MODIFICATIONS.BE ADVISED THAT SEPARATE PLANS AND
 PERMIT WILL BE REQUIRED FOR SPRINKLER SYSTEM REMODEL.
  
 9.PLEASE INDICATE IF THE BUILDING/TENANT SPACE HAS A
 FIRE ALARM SYSTEM AND IF SO, WILL THE SCOPE OF WORK
 CAUSE ANY FIRE ALARM DEVICE(S) MODIFICATIONS.BE
 ADVISED THAT SEPARATE PLANS AND PERMIT WILL BE REQUIRED
 FOR THE FIRE ALARM REMODEL.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-01-24 Cont ID  
Sent By adarroug Date 2008-01-24 Time 11:35 Rev Time 0.00
Received By adarroug Date 2008-01-24 Time 11:35 Sent To M
Notes
2008-01-24 11:35:52TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-11-08 Cont ID  
Sent By adarroug Date 2007-11-08 Time 11:44 Rev Time 0.00
Received By adarroug Date 2007-11-08 Time 11:44 Sent To  
Notes
2007-11-13 08:56:06TO "BOB"#2
2007-11-08 11:44:59WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-19 Cont ID  
Sent By adarroug Date 2007-10-19 Time 11:44 Rev Time 0.00
Received By adarroug Date 2007-10-19 Time 11:44 Sent To  
Notes
2007-10-25 12:52:50TO "BOB"#8
2007-10-19 11:45:09WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-04 Cont ID  
Sent By mawillia Date 2007-10-04 Time 14:38 Rev Time 0.00
Received By mawillia Date 2007-09-12 Time 12:45 Sent To  
Notes
2007-09-15 10:36:43TO BOB SPACE #13, DVP.
2007-09-12 12:56:46WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-01-24 Cont ID  
Sent By tgordon Date 2008-01-24 Time 14:07 Rev Time 0.30
Received By tgordon Date 2008-01-24 Time 14:06 Sent To  
Notes
2008-01-24 14:07:51REVISION TO MECHANICAL PLAN PAGE M1.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-11-13 Cont ID  
Sent By tgordon Date 2007-11-13 Time 15:21 Rev Time 0.20
Received By tgordon Date 2007-11-13 Time 15:21 Sent To  
Notes
2007-11-13 15:21:57RE-STAMP PAGE ME1.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-10-26 Cont ID  
Sent By tgordon Date 2007-10-26 Time 12:20 Rev Time 0.30
Received By tgordon Date 2007-10-26 Time 12:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-09-17 Cont ID  
Sent By tgordon Date 2007-09-17 Time 11:17 Rev Time 0.30
Received By tgordon Date 2007-09-17 Time 11:16 Sent To  
Notes
2007-09-17 11:50:32PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) NEED TO SHOW ON MECHANICAL PLANS PAGE M1 THE SUPPLY
 AIR CFM'S AT THE GRILL OVER STYLING "B".
  
 2) SHOW RETURN AIR GRILLS ON MECHANICAL PLANS TO COMPLY
 WITH MECH. 601.4.
  
 4) PLEASE CHECK AND STATE (CODE WISE) WHERE THE OUTDOOR
 AIR CALCULATIONS ARE FROM ON PLAN ME1. SEE MECH. TABLE
 403.3 FOR BEAUTY SHOP AND NAIL SALON. 25 PERSONS PER
 1000 SQUARE FEET 2500 SQ.FT. / 1000 =2.5 X 25 =62.5
 PERSONS AT 25 CFM'S EACH =1562.5. AND YOU MAY ALSO
 CALCULATE NAIL SALON AT 4 SEATS X 25 CFM'S =100 CFM'S.
 ALSO SEE MECH. 403.3 THE OCCUPANT LOAD UTILIZED FOR
 DESIGN OF THE VENTILATION SYSTEM SHALL NOT BE LESS THAN
 THE NUMBER DETERMINED FROM THE ESTIMATED MAXIMUM
 OCCUPANT LOAD RATE INDICATED IN TABLE 403.3 .
  
 ** 403.4 ASHRAE 62 ALTERNATIVE.IN LIEU OF COMPLIANCE
 WITH SECTION 403.1 THROUGH SECTION 403.3 , MECHANICAL
 VENTILATION MAY BE IMPLEMENTED IN COMPLIANCE WITH
 ASHRAE 62 INCLUDING APPROVED ADDENDA.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-11-07 Cont ID  
Sent By jleech Date 2007-11-07 Time 09:46 Rev Time 0.00
Received By jleech Date 2007-11-07 Time 09:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-10-02 Cont ID  
Sent By jleech Date 2007-10-02 Time 08:47 Rev Time 0.00
Received By jleech Date 2007-10-02 Time 08:47 Sent To  
Notes
2007-10-02 09:18:06DENIED;
 1.LIST THE ALTERATION LEVEL, TO COMPLY WITH THE FBC
 EXISTING BUILDING CODE.
 2. BREAK SINK SHALL COMPLY WITH FBC BUILDING CHAPTER 11
 SECTIONS 11-4.24.1 THRU 11-4.24.7.
 11-4.24.2 HEIGHT
 11-4.24.3 KNEE CLEARANCE, (NO DOORS IN CLEAR
 FLOOR SPACE)
 11-4.24.4 SINK DEPTH 6 1/2" MAX
 11-4.24.5 CLEAR FLOOR SPACE, ( SHOW ON PLANS)
 11-4.24.6 RAP EXPOSED PIPES.
 11-4.24.7 FAUCET, SPEC TYPE TO BE USED ON
 PLANS.
 3. SIZE ALL PIPES ON THE SANITARY ISOMETRIC.
 4. WATER SEVICE IS NOT LARGE ENOUGH SEE FBC PLUMBING
 TABLE 603.1. TOTAL FU'S IS 30.
 5. DRESSING ROOM TO COMPLY WITH FBC BUILDING CHAPTER
 11, SECTION 11-4.35.2 THRU 11-4.35.5
 11-4.35.2 CLEAR FLOOR SPACE OK
 11-4.35.3 DOORS OK
 11-4.35.4 BENCH REQUIRED. ( SHOW DETAIL WITH
 ALL REQUIRED MEASUREMENTS)
 11-4.35.5 MIRROR REQUIRED. ( SHOW DETAIL)
 6. SHOW SIZE OF WATER HEATERON PLANS.
 7. SHOWTYPE OF THERMAL EXPANSION PER FBC PLUMBING
 SECTION607.3.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status N Date 2007-09-21 Cont ID  
Sent By choops Date 2007-09-21 Time 14:23 Rev Time 0.00
Received By choops Date 2007-09-21 Time 14:23 Sent To  
Notes
2007-09-21 14:23:32*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.