| 2007-09-15 11:26:15 | 2007-09-15 11:26:15 |
| | |
| | ** DENIED ** |
| | |
| | 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS |
| | WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES |
| | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | 2) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS AS |
| | THERE ARE SOME LIGHTING FIXTURES WHICH DO NOT SHOW |
| | CIRCUITING OR CONTROLS. |
| | FBC 106.3.5.4 |
| | 240.4,310.16,408.4 ETC |
| | |
| | 3) NOTE: PLEASE SUBMIT A FIXTURE LEGEND, INCLUDING |
| | INFORMATION FOR NEW AND EXISTING FIXTURES. |
| | PLEASE SEE 13-415.2, 13-415.1.C. |
| | PLEASE SEE THE LIGHTING LEVELS FOR TRACK LIGHTING IS |
| | REQUIRED TO MEET 13-415.2.ABC.1.1, 13-415.2.ABC.1.2. |
| | (SEE PARAGRAPH (3) FOR LINE VOLTAGE TRACK). |
| | THIS IS REQUIRED TO BE THE LARGER OF THE LOADS BASED ON |
| | LINEAR FEET OF TRACK OR FIXTURE WATTAGE WHICH EVER IS |
| | GREATER. |
| | THE WATTAGE ON TRACK FIXTURES SEEM LOW, HOWEVER IN |
| | EITHER CASE THE LINEAR WATTAGE IS GREATER. |
| | PLEASE SE METHOD C AS SUBMITTED IS EXCEEDED FOR |
| | INTERIOR LIGHTING ALLOWANCES BASED ON PLANS AND |
| | LIGHTING AS SUBMITTED. |
| | |
| | 4) NOTE: PLEASE SEE NO LIGHTING CONTROLS AS REQUIRED |
| | PER 13-415.1.ABC.1.1, .1.2 AND .1.3 IS SUBMITTED. THE |
| | PLANS INDICATE SOME SORT OF LIGHTING CONTACTOR LOCATED |
| | BY THE PANEL HOWEVER DEVICES, OVER RIDES, TIMES, OVER |
| | RIDE TIMES, ANY OCCUPANCY SENSORS OR TIMER INFORMATION |
| | WERE SUBMITTED FOR REVIEW. 13-101. |
| | |
| | 5) NOTE: PLEASE SEE MISSING WINDOW RECEPTACLES WHICH |
| | WILL BE REQUIRED PER 210.62, 90.4 AND LOADS PER |
| | 220.43. |
| | |
| | 6) NOTE: PLEASE SEE TRACK LIGHTING CALCULATIONS ON LOAD |
| | CALCULATIONS NEED TO BE SHOWN PER 220.43. |
| | |
| | 7) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING |
| | CONDUCTOR FROM MAIN DISCONNECT TO THE NEW SUB PANEL *B* |
| | AND FROM *B* TO *C*. |
| | 250.110, 250.24, 250.122, ETC |
| | |
| | 8) NOTE: RISER INDICATES NEW 300AMP SERVICE, WHAT IS |
| | THE SIZE OF THE EXISTING SERVICE FOR THIS SPACE? WHAT |
| | IS THE LOAD ON THE EXISTING SERVICE GUTTER CONDUCTORS |
| | WITH NEW LOAD NOW ADDED? |
| | NOT ENOUGH INFORMATION WAS GIVEN FOR NEW AND EXISTING |
| | LOADS. |
| | 220, 240, 310.16, 215.5, |
| | FBC 106.3.5.1.2 |
| | |
| | 9) NOTE: PLEASE SEE 422.13 AS THE LOAD FOR WATER HEATER |
| | IS NOW CONSIDERED A CONTINUOUS LOAD UNDER THE 2005 NEC |
| | WHICH REQUIRES THIS LOAD TO BE SHOWN AT 125%. |
| | |
| | 10) NOTE: PLEASE SEE 220.54 AND VERIFY LOAD FOR THE |
| | DRYER AS SHOWN. PLEASE SEE THIS IS BEING SHOWN ON A |
| | 20AMP CIRCUIT WITH LOAD AT 19AMPS? |
| | |
| | 11) NOTE: PLEASE SEE CIRCUITING ON PLANS NEEDS TO |
| | COORDINATE WITH THE PANEL SCHEDULES. |
| | PLEASE SEE THE DISPOSAL IS SHOWN TO CIRCUIT B-36, |
| | HOWEVER THIS IS THE SIGN CIRCUIT? |
| | FBC 106.1.2, 106.3.5.1.2, |
| | NEC 408.4 |
| | |
| | 12) NOTE: PLEASE SEE COMMENTS FROM BUILDING AND FIRE |
| | FOR ANY POSSIBLE HAZARDOUS CHEMICAL STORAGE/MIXING |
| | AREAS WHICH MAY BE OF CONCERN FOR LIFE SAFETY, ETC. |
| | THIS MAY AFFECT ELECTRICAL PLANS AND DESIGN IN |
| | GENERAL. |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |