Plan Review Details - Permit 07090276
Plan Review Stops For Permit 07090276
Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-01-27 Cont ID  
Sent By mwennerg Date 2009-01-27 Time 11:23 Rev Time 0.00
Received By mwennerg Date 2009-01-27 Time 11:23 Sent To  
Notes
2009-01-27 11:30:03***PROVISO***
  
 REVSION #2 DATED 12/24/08
  
 1) F.M PLACARDING WILL BE ACCEPTED UPON APPROVAL OF
 WEST PALM BEACH FIRE RESCUE. THIS TYPE OF MONITORING
 SYSTEM IS CURRENTLY UNDER REVIEW BY THIS OFFICE FOR
 APPROVAL.
  
 2) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS. SHEET
 FA-6, NOTE #8
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-12-15 Cont ID  
Sent By mwennerg Date 2008-12-15 Time 09:44 Rev Time 0.00
Received By mwennerg Date 2008-12-15 Time 09:44 Sent To  
Notes
2008-12-15 09:59:09REVISION DATED 12/8/08.
  
  
 1) SHEET FA-6 SCOPE OF WORK NOTE #5 SHOULD READ UL
 CERTIFICATED FOR CENTRAL STATION SERVICE.
  
 2) SHEET FA-6 FIRE ALARM NOTE # SHOULD READ GENERAL
 FIRE ALARM UPON ANY DUCT SMOKE DETECTOR ACTIVATION.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2007-10-03 Cont ID  
Sent By mwennerg Date 2007-10-03 Time 11:32 Rev Time 0.00
Received By mwennerg Date 2007-10-03 Time 11:32 Sent To  
Notes
2007-10-03 11:33:36PLANS APPROVED AND STAMPED REGARDING REQUIREMENTS FOR
 UL CERTIFICATION AND DUCT SMOKE DETECTORS INITIATING A
 GENERAL FIRE ALARM.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-01-13 Cont ID  
Sent By adarroug Date 2009-01-13 Time 09:22 Rev Time 0.00
Received By adarroug Date 2009-01-13 Time 09:22 Sent To FIRE
Notes
2009-01-13 09:23:07TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-03 Cont ID  
Sent By mwennerg Date 2007-10-03 Time 11:33 Rev Time 0.00
Received By mwennerg Date 2007-09-11 Time 12:40 Sent To  
Notes
2007-09-11 12:40:40TO "F" BOX


Account Summary | Usage Policy | Privacy Policy