Plan Review Details - Permit 07090086
Plan Review Stops For Permit 07090086
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-11-01 Cont ID  
Sent By mwennerg Date 2007-11-01 Time 09:44 Rev Time 0.00
Received By mwennerg Date 2007-11-01 Time 09:44 Sent To  
Notes
2007-11-01 09:46:03ADD SMOKE DETECTOR TO ELECTRICAL ROOM 203
 ADD SMOKE DETECTOR TO STORAGE ROOM 214
 ADD STROBE TO CONFERENCE ROOM 226

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-09-27 Cont ID  
Sent By mwennerg Date 2007-09-27 Time 12:33 Rev Time 0.00
Received By mwennerg Date 2007-09-27 Time 12:33 Sent To  
Notes
2007-09-27 12:50:08***DENIED***
  
 TWO (2) SETS OF PLANS WERE STAMPED HOWEVER THIS WRITER
 NOW REALIZES THAT THIS BUILDING MAY BE PROTECTED BY AN
 AUTOMATIC FIRE SPRINKLER SYSTEM. THIS INFORMATION
 SIGNIFICANTLY IMPACTS THIS REVIEW.
  
 1) IF BUILDING IS PROTECTED BY AN AUTOMATIC FIRE
 SPRINKLER SYSTEM, PLEASE ADVISE AND SHOW APPLICABLE
 EQUIPMENT ON PLANS.
  
 2) IF BUILDING IS PROTECTED BY AN AUTOMATIC FIRE
 SPRINKLER SYSTEM, THE FIRE ALARM SHALL BE UL CERTIFIED
 FOR CENTRAL STATION SERVICE.
  
 3) PLEASE INCLUDE A SEQUENCE OF OPERATION ON THE
 PLANS.
  
 4) PLEASE ILLUSTRATE MONITORING ON THE PANEL DIAGRAM.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-26 Cont ID  
Sent By adarroug Date 2007-10-26 Time 10:10 Rev Time 0.00
Received By adarroug Date 2007-10-26 Time 10:10 Sent To FIRE
Notes
2007-10-26 10:10:45TO "F" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-09-27 Cont ID  
Sent By mwennerg Date 2007-09-27 Time 12:52 Rev Time 0.00
Received By mwennerg Date 2007-09-06 Time 15:55 Sent To  
Notes
2007-09-06 15:55:36TO "F" BOX