| Plan Review Stops For Permit 07090058 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2007-11-11 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-11-11 |
Time |
14:47 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-11-11 |
Time |
14:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-09-26 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-09-26 |
Time |
13:25 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-09-26 |
Time |
13:25 |
Sent To |
|
|
| Notes |
| 2007-09-26 13:32:22 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | | | | 1.)POOL SAFETY REQUIREMENTS FBC R4101.17 ARE TO BE | | | INCORPORATED INTO THE PLAN SO THAT DESIGN INTENT IS | | | CLEAR.PLEASE REVISE THE PLAN. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2007-11-02 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-11-02 |
Time |
16:09 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-11-02 |
Time |
15:49 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-09-13 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-09-13 |
Time |
10:59 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-09-13 |
Time |
10:33 |
Sent To |
P |
|
| Notes |
| 2007-09-13 10:51:21 | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING: | | | | | | THERE IS AN ELECTRICAL "PANEL" SHOWN ON THE ELECTRICAL | | | SCHEMATIC. THIS WOULD APPEAR TO BE A "POOL PANEL". IF | | | IT IS EXISTING PLEASE INDICATE ON THE PLAN. IF IT IS | | | BEING INSTALLED AS PART OF THIS PERMIT, SUBMIT THE | | | FOLLOWING DETAILS ON THE PLAN: | | | | | | PLEASE SUBMIT DETAILS FOR THE PANEL | | | SHOWN ON THE SCHEMATIC, FEEDER AND CONDU | | | IT SIZE AND TYPE, PANEL RATING AND OCP, | | | PANEL SCHEDULE AND COMPUTED LOAD, ETC. | | | | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2007-09-25 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-09-25 |
Time |
10:40 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2007-09-25 |
Time |
10:40 |
Sent To |
B |
|
| Notes |
| 2007-09-25 10:41:33 | NOTE: THERE IS NO POOL HEATER. |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2007-09-05 |
|
|
Cont ID |
|
| Sent By |
swurafti |
Date |
2007-09-05 |
Time |
11:41 |
Rev Time |
0.00 |
| Received By |
swurafti |
Date |
2007-09-05 |
Time |
11:41 |
Sent To |
|
|
| Notes |
| 2007-09-05 11:41:48 | HISTORIC APPROVED JPAPA |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-10-31 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-10-31 |
Time |
09:38 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-10-31 |
Time |
09:38 |
Sent To |
Z |
|
| Notes |
| 2007-10-31 09:38:16 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-11-11 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-11-11 |
Time |
14:47 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-09-06 |
Time |
14:24 |
Sent To |
|
|
| Notes |
| 2007-09-06 14:24:28 | TO "Z" BOX |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2007-09-25 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-09-25 |
Time |
10:40 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2007-09-25 |
Time |
10:40 |
Sent To |
G |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2007-11-02 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-11-02 |
Time |
11:08 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-11-02 |
Time |
11:08 |
Sent To |
E |
|
| Notes |
| 2007-11-02 11:09:07 | ***APPROVED - RESUB #1*** | | | | | | | | | SENT TO "E" - BT |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2007-09-10 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-09-10 |
Time |
10:37 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-09-10 |
Time |
10:37 |
Sent To |
E |
|
| Notes |
| 2007-09-10 10:39:28 | ***FAILED*** | | | | | | | | | 1)AS THE SURVEY DOES NOT SHOW AN EXISTING PERMANENT | | | FENCE COMPLETELY SURROUNDING THE POOL, A FENCE PERMIT | | | SHALL BE SUBMITTED CONCURRENTLY AND SHALL CONFORM TO | | | THE MINIMUM STANDARDS PROVIDED BELOW. | | | | | | PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND LAND | | | DEVELOPMENT REGULATIONS, SECTION, 94-304(D)(2)(B)+(C): | | | | | | B.EVERY SWIMMING POOL SHALL BE ENCLOSED BY A FENCE | | | OR SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT | | | ACCESS BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF | | | THE RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED. | | | BARRIERS OR FENCES SHALL BE AT LEAST FOUR FEET IN | | | HEIGHT ABOVE GRADE. | | | C.ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE | | | THROUGH A BUILDING OR THROUGH A SELF-CLOSING AND | | | SELF-LATCHING GATE OR THROUGH A SCREEN ENCLOSURE DOOR | | | WITH LATCHES PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF | | | GATE. AT LEAST 90 PERCENT OF THE SURFACE AREA OF ALL | | | SCREEN ENCLOSURES SHALL BE SCREENING MATERIAL THROUGH | | | WHICH AIR SHALL FLOW. ALL POOLS LOCATED ON A CORNER LOT | | | SHALL BE SCREENED AT THE CORNER LOT LINE BY AT LEAST A | | | 42-INCH HIGH LANDSCAPE BUFFER, AS MEASURED FROM GRADE, | | | AT THE PROPERTY LINE, TO ENSURE PRIVACY. | | | | | | 2)PLEASE PROVIDE SETBACK DIMENSIONS FROM THE | | | PROPOSED POOL EQUIPMENT TO THE PROPERTY LINES. | | | | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING | | | TECHNICIAN | | | (561)805-6720 |
|
|