Plan Review Details - Permit 07090045
Plan Review Stops For Permit 07090045
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2008-04-16 Cont ID  
Sent By mjacobs Date 2008-04-16 Time 18:18 Rev Time 0.00
Received By mjacobs Date 2008-04-16 Time 16:04 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-01-25 Cont ID  
Sent By mjacobs Date 2008-01-25 Time 09:43 Rev Time 0.00
Received By mjacobs Date 2008-01-25 Time 08:35 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-01-08 Cont ID  
Sent By mjacobs Date 2008-01-08 Time 11:07 Rev Time 0.00
Received By mjacobs Date 2008-01-07 Time 13:11 Sent To PC
Notes
2008-01-07 15:57:49REVIEW IN PROGRESS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-12-14 Cont ID  
Sent By mjacobs Date 2007-12-14 Time 10:02 Rev Time 0.00
Received By mjacobs Date 2007-12-13 Time 14:58 Sent To  
Notes
2007-12-14 05:45:56 
 BUILDING PLAN REVIEW
 PERMIT: 07090045
 ADD: 114 S. NARCISSUS AVE
 CONT: YOUCHAK & YOUCHAK, INC.
 TEL: (561)832-3800
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006/2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 **= NEW COMMENT**
 REVIEW: 3RD 12/13/07
 ACTION: DENIED
  
 1) OK
 2)FBC 3202.2DOORS AND WINDOWS SHALL NOT OPEN OR
 PROJECT INTO THE PUBLIC RIGHT-OF-WAY. THE DOOR ON THE
 SOUTH ELEVATION CANNOT SWING OVER THE PROPERTY LINE.
 **THE DOORS SHALL BE RECESS, TO PREVENT THEM FROM
 SWINGING INTO THE PUBLIC RIGHT-RIGHT- WAY. ** SHOW THE
 ENTRANCE DOOR CHANGE ON ALL PAGES REFLECTING THE
 ENTRANCE. **
 SHEET C6A WHICH SHOWS THE PROPOSED NEW MAIN ENTRANCE
 INDICATES THE NEW DOOR AS A 3? X 7?. THE PRODUCT
 APPORVAL SUBMITTED IS FOR A 4-0 X 7-0 DOOR. WILL THE
 EXISTING GLASS REMAIN OR WILL IT BE REMOVED TO CREATE A
 LARGER OPENING? CLARIFY.
  
 3)PER FBC TABLE 704.8 NO OPENINGS ARE PERMITTED IN
 WALLS 3 FEET OR LESS FROM THE PROPERTY LINE. FOR MORE
 INFORMATION SEE TABLE 602. INDICATE THE DISTANCE
 BETWEEN EACH PROPERTY LINE AT THE NORTH ELEVATION.
 **THE LOCATION OF THE PREVIOUS DOOR ON NARCISSUS WAS
 CONSTRUCTED TO PREVENT IT FROM SWINGING OVER THE PUBLIC
 RIGHT-OF WAY. THE NEW DOOR LOCATION SHALL MEET THE
 REQUIREMENT OF FBC 3202.2. WHEN THE OCCUPANT LOAD IS
 MORE THAN 50 THE DOOR SHALL SWING IN THE DIRECTION OF
 EGRESS TRAVEL FBC 1008.1.2. ** THE DOORS SHALL BE
 RECESS, TO PREVENT THEM FROM SWINGING INTO THE PUBLIC
 RIGHT-OF- WAY.
 **THE MAIN ENTRANCE DOOR IS IN THE SAME LOCATION
 SWINGING INTO THE PUBLIC RIGHT-OF-WAY ON MANY PAGES.
 ALL PAGES WHICH SHOW THE MAIN ENTRANCE SHALL SHOW
 CLEARLY HOW IT WILL BE CONSTRUCTED. IF CHANGES WERE
 MADE, SHOW IT ON ALL PAGES. **
  
 4)OK
 5)OK
 6)OK
 7)OK
 8)OK
 9)OK
 10)OK
 11)OK
  
 PAGES 9-11 DO NOT SHOW THE ITEMS SPECIFIC TO THE
 SHUTTERS.
 12)106.3.3* PRODUCT APPROVALS- 2004 THOSE PRODUCTS
 THAT ARE REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. THE PRODUCT
 APPROVALS SUBMITTED SHALL INDICATE WHICH ITEMS OR
 SYSTEMS WILL BE USED TO INSTALL THE PRODUCT. THE
 PRODUCT APPROVALS SHALL BE APPROVED IN WRITING BY THE
 DESIGNER OF RECORD.
 **NOTED: ON THE PRODUCT APPROVAL, MARK WHICH DETAILS
 APPLY TO THIS JOB.PLEASE USE INK RATHER THAN A
 HIGHLIGHTER. COMPLETE THE ATTACHED INSTALLATION
 SCHEDULE OR PROVIDE ALL INFORMATION TO SHOW CODE
 COMPLIANCE IN ANOTHER FORMAT (SHUTTERS) **ON PAGES 9-11
 INDICATE WHICH ROW AND COLUMN PERTAIN TO THE SHUTTER
 INSTALLATION. **
  
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-11-14 Cont ID  
Sent By mjacobs Date 2007-11-14 Time 13:54 Rev Time 0.00
Received By mjacobs Date 2007-11-10 Time 08:13 Sent To  
Notes
2007-11-14 13:55:34 
  
  
  
  
  
  
 BUILDING PLAN REVIEW
 PERMIT: 07090045
 ADD: 114 S. NARCISSUS AVE
 CONT: YOUCHAK & YOUCHAK, INC.
 TEL: (561)832-3800
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006/2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
 **= NEW COMMENT**
 REVIEW: 2ND 11/10/07
 ACTION: DENIED
  
 1) OK
  
 2)FBC 3202.2DOORS AND WINDOWS SHALL NOT OPEN OR
 PROJECT INTO THE PUBLIC RIGHT-OF-WAY. THE DOOR ON THE
 SOUTH ELEVATION CANNOT SWING OVER THE PROPERTY LINE.
 **THE DOORS SHALL BE RECESS, TO PREVENT THEM FROM
 SWINGING INTO THE PUBLIC RIGHT-RIGHT- WAY.**
 FBC11-4.5.2 CHANGES IN LEVEL GREATER THAN ? INCH SHALL
 BE ACCOMPLISHED BY MEANS OF A RAMP THAT COMPLIES WITH
 SECTION 11-4.7 OR 11-4.8. THIS SECTION REFERS TO ALL
 DOORS.
  
 3)PER FBC TABLE 704.8 NO OPENINGS ARE PERMITTED IN
 WALLS 3 FEET OR LESS FROM THE PROPERTY LINE. FOR MORE
 INFORMATION SEE TABLE 602. INDICATE THE DISTANCE
 BETWEEN EACH PROPERTY LINE AT THE NORTH ELEVATION.
 **THE LOCATION OF THE PREVIOUS DOOR ON NARCISSUS WAS
 CONSTRUCTED TO PREVENT IT FROM SWINGING OVER THE PUBLIC
 RIGHT-OF WAY. THE NEW DOOR LOCATION SHALL MEET THE
 REQUIREMENT OF FBC 3202.2. WHEN THE OCCUPANT LOAD IS
 MORE THAN 50 THE DOOR SHALL SWING IN THE DIRECTION OF
 EGRESS TRAVEL FBC 1008.1.2. ** THE DOORS SHALL BE
 RECESS, TO PREVENT THEM FROM SWINGING INTO THE PUBLIC
 RIGHT-RIGHT- WAY.** FBC11-4.5.2 CHANGES IN LEVEL
 GREATER THAN ? INCH SHALL BE ACCOMPLISHED BY MEANS OF A
 RAMP THAT COMPLIES WITH SECTION 11-4.7 OR 11-4.8. THIS
 SECTION REFERS TO ALL DOORS.
  
 4)OK
 5)OK
 6)OK
 7)OK
 8)OK
  
 9)FBC 106.3.5.1.1 SUBMIT THE LIFE SAFETY PLAN
 INDICATING THE MEANS OF EGRESS, EXIT ACCESS, EXIT, EXIT
 DISCHARGE. THE EXTERIOR ELEVATIONS SHALL INCLUDE ALL
 STEPS, RAMPS AND LANDINGS LEADING TO OR FROM THE EGRESS
 DOORS.
 **ARE ALL THE EXITS SHOWN ON DRAWINGS HANDI-CAP
 ACCESSIBLE? IF NOT, THE ONES WHICH ARE SHALL BE CLEARLY
 SHOWN.
  
 10)SHOW THE ACCESSIBLE ROUTE LEADING TO THE EXIT
 DOORS. SIGNS SHALL BE PLACE IN ACCORDANCE WITH SECTIONS
 11-4.30.6 / 11-4.1/ 11-4.3.
 ** NOTED: HOWEVER, IT SEEMS AS THOUGH ALL THE DOORS ARE
 NOT HANDI-CAP ACCESSIBLE.**
  
 11)OK
 12)106.3.3* PRODUCT APPROVALS- 2004 THOSE PRODUCTS
 THAT ARE REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. THE PRODUCT
 APPROVALS SUBMITTED SHALL INDICATE WHICH ITEMS OR
 SYSTEMS WILL BE USED TO INSTALL THE PRODUCT. THE
 PRODUCT APPROVALS SHALL BE APPROVED IN WRITING BY THE
 DESIGNER OF RECORD.
 **NOTED: ON THE PRODUCT APPROVAL, MARK WHICH DETAILS
 APPLY TO THIS JOB.PLEASE USE INK RATHER THAN A
 HIGHLIGHTER. COMPLETE THE ATTACHED INSTALLATION
 SCHEDULE OR PROVIDE ALL INFORMATION TO SHOW CODE
 COMPLIANCE IN ANOTHER FORMAT(SHUTTERS)
  
 **NEW**
 A) 2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE. DUE TO THE FACT
 THAT THE INTERIOR CONSTRUCTION OF THE BUILDING WAS
 COMPLETELY DEMOED, THIS ALTERATION SEEMS TO BE A LEVEL
 3 ALTERATION.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-04 Cont ID  
Sent By jleech Date 2007-10-04 Time 10:31 Rev Time 0.00
Received By mjacobs Date 2007-10-02 Time 06:07 Sent To  
Notes
2007-10-03 18:57:25BUILDING PLAN REVIEW
 PERMIT: 07090045
 ADD: 114 S. NARCISSUS AVE
 CONT: YOUCHAK & YOUCHAK, INC.
 TEL: (561)832-3800
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006/2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B) PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS, PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT. IF YOUR PROJECT WILL REQUIRE A
 RESIDENT INSPECTOR OR IF YOUR PROJECT IS A THRESHOLD
 BUILDING REQUIRING A THRESHOLD INSPECTOR THEN (3) THREE
 SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED FOR PERMIT
 ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS WEST PALM
 BEACH ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 2)FBC 3202.2DOORS AND WINDOWS SHALL NOT OPEN OR
 PROJECT INTO THE PUBLIC RIGHT-OF-WAY. THE DOOR ON THE
 SOUTH ELEVATION CANNOT SWING OVER THE PROPERTY LINE.
  
 3)PER FBC TABLE 704.8 NO OPENINGS ARE PERMITTED IN
 WALLS 3 FEET OR LESS FROM THE PROPERTY LINE. FOR MORE
 INFORMATION SEE TABLE 602. INDICATE THE DISTANCE
 BETWEEN EACH PROPERTY LINE AT THE NORTH ELEVATION.
  
 4)ALL PLANS SUBMITTED AFTER OCTOBER, 1, 2004 SHALL BE
 DESIGNED TO THE 2004 FLORIDA BUILDING CODE WITH THE
 2006 AND 2007 REVISIONS. THERE IS SOME INFORMATION ON
 SHEET C2 WHICH REFER TO THE PREVIOUS CODE E.G. ASCE
 7-98 WAS IN THE 2001 CODE SEE CHAPTER 35 FOR THE NEW
 REFERENCE STANDARDS. WE ARE USING THE CITY OF WEST PALM
 BEACH AMENDMENTS NOT PALM BEACH COUNTY AMENDMENTS.
 THERE IS NO TABLE 500 IN THE 2004 FBC.
  
 5)61G15-23.002 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF CHAPTER 471,
 F.S., SHALL BE SEALED, SIGNED AND DATED BY THE
 PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE. ENGINEERS
 SHALL LEGIBLY INDICATE THEIR NAME, ADDRESS AND LICENSE
 NUMBER, AS WELL AS, THE NAME, ADDRESS, AND CERTIFICATE
 OF AUTHORIZATION NUMBER OF THE ENGINEERING BUSINESS ON
 EACH SHEET.
  
 6)FBC 1003.5.2 WHERE CHANGE IN ELEVATION OF 12 INCHES
 OR LESS OCCURS IN EXIT ACCESS CORRIDORS, EXITS AND EXIT
 DISCHARGE, RAMPS COMPLYING WITH SECTION 1010 SHALL BE
 PROVIDED. THE RAMP SHALL BE IN CONFORMANCE WITH SECTION
 11-4.8.
  
 7)INDICATE THE CLEAR FLOOR SPACE ON THE DRAWINGS FOR
 THE HANDI-CAP LAVATORIES AND URINALS PER SEC 11-4.18
 AND 11-4.19.
  
 8)TABLE 803.3 MINIMUM INTERIOR FINISH CLASSIFICATION;
 PROVIDE INFORMATION BASED ON INTERIOR FINISH
 REQUIREMENTS BASED ON OCCUPANCY.
  
 9)FBC 106.3.5.1.1 SUBMIT THE LIFE SAFETY PLAN
 INDICATING THE MEANS OF EGRESS, EXIT ACCESS, EXIT, EXIT
 DISCHARGE. THE EXTERIOR ELEVATIONS SHALL INCLUDE ALL
 STEPS, RAMPS AND LANDINGS LEADING TO OR FROM THE EGRESS
 DOORS.
  
 10)SHOW THE ACCESSIBLE ROUTE IN LEADING TO THE EXIT
 DOORS. SIGNS SHALL BE PLACE IN ACCORDANCE WITH SECTIONS
 11-4.30.6 / 11-4.1/ 11-4.3.
  
 11)FBC 11-5.2 WHERE FOOD OR DRINK IS SERVED AT
 COUNTERS EXCEEDING 34 INCHES IN HEIGHT FOR CONSUMPTION
 BY CUSTOMERS SEATED ON STOOLS OR STANDING AT THE
 COUNTER, A PORTION OF THE MAIN COUNTER SHALL BE 60
 INCHES IN LENGTH AND COMPLY WITH SECTION 11-4.32 OR
 SERVICE TABLES SHALL BE AVAILABLE. THE HEIGHT AND KNEE
 CLEARANCES SHALL MEET THE REQUIREMENTS OF 11-4.32.2/
 11-4.32.3 AND 11-4.32.4
  
 12)106.3.3* PRODUCT APPROVALS- 2004 THOSE PRODUCTS
 THAT ARE REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. THE PRODUCT
 APPROVALS SUBMITTED SHALL INDICATE WHICH ITEMS OR
 SYSTEMS WILL BE USED TO INSTALL THE PRODUCT. THE
 PRODUCT APPROVALS SHALL BE APPROVED IN WRITING BY THE
 DESIGNER OF RECORD.
  
 NOTE: ANY ROOFING WORK WILL REQUIRE A ROOFING
 CONTRACTOR.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2008-02-16 Cont ID  
Sent By dpalmer Date 2008-02-16 Time 18:03 Rev Time 0.00
Received By dpalmer Date 2008-02-16 Time 18:03 Sent To PC
Notes
2008-02-16 18:03:16** DENIEDREVISION **
  
 1) NOTE: PLEASE SEE RISER HAS NOW HAD CONDUCTORS AND
 CONDUIT REVISED WHICH HAS SEVERAL CODE ISSUESWHICH
 NEED TO BE ADDRESSED.
  
 A) AS REDLINED AND STATED ON ALL PREVIOUS REVIEWS: *AN
 EQUIPMENT GROUNDING CONDUCTOR SHALL NOT BE INSTALLED
 BEFORE THE FIRST MEANS OF DISCONNECT. PLEASE SEE 250.24
 AND 250.6. AS THE CODE REQUIRES THE GROUNDED (NEUTRAL)
 TO BE BONDED AT THE FIRST MEANS OF DISCONNECT, IF AN
 EQUIPMENT GROUNDING CONDUCTOR IS INSTALLED FROM THE
 METER TO THAT FIRST MEANS THIS WOULD PARALLEL THE
 NEUTRAL AND CREATE OBJECTIONABLE CURRENTS WHICH IS
 SPECIFICALLY STATED IN THE SECTIONS ABOVE.
  
 B) PLEASE SEE THE HOT/PHASE CONDUCTORS HAVE NOW BEEN
 DOWN SIZED TO 3/0 CONDUCTORS AND STATES PER 310.15B.
 PLEASE SEE THAT THE SECTION NOTED IS INCORRECT. THE
 SECTION IS 310.15(B)(6)AND IS STRICTLY FOR
 *RESIDENTIAL* AND NOT FOR COMMERCIAL USE.
 THE MINIMUM HOT/PHASE CONDUCTORS FOR THE 225AMP MAINS
 IN A COMMERCIAL USE PER 310.16 IS 4/0. THIS WAS ON
 ORIGINAL RISER.
  
 C) PLEASE SEE NOW THE CONDUIT SIZE HAS ALSO BEEN
 DECREASED. PLEASE KNOW AS NOTED IN SECTION B) ABOVE THE
 CONDUCTORS ARE REQUIRED TO BE 4/0. IF YOU FIGURE THE
 SIZING PER TABLES IN CHAPTER 9, EVEN USING PVC SCHEDULE
 40, OR EMT THE 2INCH CONDUIT IS NOT LARGE ENOUGH FOR
 THE CONDUCTORS.
 PLEASE SEE CONDUIT FILL NEEDS TO BE ADDRESSED EVEN IF
 #4 EQUIPMENT GROUNDING CONDUCTOR AFTER THE FIRST MEANS
 OF DISCONNECT IS USED.
 THE 2 ? INCH CONDUIT ON ORIGINAL RISER WAS CORRECT FOR
 THE CONDUCTORS WHICH WERE SHOWN ON ORIGINAL RISER.
 THE 2INCH CONDUIT BEFORE THE MAINS ARE OK FOR 4-4/0.
  
 D) PLEASE SEE A CODE SECTION OF 250.66 IS REFLECTED ON
 RISER FOR EQUIPMENT GROUNDS HOWEVER EQUIPMENT GROUNDING
 CONDUCTORS ARE SIZED FROM 250.122.
 PLEASE ALSO SEE THE RISER SHOWS 3 #4 EQUIPMENT
 GROUNDING CONDUCTORS PER CONDUIT?? PLEASE SEE 250.122
 AS ONLY ONE EQUIPMENT GROUNDING CONDUCTOR #4 IS
 REQUIRED FOR UP TO 300AMPS.
  
 ** THERE ARE SEVERAL ITEMS WHICH NEED TO BE ADDRESSED.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-01-08 Cont ID  
Sent By dpalmer Date 2008-01-08 Time 10:18 Rev Time 0.00
Received By dpalmer Date 2008-01-08 Time 10:18 Sent To  
Notes
2008-01-08 10:18:38*** PROVISO ***
  
 ** PLEASE SEE ITEMS FROM PREVIOUS REVIEW ARE STILL IN
 NEED OF ADDRESSING.
  
  
  
 1) NOTE: PLEASE SEE PREVIOUS REVIEW WITH RESPECT TO THE
 NEW TANK-LESS WATER HEATER. PLEASE SEE THE MANUFACTURES
 SPECS/CUTS NOW SUBMITTED AS THIS UNIT IS 240V AND THE
 SERVICE IS 208V. 17250VA AT 208V IS ABOVE THE BRANCH
 CIRCUIT RATING ON PANEL SCHEDULE. THIS WAS GIVEN ON
 PREVIOUS REVIEW HOWEVER CIRCUIT WAS NOT ADJUSTED. THE
 MANUFACTURES SPECS/CUT SHEETS DO STATE 80AMPS FOR THE
 OVER CURRENT PROTECTION HOWEVER THIS IS AT THE 240V
 RATING OF THE EQUIPMENT.
 PLEASE SEE SERVICE IS 208V.
 PLEASE KNOW AS THIS IS A LISTED ITEM AT 240V IT MAY
 VERY WELL NOT BE RATED FOR 208V.
 THESE NEED TO BE ADJUSTED AND VERIFIED.
 240.4, 310.16, 110.3, 90.7
  
 2) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENT #6 WHICH
 MENTIONED THE MISSING EQUIPMENT GROUNDING CONDUCTORS
 AFTER THE FIRST MEANS OF DISCONNECT. IN FACT THE NOTE
 GAVE NOTICE THAT THE EQUIPMENT GROUNDING CONDUCTORS ARE
 *ONLY AFTER THE FIRST MEANS OF DISCONNECT*.
 PLEASE SEE RISER NOTES/SHOWS THEM BOTH BEFORE AND
 AFTER.
 THIS CAN BE RED-LINED FOR NO INSTALLATION OF THESE
 BEFORE MAINS. (FIRST MEANS OF DISCONNECT).
  
  
 ** PLEASE SUBMIT REVISIONS OR REVISED SPECS/CUT SHEETS
 BEFORE ROUGH.
 ** PLEASE BE SURE TO ADDRESS COMMENTS AND IF THERE ARE
 ANY QUESTIONS, PLEASE CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-12-30 Cont ID  
Sent By dpalmer Date 2007-12-30 Time 14:27 Rev Time 0.00
Received By dpalmer Date 2007-12-30 Time 14:27 Sent To  
Notes
2007-12-30 14:27:21 
 *** DENIED REVIEW ***
  
 ** PLEASE SEE ITEMS FROM PREVIOUS REVIEW ARE STILL IN
 NEED OF ADDRESSING.
  
 *** IMPORTANT ***
 IF ALL OTHER REVIEWS PASS AND THERE ARE NO COMMENTS
 FROM OTHER TRADES A *PROVISO* AND RED-LINED PLANS CAN
 BE SET UP FOR ELECTRICAL REVIEW FOR THE LAST TWO
 COMMENTS WHICH WOULD BE REQUIRED TO BE ADDRESSED BEFORE
 ANY ROUGH ELECTRICAL INSPECTION.
  
 1) NOTE: PLEASE SEE PREVIOUS REVIEW WITH RESPECT TO THE
 NEW TANK-LESS WATER HEATER. PLEASE SEE THE MANUFACTURES
 SPECS/CUTS NOW SUBMITTED AS THIS UNIT IS 240V AND THE
 SERVICE IS 208V. 17250VA AT 208V IS ABOVE THE BRANCH
 CIRCUIT RATING ON PANEL SCHEDULE. THIS WAS GIVEN ON
 PREVIOUS REVIEW HOWEVER CIRCUIT WAS NOT ADJUSTED. THE
 MANUFACTURES SPECS/CUT SHEETS DO STATE 80AMPS FOR THE
 OVER CURRENT PROTECTION HOWEVER THIS IS AT THE 240V
 RATING OF THE EQUIPMENT.
 PLEASE SEE SERVICE IS 208V.
 PLEASE KNOW AS THIS IS A LISTED ITEM AT 240V IT MAY
 VERY WELL NOT BE RATED FOR 208V.
 THESE NEED TO BE ADJUSTED AND VERIFIED.
 240.4, 310.16, 110.3, 90.7
  
 2) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENT #6 WHICH
 MENTIONED THE MISSING EQUIPMENT GROUNDING CONDUCTORS
 AFTER THE FIRST MEANS OF DISCONNECT. IN FACT THE NOTE
 GAVE NOTICE THAT THE EQUIPMENT GROUNDING CONDUCTORS ARE
 *ONLY AFTER THE FIRST MEANS OF DISCONNECT*.
 PLEASE SEE RISER NOTES/SHOWS THEM BOTH BEFORE AND
 AFTER.
 THIS CAN BE RED-LINED FOR NO INSTALLATION OF THESE
 BEFORE MAINS. (FIRST MEANS OF DISCONNECT).
  
 ** PLEASE BE SURE TO ADDRESS COMMENTS AND IF THERE ARE
 ANY QUESTIONS, PLEASE CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-12-06 Cont ID  
Sent By dpalmer Date 2007-12-06 Time 15:30 Rev Time 0.00
Received By dpalmer Date 2007-12-06 Time 15:30 Sent To  
Notes
2007-12-06 15:31:26** DENIED 3RD REVIEW **
  
 ** PLEASE SEE COMMENTS FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH NEW COMMENTS BASED ON
 CHANGES MADE AND NEW ITEMS NOT ON PREVIOUS PLANS. SOME
 OTHER ITEMS ARE ONLY NOW BEING SUBMITTED FOR THE FIRST
 REVIEW.
  
 1) NOTE: PLEASE SEE THE METHOD ON HOW LIGHTING
 PERFORMANCE CALCULATIONS ARE DONE WAS SUBMITTED HOWEVER
 ACTUAL LIGHTING PERFORMANCE CALCULATIONS ARE SHOWN.
 13-415.2
  
 2) NOTE: PLEASE SEE THE CIRCUITING IS NOW SHOWN,
 HOWEVER PLEASE SEE THE CIRCUITING FOR EMERGENCY AND
 EXIT LIGHTS ARE NOT PER 700.12F WHICH REQUIRES THE
 FIXTURES TO BE CIRCUITED TO THE LOCAL LIGHTING IN ANY
 ONE AREA.
 FOR EXAMPLE: IF THE BREAKER FOR THE NORMAL LIGHTING IN
 THE BATHROOMS WERE TO TRIP, THE EMERGENCY LIGHT WOULD
 NOT ILLUMINATE.
 PLEASE SEE NFPA-101 7.9.2.2
  
 3) NOTE: PLEASE SEE THE PANEL SCHEDULE *C* NOW SHOWS A
 NEW TANK-LESS WATER HEATER AT 17250 WATTS, YET THE OVER
 CURRENT PROTECTION IS TOO LOW BASED ON THE KW AND
 VOLTAGE AS SHOWN.
 PLEASE PROVIDE MANUFACTURE CUT SHEET WHICH INDICATES A
 LISTING FROM A NRTL.
 90.7, 110.3
 FBC 106.1.2
  
 4) NOTE: PLEASE SEE THE NEW PANEL SCHEDULES SUBMITTED
 ALONG WITH LOAD CALCULATIONS HAVE BEEN CHANGED AND
 THERE ARE ITEMS WHICH CAN NOT BE SEEN.
 THE PRINT IS VERY FAINT IN LOCATIONS FOR MANY ITEMS.
 PLEASE SEE THE TITLE AT THE TOP OF THE PANEL WHICH SHOW
 LOAD. THIS CAN NOT BE FIGURED AT THIS TIME.
 PLEASE SEE THE PREVIOUS PANEL SCHEDULE SHOWS THE LOAD
 FOR THE TANK-LESS WATER HEATER NOTED ABOVE AS WHAT
 APPEARS TO BE 8KW, YET CALCULATIONS DO NOT SHOW THE
 SAME??
 PLEASE SEE THE PANEL SCHEDULE ALSO DOES NOT SHOW ANY
 CONDUCTOR SIZES FOR BRANCH CIRCUITS. 240.4,408.4,310.16
 ETC
 PLEASE SEE NEC 220 FOR LOAD CALCULATIONS AND
 ADJUSTMENTS NEED.
 HOW ARE LOADS DERIVED? PLEASE CLARIFY LOADS ON
 CALCULATIONS DO NOT SEEM TO CORRELATE WITH PANEL. FOR
 EXAMPLE: PLEASE SEE AHU LOADS ON PANEL, WHICH ARE NOT
 THE SAME ON CALCULATIONS. THIS IS THE SAME AS TANK-LESS
 WATER HEATER.
 THESE ARE A COUPLE OF EXAMPLES.
 PLEASE GO OVER ALL AND MAKE ADJUSTMENTS.
  
 5) NOTE: PLEASE SEE THE RISER NOW HAS SOME OF THE
 SERVICE ENTRANCE CONDUCTORS AND FEEDERS SHOWN HOWEVER
 THE SIZES OF THESE CONDUCTORS ARE NOT RATED FOR THE
 OVER CURRENT PROTECTION.
 PLEASE KNOW THIS IS A COMMERCIAL BUILDING AND THE
 DE-RATINGS PERMITTED IN 310.15B6 MAY NOT BE USED.
 PLEASE SEE PREVIOUS NOTES MENTIONED THESE WERE NOT
 LARGE ENOUGH BASED ON 310.16, 240.4 AND 110.14 3/0'S
 ARE ONLY RATED FOR 200AMPS, YET THE MAINS ARE 225AMPS.
 PLEASE ADJUST CONDUCTORS ON BOTH SIDES OF MAIN
 DISCONNECTS.
  
 6) NOTE: PLEASE SEE RISER IS MISSING EQUIPMENT
 GROUNDING CONDUCTORS AFTER THE FIRST MEANS OF
 DISCONNECT PER 250.110, 250.24, 250.122.
 PLEASE INCLUDE ONLY AFTER THE FIRST MEANS OF
 DISCONNECT.
  
 7) NOTE: PLEASE CORRELATE AND GO OVER ALL CIRCUITING AS
 SHOWN.
 PLEASE SEE FOR EXAMPLE, THE LIGHTING AND POWER PLANS
 INDICATE CIRCUIT CHP-29 FOR SOME LIGHTS OUTSIDE AND
 POWER PLANS SHOWS THIS SAME CIRCUIT FEEDING SOME
 RECEPTACLES, HOWEVER THE PANEL SCHEDULE MENTIONS THIS
 CIRCUIT IS FOR *RAMP LIGHTS*.
 WHERE ARE THE * RAMP LIGHTS* ?
 PLEASE COORDINATE CIRCUITING AS NOTED ABOVE FOR
 EMERGENCY LIGHTING AND OTHER ITEMS ON PLANS. 408.4,
 310.16, 240.4
 FBC 106.3.5.1.2, 106.1.2
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-11-07 Cont ID  
Sent By dpalmer Date 2007-11-07 Time 15:23 Rev Time 0.00
Received By dpalmer Date 2007-11-07 Time 11:31 Sent To  
Notes
2007-11-07 15:24:01** DENIED 2ND REVIEW **
  
 ** PLEASE SEE THERE ARE COMMENTS FROM PREVIOUS REVIEW
 AND SEVERAL NEW COMMENTS DUE TO NEW INFORMATION/DETAILS
 NOW ON PLANS WHICH HAVE CREATED NEW COMMENTS.
  
 1) NOTE: PLEASE SEE THAT NO LIGHTING ENERGY/PERFORMANCE
 CALCULATIONS WERE SUBMITTED.
 PLEASE SEE 13-101.1.3, 13-415.2
 (PREVIOUS REVIEW )
  
 2) NOTE: PLEASE SEE MISSING ADA LEVELS FOR FA DEVICES.
 PLEASE SEE FBC 11-4.28.1, .2 AND .3(4).
 DEVICE LOCATIONS ARE SHOWN HOWEVER NO MINIMUM LEVELS
 COULD BE LOCATED.
  
 3) NOTE: PLEASE SEE THE ELECTRICAL SERVICE RISER IS IN
 NEED OF CHANGES.
 PLEASE SEE NO SERVICE ENTRANCE CONDUCTORS ARE SHOWN.
 CAN NOT DETERMINE OR REVIEW AMPACITY OF CONDUCTORS AT
 THIS TIME AS NONE ARE SHOWN.
 PLEASE SEE THE CONDUCTORS FROM METER TO MAIN AND MAIN
 TO PANELS ARE NOT OF SUFFICIENT SIZE. PLEASE ALSO SEE
 THAT THE NUMBER OF CONDUCTORS IS NOT SHOWN.
 PLEASE SEE NEC 240.4, 310.16.
  
 4) NOTE: PLEASE SEEM MISSING COLD WATER PIPE FOR
 GROUNDING ELECTRODE SYSTEM 250.50
  
 5) NOTE: PLEASE SEE THE LOAD CALCULATIONS SUBMITTED ARE
 FOR A RESIDENTIAL DWELLING.
 PLEASE SEE NEC 220, 220.12,220.14, 220.42, 220.44, ETC
 PLEASE SEE THAT ALL CONTINUOUS LOADS ARE TO BE SHOWN AT
 125%. 215.3, 230.42
  
 6) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS AND
 CORRELATE WITH THE SUBMITTED PANEL SCHEDULES. PLEASE
 SEE THERE ARE ELECTRICAL ITEMS ON PLANS WHICH ONLY
 CONTAIN PART OF THE NUMERICAL CIRCUIT DESIGNATION.
 (EXAMPLE ICE MACHINE).
 PLEASE THERE ARE SEVERAL ELECTRICAL RECEPTACLE
 LOCATIONS WHICH DO NOT INDICATE ANY CIRCUITS.
 PLEASE SEE AS THE ELECTRICAL DISCONNECTS FOR A/C RT
 UNITS ARE NOT SHOWN ON ELECTRICAL PLANS PLEASE INDICATE
 CIRCUITS.
 FBC 106.3.5.1.2, 106.1.2
 NEC 408.4.
  
 7) NOTE: PLEASE CLARIFY THE SAME CLEARANCE REQUIREMENTS
 FOR THE PANELS. ONE DETAIL ON SHEET 24, INDICATES
 MINIMUM CLEARANCES HOWEVER THERE IS ONE DETAIL WHICH
 SHOWS AN ELEVATION OF A COUNTER IN FRONT OF PANELS
 WHICH IS NOT PERMITTED. ONE OTHER DETAIL SHOWS A JOG IN
 COUNTER AND ANOTHER DETAIL DOES NOT.
  
 8) NOTE: PLEASE SEE DETAILS FOR FLOOR TILE LIGHTS WHERE
 THE CONNECTION DETAILS AS SHOWN DO NOT COMPLY WITH
 MANUFACTURES INSTALLATION OR WITH APPROVED CONNECTORS
 FOR USE. *SEAL-TITE* CONNECTORS ARE NOT FOR USE WITH
 THESE CABLES ARE MENTIONED.
 PLEASE KNOW THAT ALL INSTALLATIONS SHALL MEET NEC 300,
 110.3 ETC.
 THE DETAIL AS SHOWN AND AS PREVIOUSLY SPOKE ABOUT IS
 STILL NOT APPROVED AS SHOWN.
  
 9) NOTE: PLEASE SEE FS 553.80(2)(B) WIHT RESPECT TOP
 REPEAT COMMENTS. THIS IS ONLY A NOTICE GIVEN AT THIS
 TIME.
  
 ** PLEASE SEE THERE ARE SEVERAL CHANGES NEEDED AND
 ITEMS WHICH CAN NOT BE REVIEWED.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-09-25 Cont ID  
Sent By dpalmer Date 2007-09-25 Time 12:35 Rev Time 0.00
Received By dpalmer Date 2007-09-25 Time 10:09 Sent To  
Notes
2007-09-25 12:36:04** DENIED**
  
  
  
 1) NOTE: PLEASE STATE THE FOLLOWING RELEVANT CODES ON
 PLANS.
 PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH ARE
 SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE SEE THE TOP OF397-001-C2 WHICH PRINTED THE
 LS CODE A EDITION 200. THIS SEEMS TO HAVE BEEN A
 MISPRINT.
  
 ** PLEASE SEE PLANS ALSO CALL FOR *PALM BEACH COUNTY
 AMENDMENTS* HOWEVER THIS PROJECT IS NOT LOCATED IN PALM
 BEACH COUNTY JURISDICTION. THIS IS LOCATED IN THE CITY
 OF WEST PALM BEACH.
  
 2) NOTE: PLEASE SEE THE INFORMATION SHOWN ON TITLE
 BLOCKS FOR THE ENGINEERING FIRM IS IN A DELINQUENT
 STATUS WITH THE DEPARTMENT OF BUSINESS AND PROFESSIONAL
 REGUALTION.
 PLEASE UPDATE.
 FS 471.023
  
 3) NOTE: PLEASE SEE FLORIDA STATUTES 471.025 AS THIS
 AND THE FLORIDA ADMINISTRATIVE CODE 61G15-23.002 WHICH
 REQUIRES PLANS TO BE SIGNED, DATED AND SEALED BY THE
 DESIGN PROFESSIONAL.
 PLEASE SEE SOME SHEETS CONTAIN SEAL BUT NO SIGNATURE
 AND DATE, MOST SHEETS ARE NOT DATED AS REQUIRED.
 ** PLEASE KNOW THIS IS REQUIRED FOR ALL TRADES AND FOR
 ALL SHEETS WHETHER OR NOT COMMENT IS MADE BY OTHER
 TRADES.
  
 4) NOTE: PLEASE SEE PLANS DOE NOT INDICATE ANY
 EMERGENCY AND EXIT LIGHTS AS REQUIRED PER FBC CHAPTER
 10, AND NFPA-101 7.8, 7.9.
 PLEASE SEE 700.12F OF NFPA-70 FOR CIRCUITING REQUIRED.
 PLEASE KNOW THE BATHROOMS WHEN CONTAINING PARTITIONS
 AND NOT A SINGLE POINT OF USE WILL REQUIRE AN EMERGENCY
 BATTERY BACK UP FIXTURE OF SOME SORT.
 ** PLEASE SEE POSSIBLE COMMENTS FROM THE FIRE MARSHAL.
  
 5) NOTE: PLEASE SEE MISSING SIGN CIRCUIT PER 600.5 AND
 LOAD FOR THIS SAME SIGN CIRCUIT.
  
 6) NOTE: PLEASE SHOW AND COMPLETE LOCATIONS OF ALL A/C
 SYSTEMS ON ELECTRICAL PLANS.
 IT IS BEING ASSUMED THESE UNITS ARE ROOFTOP PACKAGE
 UNITS ALTHOUGH THE MECHANICAL PLANS ARE NOT CLEAR.
 PLEASE SEE MISSING REQUIRED DISCONNECTS PER 440.11 AND
 MISSING GFI RECEPTACLES PER 210.63 AND 210.8B.
  
 7) NOTE: PLEASE SEE THE RISER INDICATES MAIN AHEAD OF
 PANELS HOWEVER THE PLANS DO NOT INDICATE THESE FOR
 THEIR LOCATIONS.
 PLEASE KNOW THE SERVICE DISCONNECTING MEANS IS NOT
 COMPLETE AT THIS TIME ON PLANS.
 PLEASE KNOW THE LOCATION OF THE SERVICE DISCONNECTING
 MEANS NEEDS TO BE DETERMINED FOR LOCATION.
 PLEASE SEE NOTE BELOW WITH RESPECT TO THE PANEL
 LOCATIONS WHICH DOES NOT MEET CODE.
 230.70, 230.71, 110.26
  
 8) NOTE: PLEASE SEE THE RISER IS NOT COMPLETE WITH THE
 SERVICE ENTRANCE CONDUCTORS, CONDUCTORS TO MAINS,
 CONDUCTORS FROM MAINS TO PANELS ETC.
 240.4, 310.16 ETC
 FBC 106.1.2, 106.3.5.1.2
  
 9) NOTE: PLEASE SEE MISSING COMPLETED GROUNDING
 ELECTRODE SYSTEM PER 250.50. PLEASE KNOW THAT QUOTING
 THE CODE IN LIEU OF THE REQUIRED MINIMUM DETAIL IS NOT
 ACCEPTABLE.
 PLEASE ADJUST RISER.
 PLEASE ALSO SEE THAT THE SIZE OF THE GROUNDING
 ELECTRODE CONDUCTOR IS NOT LARGE ENOUGH AND NEEDS TO
 MEET THE MINIMUM SIZES PER 250.66.
  
 10) NOTE: PLEASE SEE THE LOCATION OF THE PANEL(S) IN DJ
 BOOTH AREA DOES NOT MEET 110.26. IN FACT THERE IS A
 COUNTER BEING SHOWN DIRECTLY IN FRONT OF ONE OF THE
 PANELS WHICH IS STRICTLY PROHIBITED.
 PLEASE SEE NOTES ABOVE WITH RESPECT TO SERVICE, PANELS,
 OVER CURRENT PROTECTION AND LOCATIONS OF ALL SERVICE
 EQUIPMENT AND PANELS.
 PLEASE ADJUST AS REQUIRED.
  
 11) NOTE: PLEASE CORRELATE RISER DIAGRAM AND PANELS.
 PLEASE SEE PANEL CH IS SHOWN AS 225AMP AND ALSO AS
 200AMP ON PANEL SCHEDULE.
 FBC 106.1.2 FOR COORDINATION.
  
 12) NOTE: PLEASE PROVIDE AIC RATINGS FOR ALL SERVICE
 EQUIPMENT INCLUDING MAINS PER 110.9.
 FBC 106.1.2
  
 13)NOTE: PLEASE SEE NO ENERGY CALCULATIONS WERE
 SUBMITTED. IF INSTALLING NEW AIR CONDITIONED SPACE,
 THEN THESE WILL BE REQUIRED. IF NO NEW A/C EQUIPMENT IS
 BEING INSTALLED, THEN PLEASE SUBMIT LIGHTING
 PERFORMANCE CALCULATIONS PER 13-415.2
  
 14) NOTE: PLEASE SEE THERE ARE SEVERAL CIRCUITS IN
 WHICH THE KVA LOAD SHOWN FAR EXCEEDS THE RATING OF THE
 BRANCH CIRCUIT AND BRANCH CIRCUIT OVER CURRENT
 PROTECTION.
 PLEASE SEE FOR EXAMPLE 3.2 KVA ON SINGLE POLE 20AMP
 BRANCH CIRCUIT.(MAX 1920VA)
 PLEASE SEE THAT ALL CONTINUOUS LOADS ARE TO BE SHOWN AT
 125%.
 PLEASE SEE 215.3, 230.42, 408.4, 240.4, 310.16 ETC
 PLEASE BE SURE TO ADJUST PANEL SCHEDULE FOR CIRCUITING
 AND LOADS.
 FBC 106.1.2, 106.3.5.1.2
  
 15) NOTE: PLEASE CORRELATE ALL CIRCUITING ON PLANS WITH
 PANEL SCHEDULES. PLEASE SEE FOR EXAMPLE CIRCUITS: CHP-5
 ON PLANS, YET THIS IS CHP-5,7 ON PANEL SCHEDULE. CHP-3
 ON PLANS, YET PANEL SCHEDULE INDICATES THIS AS ONE OF
 THE AIR HANDLERS. PLANS DO NOT INDICATE THE AIR HANDLER
 UNDER THE BAR.
 PLEASE CORRELATE ALL AND ADJUST CIRCUITS TO ALL AREAS,
 EQUIPMENT AND SPECIFIC ROOMS.
 PLEASE SEE 2-POLE CIRCUITS ON PANELS YET SHOWN AS
 SINGLE POLE CIRCUITS ON PLANS.
 PLEASE SEE 408.4, 310.16, 240.4 AS CIRCUITS,
 CONDUCTORS, LOADS ETC NEED TO BE VERIFIED AND CAN NOT
 BE DONE AT THIS TIME.
  
 16) NOTE: PLEASE SUBMIT COMPLETED LOAD CALCULATIONS PER
 NEC 220.
 PLEASE SEE 220.12, 220.14, 220.42, 220.44 FOR EXAMPLE.
 FBC 106.3.5.1.2, 106.1.2
  
 17) NOTE: PLEASE SEE PLANS MENTIONS THERE WILL BE A
 FIRE ALARM PANEL AND DEVICES BEING SUBMITTED AND DONE
 UNDER A SEPARATE PERMIT. THIS IS OK, HOWEVER PLEASE
 KNOW THE MINIMUM LOCATIONS AND LEVELS FOR ADA
 COMPLIANCE PER FBC CHAPTER 11 IS REQUIRED TO BE SHOWN
 ON THE BASE PLANS FOR MINIMUM DESIGN INTENT.
 PLEASE SE E11-4.28, .1, .2 AND .3(4).
  
 18) NOTE: PLEASE CORRELATE THE ELECTRICAL EQUIPMENT
 SCHEDULE AND PANEL SCHEDULE(S).
 FOR EXAMPLE PLEASE SEE THE DISHWASHER WHICH IS SHOWN AS
 208, 40MP AND 208/50AMP.
  
 19) NOTE: PLEASE KNOW AS FOR INFORMATIONAL PURPOSE
 ONLY. ALL LOW VOLTAGE SYSTEMS SUCH AS PHONE, CATV, AND
 DATA ETC ARE REQUIRED TO BE UNDER SEPARATE PERMITS.
 THE PLANS MAY CONTAIN THIS LOW VOLTAGE INFORMATION AND
 ANY LV PERMIT APPLICATIONS MAY REFERENCE THE BASE PLANS
 ONCE ISSUED FOR PERMIT.
 ANY LOW VOLTAGE NOT INCLUDED ON BASE BUILD OUT PLANS
 WILL REQUIRE SEPARATE PLANS.
 IF THERE ARE ANY QUESTIONS ON THIS PLEASE DO NOT
 HESITATE IN CONTACTING THIS REVIEWER.
  
 20) NOTE: PLEASE KNOW AS THERE ARE SEVERAL ITEMS WHICH
 ARE NOT ON PLANS AT THIS TIME OR NEED TO BE REVISED OR
 CHANGED, THERE MAY BE NEW COMMENTS ON THE FOLLOWING
 REVIEW WHICH CAN NOT BE MADE AT THIS TIM.
  
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-01-07 Cont ID  
Sent By mwennerg Date 2008-01-07 Time 11:20 Rev Time 0.00
Received By mwennerg Date 2008-01-07 Time 11:20 Sent To  
Notes
2008-01-07 11:22:02PLANS WERE PASSED ON 12/24/07. NEW FP, FA AND LIFE
 SAFETY SHEETS STAMPED, SIGNED AND DATED ON THIS DATE.
 IN ADDITION TO CUT SHEETS AND CALCULATIONS, PLEASE
 SUBMIT INFORMATION FOR DOUBLE DETECTOR CHECK ASSEMBLY
 WHEN SUBMITTING FOR FIRE SPRINKLER PERMIT.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-12-24 Cont ID  
Sent By mawillia Date 2007-12-24 Time 14:36 Rev Time 0.00
Received By mawillia Date 2007-12-24 Time 13:50 Sent To  
Notes
2007-12-24 14:36:25******APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED;HOWEVER THE APPROPIATE PLAN SHEETS TO
 BE FIRE-STAMPED WHEN THE OTHER PLAN REVIEWS HAVE BEEN
 SATISFIED.
  
  
 CAPT MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-11-20 Cont ID  
Sent By mawillia Date 2007-11-20 Time 12:53 Rev Time 0.00
Received By mawillia Date 2007-11-20 Time 11:47 Sent To  
Notes
2007-11-20 12:52:33******UNSAT*****
  
 *OLD COMMENTS:THE FOLLOWING COMMENTS FROM THE
 PREVIOUS FIRE PLAN REVIEW COMMENT STILL NEED TO BE
 ADDRESSED.
  
 10.ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM AN
 AREA HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS
 SHALL BE PROVIDED WITH PANIC HARDWARE OR FIRE EXIT
 HARDWARE.
  
 11.PROVIDE PRESCRITIVE STRENGHT AND SPECIFICATIONS
 FOR THE HANDRAILS.
  
 *NEW COMMENT:
  
 AA.KNOX LOCKING CAPS REQUIRED FOR THE FIRE DEPARTMENT
 CONNECTION.FOR AN APPLICATION, CONTACT WEST PALM
 BEACH FIRE PREVENTION BUREAU AT 561-805-6722.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS
 ADDRESSED
  
  
 CAPT MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-10-11 Cont ID  
Sent By mawillia Date 2007-10-11 Time 14:00 Rev Time 0.00
Received By mawillia Date 2007-10-11 Time 11:04 Sent To  
Notes
2007-10-11 11:43:32******DENIED*****
  
  
 01.ON THE SHEET TITLED GENERAL NOTES & LEGEND
 (DRAWING NUMBER 397-001-C2) UNDER BUILDING DESIGN DATA,
 AN INCORRECT/MISPRINT REFERENCE TO NFPA 101(200
 EDITION) IS LISTED.AS LISTED IN THE APPLICABLE CODES
 OF THE SAME SHEET, THE 2003 EDITION SHALL BE
 REFERENCED.
  
 02.THE NUMERICAL ADDRESS OF THE PROJECT SITE SHALL BE
 IN THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 03.ALL STRUCTURES UNDERGOING CONSTRUCTION,
 ALTERATION, OR DEMOLITION OPERATIONS SHALL COMPLY WITH
 NFPA 241.
  
 04.THE DEMOLITION AND/OR THE CONSTRUCTION OPERATIONS
 SHALL NOT INTERFERE OR HINDER EMERGENCY RESPONSE ACCESS
 TO THE PROPERTY OR VICINITY THEREOF (INCLUDING STREETS,
 ALLEYS, FIRE LANES) .
  
 05.PROVIDE TEMPORARY ADDRESS NUMBERS IF THE
 DEMOLITION EXTERIOR ELEVATION OPERATION HAS CAUSE FOR
 THE EXISTING ADRRESS TO BE REMOVED.
  
 06.ON THE NEW NITECLUB FRONT ELEVATION, SHOW/DISPLAY
 THE NUMERICAL ADDRESS ON THE BUILDING (NOT DOOR) TO BE
 VISIBLE FROM SOUTH NARCISSUS AVENUE.HURRICANE
 SHUTTERS SHALL NOT BE PERMITTED TO COVER OR CONCEAL
 ADDRESSES.
  
 07.PROVIDE A LIFE SAFETY PLAN SHEET WHICH ILLUSTRATES
 TRAVEL DISTANCE TO THE EXITS.EXIT LIGHTS, EMERGENCY
 LIGHTS, AND FIRE EXTINGUISHER(S) MAY ALSO BE INCLUDED
 ON THIS PLAN SHEET.
  
 08.NO EXIT LIGHTS AND EMERGENCY LIGHTS SHOWN IN THE
 REFLECTED CEILING LIGHTING PLAN.
  
 09.MEANS OF EGRESS FROM A ROOM OR SPACESHALL NOT BE
 PREMITTED THROUGH KITCHENS, STOREROOMS, RESTROOMS,
 CLOSETS, STAGES, DJ BOOTHS, OR HAZARDOUS AREAS.
  
 10.ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM AN
 AREA HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS
 SHALL BE PROVIDED WITH PANIC HARDWARE OR FIRE EXIT
 HARDWARE.
  
 11.PROVIDE PRESCRITIVE STRENGHT AND SPECIFICATIONS
 FOR THE HANDRAILS.
  
 12.PROVIDE SPECIFIATIONS OR DETAILS OF THE ADA RAMP.
  
 13.SPECIFY THE INTERIOR WALL AND CEILING FINISH
 MATERIAL FOR THE EXITS, EXIT AISLE CORRIDORS, AND ALL
 OTHER SPACES IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 14.SPECIFY THE INTERIOR FLOOR FINISH IN TERMS OF
 CLASS I OR CLASS II.
  
 15.FIRE ALARM SYSTEM TO BE CLASS A OR FULLY
 ADDRESSABLE, MONITORED, AND SHALL BE UL CERTIFICATED
 FOR CENTRAL STATION.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS
 ADDRESSED
  
  
 CAPT MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-04-11 Cont ID  
Sent By adarroug Date 2008-04-11 Time 14:05 Rev Time 0.00
Received By adarroug Date 2008-04-11 Time 14:05 Sent To  
Notes
2008-04-11 14:08:45TO "COMM" BD#18

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-01-22 Cont ID  
Sent By adarroug Date 2008-01-22 Time 12:15 Rev Time 0.00
Received By adarroug Date 2008-01-22 Time 12:15 Sent To B
Notes
2008-01-22 12:17:18TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-12-28 Cont ID  
Sent By spalmer Date 2007-12-28 Time 15:29 Rev Time 0.00
Received By spalmer Date 2007-12-28 Time 15:29 Sent To  
Notes
2007-12-28 15:29:12TO COMM BOARD # 40

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-11-30 Cont ID  
Sent By adarroug Date 2007-11-30 Time 16:34 Rev Time 0.00
Received By adarroug Date 2007-11-30 Time 16:34 Sent To  
Notes
2007-12-03 08:47:39TO "COMM" BD#45
2007-11-30 16:34:54WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-25 Cont ID  
Sent By adarroug Date 2007-10-25 Time 11:11 Rev Time 0.00
Received By adarroug Date 2007-10-25 Time 11:11 Sent To  
Notes
2007-10-30 14:46:58TO "BOB"#14
2007-10-25 11:12:02WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-11 Cont ID  
Sent By mawillia Date 2007-10-11 Time 11:04 Rev Time 0.00
Received By mawillia Date 2007-09-06 Time 16:54 Sent To  
Notes
2007-09-24 09:54:00TO "BOB"#1
2007-09-06 16:54:48WAITING FOR "BOB"--OK TO ROUTE TO "BOB" PER "RBROWN"

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2008-04-14 Cont ID  
Sent By tgordon Date 2008-04-14 Time 12:21 Rev Time 0.30
Received By tgordon Date 2008-04-14 Time 12:21 Sent To  
Notes
2008-04-14 12:22:20REVISION TO MECH. PLAN 397-001-C19.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-12-31 Cont ID  
Sent By tgordon Date 2007-12-31 Time 11:30 Rev Time 0.45
Received By tgordon Date 2007-12-31 Time 11:30 Sent To  
Notes
2007-12-31 11:38:40*** PROVISO ***
 1) OUTSIDE AIR INTAKE SHALL BE A MINIMUM OF 10 FEET
 FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS
 VENTS, CHIMNEYS, PLUMBING VENTS, ETC., SEE 2004 FBC/M
 401.5.1.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-12-10 Cont ID  
Sent By tgordon Date 2007-12-05 Time 14:45 Rev Time 1.30
Received By tgordon Date 2007-12-05 Time 14:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-11-08 Cont ID  
Sent By tgordon Date 2007-11-08 Time 08:12 Rev Time 2.30
Received By tgordon Date 2007-11-08 Time 08:12 Sent To  
Notes
2007-11-08 10:27:51PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) SEE PLANS PAGE C19A SHOWS THREE 8" DIA. GRAVITY
 EXHAUSTS, PAGE C19 SHOWS ONLY TWO BATHROOM EXHAUST
 FANS, PLEASE EXPLAIN OR CORRECT.
  
 2) PAGE C19A IS STATING GRAVITY EXHAUST. PAGE C19 FAN
 SCHEDULE SHOWS ELECTRICAL EXHAUST FANS, PLEASE EXPLAIN
 OR CORRECT.
  
 3) PAGE C19 FAN SCHEDULE SHOWS TWO EXHAUST FANS EACH AT
 405 CFM'S WITH A 4" DUCT, THAT WOULD PUT THE AIR
 VELOCITY AROUND 4,600 FPM. PLEASE SUBMIT DETAILED
 MANUFACTURER'S SPECIFICATION'S AND INSTALLATION
 INSTRUCTIONS FOR BATHROOM EXHAUST FANS.
  
 4) HVAC SCHEDULE SHOW THE HEATERS AT 150 BTUH THAT
 WOULD BE ABOUT 0.04 KW, ELECTRICAL PLANS SHOW THE
 HEATERS AT 12 KW. PLEASE CORRECT.
  
 5) PAGE C19 SHOWS THE SPACE ABOVE THE LAVATORIES IS AN
 OPEN PLENUM. PLEASE ADD A NOTE THAT STATES NO
 COMBUSTIBLE MATERIALS PERMITTED IN PLENUM, TO COMPLY
 WITH 2004 FBC/M 602.2.1. AND NO EXHAUST DUCTS UNDER
 POSITIVE PRESSURE, CHIMNEYS,OR VENTS PERMITTED IN
 PLENUM, TO COMPLY WITH 2004 FBC/M 601.3.
  
 6) PAGE C19 SHOWS THREE FLEX DUCTS, PLEASE SHOW SIZE OF
 FLEX, SEE 2004 FBC 106.3.5.
  
 7) PAGE C19 LEGEND SHOWS THE SYMBOL FOR AN EXHAUST FAN,
 SEE SYMBOLS IN BATHROOMS ARE SHOWING AS RETURN GRILLS.
 PLEASE CORRECT.
  
 8) SEE PAGE C19 MAKEUP AIR VENTILATION RATE. DO YOU
 MEAN OUTDOOR AIR? SEE 2004 FBC/M CH. 2 DEFINITIONS.
  
 9) MAKEUP AIR CALCULATIONS (OUTDOOR AIR ?) SHOWS 6000
 CFM AND 810 CFM BEING EXHAUSTED AT BATHROOMS = 5,190
 CFM OF POSITIVE PRESSURE. SEE 2004 FBC/M 403.1
 VENTILATION SYSTEM.
 MECHANICAL VENTILATION SHALL BE PROVIDED BY A METHOD OF
 SUPPLY AIR AND RETURN OR EXHAUST AIR. THE AMOUNT OF
 SUPPLY AIR SHALL BE APPROXIMATELY EQUAL TO THE AMOUNT
 OF RETURN AND EXHAUST AIR. IF OUTDOOR AIR CALCULATIONS
 WERE DONE BY ASHRAE 62.1 STANDARD THE BUILDING WOULD
 NOT BE AT SUCH A POSITIVE PRESSURE. PLEASE LOOK INTO.
 SEE 2004 FBC/M 403.4.
  
 10) PAGE C19 SHOWS A LARGE 72" X 32" GRILL, SEE YELLOW
 HIGH LIGHT ON PLAN. PLEASE EXPLAIN OR CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-09-24 Cont ID  
Sent By tgordon Date 2007-09-24 Time 11:49 Rev Time 0.45
Received By tgordon Date 2007-09-24 Time 11:49 Sent To  
Notes
2007-09-24 12:17:03PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE REMOVE THE ROOF FRAMING LAY-OUT FROM THE
 MECHANICAL PLAN PAGE 397-001-C19, AS IT CAN NOT BE READ
 AT THIS TIME.
  
 2) PLEASE SUBMIT A MECHANICAL PLAN THAT SHOW THE
 LOCATION OF THE EXISTING A/C UNITS AND ANY NEW UNITS.
 SHOW ALL NEW AND EXISTING SUPPLY AND RETURN AIR DUCTS.
 STATE WHAT IS NEW AND EXISTING ON PLAN.
  
 3) SHOW BATHROOM EXHAUST FANS AND CFM'S ON MECHANICAL
 PLAN, SEE FBC/M 403.3.
  
 4) MECHANICAL PLAN SHOWS A RETURN AIR DUCT IN THE
 BATHROOM, RETURN AIR GRILLS ARE NOT PERMITTED IN
 RESTROOM, SEE FBC/M 407.1. PLEASE CORRECT.
  
 5) THERE ARE TWO HVAC SCHEDULES ON THE MECHANICAL PLAN,
 PLEASE EXPLAIN OR CORRECT.
  
 6) SHOW OUTDOOR AIR CALCULATIONS ON MECHANICAL PLAN,
 SEE FBC/M 401.2.
  
 7)CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, SEE F.B.C. 106.1.1.
  
 8) THE CERTIFICATE OF AUTH. FOR YOUCHAK & YOUCHAK IS
 DELINQUENT, PLEASE CORRECT.
  
 9) WHEN SIGNING AND SEALING PLANS THE DATE MUST ALSO
 APPEAR, SEE FAC 61G15-23.002. PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 5 Status P Date 2008-04-17 Cont ID  
Sent By jleech Date 2008-04-17 Time 09:15 Rev Time 0.00
Received By jleech Date 2008-04-16 Time 07:36 Sent To  
Notes
2008-04-17 09:16:25PLUMBING REVISIONS SHT'S 20A, 20C AND NEW SHEET 32

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-01-08 Cont ID  
Sent By jleech Date 2008-01-08 Time 08:28 Rev Time 0.00
Received By jleech Date 2008-01-08 Time 08:06 Sent To  
Notes
2008-01-08 08:38:12PROVISO;
 703.4 EXISTING DRAIN AND SEWER INTEGRITY.
 708.3.5 CLEANOUTS REQUIRED.

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-12-21 Cont ID  
Sent By jleech Date 2007-12-21 Time 08:37 Rev Time 0.00
Received By jleech Date 2007-12-19 Time 07:59 Sent To  
Notes
2007-12-21 09:20:48DENIED;
 FROM OLD PLAN REVIEW;
 1. OK
 2. NO. MINUMUM PLUMBING FIXTURES TABLE 403.1 (A-2) THE
 TOP TABLE SHOULD BE USED IN THIS SECTION, THIS IS A
 NIGHTCLUB/BAR. NO KITCHEN TO PREPARE FOOD. 4-TOILETS
 ARE REQUIRED IN EACH BATHROOM, 1/40.
 3. YES
 4. NO NOTE ABOUT DRY VENT TO BE WASHED IS NOT THE
 ANSURE VENTS ARE STILL SHOWN IN AN AREA WHERE NO
 FIXTURE WILL WASH THEM.
  
 5. NO VENTING OF THE SANITARY SYSTEM IS STILL NOT
 CORRECT. I.E. NO VENTSHOWN ON SANITARY RISER DIAGRAM
 BACK BAR. VENTS IN BATHROOMS SHOULD
 COME FROM THE FIXTURES, NOT OF THE BRANCH DRAINS.
 (EXSTEND URINAL PIPE INTO A VENT.
 6. YES
 NEW COMMENTS
 1. RISER DIAGRAMS ARE VERY HARD TO FOLLOW. FBC BUILDING
 CHAPTER 1 WPB ADMINISTRATION SECTION 106.1.1. PLEASE
 DELETE THE OUTLINES OF THE EQUIPMENT, CEILING AND
 FLOOR. INDIRECT WASTE LINES LOOK LIKE THERE TIED INTO
 THE SANITARY SYSTEM, I.E. DISH WASHERS, SEE FBC
 PLUMBING SECTION 802.2.
 2. DRINKING FOUNTAIN IS NOT PERMITED TO BE IN A
 BATHROOM. PLUMBING SECTION 410.2. ALSO DRINKING
 FOUNTAIN IS REQUIRED TO MEAT THE ACCESSIBILITY CODE
 SECTIONS 11-4.15.1 THRU 11-4.15.5. SHOW DETAIL ON
 PLANS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-11-17 Cont ID  
Sent By jleech Date 2007-11-17 Time 07:59 Rev Time 0.00
Received By jleech Date 2007-11-17 Time 06:21 Sent To  
Notes
2007-11-17 08:25:23DENIED;
 1. OLD COMMENT 2F; (NO) FLOOR DRAINS ARE STILL SHOWN ON
 SANITARY RISER DIAGRAM. ALL INDIRECT WASTES SHALL GO TO
 AAPPROVED WASTE RECEPTOR AS DISCRIBED IN FBC-PLUMBING
 SECTION 802.3.
 NEW COMMENTS;
 2.TABLE 403.1(A-2) MIN. FIXTURE REQUIREMENTS HAS NOT
 BEEN MET. WOMANS ROOM REQUIRES 3 TOILETS, AND A
 DRINKING FOUNTAIN IS ALSO REQUIRED.
 3. WATER SERVICE IS NOT LARGE ENOUGH. SEE TABLE 603.1.
 SHOW CALCULATIONS.
 4. SANITARY RISER DIAGRAM; HORIZONTAL DRY VENTS ARE NOT
 PERMITED, SEE SECTION 905.3. (HI-LIGHTED) ON ONE SET OF
 PLANS.
 (A) THE 4" A.A.V.SHALL BE UPSTREAM OF THE
 FIXTURE GROUP (BAR) SEE SECTION 909.1, WET VENT.
 5. PLUMBING FIXTURELIST;ARE ALL TOILETS HANDICAP
 HIGHT?
 6. WATER RISER DIAGRAM; HOT WATER TO THE HAND SINKS AND
 LAVATORY'S SHOULD BE NO HOTER THAN 110, THE DISHWASHERS
 AND WASH SINKS WOULD REQUIRE HOTER WATER. SHOW HOW THIS
 WILL BE DONE.

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-09-26 Cont ID  
Sent By jleech Date 2007-09-26 Time 10:32 Rev Time 0.00
Received By jleech Date 2007-09-25 Time 14:22 Sent To  
Notes
2007-09-26 10:34:16DENIED;
 1.SEALED PLANS TO HAVE DATE WITH SIGNITURE.
 2. PLANS SEEM TO MEET FBC-2004 EXISTING BUILDING
 CHAPTER 7 ( LEVEL 3 ). THIS WOULD MEAN THE BATHROOMS
 ARE REQUIRED TO MEET THE REQUIREMENTS OF CHAPTER 11,
 HANDICAP REQUIREMENTS. ( BATHROOMS DO NOT COMPLY) 3.
 SHOW ON PLANS COMPLIANCE TO FBC-2004 PLUMBING TABLE
 403.1 (1A-2) NUMBER OF PEOPLE, FIXTURES REQUIRED. 4.
 SANITARY RISER DIAGRAM; ( FROM LEFT TO RIGHT)
 A)ICE BIN INDIRECT WASTE MUST GO DIRECTLY TO
 FLOOR SINK, NOT TIE INTO HAND SINK.
 B) DISHWASHER TO BE INDIRECTLY WASTED SEC.802.2
 TO A FLOOR SINK.
 C) ICE BIN NOT PERMITED TODISCHARGEINTO
 BATHROOM FLOOR DRAIN. (FLOOR SINK REQUIRED)
 D) TOILETS NOT VENTED
 E) ICE MACHINE CANNOT DISCHARGE INTO WOMANS ROOM
 FLOOR DRAIN.
 F) FLOOR SINKS OR HUB DRAINS ARE REQUIRED FOR
 ALL INDIRECT WASTE SEE SECTIONS 802.3 AND 802.3.1
 G) WATER AND SANITARY RISER DIAGRAMS ARE REQUIRED TO BE
 ISOMETRIC IN DESIGN AND REFLECT THE FLOOR PLAN.
 5. HOT WATER IS REQUIRED FOR THE HAND SINKS AND
 DISHWASHERS SECTION607.1.1.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2007-11-15 Cont ID  
Sent By mflis Date 2007-11-15 Time 16:17 Rev Time 0.00
Received By mflis Date 2007-11-15 Time 16:17 Sent To  
Notes
2007-11-15 16:18:37ZONING REVIEW: PASSED
  
 1) AWNINGS SHALL BE SEPARATE PERMIT.
 2) SIGNAGE SHALL BE SEPARATE PERMIT.
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 1 Status F Date 2007-10-09 Cont ID  
Sent By mflis Date 2007-10-09 Time 11:01 Rev Time 0.00
Received By mflis Date 2007-10-09 Time 11:01 Sent To  
Notes
2007-10-09 11:03:16ZONING REVIEW: FAILED
  
 1) PROFESSIONAL SEALS REQUIRE DATES
  
 2) AWNING AND SIGNAGE SHALL BE SUBMITTED UNDER SEPARATE
 PERMITS
  
 MATT FLIS - 822-1445