Plan Review Details - Permit 07090042
Plan Review Stops For Permit 07090042
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2008-10-15 Cont ID  
Sent By shill Date 2008-10-15 Time 08:23 Rev Time 0.00
Received By shill Date 2008-10-15 Time 08:23 Sent To  
Notes
2008-10-15 08:25:40***PROVISOS***
  
 SEPARATE ROOF PERMIT REQUIRED
  
 SUBMIT PRODUCT APPROVAL FOR WINDSOR REPUBLIC DOORS,
 SKYLIGHTS (-87PSF) AS A REVISION
  
 SUBMIT MECHANICAL EQUIPMENT ENGINEERING FBC1609
  
 CORRELATE REFLECTED CEILING PLAN WITH ELECTRICAL
 DRAWINGS PRIOR TO INSTALLATION
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2008-10-10 Cont ID  
Sent By shill Date 2008-10-10 Time 16:11 Rev Time 0.00
Received By shill Date 2008-10-10 Time 16:11 Sent To  
Notes
2008-10-10 16:13:24****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 COMMENTS FROM PREVIOUS LIST, NUMBERING REMAINS THE SAME
 FOR CONSISTENCY
  
 2.) IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY PRIOR
 TO PERMIT ISSUANCE, 2300 N JOG RD. PLEASE CALL
 561-233-5025 FOR MORE INFORMATION. THE PLANS MUST BE
 STAMPED AND THE RECEIPT IS TO BE INCLUDED WITH THE
 PERMIT APPLICATION.
  
 PLEASE PROVIDE IMPACT FEE RECEIPT. THE BILL AND STAMPED
 PLANS WERE PROVIDED, BUT A RECEIPT SHOWING THIS HAS
 BEEN PAID MUST BE SUBMITTED (EITHER VIA FAX 805-6731 OR
 EMAIL OR DELIVER TO FRONT COUNTER).
  
 PERMIT WILL BE ISSUED WITH PROVISOS:
  
 SEPARATE ROOF PERMIT REQUIRED
  
 SUBMIT PRODUCT APPROVAL FOR WINDSOR REPUBLIC DOORS,
 SKYLIGHTS (-87PSF) AS A REVISION
  
 SUBMIT MECHANICAL EQUIPMENT ENGINEERING FBC1609
  
 CORRELATE REFLECTED CEILING PLAN WITH ELECTRICAL
 DRAWINGS PRIOR TO INSTALLATION
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-09-17 Cont ID  
Sent By shill Date 2008-09-15 Time 15:34 Rev Time 0.00
Received By shill Date 2008-09-15 Time 15:34 Sent To  
Notes
2008-09-17 13:24:24****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 COMMENTS FROM PREVIOUS LIST, NUMBERING REMAINS THE SAME
 FOR CONSISTENCY
  
 1.) A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO
 PERMIT PICKUP, FS713.13.
  
 2.) IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY PRIOR
 TO PERMIT ISSUANCE, 2300 N JOG RD. PLEASE CALL
 561-233-5025 FOR MORE INFORMATION. THE PLANS MUST BE
 STAMPED AND THE RECEIPT IS TO BE INCLUDED WITH THE
 PERMIT APPLICATION.
  
 3.) AS THIS IS A THRESHOLD BUILDING AS DEFINED IN
 FS553.71(7), PLEASE ARRANGE WITH KEN CONRAD,
 561-805-6666, A MEETING INVOLVING THE OWNER, SPECIAL
 INSPECTOR, JOB INSPECTOR, CONTRACTOR AND ENGINEER. THIS
 MUST BE DONE PRIOR TO PERMIT ISSUANCE. THREE ORIGINAL
 SETS OF ALL DOCUMENTS ARE REQUIRED FOR PERMITTING AND
 FOR ALL SUBSEQUENT SUBMITTALS. SEE FBC*109.3.6.
  
 4.) PLEASE KEEP THE THRESHOLD INSPECTION PLAN (AND
 OTHER DOCUMENTS WHICH HAVE BEEN REVIEWED AND STAMPED)
 AS A PART OF THE PERMIT PACKAGE. THE PLAN AND THE
 PROPOSED SPECIAL INSPECTOR MUST BE APPROVED BY KEN
 CONRAD (SEE OTHER COMMENTS, 561-805-6666) PRIOR TO
 PERMIT ISSUANCE.
  
 5-56.) ADDRESSED.
  
 PERMIT WILL BE ISSUED WITH PROVISOS:
  
 SEPARATE ROOF PERMIT REQUIRED
  
 SUBMIT PRODUCT APPROVAL FOR WINDSOR REPUBLIC DOORS,
 SKYLIGHTS (-87PSF) AS A REVISION
  
 SUBMIT MECHANICAL EQUIPMENT ENGINEERING FBC1609
  
 CORRELATE REFLECTED CEILING PLAN WITH ELECTRICAL
 DRAWINGS PRIOR TO INSTALLATION
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-06-10 Cont ID  
Sent By shill Date 2008-06-10 Time 10:36 Rev Time 0.00
Received By shill Date 2008-06-06 Time 14:53 Sent To  
Notes
2008-06-10 10:36:32****CORRECTIONS****
 ***REVISED 6/23/08***
 ***REVISED 7/22/08 (ITEM 54)**
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 COMMENTS FROM PREVIOUS LIST, NUMBERING REMAINS THE SAME
 FOR CONSISTENCY
  
 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO
 PERMIT PICKUP, FS713.13.
  
 2.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY
 PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.PLEASE CALL
 561-233-5025 FOR MORE INFORMATION.THE PLANS MUST BE
 STAMPED AND THE RECEIPT IS TO BE INCLUDED WITH THE
 PERMIT APPLICATION.
  
 3.)AS THIS IS A THRESHOLD BUILDING AS DEFINED IN
 FS553.71(7), PLEASE ARRANGE WITH HAROLD PISKURA
 (INSPECTION SERVICES MANAGER - TEL:561 805 6711), A
 MEETING INVOLVING THE OWNER, SPECIAL INSPECTOR, JOB
 INSPECTOR, CONTRACTOR AND ENGINEER.THIS MUST BE DONE
 PRIOR TO PERMIT ISSUANCE.THREE ORIGINAL SETS OF ALL
 DOCUMENTS ARE REQUIRED FOR PERMITTING AND FOR ALL
 SUBSEQUENT SUBMITTALS.SEE FBC*109.3.6.
  
 THREE COMPLETE COLLATED SETS OF PERMIT DOCUMENTS
 REQUIRED FOR PERMIT ISSUANCE.ONLY TWO SETS OF THE
 SUBMITTAL PREPARED BY WOJCIESZAK & ASSOCIATES (ROOFTOP
 EQUIPMENT) WERE SUBMITTED, AND THE SUBMITTAL INCLUDED
 PHOTOCOPIES OF ENGINEERING.SEE FAC61G15-23.002,
 DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS.SEE OTHER COMMENT REGARDING THIS
 SUBMITTAL.
  
 4.)PLEASE KEEP THE THRESHOLD INSPECTION PLAN (AND
 OTHER DOCUMENTS WHICH HAVE BEEN REVIEWED AND STAMPED)
 AS A PART OF THE PERMIT PACKAGE.THE PLAN AND THE
 PROPOSED SPECIAL INSPECTOR MUST BE APPROVED BY HAROLD
 PISKURA (SEE OTHER COMMENTS, 561-805-6711) PRIOR TO
 PERMIT ISSUANCE.
  
 5.)ADDRESSED.
  
 6.)ADDRESSED; THE PLANS WILL BE STAMPED WITH A5 FLOOD
 ZONE DESIGNATION, FORM BOARD SURVEY REQUIRED
 (INFORMATIONAL ONLY).
  
 7-38.) ADDRESSED.
  
 39.)SELECT THE APPROVED ASSEMBLY YOU ARE USING IN THE
 ROOF PRODUCT APPROVAL.
  
 NOT ADDRESSED.THIS CAN BE DONE BY THE ROOFING
 CONTRACTOR AT THE TIME OF ROOF PERMIT APPLICATION. THIS
 WILL BE A PROVISO ITEM.
  
 40.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL IN
 ADDITION TO THE NOAS PROVIDED.IF A FLORIDA STATE
 PRODUCT APPROVAL IS UNAVAILABLE, PLEASE ADVISE AND A
 LOCAL PRODUCT APPROVAL WILL BE ISSUED USING THE NOA.
  
 PLEASE PRINT THE FLORIDA STATE PRODUCT APPROVALS IF
 AVAILABLE, WWW.FLORIDABUILDING.ORG
  
 41.)AN EVALUATION REPORT FOR WINDSOR REPUBLIC DOORS
 WAS SUBMITTED.FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED.PLEASE SEE WWW.FLORIDABUILDING.ORG; THIS
 COMPANY HAS FIVE DIFFERENT PRODUCT APPROVALS FOR SIDE
 HINGED DOORS.IT IS LIKELY THAT THE INFORMATION
 REQUIRED IS AVAILABLE ON THIS WEBSITE.
  
 42-46.) ADDRESSED.
  
 47.) THE GATE SWING WAS REVISED, BUT DOOR 323 NOW DOES
 NOT COMPLY WITH FBC1007.2 (DOOR SWING CHANGED SINCE
 LAST REVIEW), DOOR ENCROACHMENT, AS THE DOOR NOW OPENS
 ONLY 90DEGREES (OBSTRUCTED BY THE GATE FROM OPENING
 180DEGREES).AS DISCUSSED, THIS CAN BE REDLINED WITH A
 PROVISO THAT A REVISION BE SUBMITTED CHANGING DOOR
 HINGE OR DOOR SWING.
  
 48.)PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER
 OF RECORD, (SHOP DRAWING REVIEW STAMP OR LETTER),
 FBC*106.3.3.SHEET A9 SPECIFIES MOST OF THE COMPONENTS
 AND CLADDING.HOWEVER, FOR OTHER ITEMS, PLEASE
 REVIEW.
  
 49.)PROVIDE PRODUCT APPROVAL FOR THE SKYLIGHTS SHOWN
 ON A4.0, FAC9B72.
  
 3RD REVIEW, THE NEGATIVE DESIGN PRESSURE FOR ROOF
 COMPONENTS & CLADDING, ZONES 2 AND 3, IS -87.THE
 SKYLIGHT SPECIFIED ON A4.0 HAS A DP LIMITATION OF -80.
 THE PRODUCT APPROVAL SUBMITTED WAS A FLORIDA STATE
 PRODUCT APPROVAL; THE PRODUCT SPECIFIED ON THE PLAN
 REFERS TO A MIAMIDADE NOA.PLEASE RESOLVE THE DESIGN
 PRESSURE ISSUE AND CORRELATE PAPERWORK.
  
 50-53.) ADDRESSED.
  
 NEW COMMENTS:
  
 54.) REGARDING THE SUBMITTAL PREPARED BY WOJCIESZAK &
 ASSOCIATES:
  
 DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS
 AND ARE TO INCLUDE ALL INFORMATION REQUIRED BY
 FAC61G15-23.002, FS471 (CERTIFICATE OF AUTHORIZATION,
 PRINTED NAME AND LICENSE NUMBER OF INDIVIDUAL SEALING
 THE DOCUMENT, ETC.).THE ONLY EXCEPTION TO THIS
 REQUIREMENT IS PRODUCT APPROVALS, WHICH HAVE AN
 EXCEPTION TO THE REQUIREMENT FOR ORIGINAL DOCUMENTS
 WITHIN THE FLORIDA STATUTE.ALSO, PLEASE NOTE THE
 FOLLOWING:
  
 A. THE SUBMITTAL INCLUDES SPEC SHEETS (TOP RIGHT STATES
 JOB: SARI, LOUVER, MARK 4 AND JOB: TEMPLE ISRAEL, FAN,
 MARK SF 1 & 2) WHICH BOTH REFER TO NOA03-0422.05,
 GREENHECK SEVERE DUTY LOUVERED ENCLOSURES FLORIDA STATE
 PRODUCT APPROVAL 4825.1.PLEASE PRINT THE PRODUCT
 APPROVAL, THREE SETS.BASED ON THE NOA WHICH I VIEWED
 ONLINE, THIS PRODUCT APPEARS CODE COMPLIANT.SEE
 COMMENT 48; HAVE THE DESIGNER REVIEW THE PRODUCT PRIOR
 TO RESUBMITTAL (SHOP DRAWING REVIEW STAMP OR SIGNED AND
 SEALED LETTER).
  
 B. THE SUBMITTAL INCLUDES AN UNSIGNED LETTER FROM RICE
 ENGINEERING WHICH STATES THAT H-CUE 060-200 (EXHAUST
 FAN, SPEC SHEET REFERS TO MARK EF 14 & 15), WILL
 WITHSTAND WINDS UP TO 150MPH.BASED ON THE INFORMATION
 FOUND AT
 HTTP://WWW.GREENHECK.COM/PDF/FANS/PROMOHIGHWINDFANSNOVE
 MBER2006.PDF, IT APPEARS THAT THIS PRODUCT MAY HAVE A
 MIAMIDADE NOA OR FLORIDA STATE PRODUCT APPROVAL, BUT I
 WAS UNABLE TO LOCATE.THE LETTER STATES THAT THIS
 PRODUCT IS LIMITED TO -61 PSF.THEREFORE, THIS PRODUCT
 IS ACCEPTABLE FOR USE IN ZONE 1 BUT NOT ZONES 2 OR 3.
 PROVIDE THREE SETS OF PRODUCT APPROVALS, REVIEWED BY
 DESIGNER OF RECORD, AND CLARIFY INSTALLATION LOCATIONS
 OR APPLY FOR LOCAL PRODUCT APPROVAL IF AN EVALUATION
 REPORT (MIAMIDADE NOA OR FLORIDA STATE PRODUCT
 APPROVAL) IS NOT AVAILABLE.IT IS SUGGESTED THAT THE
 LOCATIONS BE INCLUDED ON SHEET A4.0 WHICH SHOWS ROOFTOP
 EQUIPMENT.NOTE THAT THE EDGE ZONE IS 14FEET, SEE
 SHEET S7.
  
 C. THE SUBMITTAL INCLUDES AN UNSIGNED LETTER FROM RICE
 ENGINEERING WHICH STATES THAT MODEL H-GB BELT DRIVE
 ROOF DOWNBLAST CENTRIFUGAL EXHAUST FAN, (AKA SPUN
 ALUMINUM ROOFTOP FAN, SPEC SHEET REFERS TO MARK EF 17),
 WILL WITHSTAND WINDS UP TO 150MPH.BASED ON THE
 INFORMATION FOUND AT
 HTTP://GFCPORTAL.COM/PDF/FANS/SPECIFICATIONS/CSI_%20HGB
 _%20SPEC_OCTOBER2007.RTF, IT APPEARS THAT THIS PRODUCT
 IS INCLUDED IN MIAMIDADE NOA 07-0503.07.THIS PRODUCT
 IS LIMITED TO -61 PSF.THEREFORE, THIS PRODUCT IS
 ACCEPTABLE FOR USE IN ZONE 1 BUT NOT ZONES 2 OR 3.
 PROVIDE THREE SETS OF PRODUCT APPROVALS, REVIEWED BY
 DESIGNER OF RECORD, AND CLARIFY INSTALLATION LOCATIONS.
 IT IS SUGGESTED THAT THE LOCATIONS BE INCLUDED ON SHEET
 A4.0 WHICH SHOWS ROOFTOP EQUIPMENT.NOTE THAT THE EDGE
 ZONE IS 14FEET, SEE SHEET S7.
  
 D. THE REPORTS FOR THE TRANE COMPANY ENTITLED SOUTH
 FLORIDA HURRICANE WIND LOAD LOAD ANALYSIS &
 CALCULATIONS PREPARED BY STAMOS & ASSOCIATES INC. ARE
 REQUIRED TO BE ORIGINAL AND TO INCLUDE ALL INFORMATION
 REQUIRED BY FAC61G15-23.002.CALCULATIONS ARE TO BE
 EITHER SIGNED, SEALED AND DATED ON EACH SHEET OR
 INCLUDE AN INDEX SHEET AS WELL AS ALL INFORMATION
 REQUIRED BY FAC61G15-23.002.THE ENGINEERING IS DATED
 10/21/93; THE ASCE STANDARD FOR WIND HAS BEEN REVISED
 THREE TIMES SINCE THAT DATE; THE CALCULATIONS WERE DONE
 IN ACCORDANCE WITH SFBC (A CODE NO LONGER IN EFFECT)
 AND SHOULD BE DONE IN ACCORDANCE WITH FBC/ASCE; PLEASE
 UPDATE ENGINEERING.THE CALCULATIONS SUBMITTED REFER
 TO SFBC AND APPLICABLE SFBC CODE REFERENCES; PLEASE
 REVISE TO REFLECT THE CURRENT CODE.THE CALCULATIONS
 USE P=37PSF FROM SFBC TABLE 2309.2; PLEASE USE
 PRESSURES AS PER FBC2004 SECTION 1609 OR ASCE7-02.
 DESIGN PRESSURES MUST BE CONSISTENT WITH PRESSURES
 DECLARED BY THE STRUCTURAL ENGINEER.PLEASE SPECIFY
 MINIMUM DISTANCE OF ROOFTOP UNIT TO EDGE OF ROOF
 (LOCATION IN ZONE 1 OR ZONE 2); IT IS NOT CLEAR WHY
 37PSF HAS BEEN USED OR IF ROOFTOP EQUIPMENT LOCATION
 WILL AFFECT DESIGN.THE CALCULATIONS STATE ON SHEET 3
 THAT REAR PANEL INFORMATION IS NOT AVAILABLE; PLEASE
 REVISE CALCULATIONS TO INCLUDE ALL APPLICABLE
 INFORMATION. THE CALCULATIONS STATE THAT SOME OF THE
 SCREW FASTENER PATTERN CALCULATIONS WERE OMITTED DUE TO
 ADEQUATE FASTENERS ILLUSTRATED, PLEASE REVISE TO
 INCLUDE ALL APPLICABLE INFORMATION.THE DESIGN WAS FOR
 120MPH, MOST LIKELY SUSTAINED RATHER THAN 3SECOND GUST;
 PLEASE CLARIFY DESIGN CRITERIA.
  
 E. A LETTER PREPARED BY KIRBY BICKNELL, PE AND REVIEWED
 BY JOHN D. BUEROSSEE, PE REGARDING THE EXTREME
 CONDITION MOUNTING KIT WAS SUBMITTED.DOCUMENTS
 PREPARED BY AN ENGINEER AND SUBMITTED FOR PUBLIC RECORD
 ARE TO BE SIGNED, SEALED, DATED ORIGINALS.PROVIDE THE
 SPEC SHEETS FOR THIS PRODUCT ALONG WITH ORIGINAL
 ENGINEERING IF A PRODUCT APPROVAL IS NOT AVAILABLE.
  
 F. ENGINEERING PREPARED BY BROMLEY COOK FOR PRECISION
 ALUMINUM PRODUCTS WAS PROVIDED.THIS PRODUCT REQUIRES
 FLORIDA STATE OR LOCAL PRODUCT APPROVAL, FAC9B72.
 PLEASE VERIFY; A MIAMIDADE NOA MAY BE AVAILABLE.
  
 ** MECHANICAL EQUIPMENT ENGINEERING FOR WIND CAN BE A
 PROVISO ITEM.ALL ITEMS 54A THROUGH F TO BE ADDRESSED
 THROUGH PLAN REVIEW AS A REVISION PRIOR TO
 INSTALLATION. ** (REVISED 7/22/8
  
 54.)PAYMENT OF IMPACT FEES AND APPROVAL OF THE
 SPECIAL INSPECTOR BY HAROLD PISKURA ARE REQUIRED PRIOR
 TO PERMIT ISSUANCE.ALL OTHER ISSUES IN THIS LIST CAN
 BE PROVISO ITEMS (SUBMITTED PRIOR TO INSTALLATION,
 AFTER PERMIT ISSUANCE).
  
 ***NEW COMMENTS 6/23/8***
  
 55.)SHEETS A3.0, A3.1, AND A3.2 WERE REMOVED FROM ONE
 SET AND RETAINED BY ANOTHER REVIEWER.PLEASE PRINT
 ANOTHER SET OF THESE SHEETS AND INSERT INTO THE SET
 FROM WHICH THEY HAVE BEEN REMOVED.
  
 56.)THIS PERMIT WILL BE ISSUED WITH THE PROVISO THAT
 THE REFLECTED CEILING PLAN IS TO BE REVISED TO
 CORRELATE WITH THE ELECTRICAL DRAWINGS PRIOR TO
 INSTALLATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-03-18 Cont ID  
Sent By shill Date 2008-03-18 Time 08:51 Rev Time 0.00
Received By shill Date 2008-03-07 Time 17:53 Sent To  
Notes
2008-03-18 08:56:12****CORRECTIONS****
 ****REVISED 3/18/8***
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 COMMENTS FROM PREVIOUS LIST, NUMBERING REMAINS THE SAME
 FOR CONSISTENCY
  
 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO
 PERMIT PICKUP, FS713.13.
  
 2.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY
 PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.PLEASE CALL
 561-233-5025 FOR MORE INFORMATION.THE PLANS MUST BE
 STAMPED AND THE RECEIPT IS TO BE INCLUDED WITH THE
 PERMIT APPLICATION.
  
 3.)AS THIS IS A THRESHOLD BUILDING AS DEFINED IN
 FS553.71(7), PLEASE ARRANGE WITH HAROLD PISKURA
 (INSPECTION SERVICES MANAGER - TEL:561 805 6711), A
 MEETING INVOLVING THE OWNER, SPECIAL INSPECTOR, JOB
 INSPECTOR, CONTRACTOR AND ENGINEER.THIS MUST BE DONE
 PRIOR TO PERMIT ISSUANCE.THREE ORIGINAL SETS OF ALL
 DOCUMENTS ARE REQUIRED FOR PERMITTING AND FOR ALL
 SUBSEQUENT SUBMITTALS.SEE FBC*109.3.6.
  
 4.)PROVIDE THE THRESHOLD INSPECTION PLAN.THE
 APPROVED CONTRACT WITH THE THRESHOLD INSPECTOR WILL BE
 REQUIRED IN THE PERMIT PACKAGE PRIOR TO PERMIT
 ISSUANCE.
  
 2ND REVIEW; I WAS UNABLE TO LOCATE THE COMPLIANCE
 STATEMENT AS REQUIRED BY FS553.79(7)(D).THIS IS
 REQUIRED FOR THE ARCHITECT AND ENGINEER.PLEASE ADVISE
 AS TO LOCATION OF THIS STATEMENT.
  
 NOTE THAT THE THRESHOLD INSPECTION PLAN IS TYPICALLY
 INCORPORATED INTO THE PLAN BY THE ARCHITECT IN ADDITION
 TO BEING A PART OF THE CONTRACT BETWEEN THE OWNER, THE
 INSPECTOR, AND THE CITY.
  
 5.)ADDRESSED.
  
 6.)ADDRESSED; THE PLANS WILL BE STAMPED WITH A5 FLOOD
 ZONE DESIGNATION, FORM BOARD SURVEY REQUIRED
 (INFORMATIONAL ONLY).
  
 7.)ADDRESSED.
  
 8.)FIRE SPRINKLER PLANS REQUIRED IF SPRINKLERS ARE
 REQUIRED FOR CODE COMPLIANCE, FBC*106.3.5.1.1(5),
 FS553.79 (2).
  
 SHEETS FS 1, 2, AND 3 WERE ADDED.HOWEVER, THEY DO NOT
 SHOW SPRINKLER HEAD LAYOUT, ONLY HAZARD CLASSIFICATION
 PER NFPA.PLEASE PROVIDE PLANS AS REQUIRED.
  
 9-24.) ADDRESSED.
  
 25.)THE GATES ARE REQUIRED TO BE ACCESSIBLE,
 FBC11-4.1.3(9), ACCESSIBLE MEANS OF EGRESS.PROVIDE A
 DETAIL TO SHOW COMPLIANCE.
  
 THE RESPONSE LETTER STATES THAT A10.1 SHOWS THIS
 HARDWARE GROUP AS ACCESSIBLE.SEE HARDWARE GROUP 13
 AND 14; I AM UNABLE TO DISCERN FROM THE DESCRIPTION
 THAT THIS IS ACCESSIBLE HARDWARE.PLEASE CLARIFY,
 EITHER BY REVISING THE DESCRIPTION OR INCLUDING SPEC
 SHEETS FOR THE GATE HARDWARE.
  
 26-36.) ADDRESSED.
  
 37.)SIGN THE OWNER/AGENT LINE OF THE ENERGY CALC,
 FBC13-103.1.
  
 38.)ADDRESSED.
  
 39.)SELECT THE APPROVED ASSEMBLY YOU ARE USING IN THE
 ROOF PRODUCT APPROVAL.
  
 NOT ADDRESSED.THIS CAN BE DONE BY THE ROOFING
 CONTRACTOR AT THE TIME OF ROOF PERMIT APPLICATION.
  
 40.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL IN
 ADDITION TO THE NOAS PROVIDED.IF A FLORIDA STATE
 PRODUCT APPROVAL IS UNAVAILABLE, PLEASE ADVISE AND A
 LOCAL PRODUCT APPROVAL WILL BE ISSUED USING THE NOA.
  
 PLEASE PRINT THE FLORIDA STATE PRODUCT APPROVALS,
 WWW.FLORIDABUILDING.ORG
  
 41.)FOR THE EXCLUSIVE WOOD DOORS AND THE REPUBLIC
 DOORS, PRINT THE FLORIDA STATE PRODUCT APPROVAL,
 EVALUATION REPORT AND INSTALLATION INSTRUCTIONS FROM
 THE INTERNET.
  
 NOT ADDRESSED.THE PAPERWORK PROVIDED SHOWS A DESIGN
 PRESSURE OF +-47, SEE SHEET S10, 59.2 REQUIRED.
  
 42.)FOR THE REPUBLIC DOORS, MARK WHICH PRODUCT(S) YOU
 ARE INSTALLING.
  
 2ND REVIEW, FL4304 WAS CIRCLED.PLEASE GO TO THE
 WEBSITE, WWW.FLORIDABUILDING.ORG, AND PRINT THE PRODUCT
 APPROVAL.CONFIRM THAT THE SUPPLEMENTARY DOCUMENTATION
 (EVALUATION REPORT, INSTALLATION INSTRUCTIONS) MATCHES
 THE ONES ON THE INTERNET.NOTE THAT FL4304 (CIRCLED ON
 THE LIST OF MANUFACTURER?S PRODUCTS) HAS A DESIGN
 PRESSURE OF 114, BUT THE PAPERWORK IS FOR A DOOR WITH A
 DESIGN PRESSURE OF 60PSF.IT DOES NOT APPEAR TO BE THE
 SAME DOOR.
  
 43.)WHEN RESUBMITTING, PLEASE INCLUDE A RESPONSE
 LETTER STATING HOW AND WHERE EACH ITEM WAS ADDRESSED.
  
 NEW COMMENTS:
  
 44.)SHOW ALL REQUIRED DETECTABLE WARNINGS,
 FBC11-4.29.5.
  
 45.)A SECOND EXIT DOOR WAS ADDED TO THE CHAPEL.SEE
 LANDSCAPE SHEETS.THE LANDSCAPE PLANS WERE NOT REVISED
 TO REFLECT FLOOR PLAN CHANGES TO THE CHAPEL AND THE
 OFFICE AREA.IT APPEARS THAT THIS DOOR OPENS ONTO AN
 AREA WHICH IS NOT PAVED AND HAS AN IRRIGATION HEAD AT
 THIS LOCATION.SEE FBC1008.1.5, DOOR LANDING REQUIRED,
 AND FBC1003.4, FLOOR SURFACE.
  
 46.)A1.1, SEE FBC 1024.10, AISLE ACCESSWAYS.SHOW
 MINIMUM REQUIRED WIDTH.
  
 47.)PLEASE SHOW OCCUPANT LOAD SERVED BY THE DOUBLE
 GATES, ADJACENT TO CLASSROOM 331.SEE FBC1008.1.2. THE
 PATH OF EGRESS IS SHOWN AS GOING TOWARDS THE ASSEMBLY
 AREA RATHER THAN TOWARDS THE PARKING LOT. PLEASE
 EXPLAIN THE LOGIC AS IT APPEARS THAT THE EGRESS PATH
 WILL MOST LIKELY BE GOING TOWARDS THE PARKING LOT AREA.
 IT ALSO APPEARS THAT, IF USED, OCCUPANT LOAD WHICH
 THESE GATES SERVE MAY BE GREATER THAN 50.CAN THESE
 GATES SWING BOTH DIRECTIONS (180 DEGREE SWING RATHER
 THAN 90DEGREE AS SHOWN)?
  
 48.)PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER
 OF RECORD, (SHOP DRAWING REVIEW STAMP OR LETTER),
 FBC*106.3.3.SHEET A9 SPECIFIES MOST OF THE COMPONENTS
 AND CLADDING.HOWEVER, FOR OTHER ITEMS, PLEASE
 REVIEW.
  
 49.)PROVIDE PRODUCT APPROVAL FOR THE SKYLIGHTS SHOWN
 ON A4.0, FAC9B72.
  
 50.)PLEASE CORRELATE A9 AND S10.FOR INSTANCE,
 OPENINGS 1 AND 2 ARE SHOWN AS 2X8 ON A9, 1FT8IN X
 7FT8IN ON S10.ARE THE OPENINGS THE SAME?IF NOT,
 PLEASE CORRELATE.
  
 51.)INFORMATIONAL ONLY; S10 HAS TWO SETS OF DESIGN
 PRESSURES, ZONE 4 AND ZONE 5.ALL PRODUCT APPROVALS
 WILL BE REVIEWED TO THE MOST STRINGENT.IF THIS IS NOT
 ACCEPTABLE, PLEASE REVISE SO THAT ONLY ONE NEGATIVE
 DESIGN PRESSURE IS INCLUDED FOR EACH OPENING.
  
 52.ELECTRIC SHEETS ARE MISSING FROM THE SET WHICH WAS
 REVIEWED FOR BUILDING.WHEN RESUBMITTING, PLEASE
 CONFIRM THAT EACH SET IS COMPLETE AND IDENTICAL.
  
 53.ON A1.1, THERE ARE DARK LINES ACROSS THE AREA
 WHERE THE PEW AISLES CONVERGE, ADJACENT TO THE STAGE.
 WHAT ARE THESE LINES?
  
 54.)WHEN RESUBMITTING, PLEASE CLOUD ALL CHANGES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-05 Cont ID  
Sent By shill Date 2007-10-05 Time 11:57 Rev Time 0.00
Received By shill Date 2007-10-05 Time 11:57 Sent To  
Notes
2007-10-05 11:57:44****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO
 PERMIT PICKUP, FS713.13.
  
 2.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY
 PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.PLEASE CALL
 561-233-5025 FOR MORE INFORMATION.THE PLANS MUST BE
 STAMPED AND THE RECEIPT IS TO BE INCLUDED WITH THE
 PERMIT APPLICATION.
  
 3.)AS THIS IS A THRESHOLD BUILDING AS DEFINED IN
 FS553.71(7), PLEASE ARRANGE WITH HAROLD PISKURA
 (INSPECTION SERVICES MANAGER - TEL:561 805 6711), A
 MEETING INVOLVING THE OWNER, SPECIAL INSPECTOR, JOB
 INSPECTOR, CONTRACTOR AND ENGINEER.THIS MUST BE DONE
 PRIOR TO PERMIT ISSUANCE.THREE ORIGINAL SETS OF ALL
 DOCUMENTS ARE REQUIRED FOR PERMITTING AND FOR ALL
 SUBSEQUENT SUBMITTALS.SEE FBC*109.3.6.
  
 4.)PROVIDE THE THRESHOLD INSPECTION PLAN.THE
 APPROVED CONTRACT WITH THE THRESHOLD INSPECTOR WILL BE
 REQUIRED IN THE PERMIT PACKAGE PRIOR TO PERMIT
 ISSUANCE.
  
 5.)THE PRINTED NAME OF THE PERSON SEALING THE
 DOCUMENT IS TO BE ON EACH SHEET, SLIDER ENGINEERING,
 FAC61G15-23.002.
  
 6.)THIS PROJECT IS IN AN A5 HIGH HAZARD FLOOD ZONE. A
 FORM BOARD ELEVATION CERTIFICATE AND FFE CERTIFICATE
 WILL BE REQUIRED TO BE FILED WITH THIS OFFICE DURING
 THE CONSTRUCTION PROCESS.ALL FFES, INCLUDING
 MECHANICAL EQUIPMENT, ARE TO BE 6? ABOVE BASE FLOOD
 ELEVATION, CITY OF WEST PALM BEACH MUNICIPAL CODE
 94-546(B).INCLUDE THIS REQUIREMENT ON THE PLAN.
  
 7.)PROVIDE A CODE SUMMARY; HOW COMPLIANCE WITH FBC
 TABLE 503, DECLARE MIXED OR NONSEPARATED USE,
 INCIDENTAL OR ACCESSORY USES, FBC302.ALL AREA
 INCREASE CALCULATIONS ARE TO BE ON THE PLAN.IF ANY
 FIRE RATED WALLS ARE REQUIRED, SHOW ON THE PLAN AND
 PROVIDE DETAILS.
  
 8.)FIRE SPRINKLER PLANS REQUIRED IF SPRINKLERS ARE
 REQUIRED FOR CODE COMPLIANCE, FBC*106.3.5.1.1(5),
 FS553.79 (2).
  
 9.)SEE CITY OF WEST PALM BEACH STANDARD FOR PARKING
 STRIPING, SEE ATTACHED AND ZONING COMMENTS, SHEET
 A1.0.
  
 10.)PLEASE NOTE THAT THE ROOM DESIGNATION NUMBERS ARE
 DIFFERENT ON SHEET A1.0 FROM OTHER SHEETS IN THE PLAN.
 IT IS NOT A REQUIREMENT FOR THEM TO BE CONSISTENT, BUT
 NOTE THAT SHEET A1.0 IS THE EASIEST SHEET TO USE FOR
 REFERENCE AS IT SHOWS THE ENTIRE PLAN.
  
 11.)SIMMONS & WHITE SHEET 2, RAMP SLOPE IS SHOWN AS
 12:1 MAX.DO YOU MEAN 1:12?
  
 12.)NO ACCESS AISLE SHOWN FOR PARKING SPACE 55,
 A1.0.
  
 13.)THERE APPEARS TO BE AN UNNECESSARY ACCESS AISLE
 BETWEEN TWO NON ACCESSIBLE SPACES, 58 AND 59, IS THIS
 CORRECT?A1.0
  
 14.)SHOW THE PASSENGER LOADING ZONE FBC11-4.6.6.
  
 15.)PROVIDE A DETAIL FOR THE RAMP HANDRAIL SHOWN ON
 A1.0, EAST SIDE.FBC11-4.8.5.
  
 16.)PROVIDE A DETAIL FOR THE STAIR HANDRAILS,
 FBC11-4.9.4.THE HANDRAILS SHOWN DO NOT APPEAR TO HAVE
 THE HANDRAIL EXTENSIONS AT THE BOTTOM FBC11-4.9.4(2)
 (12INCHES PLUS WIDTH OF ONE TREAD).
  
 17.)A LANDING IS REQUIRED AT THE BOTTOM OF THE RAMP,
 A2.0 FBC11-4.8.4.
  
 18.)HANDRAIL EXTENSIONS REQUIRED TOP AND BOTTOM OF
 THE RAMP A2.0 FBC11-4.8.5.
  
 19.)A2.0 SHOWS DETAIL INDICATOR 7-A7.5 IN THE
 SANCTUARY AREA, BUT THIS DETAIL IS FOR A GATE.ALSO
 SEE 2-A7.3, CHECK ALL.
  
 20.)A2.0 DETAIL INDICATOR 3-A7.5 AT THE RAMP IS FOR
 THE STAIR DETAIL; SHOULD THIS BE 4-A7.5?PROVIDE THE
 HEIGHT, SEE FBC11-4.4.
  
 21.)ON THE LIFE SAFETY PLAN, PLEASE SHOW EGRESS WIDTH
 AND OCCUPANT LOAD SERVED FOR EACH COMPONENT, OCCUPANT
 LOAD, TRAVEL DISTANCE, WIDTH OF COMPONENTS OF MEANS OF
 EGRESS (HALLWAYS AND DOORS, ETC.), OVER ALL DIMENSIONS
 FOR THE AREAS.THE EGRESS PLAN A2.3 SHOWS EXITING FROM
 THE SANCTUARY, BUT EXIT DISCHARGE IS TO BE TO THE
 PUBLIC WAY.THE LIFE SAFETY PLAN SHOULD CLEARLY SHOW
 COMPLIANCE WITH FBC CHAPTER 10.TOTAL OCCUPANT LOAD
 WAS SHOWN ON ANOTHER SHEET, BUT SOME OF THESE AREAS
 SHARE THE EXIT ACCESS AND THIS NUMBER IS NOT SHOWN ON
 THE PLAN.PLEASE LABEL ROOM NUMBERS.PLEASE CONTACT
 ME IF YOU WISH TO DISCUSS.
  
 22.)AREAS INCLUDED IN THE OCCUPANT LOAD ON A2-2 ARE
 NOT ENTIRELY CLEAR.FOR INSTANCE, HOW WAS THE STAGE
 AREA INCLUDED IN THIS CHART, OR ACCESSORY STORAGE
 AREAS?SEE FBC TABLE 1004.1.2.
  
 23.)AREA 201 DOES NOT APPEAR TO BE INCLUDED AS HAVING
 AN OCCUPANT LOAD.SEE FBC1004.1.2, NUMBER OF OCCUPANTS
 CANNOT BE LESS THAN FBC TABLE 1004.1.2.IT APPEARS
 THAT THE OCCUPANT LOAD PROVIDED IS ACTUAL OCCUPANT
 LOAD, FBC1004.1.1.
  
 24.)TOTAL OCCUPANT LOAD GOING THROUGH EXIT DISCHARGE
 336A, 336D IS NOT SHOWN.
  
 25.)THE GATES ARE REQUIRED TO BE ACCESSIBLE,
 FBC11-4.1.3(9), ACCESSIBLE MEANS OF EGRESS.PROVIDE A
 DETAIL TO SHOW COMPLIANCE.
  
 26.)SHOW WHEELCHAIR AREAS AND SEATING, FBC11-4.33.3.
  
 27.)IF TOILET ROOMS ARE PROVIDED, THEN EACH PUBLIC
 AND COMMON USE TOILET ROOM SHALL COMPLY WITH
 FBC11-4.22, FBC11-4.1.3(11).PRIVATE TOILET SPACES
 SHALL BE ADAPTABLE, SEE BATHROOM ADJACENT TO AREA 103
 SHEET A2.1.PROVIDE A GRAB BAR BACKING DETAIL AND SHOW
 TURNING RADIUS, DOOR MANEUVERING CLEARANCE FBC11 FIGURE
 25.ALSO SHOW DISTANCE REQUIRED FOR TWO DOORS IN A
 SERIES, FBC11-4.13.7.
  
 28.)LOUNGE SINKS ARE TO COMPLY WITH FBC11-4.2.4,
 PROVIDE A DETAIL.THE SECTIONS SHOWN ON A7.2 SHOW
 DOORS BLOCKING THE REQUIRED KNEE CLEARANCE.
 FBC11-4.24.3.
  
 29.)DOUBLE DOORS IN ROOMS 316 AND 317, ONE LEAF IS TO
 MEET THE REQUIREMENTS OF FBC11-4.13, FBC11-4.13.4.
  
 30.)PROVIDE A DETAIL AND SHOW LOCATION OF SEATING
 COMPLYING WITH FBC11-4.1.3(18) AND (19).
  
 31.)SHOW COMPLIANCE WITH FBC11-4.1.3(19)(B).IF YOU
 FEEL THAT THIS (OR ANY OF THE ACCESSIBILITY
 REQUIREMENTS) DOES NOT APPLY, PLEASE CONTACT ME AND
 DOCUMENT THE EXEMPTION IN WRITING WITH THE
 RESUBMITTAL.
  
 32.)PROVIDE ROOF DRAINAGE CALCULATIONS, FBC1503.4.
 SHOW LOCATION OF SCUPPERS AND HEIGHT OF SCUPPER IN THE
 PARAPET WALL.
  
 33.)A10.0, WALL FINISH W1 STATES TO SEE SHEET A- FOR
 DETAILS.PLEASE COMPLETE REFERENCE.
  
 34.)ROOM 316 AND 317 SHOW W1 ON THE FLOOR PLAN DETAIL
 A7.0, W1* FOR FINISH.IT IS NOT CLEAR WHAT THE
 ASTERISK DESIGNATES.PROVIDE THE DETAIL FBC1210.2.
 CHECK ALL BATHROOM WALL FINISHES AND REVISE A10.0
 ACCORDINGLY.
  
 35.)DETAIL 2 A6.0 HAD TEXT AT THE TOP RIGHT WHICH IS
 ILLEGIBLE (CUT OFF).EITHER REMOVE THE PARTIAL TEXT OR
 PROVIDE THE TEXT IN A LEGIBLE FORMAT.
  
 36.)SHEET S10 STATES EDGE ZONE IS *'*", PLEASE
 REVISE.
  
 37.)SIGN THE OWNER/AGENT LINE OF THE ENERGY CALC,
 FBC13-103.1.
  
 38.)PROVIDE ROOF COMPONENTS AND CLADDING DESIGN
 PRESSURE, FBC1603.1.4.
  
 39.)SELECT THE APPROVED ASSEMBLY YOU ARE USING IN THE
 ROOF PRODUCT APPROVAL.
  
 40.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL IN
 ADDITION TO THE NOAS PROVIDED.IF A FLORIDA STATE
 PRODUCT APPROVAL IS UNAVAILABLE, PLEASE ADVISE AND A
 LOCAL PRODUCT APPROVAL WILL BE ISSUED USING THE NOA.
  
 41.)FOR THE EXCLUSIVE WOOD DOORS AND THE REPUBLIC
 DOORS, PRINT THE FLORIDA STATE PRODUCT APPROVAL,
 EVALUATION REPORT AND INSTALLATION INSTRUCTIONS FROM
 THE INTERNET.
  
 42.)FOR THE REPUBLIC DOORS, MARK WHICH PRODUCT(S) YOU
 ARE INSTALLING.
  
 43.)WHEN RESUBMITTING, PLEASE INCLUDE A RESPONSE
 LETTER STATING HOW AND WHERE EACH ITEM WAS ADDRESSED.
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2008-09-30 Cont ID  
Sent By dpalmer Date 2008-09-30 Time 11:21 Rev Time 0.00
Received By dpalmer Date 2008-09-30 Time 11:21 Sent To  
Notes
2008-09-30 11:23:37 
 ** TEMPORARY DENIED REVIEW **
  
 1) NOTE: PLEASE SEE REVIEW NOTES FROM PREVIOUS REVIEW.
 PROVISO IS SET FOR NOTES #2 AND 3 HOWEVER NO LETTER
 SUBMITTED FOR NOTE #1 NOR FEE BALANCE PAID.
 ** ELECTRICAL PLANS ARE ALREADY STAMPED AND REVIEW WILL
 GO INTO A "P" STATUS ONCE REVIEW NOTE #1 IS ADDRESSED
 FROM PREVIOUS REVIEW.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-08-27 Cont ID  
Sent By dpalmer Date 2008-08-27 Time 16:04 Rev Time 0.00
Received By dpalmer Date 2008-08-27 Time 16:04 Sent To  
Notes
2008-08-27 16:05:02 
  
  
  
  
 ** TEMPORARY DENIED **
  
 *** NOTE #1 NEEDS TO BE ADDRESSED AT THIS TIME. COMMENT
 #2 AND #3 CAN BE DONE AS A PROVISO.
  
  
 1) NOTE: THE LETTER OF UNDERSTANDING FROM OWNER NEEDS
 TO BE SUBMITTED WITH REFERENCE TO THE 4X FEE WHICH WAS
 NOT PAID. THE LETTER IS TO ACKNOWLEDGE THE FEE AMOUNT
 AND UNDERSTAND THAT A HOLD WILL BE PLACED ON THE
 CERTIFICATE OF OCCUPANCY UNTIL FEE IS PAID IN FULL. FOR
 ANY TECHNICAL LEGAL QUESTIONS PLEASE CONTACT THE CITY
 ATTORNEY?S OFFICE.
  
 2) NOTE: LOCATION OF UPS IN HALL WITH THE SIZE AS
 SPECIFIED ON THE MANUFACTURE CUT SHEETS NEEDS TO BE
 VERIFIED. IN FACT BASED ON THE UNIT SPEC SHEETS THE
 UNIT AS SUBMITTED IS TOO LARGE FOR LOCATION.
 PLEASE REVISE AND SUBMIT DOCUMENTS AS NEEDED.
  
 2) NOTE: SHEETS E-7.0 AND E-8.0 CONTAIN THE NOTES FOR
 MINIMUM CD LEVELS FOR STROBE DEVICES TO MEET FBC
 11-4.28.3(4) HOWEVER PLANS STILL SHOW SEVERAL STROBE
 LOCATIONS WITH CANDELA LEVELS BELOW THE MINIMUM OF 75.
 (MANY AT 15)
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-06-18 Cont ID  
Sent By dpalmer Date 2008-06-18 Time 12:07 Rev Time 0.00
Received By dpalmer Date 2008-06-18 Time 12:07 Sent To  
Notes
2008-06-18 12:08:04** DENIED3RD REVIEW **
  
 ** PLEASE SEE THERE ARE SEVERAL COMMENTS FROM THE TWO
 PREVIOUS REVIEWS WHICH ARE STILL IN NEED OF ADDRESSING.
 THERE ARE ALSO SOME NEW COMMENTS DUE TO SOME CHANGES
 MADE TO PREVIOUS PLANS, DESIGN ETC.
  
 1) NOTE: THERE WAS A MEETING HELD AFTER THE LAST REVIEW
 IN WHICH THE LIGHTING CONTROL SYSTEM WAS GOING TO BE
 SUBSTANTIALLY CHANGED/REVISED. THIS REVIEWER MENTIONED
 TO POSSIBLY HAVE AN ADDITIONAL MEETING BEFORE PLANS
 WERE RESUBMITTED TO GO OVER ANY QUESTIONS FOR CHANGES
 WHICH WERE GOING TO BE MADE. NO CONTACT WAS MADE TO
 THIS REVIEWER. THE COMMENTS BELOW ARE BASED ON PLANS
 AND SUPPORTING REQUIRED DOCUMENTS WHICH DO NOT SHOW *
 MINIMUM* BUILDING CODE COMPLIANCE.
  
 ** THERE ARE EXTENSIVE EXAMPLES WHICH ARE LISTED BELOW
 UNDER NOTES. THESE ARE GIVEN AS A BENEFIT IN AN EFFORT
 FOR PLANS TO BE CORRECTED ON THE FOLLOWING REVIEW FOR
 PERMIT ISSUANCE. THE EXAMPLES ARE GIVEN AS A BENEFIT
 ONLY AND NOT AN EXHAUSTED LIST OF EVERY SPECIFIC ITEM.
 THE CODE SECTIONS ARE ONCE AGAIN GIVEN.
  
 2) NOTE: PLEASE SEE FBC 13-415.2.ABC.1.1, .1.2, .1.3,
 13-400, 13-400.3.A, 13-415.2 ETC AS THE SUBMITTED
 ENERGY CALCULATIONS DO NOT CORRELATE WITH THE SUBMITTED
 PLANS. PLEASE SEE THERE SEVERAL LIGHTING FIXTURES,
 WATTAGES ETC ON PLANS WHICH ARE NOT SHOWN FOR THE
 CORRECT NUMBER OF FIXTURES, WATTAGES OF FIXTURES IN THE
 INPUT DATA REPORT OF THE SUBMITTED ENERGY CALCULATIONS.
 THE INPUT DATA REPORT WILL BE NOTED AS IDR FOR THE
 REMAINDER OF THIS COMMENT.
  
 FOR EXAMPLE:
 PLEASE SEE FIXTURE M WHICH IS SHOWN FOR AN EXTERIOR
 LIGHT FIXTURE ON PLANS AT THE FRONT ENTRANCE AND ON THE
 FIXTURE LEGEND HOWEVER THESE ARE NOT SHOWN/LISTED ON
 THE IDR FOR EXTERIOR LIGHT FIXTURES.
  
 FOR EXAMPLE:
 PLEASE SEE PLANS WHICH SHOWS A TOTAL OF 50+ 35W
 FIXTURES WHICH ARE LABELED WITH DIFFERENT ALPHA
 DESIGNATIONS YET THE IDR ONLY SHOWS 22- TOTAL 35W
 FIXTURES. PLANS CLEARLY SHOW A SUBSTANTIALLY HIGHER
 AMOUNT OF FIXTURES.
  
 FOR EXAMPLE:
 PLEASE SEE THE *H-1* FIXTURE SHOWN ON PLANS WHICH IS
 LISTED ON THE FIXTURE LEGEND AS 2-26W BULBS WHICH IS
 ABOUT 52WATTS/VA, YET THE IDR DOES NOT INCLUDE ANY 52W
 FIXTURES. THE CLOSEST WATTAGE OR VA LISTED IS NOTED AS
 THE STAIR FIXTURES. THE STAIR FIXTURES LISTED ON THE
 FIXTURE LEGEND ARE SHOWN AS 28W AND TWO IN EACH RAIL
 GIVES THE 56WATTS ALREADY ACCOUNTED FOR.
  
 ***** THIS IS ONLY A FEW EXAMPLES OF THE EXTERIOR
 LIGHTS SHOWN ON PLANS WHICH DO NOT COORDINATE WITH THE
 SUBMITTED ENERGY CALCULATIONS. THERE ARE OTHERS.
  
 PLEASE SEE THE SAME SECTIONS OF THE CODES ABOVE IN THIS
 SAME NOTE FOR ALL FIXTURES ON THE INTERIOR OF THE
 BUILDING WHICH IS REQUIRED TO BE PLACED INTO THE
 SUBMITTED IDR/ENERGY CALCULATIONS.
 SOME ADDITIONAL EXAMPLES OF FIXTURES ON THE INTERIOR
 LIGHTS WILL ALSO BE GIVEN AS A BENEFIT.
  
 FOR EXAMPLE:
 PLEASE SEE THE AREAS SUCH AS ROOM #100/SANCTUARY WHICH
 ARE STILL SHOWING FIXTURES WHICH ARE NOT LISTED ON THE
 IDR.
 PLEASE SEE THE TRACK LIGHTING FIXTURES WHICH BASED ON
 THE WATTAGE OF FIXTURE LEGEND IS NOT LISTED ON THE
 IDR.
  
 FOR EXAMPLE:
 PLEASE SEE THE *G1* FIXTURES IN SAME ROOM #100 ARE NOT
 THE SAME AS ON IDR.
  
 FOR EXAMPLE:
 PLEASE SEE THERE ARE STILL LIGHTING FIXTURES SHOWN IN
 ROOM # 100 WHICH DO NOT DESIGNATIONS AND ARE NOT LISTED
 ON THE IDR. THE SYMBOL IS SHOWING THESE TO BE LIGHTING
 FIXTURES WHICH ARE A PENDANT TYPE BASED ON THE SYMBOL
 LEGEND. THERE IS ROUGHLY AN 11 OF THESE FIXTURES NOT
 ACCOUNTED FOR. PLEASE SEE COMMENTS WITH RESPECT TO
 CONTROLS.
  
 FOR EXAMPLE:
 PLEASE SEE AHU-1 ZONE. THESE FIXTURES ARE SHOWN IN THE
 IDR AS 71W YET THE PLANS DO NOT SHOW THESE SAME TYPES
 AND WATTAGES?
  
 FOR EXAMPLE:
 PLEASE SEE FIXTURES SUCH AS Z-1 WHICH ARE NOT LISTED ON
 THE LEGEND WITH ANY TYPE OF WATTAGE OR ALLOWANCE.
  
 FOR EXAMPLE:
 PLEASE SEE FIXTURE *T* WHICH IS NOT LISTED WITH ANY
 WATTAGE. THIS CAN NOT BE CONFIRMED IN ZONE RTU3B. IN
 FACT THE PLANS CALL FOR *TBD* WHICH IS * TO BE
 DETERMINED*. THE MINIMUM CODE COMPLIANCE IS REQUIRED ON
 PLANS. FIXTURES DURING ANY PROJECT MAY BE REVISED. WHEN
 FIXTURES ARE REVISED PLANS ALONG WITH REVISED ENERGY
 CALCULATIONS ARE REQUIRED AND SUBMITTED BEFORE
 INSPECTIONS/FINALS. PLANS AND CALCULATIONS ARE REQUIRED
 TO SHOWN MINIMUM CODE COMPLIANCE BEFORE ISSUANCE.
  
 FOR EXAMPLE:
 PLEASE SEE PLANS SHOW *TT* FIXTURES IN RTU5 ZONE. AS
 THE FIXTURE LEGEND DOES NOT LIST ANY TYPE *TT* FIXTURE
 ON ELECTRICAL OR ARCHITECTURAL PLANS IT IS NOT KNOWN
 WHAT THESE ARE GOING TO BE? NEED TO COMPLETE MINIMUM AT
 THIS TIME.
  
 FOR EXAMPLE:
 PLEASE SEE SAME ZONE RTU-5 WHICH DOES NOT INCLUDE ANY
 *F1* FIXTURE AS SHOWN ON PLANS AND LISTED ON THE
 FIXTURE LEGEND.
  
 FOR EXAMPLE:
 PLEASE SEE SAME ZONE RTU-5 WHICH DOES NOT LIST ANY TYPE
 *C* FIXTURES WHICH ARE LISTED ON PLANS AND ON FIXTURE
 LEGEND.
  
 FOR EXAMPLE:
 PLEASE SEE THIS SAME ZONE RTU-5 WHICH SHOWS A TOTAL OF
 24-8A WATT *B* FIXTURES YET PLANS CLEARLY SHOW 32-84W
 FIXTURES.
  
 FOR EXAMPLE:
 PLEASE SEE AHU11 WHICH SHOWS A 42W FIXTURE HOWEVER
 PLANS SHOW ALL 84 WATT FIXTURES.
  
 FOR EXAMPLE:
 PLEASE SEE FIXTURES NOW ADDED IN CHAPEL NOT IN THE IDR.
 (A2)
  
 FOR EXAMPLE:
 PLEASE SEE THERE ARE SEVERAL FIXTURES LISTED ON PLANS
 YET THEY ARE NOT LISTED ON THE FIXTURE LEGEND WITH ANY
 TYPE OF WATTAGE. THESE ARE REQUIRED TO BE COMPLETE AT
 THIS TIME WITH MINIMUM DESIGN ALLOWANCES.
 SEE Z1, TT, T, ETC. SOME ALREADY NOTED ABOVE.
 SEE CHAPEL FOR SYMBOLS SHOWN BUT NOT ANY DESIGNATIONS.
  
 *** THESE ARE SOME EXAMPLES AS A BENEFIT TO THE DESIGN
 TEAM TO SEE THE TYPES OF ITEMS WHICH ARE STILL IN NEED
 OF CORRECTIONS. THIS IS IN NO WAY AN EXHAUSTED LIST. **
 THIS REVIEWER CAN NOT EMPHASIZE ENOUGH TO PLEASE BE
 SURE ALL COMPONENTS SHOWN AND LISTED IN BUILDING ARE
 PLACED INTO THE INPUT DATA REPORT. (IDR). THIS IS
 REQUIRED FOR ALL TRADE COMPONENTS.
 ****
 THERE WILL BE COMMENTS BELOW WHICH MAY VERY WELL AFFECT
 ENERGY CALCULATIONS.
  
 3) NOTE: PLEASE SEE AS NOTED ON PREVIOUS REVIEW
 LIGHTING CONTROLS FOR ALL FIXTURES IN ALL AREAS ARE NOT
 SHOWN TO BE COMPLETE/COMPLIANT AT THIS TIME. PLEASE SEE
 13-415.1.ABC.1.1, .1.2, .1.3, AND .1.4.
  
 FOR EXAMPLE:
 PLEASE SEE FIXTURES AS NOTED ABOVE IN NOTES WHICH ARE
 LOCATED IN ROOM #100. THESE SHOW A NUMBER IN A ROUND
 CIRCLE HOWEVER THERE IS NOT LEGEND OR NOTES ON WHAT
 THESE NUMBERS REPRESENT. AS THE FIXTURES ARE NOT
 LABELED IT IS NOT POSSIBLE TO GIVE EXACT LOCATION.
 THESE ARE THE FIXTURES (BASED ON SYMBOL LEGEND) THAT
 HAVE THE CIRCLE NUMERICAL DESIGNATIONS, 10, 11, 13 AND
 14. THESE ARE NOTED AS PENDANT FIXTURES ON SYMBOL
 LEGEND. THERE ARE OTHER FIXTURES SUCH AS THE *G1* WHICH
 ARE SHOWING A FIXTURE DESIGNATION HOWEVER THE ONLY A
 NUMBER 12 IN A CIRCLE.
 PLEASE CLARIFY.
  
 FOR EXAMPLE:
 PLEASE SEE SOME OUTSIDE EXTERIOR LIGHTS WHICH ARE NOTED
 TO TIME CLOCK YET THE TIME CLOCK SCHEDULE DOES NOT LIST
 ANY OF THESE CIRCUITS. SEE THE TC SCHEDULE IS MISSING
 #22, #37.
  
 ** PLEASE SEE COMMENTS BELOW WITH RESPECT TO EGRESS
 LIGHTING WHICH WILL HAVE AN AFFECT ON CIRCUITING,
 LIGHTS ETC.
  
 4) NOTE: PLEASE SEE THERE ARE CIRCUITS LISTED ON THE
 PLANS TO NOW GO TO A NEW UPS FOR EMERGENCY BACK UP
 FIXTURES YET THE SCHEDULE SHOWN ON E-12.0 DOES NOT SHOW
 THESE FIXTURES.
  
 FOR EXAMPLE:
 PLEASE SEE MISSING CIRCUITS, 1L3-1, 1L3-22 AND 1L3-37.
 THE PLANS SHOW LIGHT FIXTURES *H* AT FRONT ENTRANCE TO
 THIS UNIT, THE FIXTURES *H* AT REAR ENTRY/COVERED ARE
 ALSO BUT NOT LISTED.
  
 FOR EXAMPLE:
 PLEASE VERIFY FIXTURES *W-2* WHICH ARE LISTED AS THE
 WATER FEATURE LIGHTS ON THE UPS.
  
 NFPA-101 2003 7.8, 7.9,
 FBC 106.1.2 FOR COORDINATION.
  
 5) NOTE: PLEASE SEE THAT COMPLIANCE WITH THE MINIMUM
 LIFE SAFETY CODE HAS NOT BEEN SHOWN AT THIS TIME. THERE
 ARE ALSO SEVERAL COMMENTS WITH RESPECT TO COORDINATION
 OF PLANS.
 PLEASE SEE NFPA-101 7.8, 7.9, 7.8.1.3, 7.9.2. AS THE
 SUBMITTED PHOTO-METRICS DO NOT COORDINATE WITH PLANS IN
 MANY LOCATIONS THERE IS THE NEED FOR MANY ITEMS TO BE
 ADJUSTED AND REVISED.
  
 FOR EXAMPLE:
 PLEASE SEE ELECTRICAL LIGHTING PLANS CLEARLY SHOW
 FIXTURES A AND AE IN OUTSIDE CORRIDORS YET THE
 SUBMITTED PHOTO-METRICS CLEARLY DO NOT SHOW THESE SAME
 FIXTURES. IN FACT IN THE SOUTH OUTSIDE CORRIDORSHOWN
 ON THE PHOTO-METRICS SHOWS A EM-2 FIXTURE. THIS
 FIXTURES HAS A LISTED 2000 LUMENS ON PHOTO-METRIC
 SHEETS YET THE FIXTURES WHICH ARE ACTUALLY SHOWN ON
 PLANS ARE 1400 LUMEN FIXTURES. HOW IS THIS POSSIBLE?
  
 FOR EXAMPLE:
 PLEASE SEE PLATFORM EGRESS AREA ON THE EAST SIDE OF
 BUILDING WHICH BASED ON THE PHOTO-METRICS SHOWN ON
 SHEET E-16.0 IS BLANK.
  
 FOR EXAMPLE:
 PLEASE SEE AREAS SUCH AS ROOM 334 WHICH DOES NOT MATCH
 WITH ELECTRICAL PLANS.
  
 FOR EXAMPLE:
 PLEASE SEE LIBRARY WHICH SHOWS EMERGENCY FIXTURES ON
 ELECTRICAL BUT NOT THE SAME AS PHOTO-METRICS.
  
 FOR EXAMPLE:
 PLEASE SEE SEVERAL OF THE FIXTURE TYPES ON PHOTO-METRIC
 PLANS DO NOT CORRELATE WITH THE LIGHTING WHICH IS SHOWN
 ONE ELECTRICAL PLANS OR ELECTRICAL FIXTURE LEGEND.
 PLEASE ALSO SEE FIXTURE HR AS LISTED ON PHOTO-METRICS
 YET THIS FIXTURE IS NOT LISTED ON ELECTRICAL PLANS
 FIXTURE LEGEND OR SHOWN ON PLANS.
 PLEASE SEE SITE PLANS WHICH SHOW COMPLETELY DIFFERENT
 FIXTURES THAN ON FIXTURE LEGEND FOR THE SAME FIXTURES.
  
 PLEASE BE SURE TO COORDINATE ALL FIXTURES ON SITE PLAN
 AS LISTED, ELECTRICAL PLANS AND PHOTO-METRICS.
  
 ** AS SOME AREAS ARE NOT COMPLETE, NOT SAME FIXTURES,
 SAME WATTAGE, LEVELS ETC COMPLIANCE HAS NOT BEEN
 SHOWN.
  
 6) NOTE: PLEASE SEE CIRCUITS ON E-4.0 WHICH SHOWS FRONT
 DOOR J-BOXES WITH P1-22,24 AND 26, YET THE PANEL
 SCHEDULE FOR P1 SHOWS OTHER LOCATIONS AND CIRCUITS
 BEING SERVED.
  
 7) NOTE: THE RISER NOW SHOWS TWO NEW MAINS INSTEAD OF
 THE PREVIOUS MLO MAIN DISTRIBUTION BOARD. PLEASE BE
 SURE TO SHOW A BOND FROM EACH MAIN ON RISER TO EACH
 GROUNDING ELECTRODE AS SHOWN. 250.58
  
 8) NOTE: AS THE RISER HAS NOW BEEN REVISED TO SHOW TO
 MAINS INSIDE BUILDING. PLEASE SEE THE SITE ELECTRICAL
 PLANS E-000 IS STILL SHOWING A MAIN OUTSIDE.
  
 9) NOTE: PLEASE SEE REVISED LAYOUT OF LIGHTING ON E-6.0
 IS NOT THE SAME AS E-3.0.
 PLEASE ALSO SEE THE ARCHITECTURAL PLANS WHICH ARE ALSO
 REQUIRED TO SHOW MINIMUM LIGHTING FOR LIFE SAFETY CODE/
 NFPA-101 2003 DO NOT CORRELATE WITH THE ELECTRICAL
 PLANS.
  
 FOR EXAMPLE:
 IN FACT PLEASE SEE SHEET A-3.0 FOR EXAMPLE WHICH DOES
 NOT SHOW ANY EMERGENCY EGRESS LIGHTS IN ROOM #100. THIS
 ROOM ON THE ELECTRICAL PLANS HAS SEVERAL EMERGENCY
 LIGHTS WHICH ARE SHOWN.
  
 FOR EXAMPLE:
 PLEASE SEE ROOM #105 WHICH DOES NOT SHOW ANY EMERGENCY
 LIGHT FIXTURES.
  
 FOR EXAMPLE:
 PLEASE SEE THE OUTSIDE CORRIDORS, LIBRARY, ETC. THESE
 ARE SOME EXAMPLES, BUT THERE ARE TOO NUMEROUS TO LIST.
  
 ** IT IS IMPORTANT TO KNOW THE LIGHTING REQUIRED TO BE
 SHOWN BY THE ARCHITECT FOR LIFE SAFETY PLANS NEED TO
 COORDINATE. THESE CORRECTIONS ARE REQUIRED WHETHER OR
 NOT COMMENT IS MADE BY ANY OTHER TRADE OR REVIEWER.
 PLEASE ALSO KNOW EVEN IF ANY OF THESE SHEETS CONTAIN
 STAMPS FROM OTHER TRADES, THEY NEED TO BE REVISED AND
 CORRECTED.
  
 10) NOTE: PLEASE BE SURE TO SUBMIT THREE COMPLETE SETS,
 SIGNED DATED AND SEALED BY THE DESIGNERS OF RECORD AS
 REQUIRED BY FAC 61G15-23.002. IT HAS NO BEARING ON
 WHETHER OR NOT THE SET IS THE PLANS WHICH REMAIN ON
 FILE. THE FLORIDA ADMINISTRATIVE CODE SECTION GIVEN
 REQUIRES ALL SETS AND DOCUMENTS DONE BY ANY LICENSED
 PROFESSIONAL ENGINEER TO CONTAIN AN ORIGINAL SIGNATURE
 DATE AND RAISED SEAL.
 PLEASE SEE SHEET(S) WHICH ARE IN FACT PHOTO-COPIES OF
 SIGNED AND SEALED PLANS WHICH ARE IN ONE OF THESE SETS
 SUBMITTED.
 PLEASE BE SURE TO GO THROUGH ALL SHEETS, PLANS AND
 DOCUMENTS.
  
 11) NOTE: PLEASE TAKE A LOOK AT THE SIZE AND SPECS FOR
 THE NEW UPS FOR EMERGENCY LIGHT FIXTURES WHICH IS BEING
 SHOWN TO BE INSTALLED FLASH INSIDE THE CORRIDOR WALL.
 PLEASE BE SURE THIS CAN BE INSTALLED INSIDE THE WALL AS
 SHOWN WITH TEMPERATURE AND HEAT CONSIDERATIONS PER
 LISTING.
 PLEASE ALSO SEE THE DIMENSIONS APPEAR TO BE LARGER THAN
 THE AREA IN WHICH IS SHOWN ON PLANS.
 THIS IS NOT SOMETHING THAT WANTS TO BE FOUND OUT AT A
 LATER DATE CAUSING WALLS ETC TO BE MOVED OR
 RE-DESIGNED. IF THIS IS VERIFIED THEN WILL BE AN
 ON-SITE ITEM. THIS IS ONLY NOTED FOR LISTING,
 INSTALLATION ETC AT THIS TIME.
 110.3,90.7.
  
 12) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO AIC
 RATING HAS PANELS AND RISER NOW REVISED SHOWING RATINGS
 FOR PANELS AND BRANCH BREAKERS. ALL BRANCH BREAKERS
 SHOWN WITH 42K RATING.
 NO RESPONSE NEEDED.
  
 13) NOTE: PLEASE SEE THE PREVIOUS REVIEW GAVE NOTICE TO
 FLORIDA STATUTES 553.80(2)(B) WITH RESPECT TO REPEAT
 COMMENTS FOR CODE COMPLIANCE. THE SECOND REVIEW THE
 SECTION OF THE STATUTE WAS GIVEN AS THERE WERE CODE
 SECTIONS REPEATED FOR THE SAME CODE COMPLIANCE REQUIRED
 ON PLANS AND SUPPORTING DOCUMENTS. THERE WERE ONCE
 AGAIN REPEATED CODE SECTIONS NOT IN COMPLIANCE. PLEASE
 KNOW AS REQUIRED UNDER THE ABOVE STATUE AS GIVEN THE
 FEE OF FOUR TIMES THE PERMIT FEE ATTRIBUTED TO PLAN
 REVIEW HAS BEEN ASSESSED. THIS FEE IS ASSESSED UNDER A
 STATUTORY REQUIREMENT AND IS NOT A REQUIRED FEE ON A
 LOCAL LEVEL. THE FLORIDA STATUTES ALSO REQUIRES THIS
 FEE TO BE PAID BEFORE PLANS ARE TO BE RESUBMITTED.THE
 FEE WHICH IS NOW ASSESSED AND REQUIRED TO BE PAID IS
 $46,097.90.
 ** PLEASE KNOW ONE SET OF ELECTRICAL PLANS AND
 SUPPORTING ENERGY CALCULATIONS WILL BE RETAINED BY THIS
 OFFICE AND PLACED WITH PREVIOUS RETAINED PLANS.
 ** IT IS RECOMMENDED THAT A MEETING BE HELD TO GO OVER
 COMMENTS BEFORE PLANS ARE RESUBMITTED FOR THE FOURTH
 REVIEW.
  
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-02-16 Cont ID  
Sent By dpalmer Date 2008-02-16 Time 12:32 Rev Time 0.00
Received By dpalmer Date 2008-02-14 Time 19:24 Sent To  
Notes
2008-02-16 12:32:53*** DENIED 2ND REVIEW ***
  
 ** PLEASE SEE THERE ARE SEVERAL ITEMS FROM PREVIOUS
 REVIEW WHICH ARE STILL IN NEED OF ADDRESSING. AS
 MENTIONED ON PREVIOUS REVIEW AS THERE WAS ALSO
 INFORMATION NOT YET SUBMITTED THERE MAY ALSO BE NEW
 COMMENTS.
 ** PLEASE SEE NOTES BELOW AS THERE IS INFORMATION NOT
 YET SUBMITTED WHICH MAY GENERATE NEW COMMENTS ON THE
 FOLLOWING REVIEW WHICH CAN NOT POSSIBLY BE MADE AT THIS
 TIME.
  
 1) NOTE: ** IMPORTANT** WHEN CALLING THIS
 OFFICE/REVIEWER AND LEAVING VOICEMAIL PLEASE BE SURE TO
 LEAVE A RETURN PHONE NUMBER.
  
 2) NOTE: ** IMPORTANT** PLEASE SEE PREVIOUS REVIEW NOTE
 AT THE END OF REVIEW WHICH WAS ** AND LABELED AS
 IMPORTANT** WHICH SPECIFICALLY REQUESTED FOR ALL
 OLD/VOIDED SHEETS TO BE COMPLETELY REMOVED FROM SETS.
 THIS WOULD CREATE SETS WHICH DO NOT CONTAIN ANY OF THE
 OLD SHEETS AND ONLY NEW SHEETS FOR REVIEW. ANY OLD AND
 VOIDED SHEETS WOULD BE SUBMITTED ALONG WITH NEW SETS
 SEPARATELY AND ONLY NEED ONE SET OF THE OLD SHEETS.
 PLANS SUBMITTED CONTAIN ALL THE OLD AND ALL THE NEW
 SHEETS CREATING SETS WHICH ARE TWICE AS LARGE AS NEED
 BE.
 ** THIS WILL HELP THE REVIEW PROCESS AND EXPEDITE THE
 REVIEWS. THANKING YOU IN ADVANCE FOR ATTENTION TO
 THIS.
  
 3) NOTE:** THIS COMMENT WITH RESPECT TO LIFE SAFETY
 EGRESS LIGHTING WILL BE BROKEN UP INTO SUB-SECTIONS.
 PLEASE ALSO KNOW THAT SOME EXAMPLES WILL BE GIVEN BUT
 ARE NO ALL LOCATIONS IN QUESTION.
 PLEASE SEE NOTE #3 FROM PREVIOUS REVIEW WITH RESPECT TO
 MINIMUM LIGHTING LEVELS FOR ALL DESIGNATED EGRESS
 PATHS.
 PLEASE SEE THERE ARE SEVERAL AREAS ON PLANS WHERE NO
 EMERGENCY BATTERY BACK UP LIGHT FIXTURES IS SHOWN. THE
 PREVIOUS REVIEW GAVE SOME AREAS OF EXAMPLES AND MANY
 LIGHTING FIXTURE TYPES IN SOME OF THOSE AREAS WERE
 ADJUSTED HOWEVER MANY AREAS WERE STILL NOT CHANGE OR
 THE FIXTURES WERE NOT ADJUSTED.
  
 A) PLEASE SEE THE PREVIOUS REVIEW MENTIONED TO PROVIDE
 PHOTO-METRICS FOR EGRESS PATHS HOWEVER NONE WERE
 SUBMITTED. PLEASE SEE THE AREAS OF STAIRS REQUIRE A
 LEVEL OF 10FT CANDLES UNDER NORMAL AND IS PERMITTED
 DOWN TO 1FT CANDLE UNDER EMERGENCY CONDITIONS. NFPA-101
 7.8.1.3, 7.9.2.2.
 THERE ARE NO SUBMITTED PHOTO-METRICS LEVELS FOR ANY
 EGRESS PATHS. PLEASE SUBMIT. PLANS NOW INCLUDE A NEW
 BATTERY BACK UNIT WAS NOW ADDED TO RISER FOR MOST OF
 THE CIRCUITS BUT NOT ALL. ONLY CIRCUITS 1L3, 23, 29,
 AND 33 ARE SHOWN YET THERE ARE OTHER CIRCUITS FOR
 OUTSIDE EGRESS LIGHTS WHICH ARE NOT SHOWN. PLEASE
 SUBMIT THE NEW SPECS/CUT SHEETS ON THIS PROPOSED UNIT.
 PLEASE INDICATE TIME IN EMERGENCY UNDER LOAD OF
 CIRCUITS.
 FAC 61G15-33.004.
  
 B) PLEASE SEE SOME EGRESS PATH HAD ALL LIGHT FIXTURES
 CHANGED TO BATTERY BACK UP FIXTURES. THIS WAS NOT THE
 REQUEST HOWEVER THIS IS NOT A CODE ISSUE. PLEASE SEE
 THERE ARE SEVERAL OTHER AREAS IN WHICH NO EMERGENCY
 LIGHTING FIXTURES WERE LOCATED.
 PLEASE SEE SOCIAL HALL, BASED ON THE FIXTURE LEGEND
 NONE OF THESE FIXTURES IN AREAS OF EGRESS ARE BATTERY
 BACK UP.
 PLEASE SEE SANCTUARY, BASED ON THE FIXTURE LEGEND NONE
 OF THESE FIXTURES IN EGRESS AREAS ARE BATTERY BACK UP.
 PLEASE SEE LOBBY AREAS, BASED ON FIXTURE LEGEND NONE OF
 THESE FIXTURES IN EGRESS AREAS ARE BATTERY BACK UP.
 PLEASE SEE CHAPEL, NONE OF THESE FIXTURES AREA BATTERY
 BACK UP BASED ON FIXTURE LEGEND AND THE OCCUPANCY LOAD
 OF THE ROOM CERTAINLY REQUIRES THIS.
 PLEASE SEE SOME HANDRAILS WHICH DO NOT SHOW ANY LIGHTS
 (NE CORNER)
 PLEASE SEE CHAPEL WHICH BASED ON LIFE SAFETY PLANS
 INDICATES EGRESS INTO COURTYARD AREA WHICH COULD NOT
 LOCATE BACK UP LIGHTING TO OUTDOOR EGRESS HALLWAYS.
 ONCE THE PHOTO-METRICS ARE SUBMITTED THE LIGHTING
 LEVELS IN THAT ARE MAY BE SUFFICIENT WITH THE BATTERY
 BACK UP OF THE *A* FIXTURES WHICH ARE ALL SHOWN AS
 BATTERY BACK UP.
 PLEASE SEE LIBRARY, NONE OF THESE FIXTURES BASED ON THE
 FIXTURE LEGEND INDICATES ANY OF THESE AS BATTERY BACK
 UP. BASED ON OCCUPANCY AND LOAD OF ROOM, THIS IS
 REQUIRED.
 PLEASE SEE EGRESS PATHS FROM BUILDING TO STAIRS, NO
 FIXTURES COULD BE LOCATED FOR ILLUMINATION OF PLATFORM
 AREAS.
 ** PLEASE SEE THERE ARE OTHER AREAS ON PLANS SHOW WHERE
 EVERY SINGLE FIXTURE WAS CHANGED TO BATTERY BACK UP.
 THIS OFFICE ONLY REQUESTED TO MEET THE LIFE SAFETY
 CODE.
 WAS THE INTENT ON PLANS FOR ALL *B* FIXTURES WHICH ARE
 IN CLASSROOMS, OFFICES, STORAGE ROOMS, CLOSETS ETC TO
 ALL BE BATTERY BACK UP?
 WAS IT INTENDED FOR ALL *A* FIXTURES TO BE BATTERY
 BACK? SOME LOCATIONS ARE CLEAR AS TO WHY THESE WOULD BE
 CHANGED HOWEVER IS IT NOT UNDERSTOOD WHY MOST AREAS
 WHICH REQUIRE BATTERY BACK UP FIXTURES DO NOT CONTAIN
 ANY AND THEN OTHER AREAS WHICH DO NOT REQUIRE ANY
 CONTAIN ALL FIXTURES AS BATTERY BACK UP. SOME OF THE
 *A* FIXTURES WERE CHANGED TO *AE* FIXTURES.
 ** THERE IS NOTHING IN THE CODE WHICH PROHIBITS
 DESIGNER TO DESIGN ALL FIXTURES IN A BUILDING BEING
 BATTERY BACK UP HOWEVER THE REQUIRED EGRESS PATHS MUST
 CONTAIN THE MINIMUM TO MEET THE 1FT CANDLE LEVEL.
  
 C) PLEASE SEE COMMENTS BELOW IN NOTE #5E WITH RESPECT
 TO OCCUPANCY SENSORS ON EGRESS LIGHTING. FBCAND LS
 CODE.
  
 AS THERE ARE STILL MANY QUESTIONS AND SOME ITEMS ARE
 MISSING CAN NOT REVIEW ALL FOR CODE COMPLIANCE AT THIS
 TIME. REVIEW CAN ONLY BE BASED ON PLANS SUBMITTED.
  
 4) NOTE: PLEASE SEE THERE ARE SEVERAL SYMBOLS ON PLANS
 WHICH ARE NOT IN LEGEND FOR SYMBOLS, ARE NOT IN FIXTURE
 LEGEND AND DO NOT CONTAIN ANY CIRCUITING ETC. IT IS
 UNCLEAR WHAT MANY OF THESE ARE.
 PLEASE SEE SANCTUARY AREA WHICH CONTAINS A D IN A
 SQUARE BOX WHICH INDICATE 1INCH CONDUIT TO ER? PLEASE
 SEE LOBBY AREA WHICH ANOTHER CIRCLE SYMBOL WITH SQUARE
 BOX WHICH INDICATES TO ER, TO WPD?
 PLEASE SEE SOCIAL AREA WHICH CONTAINS THE SAME WHICH
 STATES TO ER, WPB?
 PLEASE BE SURE ALL SYMBOLS ON PLANS ARE ON LEGEND FOR
 WHAT THESE ARE.
 PLEASE SEE LIGHTING FIXTURES ON THE ELECTRICAL PLANS
 WHICH ARE NOT THE SAME AS THE FIXTURES SHOWN ON
 ARCHITECTURAL PLANS.(EXAMPLE: EXTERIOR) PLEASE KNOW
 AS THERE ARE OTHER COMMENTS ON ELECTRICAL PLANS AND
 WILL HAVE ADJUSTMENTS ON FIXTURES ETC PLEASE BE SURE
 THE INFORMATION IS FORWARDED TO THE ARCHITECT FOR
 COORDINATION.
 FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION.
  
 5) NOTE: PLEASE SEE PREVIOUS NOTE WITH RESPECT TO FBC
 AND CHAPTER 13.
 PLEASE SEE THE COMMENTS BELOW WILL BE IN SECTIONS AS
 PREVIOUS REVIEW AND THE INPUT DATA REPORT WILL BE NOTED
 AS IDR.
  
 A) PLEASE SEE THAT NOT ENOUGH DETAILS WERE SUBMITTED
 FOR MAIN AREAS FOR LIGHTING CONTROLS. NO DETAILS ON THE
 DEVICES, POWER PACKS, SCHEDULING OF PROPOSED, ZONES
 ETC. PLANS SHOW SOME NEW OCCUPANCY SENSOR TYPE DEVICES
 YET NOT ENOUGH INFORMATION ON THESE WAS PROVIDED. HOW
 WILL ALL AREAS BE CONTROLLED?
 FOR EXAMPLE: LOBBY AREAS, OVER RIDES, OCCUPANCY
 SENSORS, ACCENT LIGHTING, DISPLAY LIGHTING ETC. PLEASE
 SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.
  
 B) PLEASE SEE THAT NOT ENOUGH INFORMATION IS PROVIDED
 FOR EXTERIOR LIGHTING CONTROLS. PLANS SHOW A LIGHTING
 CONTACTOR AND SOME LOCATIONS NOTE THERE WILL BE A
 ASTRONOMICAL TIME CLOCK HOWEVER PLEASE SEE THE REQUIRED
 BATTERY BACK UP OF 10HRS IF PROPOSING A TC COULD NOT BE
 LOCATED.
 PLEASE SEE 13-415.1.ABC.1.4 ALSO 13-415.1.ABC.2
  
 C) PLEASE SEE THE INFORMATION ON THE IDR DOES NOT
 CORRELATE WITH PLANS. PLEASE SEE THE EXTERIOR LIGHTING
 FOR EXAMPLE WHICH STATES ALL FIXTURES AS ONLY BEING 1.
 THIS IS NOT POSSIBLE WHEN THE ARE DOZENS OF FIXTURES ON
 PLANS FOR EACH TYPE. THE IDR REQUIRES EACH FIXTURE,
 EACH TYPE, AND METHOD OF CONTROL TO COORDINATE WITH
 PLANS. AT THIS TIME AS FIXTURES ARE ONLY INDICATE AS 1
 (ONE) AT EACH LOCATION ON THE IDR,THE SPECIFIC
 FIXTURES, COUNTS ETC CAN NOT BE DETERMINED.
  
 D) PLEASE SEE THE IDR FOR ALL INTERIOR LIGHTS DOES NOT
 COORDINATE. PLEASE SEE THAT ALL LIGHTING IS REQUIRED TO
 BE FIGURED PER 13-415.2.ABC.1.1 AND .1.2
 PLEASE SEE 13-415.2, 13-400
 PLEASE KNOW AS THERE ARE FIXTURES ON THE IDR WHICH ARE
 NOT ON FIXTURE LEGEND AND FIXTURES ON THE FIXTURE
 LEGEND WHICH ARE NOT ON THE IDR.
 FOR EXAMPLE:
 500W COMPACT FLUORESCENT FIXTURES ON IDR, NOT ON
 LEGEND.
 250W ON FIXTURE LEGEND NOT ON IDR.
 PLEASE SEE FIXTURE COUNTS ON PLANS COMPARED TO FIXTURES
 IN AREAS ON THE IDR.
 ** PLEASE KNOW THERE ARE SEVERAL MORE WHICH DO NOT
 CORRELATE AND ONLY A COUPLE OF EXAMPLES ARE GIVEN.
  
 E) PLEASE SEE CORRIDOR 335 WHICH INDICATES ONE WALL
 DEVICE AT EACH END OF THIS LONG EGRESS PATH. PLEASE SEE
 FBC 1006.1.2 AND NFPA-101 7.8.1.2.2 WITH RESPECT TO
 AUTOMATED DEVICES IN EGRESS PATHS. THIS IS PERMITTED BY
 BOTH CODES HOWEVER THE COVERAGE OF SUCH UNITS SHALL BE
 SUFFICIENT FOR ENTIRE LENGTH, THE DEVICES ARE REQUIRED
 TO BE 15MINS OF TIME AND PLANS SHOW 10MINS.
 PLEASE ALSO SEE THE DEVICES SHALL ALSO BE FAIL-SAFE ON
 DEVICES. THIS WOULD ALSO BE FOR OTHER AREAS WHERE
 OCCUPANCY SENSORS ARE BEING USED FOR EGRESS LIGHTING.
  
 F) PLEASE INCLUDE NOTES ON PLANS ARE REQUIRED PER
 13-413.1.ABC.2, .2.1 AND .2.2
  
 G) PLEASE BE SURE THE OWNER AGENT HAS FILLED OUT
 SECTION ON CERTIFICATION SHEET AND SIGNED WHEN NEW
 CALCULATIONS ARE SUBMITTED.
 13-103.1.1.1
  
 6) NOTE: PLEASE BE SURE ALL EMERGENCY AND EXIT LIGHTS
 ARE CIRCUITED PER 700.12F. AS MOST FIXTURES IN MANY
 AREAS ARE ALL BATTERY BACK UP THIS IS OK, HOWEVER THIS
 NOTE REMAINS BASE DON THE FACT THERE ARE OTHER AREAS
 WHERE THERE ARE NO BATTERY BACK UP FIXTURES.
  
 7) NOTE: PLEASE SEE FAC 61G15-33.004 WHICH REQUIRES ALL
 LIGHTING AND ILLUMINATION DESIGN TO BE PART OF THE
 RESPONSIBILITY OF THE DESIGN PROFESSIONAL. IF THERE ARE
 OTHER SHEETS WHICH WILL BE PART OF THE LIGHTING BEING
 SUBMITTED FOR SCOPE OF WORK REQUIRED BY A DESIGN
 PROFESSIONAL PLEASE BE SURE ALL SHEETS CONTAINS THE
 INFORMATION FROM THAT DESIGN PROFESSIONAL AND ARE
 SIGNED, DATED AND SEALED ACCORDINGLY.
 PLEASE SEE LIGHTING PLANS SUBMITTED BY LD INC.
 THE PREVIOUS REVIEW REQUESTED PHOTO-METRICS TO BE
 SUBMITTED FOR ALL EXTERIOR LIGHTING AREAS. HOWEVER
 PLEASE SEE PLANS WHICH SHOWS AREAS WITH 0.0 (NO) LEVELS
 OF LIGHTING. HOW IS THIS POSSIBLE WHEN THERE ARE DOZENS
 OF EXTERIOR LIGHTS ON PLANS?
 PLEASE COORDINATE ALL.
 FBC 106.1.2, 106.3.5.1.2 FOR COORDINATION AND
 ADDITIONAL INFORMATION.
  
 8) NOTE: PLEASE SEE THE PREVIOUS REVIEW MENTIONED THE
 CONCERN OF THE MAIN ELECTRICAL EQUIPMENT AND OTHER
 ELECTRICAL PANELS IN A REQUIRED EGRESS HALLWAY. REVIEW
 COMMENT MENTIONED TO SEE POSSIBLE BUILDING AND FIRE
 REVIEW COMMENTS.
 THE RESPONSE MENTIONS NO CODES WERE LOCATED WHICH
 PREVENTED THIS. AT THIS TIME INFORMATION AND SCENARIOS
 WILL BE TURNED OVER TO THE BUILDING REVIEWER AND
 BUILDING OFFICIAL FOR CLARIFICATION ON WHETHER OR NOT
 THIS IS PERMITTED AND MOST OF ALL IF THIS IS SAFE FOR
 THE OCCUPANTS IN AN EMERGENCY SITUATION. THIS REVIEWER
 CAN NOT SEE HOW THIS IS NOT A HAZARD AND NEEDS
 DETERMINATION ON THIS SCENARIO.
 THE 1600AMP MDP PROTRUDES INTO A REQUIRED EGRESS HALL
 WAY.
 FBC 1001.3, 1001.4
  
 9) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #4 WHICH
 MENTIONED TO CLARIFY THE MDP1 AS SHOWN ON RISER AND
 SCHEDULE.
 PLEASE SEE THE RISER STILL CONTAINS NOTE WHICH STATES
 *MAIN DISCONNECT PANEL*. THIS PANEL BY THE SCHEDULE IS
 SHOWN AS A MAIN LUG ONLY SWITCHBOARD.
 PLEASE SEE THE CIRCUITING ON THIS PANEL WAS ALSO NOT
 UPDATED. FOR EXAMPLE: AS NOTED PREVIOUSLY: EXAMPLE; 1)
 PANEL 1L1
 3)
 5)
 7) PANEL 1L2
 9)
 11)
 THIS IS AN EXAMPLE ONLY AS THIS IS STILL THREE PHASE
 EQUIPMENT.
 408.4, FBC 106.3.5.1.2, 106.1.2 FOR ADDITIONAL
 INFORMATION AND COORDINATION.
  
 10) NOTE: PLEASE COORDINATE RISER AND PANELS. PLEASE
 SEE KITCHEN PANELS 1K1 AND 1K2 WHICH ARE BOTH SHOWN AS
 400AMP ON RISER AND BEING FED FROM THE MAIN
 DISTRIBUTION BOARD WITH A 400AMP BREAKER. YET PLEASE
 SEE EACH OF THESE PANELS ARE SHOWN AS 200AMP MLO ON
 THEIR SCHEDULES WITH ONLY A SINGLE FEED OF 3/0
 CONDUCTORS.
 PLEASE COORDINATE AND ADJUST.
 PLEASE ALSO SEE THE POWER PLANS DO NOT SHOW THE
 LOCATION OF THESE PANELS. SHEET E-5.0 MENTIONS TO SEE
 SHEET E-11.0 FOR THE ENLARGED KITCHEN PLANS. IT WAS
 BEING ASSUMED THESE PANEL WERE IN THE KITCHEN HOWEVER
 COULD NOT LOCATE THESE ANYWHERE ON PLANS.
 SHEET E-6.0 ALSO DOES NOT SHOW THESE K PANELS. 240.24,
 110.26, 408.17, 240.4, 310.16, ETC
 FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION AND
 COORDINATION.
  
  
 11) NOTE: PLEASE SEE PREVIOUS NOTE WITH RESPECT TO AIC
 RATINGS FOR ALL PANELS, BREAKER AND SERVICE EQUIPMENT.
 THE MAIN SWITCH BOARD DOES NOW INDICATE THE BRANCH
 CIRCUIT RATINGS AS 65K RATED AND MAIN AT 100K. HOWEVER
 PLEASE SEE OTHER PANELS WHICH SHOW ONE AIC RATING FOR
 BOARD AND BREAKERS STILL.
 PLEASE VERIFY FOR EXAMPLE ALL PANELS SHOWING A 65K
 RATING FOR PANELS AND BRANCH BREAKERS THIS IS WITH THE
 EXCEPTION OF PANEL 1K1 WHICH SHOWS A 10K RATING. 110.9,
 110.3
 FBC106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION AND
 COORDINATION.
  
 12) NOTE: PLEASE KNOW THE SIGNED AND SEALED STRUCTURAL
 WIND LOAD CALCULATIONS SHOWING THE EPA (EFFECTIVE
 PROJECTED AREAS) OF LIGHT FIXTURES ON POLES WILL BE
 REVIEWED BY THE BUILDING REVIEWER.
  
 13) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A
 NOTICE GIVEN AT THIS TIME.
 PLEASE BE SURE TO GO OVER ALL COMMENTS AND ONCE AGAIN
 PLEASE CALL. PLEASE LEAVE PHONE NUMBER WHEN LEAVING A
 MESSAGE.
 ** PLEASE ALSO KNOW THAT AT THIS TIME ONE SET OF
 ELECTRICAL PLANS AND ENERGY CALCULATIONS ARE BEING
 RETAINED BY THIS OFFICE.
  
 ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY
 QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR
 NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  
2008-02-16 07:59:232008-02-16 07:059:23
  
 IN REVIEW
2008-02-15 19:34:00 
 2008-02-15 15:35:24
 REVIEW COMMENCED
  
 2008-02-15 19:34:00
 REVIEW STOPPED. WILL CONTINUE ON 2/16, NOTES WILL
 FOLLOW AND PLANS WILL BE IN A *FAILED STATUS*
  
  
2008-02-14 19:24:522008-02-14 19:24:52
  
 IN ELEC FOR REVIEW

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-10-07 Cont ID  
Sent By dpalmer Date 2007-10-07 Time 12:23 Rev Time 0.00
Received By dpalmer Date 2007-10-06 Time 18:46 Sent To  
Notes
2007-10-07 13:20:24NOTE ADDED:
  
 PLEASE KNOW THAT ALL LOW VOLTAGE SYSTEMS ARE REQUIRED
 TO BE UNDER SEPARATE PERMITS. IF THE LV IS SHOWN ON
 PLANS, THEN THE SUB CONTRACTOR WOULD ONLY NEED TO
 REFERENCE PLANS FOR TURN AROUND PERMIT.
 FEES ARE SEPARATE FOR VALUE OF THE SCOEP OF WORK AS
 SHWON.
2007-10-07 12:24:262007-10-07 12:24:26
  
  
 *** DENIED ***
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED
 FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS
 NOT MADE BY OTHER TRADE(S).
  
 2) NOTE: PLEASE SEE THAT COMPLIANCE WITH NFPA-101 7.8
 AND 7.9 NEEDS TO BE MET.
 PLEASE SEE THERE ARE SEVERAL AREAS IN WHICH BATTERY
 BACK UP TYPE OF LIGHTING FIXTURES ARE MISSING. PLEASE
 KNOW THAT LIGHTING IS REQUIRED FOR ALL EGRESS PATHS
 INCLUDING THAT TO THE EXIT DISCHARGE AREAS/PATHS. FOR
 EXAMPLE: PLEASE SEE THE STAIR AREAS OUTSIDE WHICH ARE
 PART OF THE EXIT DISCHARGE WHICH DO NOT CONTAIN BATTERY
 BACK UP LIGHTING.
 PLEASE SEE THE HALL WHICH DOES NOT INDICATE ANY
 EMERGENCY LIGHTING FIXTURES.
 PLEASE SEE COURTYARD AREAS AS THESE ARE EXIT PATHS
 HOWEVER AS THEY ARE NOT CONSIDERED THE PUBLIC RIGHT OF
 WAY OR SAFE DISTANCE FROM THE BUILDING, EMERGENCY
 LIGHTING FIXTURES WILL BE REQUIRED.
 PLEASE SEE ANY TOILETS WHICH ARE NOT A SINGLE POINT OF
 USE WILL ALSO REQUIRE A BATTERY BACK UP FIXTURES OF
 SOME TYPE.
 PLEASE SEE THERE ARE OTHER AREAS ALSO HOWEVER NOT ALL
 ARE LISTED.
 PLEASE SUBMIT AND PROVIDE LIGHTING PHOTO-METRICS FOR
 ALL EGRESS PATHS TO THE PUBLIC RIGHT OF WAY. PLEASE SEE
 THE LEVELS UNDER NORMAL FOR STAIRS SHALL MEET THE
 MINIMUM OF 10FT CANDLES PER 7.8.1.3 AND IS PERMITTED TO
 GO DOWN TO 1FT CANDLE UNDER EMERGENCY CONDITIONS. FBC
 106.1.2, FAC 61G15-33.004
 NFPA-101 7.8, 7.9
  
 3) NOTE: PLEASE SEE THERE ARE SOME LOCATIONS IN WHICH
 EXIT SIGNS APPEAR TO BE MISSING. PLEASE SEE CHAPEL AND
 LIBRARY FOR EXAMPLE. IF THE OCCUPANT LOAD EXCEEDS THAT
 OF THE FBC FOR THESE AREAS AN EXIT SIGN WILL BE
 REQUIRED.
 PLEASE SEE BUILDING AND FIRE MARSHAL REVIEW COMMENTS
 FOR THESE POSSIBLE LOCATIONS.
 PLEASE SEE FBC 1006.3.8.2, .3, LS-101 7.10.1.6 AND
 12.4.7.7.2 AS FLOOR PROXIMITY EXIT LIGHTING IS REQUIRED
 IN ASSEMBLY AREAS.
 PLEASE PROVIDE LOCATIONS ALONG WITH HEIGHT/LOCATION
 REQUIREMENTS.
  
 4) NOTE: PLEASE SEE THE MDP/ MAIN AS SHOWN INDICATES
 MORE THAN 42 SPACES. PLEASE SEE 408.5 AS THIS IS NOT
 PERMITTED IN THIS ENCLOSURE AS SHOWN.
 PLEASE LABEL ALL WITH COORDINATION OF CIRCUITING/PHASES
 ON PANELS.
 FOR EXAMPLE: 1,3,5 WOULD BE 1L1,
  
 5) NOTE: PLEASE CLARIFY AIC RATING AS STATED ON THE
 PANEL-BOARD. THIS STATES 100K, WHICH IS OK, HOWEVER IS
 THIS THE RATING FOR ALL BREAKERS IN THIS SAME
 ENCLOSURE?
 IF EACH IS RATED AT 100K, PLEASE FIRST VERIFY ALL
 BREAKERS AS SHOWN ARE AVAILABLE AT THIS 100K RATING.
 THERE IS NO CODE VIOLATION, HOWEVER THE 100K RATING FOR
 ALL BREAKERS AS SHOWN IS HIGH AND IF SHOWN AS 100K
 RATING FOR EACH, THEN THAT?S WHAT WILL BE REQUIRED TO
 BE INSTALLED.
 THIS IS ONLY A SUGGESTION TO VERIFY THIS.
  
 6) NOTE: PLEASE SEE THE LOCATION OF THE MDP ON E-6.0 IS
 NOT THE SAME AS E-000.
 PLEASE CORRELATE AND SEE OTHER COMMENTS.
 FBC 106.1.2.
 NEC 110.26 ETC.
  
 7) NOTE: PLEASE SEE THE LOCATIONS OF THE PANELS ALL
 APPEAR TO BE IN A EGRESS HALLWAY?
 PLEASE VERIFY THIS AS RATED EXIT PASSAGE WAYS MAY NOT
 HAVE THESE ELECTRICAL PANELS AS SHOWN.
 IF THIS IS NOT A EXIT/HALL WAY, THEN PLEASE ADJUST
 IDENTIFICATION OF THIS AREA.
 PLEASE SEE FBC CHAPTER 10, 1006.3.1, THIS WILL BE
 REVIEWED BY BUILDING, FIRE MARSHAL REVIEW COMMENTS.
 THIS IS BEING NOTED ON ELECTRICAL REVIEW AS THIS MAY
 AFFECT ELECTRICAL PANELS AND LOCATIONS.
  
 8) NOTE: PLEASE INDICATE MINIMUM WIND LOAD DESIGNS FOR
 LIGHT POLES ON ELECTRICAL PLANS.
 PLEASE SUBMIT WIND LOAD CALCULATIONS WHICH WILL BE
 REVIEWED BY THE BUILDING REVIEWER.
 PLEASE KNOW THAT ANY RE-LOCATED POLES AS SHOWN WILL BE
 REQUIRED TO MEET CURRENT WIND LOADS.
 FBC 106.1.2
  
 9) NOTE: PLEASE SUBMIT SITE LIGHTING PHOTO-METRICS FOR
 VERIFICATION OF ZONING COMPLIANCE.
 THERE ARE NO MINIMUMS FOR ELECTRICAL REVIEW HOWEVER
 ZONING DOES HAVE REGULATIONS FOR MAXIMUM LIGHTING
 LEVELS ACROSS PROPERTY LINES.
 PLEASE SEE COMMENTS BELOW WITH RESPECT TO LIGHTING FOR
 CHAPTER 13 OF THE FBC.
 FBC 106.1.2
  
 10) NOTE: PLEASE SEE THAT COMPLIANCE WITH FBC CHAPTER
 13 IS NEEDED FOR ALL LIGHTING CONTROLS IN ALL AREAS.
  
 A) PLEASE PROVIDE INFORMATION/DESIGN/TIME SCHEDULING
 ETC ON HOW LIGHTING IS BEING CONTROLLED IN COMMON
 AREAS.
 PLEASE BE SURE TO PROVIDE ZONES BASED ON MAXIMUM SQ FT
 FOR CONTROLS.
 PLEASE SEE THE OCCUPANCY DEVICES AS SHOWN IN MANY OF
 THE ROOMS AND LOCATIONS NEED TO STATE THE MAXIMUM
 TIMES. 13-415.1.ABC.1.1, .1.2 AND .1.3.
  
 B) PLEASE SEE THERE ARE SOME AREAS IN WHICH A OCCUPANCY
 SWITCH IS LOCATED IN ANOTHER ROOM THAN THE ROOM IN
 WHICH THE LIGHTING IS BEING CONTROLLED.
 FOR EXAMPLE: PLEASE SEE THE LOCATION OF THE DEVICE FOR
 FINANCIAL MANGERS OFFICE WHICH SEEMS TO CONTAIN A
 DEVICE IN THE TOILET AREA (313).
 PLEASE ALSO SEE THE SAME FM OFFICE 314 WHICH HAS A
 DEVICE WHICH FEEDS LIGHTING IN THE ROOM TO THE EAST?
 13-415.1.ABC.1.1, .1.2
  
 C) PLEASE PROVIDE MORE INFORMATION ON THE TYPES OF
 DEVICES BEING INSTALLED. PLEASE SEE THE BATHROOM/TOILET
 AREAS WHICH INDICATE A SINGLE WALL OCCUPANCY DEVICE. IF
 THIS IS A MOTION DEVICE ONLY THEN COVERAGE NEEDED IS
 NOT PROVIDED.
 PLEASE CLARIFY THESE. 13-415.1.ABC.1.1
  
 D) PLEASE SEE THAT NO LIGHTING CONTROLS COULD BE FOUND
 FOR ACCENT/DISPLAY LIGHTING. 13-415.1.ABC.1.3
  
 E) PLEASE SEE PLANS INDICATES A *S* IN A BOX WITH A TD
 DESIGNATION NEXT TO THIS, HOWEVER THE DEVICE LEGEND ON
 E-12.0 DOES NOT CONTAIN THIS DEVICE.
 PLEASE PROVIDE INFORMATION.
 13-415.1.ABC.1.1
  
 F) PLEASE PROVIDE DETAIL FOR EXTERIOR LIGHTING CONTROLS
 PER 13-415.1.ABC.1.4, 13-415.1.ABC.2
  
 G) PLEASE SEE THAT ALL SEPARATE SPACES PER
 13-415.1.ABC.1.2 ARE REQUIRED TO CONTAIN LIGHTING
 CONTROL. EXAMPLE: TOILET 316, HALL, ETC
 **PLEASE SEE LS 101 7.8.1.2.2 AND CHAPTER 10 OF THE FBC
 AS AUTOMATED OCCUPANCY DEVICES ARE PERMITTED HOWEVER
 THE SET UP/SCENARIO WILL NEED TO BE GONE OVER WITH THIS
 OFFICE.
  
  
 ** PLEASE KNOW AS THERE ARE MANY ITEMS WHICH HAVE NOT
 YET BEEN PROVIDED FOR LIGHTING CONTROLS, IT IS NOT
 POSSIBLE TO PROVIDE A COMPLETE REVIEW FOR CODE
 COMPLIANCE. THERE VERY WELL MAY BE NEW COMMENTS ON THE
 FOLLOWING REVIEW WHICH CAN NOT BE MADE AT THIS TIME.
 PLEASE CALL TO GO OVER ANY OF THESE ITEMS.
  
 11) NOTE: PLEASE SEE COMPLIANCE WITH FBC CHAPTER 13 FOR
 ENERGY CALCULATIONS/LIGHTING PERFORMANCE CALCULATIONS
 NEEDS TO BE MET.
 PLEASE SEE THE FOLLOWING WHICH WILL HAVE REFERENCE TO
 THE INPUT DATA REPORT AS IDR.
  
 A) PLEASE CORRELATE ALL LIGHTING WHICH IS ON PLANS AND
 CONSUMES ENERGY WITH THAT OF THE IDR.
 FOR EXAMPLE:
 PLEASE SEE THE EXTERIOR LIGHTING WHICH INDICATES A
 *PASSED* STATUS. PLEASE SEE THE IDR SHOWS ONLY *1-ONE*
 FIXTURE AND THIS FIXTURE AS SHOWN CONTAINS NO POWER
 USAGE. THIS IS NOT POSSIBLE WHEN THE PLANS INDICATE
 OVER 100 FIXTURES WHICH HAVE NOT BEEN PLACED ON THE
 IDR.
 PLEASE BE SURE THE FIXTURE LEGEND COORDINATES WITH THE
 LIGHTING IN THE IDR.
 PLEASE ALSO SEE FOR EXAMPLE THE INTERIOR LIGHTING WHICH
 NEEDS TO COORDINATE WITH PLANS.
 PLEASE SEE THE AREAS DO NOT MATCH.
 PLEASE SEE THE NUMBER OF FIXTURES ON EACH AND EACH
 AREA/ROOM DESIGNATION DOES NOT CORRELATE.
 PLEASE SEE SEVERAL WHICH ONLY INDICATES *ONE* FIXTURE
 WHICH IS NOT POSSIBLE.
 PLEASE SEE THE METHOD OF CONTROLS INDICATES *MANUAL
 ON/OFF* WHICH IS ALSO NOT POSSIBLE WHEN LIGHTING
 CONTROLS ARE AUTOMATED ETC.
  
 ** PLEASE BE SURE TO COORDINATE ALL FIXTURES ON PLANS
 WITH THE IDR.
 PLEASE SEPARATE TO ROOMS AND AREAS ON THE IDR. REVIEW
 OF MANY ITEMS CAN NOT BE DONE.
  
 PLEASE BE SURE TO SEE 13-415.2.ABC.1.2 FOR TRACK
 LIGHTING.
 PLEASE SEE 13-415.2.ABC.1.3 FOR EXTERIOR ALLOWANCES
 PLEASE SEE 13-415.1.A, 13-415.2 ETC.
  
 ** PLEASE SEE 2004 FBC CHAPTER 13 FOR ALL ELECTRICAL
 LIGHTING CONTROLS AND CALCULATIONS REQUIRED.
  
 12) NOTE: PLEASE CLARIFY THE GROUNDING ELECTRODE SYSTEM
 AS NOTED.
 CALLS FOR *BUILDING STEEL*, IS THIS MEANT TO BE *FOOTER
 STEEL*? IF THE STRUCTURE CONTAINS BOTH FOOTER AND
 BUILDING STEEL PLEASE SEE 250.50 AS BOTH ARE REQUIRED
 TO BE PART OF THE SYSTEM.
 PLEASE VERIFY ANY COLD WATER PIPING PER 250.50 **PLEASE
 PLACE NOTE ON PLANS FOR FBC 2704 WHICH REQUIRES METAL
 FRAMING MEMBERS TO BE BONDED.
  
 13) NOTE: PLEASE SEE KITCHEN (207) WHICH STATES A NOTE
 TO SEE E-13 FOR ELECTRICAL FOR THAT AREA HOWEVER E-13.0
 DOES NOT CONTAIN THIS.
 THIS ARE WAS HOWEVER FOUND ON E-11
 A) PLEASE SEE NEC 210.8B2 AS GFI PROTECTION IS REQUIRED
 FOR ALL 15 AND 20AMP 120V IN KITCHEN AREA WHETHER OR
 NOT THESE ARE COUNTER SPACE OUTLETS.
 PLEASE SEE THERE ARE CIRCUITS WHICH DO NOT CONTAIN THE
 REQUIRED PROTECTION.
 FOR EXAMPLE:
 PLEASE SEE 1K2-17, 1K2-19 ETC.
 B) PLEASE SEE THERE ARE WHAT APPEAR TO BE EQUIPMENT
 DESIGNATIONS ON THIS SAME LAYOUT ON E-11 WHICH ARE NOT
 ON THE EQUIPMENT LIST AS PROVIDED. PLEASE SEE FOR
 EXAMPLE:
 E-901, E-902, E49B ETC THERE ARE OTHERS.
  
 14) NOTE: PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4)
 AND STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR
 ADA REQUIRED AREAS. DEVICES ARE BEING SHOWN ON
 PLANS/LEGEND. PLEASE CORRELATE WITH PLANS, AND FA
 SHEETS SUBMITTED.
 ** PLEASE KNOW THAT THE FIRE ALARM WILL BE UNDER A
 SEPARATE PERMIT HOWEVER THE BASE LIFE SAFETY SYSTEM IS
 REQUIRED ON BASE PLANS AS SHOWN. DO NOT REMOVE FROM
 SETS.
 FBC 106.3.5.1.2
  
 15) NOTE: PLEASE CLARIFY SPACE ABOVE LINE #1 ON THE MDP
 AS THIS NOTES 2000AMP MAIN?
 PLEASE CORRELATE AS THE RISER SHOWS A MDP1, THE
 PANEL-BOARD IS MDP AND THE PLANS DO NOT INDICATE
 EITHER.
 PLEASE CORRELATE AND PLEASE SHOW LOCATION OF THE MDP ON
 PLANS.
 PLEASE SEE 110.26, 408.36
  
 16) NOTE: PLEASE CLARIFY ALL CONTINUOUS AND LARGEST
 MOTOR LOADS AT 125%.
 PLEASE SHOW. 215.3, 230.42 (SOME ARE SHOWN)
  
 17) NOTE: PLEASE SEE THAT PANEL SCHEDULES ARE TO BE
 SPECIFIC TO THE ROOMS AND AREAS IN WHICH THEY FEED.
 PLEASE SEE 408.4.
  
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.1.2, 106.5, 106.1.2
  
 ** PLEASE KNOW AS THERE WILL SEVERAL CHANGES TO PLANS,
 THERE MAY BE NEW COMMENTS WHICH ARE NOT MADE ON THIS
 REVIEW.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-10-07 09:16:442007-10-07 09:16:44
  
  
 REVIEW IN PROGRESS
2007-10-06 18:46:422007-10-06 18:46:42
  
 IN ELECTRICAL FOR REVIEW.

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2008-08-28 Cont ID  
Sent By rchokshi Date 2008-08-28 Time 13:57 Rev Time 0.00
Received By rchokshi Date 2008-08-28 Time 13:57 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2008-06-04 Cont ID  
Sent By rchokshi Date 2008-06-04 Time 14:25 Rev Time 0.00
Received By rchokshi Date 2008-06-04 Time 14:05 Sent To  
Notes
2008-06-04 14:24:53***FAILED**** PLEASE PROVIDE THE FOLLOWING:
  
 1. CIVIL DRAWING SETS PREPARED BY SIMMONS & WHITE
 REVISIONS NOT CONSISTENT.FOR EXAMPLE, SHEET #2 OF ONE
 SET HAS 1 REVISION,AND OTHER SET SAME SHEET # 2 HAS 4
 REVISIONS. SAME WAY ONE SET SHEET #3HAS NO REVISION
 OTHER SET SAME SHEEET #3 HAS ONE REVISION ETC, ETC.
 EACH SHEET OF ALL SETS MUST HAVE CONSISTENTREVISIONS
 AND UPTO LAST REVISION.ALL 3 SETS MUST BE SAME.
  
 2. STORM WATER QUALITY CALCULATIONS MUST BE APPROVED
 FROM 100045TH STREET ENGINEERING SERVICES BEFORE WE
 APPROVED.
  
 3. WATER & SEWER PLANS MUST BE APPROVED &STAMPED
 FROM 45TH STREET (MANNY G.), UTILITY DEPT BEFORE WE
 APPROVED.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2008-02-27 Cont ID  
Sent By rchokshi Date 2008-02-27 Time 09:39 Rev Time 0.00
Received By rchokshi Date 2008-02-27 Time 09:39 Sent To  
Notes
2008-02-27 09:47:08***FAILED**** PLEASE PROVIDE THE FOLLOWING:
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
 2. STORM WATER QUALITY CALCULATIONS MUST BE APPROVED
 FROM 100045TH STREET ENGINEERING SERVICES BEFORE WE
 APPROVED.
 3. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2007-10-30 Cont ID  
Sent By rchokshi Date 2007-10-30 Time 09:18 Rev Time 0.00
Received By rchokshi Date 2007-10-30 Time 08:49 Sent To  
Notes
2007-10-30 09:14:34***FAILED**** PLEASE PROVIDE THE FOLLOWING:
  
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
 2. PLEASE SHOW ON DRAWING ALL CITY STANDARDS NOTES FOR
 SIDEWALK, DRIVEWAY, APPROACH, PARKINGS, HANDICAP
 PARKINGS, DUMPSTER ENCLOSURE, YOU CAN GET A C D FROM
 1000, 45 STREET FOR ALL THESE CITY STANDARDS NOTES.
 PHONE# 494-1040
 3. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
 4. PLEASE SHOW ON CALCULATION THAT YOU HAVE CONSIDERED
 FLOOD ZONE AREA, & 5,10, 25, 100 YEAR FLOOD CRITERIA
 AND CROWN OF THE ROAD WHEN YOU DETERMINE THE FIRST
 FLOOR ELEVATION.
 5. PLEASE SHOW ON DRAINAGE DRAWINGTHE SITE AREA,
 GREEN, LAKE,PARKING AREA, IMPERVIOUS,PERVIOUS AREAYOU
 ARE DEVELOPING FOR THIS PROJECT . PLEASEMAKE SURE
 THESE AREAS SHOWN ON DRAINAGE DRAWINGS MUST MATCH WITH
 AND USED IN STORM WATER QUALITY CALCULATIONS. PLEASE
 PROVIDE A COPY OF THESE CALCULATIONS.
 6. PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE
 SO, WE CANSEE THE LAYOUT OF STORM WATER PIPES FROM
 ALL OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF THE
 CONTROL STRUCTURESWITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC ON DRAWINGS, CALCULATION FOR
 EXFILTRATION TRENCHES, PLEASE SHOW DRY DETENTION/WET
 DETENTION AREAS IN STORM WATER CALS IF YOU HAVE ALL
 THESE.
 7. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN SO YOUR SITE DO NOT GET
 FLOODED AND HAVE ENOUGH DRAINS.
 8. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, &STORM
 WATER QUALITY CALCULATIONS. STORM WATER CALS MUST BE
 APPROVED FROM 100045TH STREET ENGINEERING SERVICES.
 9. PLEASE SHOW ON DRAWINGS THE POLLUTION PREVENTION
 DETAILS,CLOTHES USED FOR SILT ETC., PLANS SHOWING SILT
 FENCE AROUND THE SITE & CATCH BASINS DURING
 CONSTRUCTION AND ALL DEMOLITION PHASE.HEIGHT OF FENCE
 SHOULD BE HIGH ENOUGH PER FDEP TO STOP DUST PARTICLES.
 YOU HAVE SHOWN SILT FENCE DURING CONSTRUCTION PHASE BUT
 NOT DURING DEMOLITION PHASE.
 10. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-09-16 Cont ID  
Sent By mawillia Date 2008-09-16 Time 11:07 Rev Time 0.00
Received By mawillia Date 2008-09-16 Time 10:43 Sent To  
Notes
2008-09-16 11:07:21*****APPROVED*****
  
 PLAN SHEETS A-1.1, A-5.1, A-10.0 & A-10.1, E-1.0 &
 E-2.0 & E-3.0, E-7.0 & E-8.0 & E-9.0, AND FS-1.0 & FS-2
 & FS-3.0 & FS-4.0 WERE STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-06-25 Cont ID  
Sent By mawillia Date 2008-06-25 Time 12:27 Rev Time 0.00
Received By mawillia Date 2008-06-24 Time 15:34 Sent To  
Notes
2008-06-25 12:22:58*****PROVISO*****
  
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED;HOWEVER THE APPROPIATE PLAN SHEETS TO
 BE FIRE-STAMPED WHEN THE OTHER PLAN REVIEWERS HAVE BEEN
 SATISFIED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 5610805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-03-27 Cont ID  
Sent By mcarsill Date 2008-03-27 Time 09:50 Rev Time 0.00
Received By mcarsill Date 2008-03-27 Time 09:36 Sent To  
Notes
2008-03-27 09:49:471. TACTILE SIGNAGE REQUIRED AT ALL EXIT DOOR
 LOCATIONS.
  
 2. THIS OFFICE PICKED UP ON THE EMERGENCY LIGHT
 FIXTURES IDENTIFIED AS A, A1, H, AND Q, HOWEVER IT
 APPEARS THAT ALL AREAS ARE NOT DIPLAYED. EMERGENCY
 LIGHTING EQUIPMENT SHALL BE DISPLAYED FOR ALL AREAS OF
 THE BUILDING. PLEASE REVIEW ALL LARGE ROOMS TO
 DETERMINE IF EMERGENCY LIGHTING EQUIPMENT EXISTS FOR
 THESE AREAS. PLEASE PROVIDE DRAWINGS.
  
 3. THE FABRIC TRACK CEILING DISPLAYED ON PAGE A-6.0
 SHALL NOT INTERFERE WITH THE SPRAY PATTERN OF ANY
 AUTOMATIC FIRE SPRINKLER HEADS. THE FIRE SPRINKLER
 HEADS IN THIS AREA SHALL BE PROPERLY INSTALLED WITH
 CONSIDERATION FOR THE FABRIC TRACK CEILING.
  
 4. HOW IS THE COOK TOP GOING TO BE PROTECTED THAT IS
 DISPLAYED ON PAGE A-7.2. THERE APPEARS TO BE NO HOOD,
 DUCT OR FIRE SUPPRESSION SYSTEM ABOVE IT, ONLY A
 MICROWAVE OVEN.
  
 5. ANOTHER EXIT SIGN APPEARS TO BE NEEDED IN CORRIDOR
 300 TO DIRECT PERSONS TO WAITNG ROOM AREA EXIT 308
 NOTED ON PAGE E-3.0.
  
 6. KEYPADS NOTED AT DOORS ON ELECTRICAL SHEETS
 ILLUSTRATING FIRE ALARM EQUIPMENT. HOW DO THESE KEYPADS
 WORK. HOW DOES SOMEONE EXIT IF THEY DO NOT KNOW THE
 NUMBERS TO PUNCH. EVERY EMERGENCY DOES NOT ACTIVATE THE
 FIRE ALARM SYSTEM. SOME EMERGENCIES COULD OCCUR THAT
 DOES NOT IMMEDIATELY ACTIVATE THE FIRE SPRINKLER OR
 FIRE ALARM SYSTEM. PLEASE EXPLAIN KEYPAD AND HOW DOES
 IT WORK.
  
 7. PLEASE PROVIDE DOCUMENTATION ON THERMAL BLANKET THAT
 PROVIDES A TWO HOUR FIRE RATING ON PAGE M-2.3.
  
 8. PLEASE INDICATE EXIT ROUTES AND EXIT LOCATIONS FROM
 PARKING AREA.
  
 9. ANY FIRE EXTINGUISHERS PLANNED FOR ACCESS TO PARKING
 AREA.
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4776 FAX

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-10-23 Cont ID  
Sent By mcarsill Date 2007-10-23 Time 16:42 Rev Time 0.00
Received By mcarsill Date 2007-10-23 Time 14:12 Sent To  
Notes
2007-10-23 14:34:201. WET FIRE HYDRANTS ARE REQUIRED PRIOR TO, DURING, AND
 AFTER CONSTRUCTION.
  
 2. CONSTRUCTION, RENOVATION, AND DEMOLITION SHALL
 COMPLY WITH NFPA 241.
  
 3. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY.
  
 4. ANY CUTTING AND WELDING OPERATIONS TO COMPLY WITH
 NFPA 51B.
  
 5. EXITS ARE TO REMAIN CLEAR AND UNOBSTRUCTED.
  
 6. IT APPEARS THAT SOME ILLUMINATED EXIT SIGNS ARE
 MISSING FROM THE ELECTRICAL DRAWINGS. ALL EXIT ACCESS
 AND EXITS ARE TO BE PROPERLY IDENTIFIED BY ILLUMINATED
 EXIT SIGNS.
  
 7. SEPARATE PLANS AND PERMITS REQUIRED FOR AUTOMATIC
 FIRE SPRINKLER SYSTEM INSTALLATION.
  
 8. SEPARATE PLANS AND PERMITS REQUIRED FOR THE
 INSTALLATION OF THE FIRE ALARM SYSTEM.
  
 9. KNOX-BOX WILL BE REQUIRED FOR THE BUILDING.
  
 10. KNOX-BOX LOCKING CAPS WILL BE REQUIRED FOR THE FIRE
 DEPARTMENT CONNECTION CONNECTED TO THE SPRINKLER
 SYSTEM.
  
 11. THE REQUIRED FIRE ALARM SYSTEM SHALL BE MONITORED
 BY A LICENSED UL LISTED CENTRAL STATION APPROVED FOR
 CENTRAL STATION SERVICE.
  
 12. PLEASE EXPLAIN KEY PAD NOTES THAT ARE LISTED ON THE
 PLANS. HOW DO THESE DEVICES IMPACT EXITING FROM THE
 BUILDING.
  
 13. PLEASE PROVIDE INTERIOR FINISH CLASSIFICATIONS FOR
 ALL WALLS. CEILING INFORMATION LOCATED.
  
 14. SEPARATE PLANS AND PERMITS REQUIRED FOR THE
 HOOD,DUCT, AND FIRE SUPPRESSION SYSTEM PLANNED FOR THE
 BUILDING.
  
 15. ALL WALK-IN COOLERS AND FREEZERS ARE TO BE
 PROTECTED BY AUTOMATIC FIRE SPRINKLER PROTECTION.
  
 16. HANDRAILS AND GUARDRAILS TO COMPLY WITH APPLICABLE
 BUILDING AND FIRE CODE REQUIREMENTS.
  
 17. BUILDING ADDRESS REQUIRED. A MINIMUM OF AT LEAST 6"
 HIGH AND AT LEAST 1" NUMBERS ARE REQUIRED.
  
 18. PLEASE PROVIDE A COMPLETE LIFE SAFETY PLAN
 ILLUSTRATING PROPOSED OCCUPANT LOADS, TRAVEL DISTANCES,
 EXIT ROUTES, EXITS AND ALL OTHER RELATED INFORMATION.
  
 19. ANY ARCHITECTURAL SOFFITS SHALL NOT INTERFERE WITH
 THE OPERATION OF ANY FIRE SPRINKLER HEADS.
  
 20. PLEASE PROVIDE EGRESS CAPACITIES FOR DOORS ON PAGE
 A-2.3.
  
 21. EGRESS SCHEMES NEED TO BE FURTHER DEFINED.
  
 22. FLAME SPREAD DETAILS NEEDED FOR FABRIC CEILING
 ILLUSTRATED ON PAGE A-3.0. INFORMATION LOCATED ON PAGE
 A-6.0
  
 23. PLEASE ILLUSTRATE SEATING AREAS PLANNED FOR THE
 HANDICAPPED IN THE ASSEMBLY AREAS.
  
 24. PLEASE DISPLAY ALL PROPOSED FIRE EXTINGUISHER
 LOCATIONS.
  
 25. ACCORDING TO THE DOOR SCHEDULE ON PAGE A-10.1 THE
 GROUP SEVEN HARDWARE HAS A DEADBOLT AND AN EXIT PANIC
 DEVICE. WHEN PANIC DEVICES ARE INSTALLED ON EXIT DOORS
 NO OTHER LOCKS OR HANDWARE IS PERMITTED.
  
 26. THE DOOR SCHEDULE DECLARES ON PAGE A-10.1 THAT ONLY
 TWO TYPES OF DOORS WILL HAVE PANIC HARDWARE. IS THIS
 TRUE AND CORRECT.
  
 27. COULD NOT LOCATE AN EMERGENCY LIGHT FIXTURE TYPES
 ON PAGE E-15.0.
  
 28. ANY OCCUPIED AREA SHALL BE EQUIPPED WITH EMERGENCY
 LIGHTING EQUIPMENT. PLEASE ILLUSTRATE EMERGENCY LIGHT
 FIXTURES.
  
 29. PLEASE DESCRIBE WHAT THE CLASSROOMS WILL BE USED
 FOR. IF CHILDREN WILL USE THESE FACILITIES, PLEASE
 PROVIDE AGES, STAFFING COUNTS, AND NUMBER OF HOURS.
  
 30. PLEASE INDICATE WHAT THE VOICE EVACUATION MESSAGE
 FOR THE FIRE ALARM SYSTEM WILL DESCRIBE TO THE
 OCCUPANTS.
  
 31. WHAT HARDWARE IS EXPECTED ON THE GATES USED TO EXIT
 THE ENCLOSED COURTYARD AREA.
  
 32. THE LARGE MONUMENTAL STAIRS LOCATED ON THE EXTERIOR
 SHALL COMPLY WITH THE APPLICABLE STAIR SECTIONS OF THE
 CODE.
  
 33. IF THE OCCUPANT LOAD DECLARED ON PAGE A-2.1 CAN BE
 EXPECTED TO BE IN THE BUILDING AT ONE TIME, CROWD
 MANAGERS MAY BE NECESSARY AND SHALL RECEIVE THE PROPER
 TRAINING.
  
 34. NO SMOKING SIGNS SHALL BE INSTALLED SINCE SMOKING
 IS ASSEMBLY OCCUPANCIES CAN BE REGULATED BY THE
 AUTHORITY HAVING JURISDICTION.
  
 35. ALL ELECTRICAL EQUIPMENT INSTALLATION TO COMPLY
 WITH NFPA 70, THE NATIONAL ELECTRICAL CODE.
  
 36. PLEASE ILLUSTRATE ON THE PLANS THE ONE THIRD
 DIAGONAL DIMENSION FOR EXITING TO REACH EXITS IN FIRE
 SPRINKLER PROTECTED BUILDINGS.
  
 37. THE COVERED AREA AND AC AREA DOES NOT REFLECT THE
 TOTAL DISPLAYED ON PAGE A-1.0
  
  
 MIKE CARSILLO, BATTALION CHIEF
 804-4709 PHONE
 804-4774 FAX

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2008-06-04 Cont ID  
Sent By kstevens Date 2008-06-04 Time 14:53 Rev Time 0.00
Received By kstevens Date 2008-06-03 Time 12:52 Sent To  
Notes
2008-06-04 14:56:45 
  
 PASSED/PROVISO
  
 A REVISION IS REQUIRED FOR SHT P-11.0.
  
 SUBMIT A REVISION FOR THE GAS RISER DIAGRAM SHOWING THE
 BRANCH LINE AND SHUT OFF VALVE FOR APPLIANCE INDICATED
 AS OVEN UNIT NUMBER G3 AND DELETE SHUT OFF VALVE AND
 UNION IN THE CEILING.
  
 THE MANUF. SPECIFICATION SHEETS FOR THE G3 OVEN AND THE
 SECOND STAGE REGULATOR ARE REQUIRED AT THE TIME OF GAS
 PERMIT APPLICATION.
  
  
  
  
 .

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2008-03-15 Cont ID  
Sent By kstevens Date 2008-03-15 Time 08:39 Rev Time 0.00
Received By kstevens Date 2008-03-15 Time 08:39 Sent To  
Notes
2008-04-04 08:07:05DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 ****FROM PREVIOUS REVIEW:
  
 1. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING
 INFORMATION IS REQUIRED TO SECURE A PERMIT.
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.-- SHOW ALL PIPING FROM THE METER TO
 THE MOST REMOTE APPLIANCE.
 ****RESPONSE NOTED, BUT THE LENGTHS OF PIPE FROM THE
 METER TO AND INCLUDING THE FIRST DROP, THE FIRST RISE
 AND SECTION OVER TO THE FIRST RISER, (12FT). ALSO THE
 DROP OUT OF THE CEILING IS ONLY SHOWN AS 2FT. PLEASE
 CLARIFY AND SHOW ALL CUT SECTION LENGHTS.
  
 B. OK
 C. OK
  
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). --TOTAL DISTANCE FROM
 THE METER TO THE MOST REMOTE OUTLET IS NOT INDICATED ON
 THE PLANS. GAS APPLIANCE SCHEDULE NOTE #4 INDICATES
 80FT DEVELOPED LENGTH FROM THE REGULATOR, BUT ADDING
 ALL CUT SECTION LENGTHS PROVIDED ON THE ISOMETRIC
 SUBMITTED ON SHT P-11.0 197FT IS INDICATED. PLEASE
 CLARIFY.
 ****RESPONSE NOTED, BUT ADDITION OF CUT SECTION LENGHTS
 SHOWN TOTALS 127FT, THIS IS WITH THE SECTIONS FROM THE
 METER TO AND INCLUDING THE FIRST DROP, AS WELL AS THE
 FIRST RISE FROM THE PE PIPE AND SECTION TO THE FIRST
 RISER (12FT) NOT ADDED. A CLARIFICATION FOR THE DROP
 DOWNSTREAM OF THE SOLINOID VALVE, (2FT),WILL BE
 REQUIRED TO BE VERIFIED.
  
 E. OK
  
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, BUT THE LOCATION OF THE INFORMATION
 ON THE ARCHITECTURAL SHEETS IS NOT INDICATED. ALSO THE
 LISTING INFORMATION AS WELL AS THE BTU LOAD OF EACH GAS
 APPLIANCE IS REQUIRED. WILL THIS INFORMATION BE
 AVAILABLE ON THE ARCHITECTURAL SHEETS? IF NOT SUBMIT
 MANUF. SPECIFICATION SHEETS TO VERIFY LISTING & BTU
 LOAD.
  
 G. N/A
 H. N/A
  
 I. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 ****RESPONSE NOTED, BUT THE MANUAL SHUT OFF VALVE IS
 NOT INDICATED, NOR IS THE UNION. ALSO NO INDICATION
 THAT THE VALVES/UNION ARE BELOW THE CEILING.
  
 J. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE
 SECOND STAGE REGULATOR. INDICATE THE MODEL NUMBER. THE
 REGULATOR SHALL BE LISTED & INDICATE TOTAL BTU OUTPUT
 THAT CORRELATES TO THE TOTAL BTU LOAD DOWNSTREAM OF THE
 REGULATOR.
 ****RESPONSE NOTED, PLEASE SUBMIT PRIOR TO INSTALLATION
 TO PREVENT REMOVAL/REPLACEMENT IN CASE REGULATOR IS NOT
 APPROVED.
  
 K. A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR. SECTION 409.4.
 --ALSO A UNION WILL BE REQUIRED DOWNSTREAM OF THE
 SHUT OFF VALVE.PLEASE SHOW ON RISER DIAGRAM.
 ****RESPONSE NOTED, BUT THE UNION IS NOT INDICATED.
  
 **********NEW COMMENT**********
  
 1B. SHT P-11.1 THE UNIT NUMBERS FROM THE GAS APPLIANCE
 SCHEDULE DO NOT REFLECT THE NUMBERS INDICATED ON THE
 GAS ISOMETRIC RISER DIAGRAM. PLEASE CORRELATE. SECTION
 106.1.1 & TABLE 402.4(2).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-11-09 Cont ID  
Sent By kstevens Date 2007-11-09 Time 08:37 Rev Time 0.00
Received By kstevens Date 2007-11-09 Time 08:37 Sent To  
Notes
2008-03-15 08:39:36DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING
 INFORMATION IS REQUIRED TO SECURE A PERMIT.
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.-- SHOW ALL PIPING FROM THE METER TO
 THE MOST REMOTE APPLIANCE.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL). GAS APPLIANCE SCHEDULE
 NOTE #4 INDICATES TABLE 402.4(24) WHICH IS LP GAS.
  
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). --TOTAL DISTANCE FROM
 THE METER TO THE MOST REMOTE OUTLET IS NOT INDICATED ON
 THE PLANS. GAS APPLIANCE SCHEDULE NOTE #4 INDICATES
 80FT DEVELOPED LENGTH FROM THE REGULATOR, BUT ADDING
 ALL CUT SECTION LENGTHS PROVIDED ON THE ISOMETRIC
 SUBMITTED ON SHT P-11.0 197FT IS INDICATED. PLEASE
 CLARIFY.
  
 E. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304. -- FOR W/H.
  
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 G. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 H. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 I. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 J. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE
 SECOND STAGE REGULATOR. INDICATE THE MODEL NUMBER. THE
 REGULATOR SHALL BE LISTED & INDICATE TOTAL BTU OUTPUT
 THAT CORRELATES TO THE TOTAL BTU LOAD DOWNSTREAM OF THE
 REGULATOR.
  
 K. A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR. SECTION 409.4.
 --ALSO A UNION WILL BE REQUIRED DOWNSTREAM OF THE
 SHUT OFF VALVE.PLEASE SHOW ON RISER DIAGRAM.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-09-29 Cont ID  
Sent By adarroug Date 2008-09-29 Time 08:42 Rev Time 0.00
Received By adarroug Date 2008-09-29 Time 08:42 Sent To  
Notes
2008-09-29 08:43:11TO"COMM" BD#49--PLANS ON RACK 3 ROLLS/PAPERWORK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-08-12 Cont ID  
Sent By adarroug Date 2008-08-12 Time 11:49 Rev Time 0.00
Received By adarroug Date 2008-08-12 Time 11:49 Sent To  
Notes
2008-08-12 11:51:40TO "COMM" BD#43/PLANS ON RACK/4 ROLLS

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-05-20 Cont ID  
Sent By adarroug Date 2008-05-20 Time 12:52 Rev Time 0.00
Received By adarroug Date 2008-05-20 Time 12:52 Sent To  
Notes
2008-06-19 08:56:476/19/08--PLANS TAKEN FROM "COMM" BD#35, AND ROUTED TO
 MIKE WILLIAMS DESK FOR FIRE REVIEW.FIRE IS THE LAST
 REVIEW ON THIS RESUB.
2008-05-20 12:56:33TO "COMM" BD#35/PLANS ON RACK/4 ROLLS AND PAPERWORK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-02-05 Cont ID  
Sent By adarroug Date 2008-02-05 Time 08:45 Rev Time 0.00
Received By adarroug Date 2008-02-05 Time 08:45 Sent To  
Notes
2008-02-05 08:46:26TO "COMM" BD#21/PLANS ON RACK/3 ROLLS AND PAPERWORK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-11-09 Cont ID  
Sent By kstevens Date 2007-11-09 Time 18:49 Rev Time 0.00
Received By kstevens Date 2007-09-06 Time 12:10 Sent To  
Notes
2007-10-01 09:15:15TO "COMM" BD#62
2007-09-06 12:11:25WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-08-27 Cont ID  
Sent By rregueir Date 2008-08-27 Time 09:09 Rev Time 0.00
Received By rregueir Date 2008-08-26 Time 16:31 Sent To  
Notes
2008-08-27 09:02:53*************PROVISO**************
  
 DOCUMENTATION FROM APPLIANCE MANUFACTURER SHALL BE
 PROVIDED SHOWING ALL OUTDOOR APPLIANCES WHICH ARE
 EXPOSED TO WIND ARE DESIGNED TO RESSIST WIND PRESSURES
 IN ACCORDANCE WITH FBCM SECTION 301.13. THIS
 INFORMATION (FOR RTU'S ONLY, OTHER APPLIANCES ALREADY
 DOCUMENTED) SHALL BE SUBMITTED FOR PLAN REVIEW PRIOR TO
 INSTALLATION OF OUTDOOR APPLIANCES.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2008-06-03 Cont ID  
Sent By rregueir Date 2008-06-03 Time 16:06 Rev Time 0.00
Received By rregueir Date 2008-06-03 Time 13:09 Sent To  
Notes
2008-06-03 16:06:46ALL PREVIOUS PLAN REVIEW COMMENTS HAVE BEEN ADEQUATELY
 ADDRESSED RELATED TO THE PLANS. PLANS HAVE BEEN STAMPED
 AS REVIEWED FOR CODE COMPLIANCE. THE FOLLOWING ISSUES
 ARE OUTSTANDING:
  
 1. THIS IS A THRESHOLD BUILDING AND AS SUCH, THREE
 COMPLETE SETS OF PLANS, SPECIFICATIONS AND SUBMITTALS
 ARE REQUIRED FOR PERMIT. PLEASE COLLATE AND SUBMIT
 THREE COMPLETE SETS OF ALL PERMIT DOCUMENTATION
 (INCLUDING PRODUCT APPROVALS, SUCH AS FOR THE
 PRE-ENGINEERED A/C STANDS) FOR PERMIT.
  
 2. THE WINDLOAD REPORT SUBMITTED BY THE MECHANICAL
 DESIGNER HAS NOT SUCCESSFULLY PASSED A BUILDING PLAN
 REVIEW. THE INFORMATION ON FANS, GRAVITY VENTS AND
 CONDENSING UNITS IS SUFFICIENT, BUT THERE ARE NOT THREE
 COPIES SUBMITTED. THE INFORMATION PROVIDED FOR THE
 ROOFTOP PACKAGE UNITS IS NOT ADEQUATE AS IT IS A REPORT
 FROM 1993. THERE HAVE BEEN MANY CHANGES TO THE CODES
 AND RELATED REFERENCE STANDARDS SINCE THAT TIME.
  
 BASED ON THE LANGUAGE IN FBCM 301.13, THE MANUFACTURER
 OF THE APPLIANCES, WHO IS RESPONSIBLE FOR THE DESIGN OF
 THE APPLIANCES, SHALL CERTIFY THAT THE APPLIANCES ARE
 DESIGNED TO WITHSTAND ANTICIPATED WIND PRESSURES IN
 ACCORDANCE WITH FBCB CHAPTER 16. ONCE THIS BECOMES THE
 ONLY OUTSTANDING ISSUE RELATED TO MECHANICAL. A PASSED
 STATUS WILL BE ENTERED AND THE MISSING WIND LOAD
 INFORMATION WILL BE COVERED IN A PROVISO IN ORDER TO
 ALLOW THE PROJECT TO MOVE FORWARD WHILE MISSING
 INFORMATION IS OBTAINED AND SUBMITTED.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-03-03 Cont ID  
Sent By rregueir Date 2008-03-03 Time 17:30 Rev Time 0.00
Received By rregueir Date 2008-02-27 Time 09:53 Sent To  
Notes
2008-03-03 17:30:44REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. OK EXCEPT:
 PG M-1.1: IT APPEARS THAT SEVERAL SG-2 LINEAR DIFFUSERS
 ARE INCORRECTLY LABELED 20 INCHES BY 1 INCH WHEN THEY
 SHOULD BE LABELED FOR 20 FEET BY 1 INCH. ALSO, THE
 RETURN GRILL FOR RTU 1C DOES NOT HAVE A SIZE OR CFM
 DESIGNATION.
  
 2. PG M-1.1 AND M-1.2: AIR BALANCES STILL DO NOT
 REFLECT THE INTRODUCTION OF OUTDOOR AIR. EXAMPLE: RTU
 1A AND RTU 1B ON EQUIPMENT SCHEDULE EACH SHOW 6400 CFM
 OF SUPPLY. THE FLOOR PLAN ON PG M-1.1 SHOWS EACH UNIT
 RETURNING 6400 CFM FROM THE SPACE. IF THESE UNITS ARE
 RETURNING 100% OF THE AIR BEING SUPPLIED, HOW WILL THEY
 BE ABLE TO INTRODUCE THE 1300 CFM OF OUTDOOR AIR THAT
 EACH UNIT CALLS FOR ON THE EQUIPMENT SCHEDULE? A
 SIMILAR CONFIGURATION AND PROBLEM OCCURS FOR RTU 2A AND
 RTU 2B. IF THE INTENTION IS FOR THE RETURN AIR FLOW TO
 BE REDUCED AS THE OUTSIDE AIR DAMPER MODULATES, WOULD
 THERE NOT BE A NEED FOR A CORRESPONDING MODULATING
 DAMPER IN THE RETURN DUCTS? ADDITIONALLY, IT IS UNCLEAR
 HOW THE GRAVITY RELIEF VENTILATORS WILL SERVE TO
 RELIEVE POSITIVE PRESSURE IN THE SPACES BEING SERVED IF
 THEY ARE TIED INTO THE RETURN AIR DUCT SYSTEM. THIS
 WOULD PUT THE GRAVITY RELIEF UNDER CONSTANT NEGATIVE
 PRESSURE. PLEASE CLARIFY.
  
 3. A-6.1: ELEVATION DRAWINGS STILL DO NOT SHOW A
 PERMANENT MEANS OF ACCESS WHICH STARTS AT GRADE LEVEL
 AS REQUIRED BY FBCM 306.5. PLEASE SHOW COMPLIANCE AND
 RESUBMIT.
  
 4. DEFERRED TO BUILDING PLAN REVIEW. PLEASE COORDINATE
 WITH ARCHITECT SHOULD BUILDING PLAN REVIEW INDICATE THE
 NEED FOR RATED ASSEMBLIES IN ANY AREAS.
  
 5. PG M-2.1: PLEASE SEE COMMENT #2 ABOVE REGARDING AIR
 BALANCE AND GRAVITY VENTILATOR DESIGN FOR RTU 3A.
 AHU-14: FLOOR PLAN SHOWS 640 CFM OF SUPPLY WHILE
 SCHEDULE ON PG M-6.0 SHOWS 450 CFM OF SUPPLY. ALSO,
 SUPPLY AND RETURN ARE BOTH SHOWN AT 640 CFM, HOW WILL
 OUTSIDE AIR BE INTRODUCED?
 AHU-13: DH-2, WHICH IS ATTACHED TO THIS AHU, DOES NOT
 APPEAR IN THE EQUIPMENT SCHEDULE ON PG M-6.0. PLEASE
 CLARIFY. SEE COMMENT ABOVE REGARDING OA INTRODUCTION.
 PLEASE CHECK ALL AIR HANDLING SYSTEMS FOR SIMILAR
 CIRCUMSTANCES ON M-2.1, M-2.2, M-3.1 AND M-3.2.
 PG M-2.2: EXHAUST GRILLS FOR EF-3 ARE MISSING
 DESIGNATIONS, SIZES AND CFM. PLEASE CORRECT.
 PG M-3.2: THERE ARE DUCTS COMING DOWN FROM ROOF IN ROOM
 322 WHICH APPEAR TO BE FROM OAU-1. THIS UNIT IS SHOWN
 ON PG M-11.0 AS A 100% OUTSIDE AIR UNIT. IT IS UNCLEAR
 AS TO WHY A 100% OUTSIDE AIR UNIT HAS A RETURN DUCT
 SYSTEM SINCE IT IS PROVIDING 100% OUTSIDE AIR. PLEASE
 CLARIFY THE DESIGN INTENT. FBC 106.1.1.
  
 6. PLEASE SEE COMMENT #2 REGARDING DESIGN OF GRAVITY
 RELIEF DAMPERS.
  
 7. OK
  
 8. OK, EXCEPT PG M-2.3: KITCHEN GREASE EXHAUST DUCT,
 VERTICAL DUCTS UNDER EF-14 AND EF-15 ARE SHOWN ON PLAN
 TO BE 16X16. EACH OF THESE FANS IS SHOWN ON EQUIPMENT
 SCHEDULE TO BE RATED AT 1912 CFM. THIS MEANS THE AIR
 VELOCITY IN THE 16X16 DUCT WOULD BE APPROXIMATELY 1074
 FEET PER MINUTE. GREASE DUCT SYSTEMS SERVING A TYPE I
 HOOD SHALL BE DESIGNED AND INSTALLED SO AS TO PROVIDE
 AN AIR VELOCITY WITHIN THE DUCT SYSTEM OF NOT LESS THAN
 1,500 FEET PER MINUTE AND NOT GREATER THAN 2,500 FEET
 PER MINUTE IN ACCORDANCE WITH FBCM 506.3.4. THE 16X16
 DUCT MAY FALL UNDER THE EXCEPTION IN THIS SECTION IF IT
 IS FOR THE PURPOSE OF TRANSITIONING TO THE SIZE OF THE
 FANS AND IT IS LESS THAN 3 FEET IN LENGTH BUT THAT CAN
 NOT BE DETERMINED FROM THESE DRAWINGS.
  
 9. OK
  
 10. OK
  
 11. M-6.0: PLEASE INCLUDE THIS NOTE ON THE OARTU
 SCHEDULE.
  
 12. OK
  
 13. OK
  
 14. OK
  
 15. OK
  
 16. OK
  
 17. WIND LOAD SUBMITTAL DATA FOR ROOFTOP EQUIPMENT WILL
 BE REVIEWED BY THE BUILDING PLAN REVIEWER.
  
 18. EQUIPMENT HEIGHT OK, PRODUCT APPROVAL SUBMITTALS
 WILL BE REVIEWED BY THE BUILDING PLAN REVIEWER.
  
 19. OK
  
 20. TO BE DETERMINED BY SUBSEQUENT BUILDING PLAN
 REVIEW.
  
 PLEASE RESPOND TO ALL REVIEW COMMENTS IN WRITING WITH
 INFORMATION ON HOW COMMENTS HAVE BEEN ADDRESSED AND
 WHERE THE REQUESTED INFORMATION CAN BE FOUND IN ORDER
 TO SPEED THE REVIEW PROCESS. ADDITIONALLY, PLEASE
 RETURN ONE SET OF OLD PLANS FOR REFERENCE. ROMOVE
 OLD/VOIDED SHEETS FROM THE PLANS BEING SUBMITTED FOR
 PERMIT PRIOR TO RESUBMITTAL.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-11-03 Cont ID  
Sent By rregueir Date 2007-11-03 Time 15:08 Rev Time 0.00
Received By rregueir Date 2007-11-01 Time 17:16 Sent To  
Notes
2007-11-03 15:08:32REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. M-1.0: GIVEN THE CONGESTED NATURE OF THE DUCT LAYOUT
 IN THE ROOM 101 SANCTUARY AREA, IT IS NOT POSSIBLE TO
 REVIEW THIS AREA OF THE PLANS. WHILE IT IS UNDERSTOOD
 THAT THE PLANS ARE DRAWN AT THE MINIMUM ALLOWED 1/8IN.
 SCALE, THE NATURE OF THE WORK AND THE VOLUME OF
 INFORMATION INCLUDED IN THIS SMALL AREA MAKES IT
 DIFFICULT TO ASCERTAIN THE NATURE AND SCOPE OF WORK IN
 THIS AREA. IT IS REQUESTED THAT, UPON RESUBMITTAL, THIS
 AREA BE REPRESENTED IN A MANNER WHICH MORE CLEARLY
 DELINEATES THE SIZES, ROUTING, LOCATIONS AND
 DESIGNATIONS OF EQUIPMENT, DUCTS AND DIFFUSERS. ONE
 SUGGESTION WOULD BE TO SHOW THIS AREA (ROOM 101
 SANCTUARY) AT A LARGER SCALE. FBC 106.1.1 AND 106.1.3.
  
 2. M-1.0: ROOM 102 SOCIAL HALL, THE AIR QUANTITIES IN
 THIS AREA DO NOT APPEAR IN BALANCE. GRILL DESIGNATIONS
 CALL FOR 8000 TOTAL CFM OF SUPPLY AND 12,800 CFM OF
 RETURN. ALSO, THE OUTDOOR AIR SCHEDULE CALLS FOR 2400
 CFM OF O.A. IN THIS AREA. HOW WILL THIS O.A. BE
 INTRODUCED IF THE RTUS ARE RETURNING MORE AIR THAN THEY
 ARE SUPPLYING? WILL ANY AIR BE EXHAUSTED TO BE REPLACED
 BY THE 2400 CFM OF O.A.? THE AMOUNT OF SUPPLY AIR SHALL
 BE APPROXIMATELY EQUAL TO THE AMOUNT OF RETURN AND
 EXHAUST AIR IN ACCORDANCE WITH FBC,M 403.1 AND THE
 MECHANICAL SYSTEM SHALL BE DESIGNED TO ASSURE THAT THE
 BUILDING IS PRESSURIZED WITH RESPECT TO OUTDOORS IN
 ACCORDANCE WITH FBC 13-409.1.ABC.2.
 NOTE: THESE COMMENTS APPLY TO ALL AREAS WHICH ARE
 REQUIRED TO BE PROVIDED WITH OUTSIDE AIR IN ACCORDANCE
 WITH FBC,M 403.3. VERIFY AIR BALANCES FOR ALL SYSTEMS
 IN ALL AFFECTED AREAS AND MAKE CORRECTIONS AS NEEDED
 PRIOR TO RESUBMITTAL.
  
 3. A-6.1: ELEVATION DRAWINGS SHOW ACCESS LADDERS FROM
 LOWER ROOF TO HIGHER ROOF AREAS. WHERE EQUIPMENT AND
 APPLIANCES REQUIRING ACCESS ARE INSTALLED ON ROOFS OR
 ELEVATED STRUCTURES AT A HEIGHT EXCEEDING 16 FEET, SUCH
 ACCESS SHALL BE PROVIDED BY A PERMANENT APPROVED MEANS
 OF ACCESS, THE EXTENT OF WHICH SHALL BE FROM GRADE OR
 FLOOR LEVEL TO THE EQUIPMENT AND APPLIANCES? LEVEL
 SERVICE SPACE. SUCH ACCESS SHALL NOT REQUIRE CLIMBING
 OVER OBSTRUCTIONS GREATER THAN 30 INCHES HIGH IN
 ACCORDANCE WITH FBC,M 306.5. PLEASE SHOW THE PERMANENT
 MEANS OF ACCESS TO BE FROM FLOOR OR GRADE TO THE ROOF
 LEVEL.
 PERMANENT LADDERS INSTALLED TO PROVIDE THE REQUIRED
 ACCESS SHALL COMPLY WITH THE FOLLOWING MINIMUM DESIGN
 CRITERIA:
 1) THE SIDE RAILING SHALL EXTEND ABOVE THE PARAPET OR
 ROOF EDGE NOT LESS THAN 30 INCHES.
 2) LADDERS SHALL HAVE RUNG SPACING NOT TO EXCEED 14
 INCHES ON CENTER.
 3) LADDERS SHALL HAVE A TOE SPACING NOT LESS THAN 6
 INCHES DEEP.
 4) THERE SHALL BE A MINIMUM OF 18 INCHES BETWEEN
 RAILS.
 5) RUNGS SHALL HAVE A MINIMUM 0.75-INCH DIAMETER AND BE
 CAPABLE OF WITHSTANDING A 300-POUND LOAD.
 THERE ARE MULTIPLE LEVELS OF ROOF WHICH APPEAR TO BE
 SEPARATED BY PARAPETS SHOWN ON PG M-4.0. SHOW A MEANS
 OF PERMANENT ACCESS AS REQUIRED BY THIS SECTION ON EACH
 OF THESE LEVELS WHERE EQUIPMENT REQUIRING SERVICE
 ACCESS IS LOCATED.
  
 4. NO WALL SCHEDULE OR FLOOR PLAN COULD BE FOUND IN
 ARCHITECTURAL PLANS SHOWING LOCATIONS OF
 FIRE-RESISTANCE RATED WALL ASSEMBLIES. PLANS COULD NOT
 BE REVIEWED FOR POTENTIAL REQUIRED OPENING PROTECTIVES
 IN DUCT PENETRATIONS OF WALLS. PLEASE INCLUDE THE
 LOCATION OF ALL FIRE RESISTANCE RATED ASSEMBLIES IN THE
 ARCHITECTURAL PLANS TO DETERMINE WHERE OPENING
 PROTECTIVES MAY BE REQUIRED. PLEASE COORDINATE BETWEEN
 MECHANICAL AND ARCHITECTURAL DESIGNERS TO ENSURE ALL
 REQUIRED OPENING PROTECTIVES ARE SHOWN ON PLANS PRIOR
 TO RESUBMITTAL. FBC,M 607.5 AND 607.8.
  
 5. M-2.0 AND M-3.0: PLEASE SEE COMMENT #1 REGARDING
 CLARITY OF PLANS AND SCOPE OF WORK. IT IS NOT POSSIBLE
 BASED ON THE LAYOUT ON THE PLANS TO DETERMINE WHICH
 DESIGNATION SYMBOL GOES WITH WHICH GRILL, DIFFUSER OR
 FAN ON THIS FLOOR PLAN. PLEASE CLARIFY. FBC 106.1.1.
  
 6. M-4.0: WHAT IS THE FUNCTION OF THE GRAVITY RELIEF
 VENTILATORS? THERE IS NO INDICATION ON FLOOR PLANS THAT
 THESE VENTILATORS COMMUNICATE WITH ANY INTERIOR
 PORTIONS OF THE BUILDING. ARE THESE FOR THE RELIEF OF
 POSITIVE PRESSURE CREATED BY THE INTRODUCTION OF
 OUTDOOR AIR? PLEASE SEE COMMENT #2 REGARDING AIR
 BALANCES.
  
 7. M-4.0: WHAT IS THE ELEVATION OF KITCHEN EXHAUST FANS
 IN RELATION TO THE PARAPET WALL TO THE SOUTH OF THE
 FANS? NO ELEVATION IS GIVEN ON THE KITCHEN ROOF
 EXHAUSTER DETAIL SHOWN ON M-9.0. EXHAUST OUTLETS THAT
 TERMINATE ABOVE THE ROOF SHALL HAVE THE DISCHARGE
 OPENING LOCATED NOT LESS THAN 40 INCHES ABOVE THE ROOF
 SURFACE IN ACCORDANCE WITH FBC,M 506.3.12.1. ALSO,
 EXHAUST OUTLETS SHALL BE LOCATED NOT LESS THAN 10 FEET
 HORIZONTALLY FROM PARTS OF THE SAME OR CONTIGUOUS
 BUILDINGS. EXCEPTION: THE MINIMUM HORIZONTAL DISTANCE
 BETWEEN VERTICAL DISCHARGE FANS AND PARAPET-TYPE
 BUILDING STRUCTURES SHALL BE 2 FEET PROVIDED THAT SUCH
 STRUCTURES ARE NOT HIGHER THAN THE TOP OF THE FAN
 DISCHARGE OPENING IN ACCORDANCE WITH FBC,M 506.3.12.3
 AND 506.5.5. CURRENTLY THE EXHAUST FANS ARE SHOWN LESS
 THAN 10 FEET FROM THE PARAPET. SHOW COMPLIANCE WITH
 THESE SECTIONS.
  
 8. KITCHEN EXHAUST: NO INFORMATION WAS PROVIDED IN
 THESE PLANS REGARDING THE COMMERCIAL KITCHEN EXHAUST
 SYSTEM OTHER THAN THAT SHOWN ON FAN SCHEDULE. THIS
 SYSTEM CAN NOT BE REVIEWED FOR CODE COMPLIANCE AT THIS
 TIME. PROVIDE SUFFICIENT DETAIL AND DOCUMENTATION TO
 DEMONSTRATE COMPLIANCE WITH FBC,M SEC. 506, 507 AND 508
 PRIOR TO PERMIT ISSUANCE AS THESE ARE CODE REQUIRED
 SYSTEMS FOR COMMERCIAL KITCHENS. SEE FBC,M 507.2.
 PROVIDE A KITCHEN LAYOUT SHOWING THE LOCATION OF ALL
 COOKING EQUIPMENT IN RELATION TO THE KITCHEN HOOD. FBC
 106.1.2. ALSO, PG A-1.0 INDICATES THAT THE YOUTH CENTER
 ROOM 213 IS TO CONTAIN A ?SECONDARY KITCHEN.? PLEASE
 SHOW ON PLANS THE LAYOUT OF THIS KITCHEN ALONG WITH
 COOKING EQUIPMENT AND REQUIRED EXHAUST SYSTEMS.
  
 9. M-5.0: PROVIDE DETAILED INFORMATION SHOWING ACCESS
 FOR SERVICE AND REPLACEMENT FOR AHU?S 12A AND 12B IN
 THE CHAPEL. SHOW COMPLIANCE WITH FBC,M 306.1 AND EITHER
 306.2 OR 306.3, WHICHEVER IS MORE APPROPRIATE FOR
 CONDITIONS. IT IS UNCLEAR WHETHER THESE UNITS ARE
 HOUSED IN AN ATTIC SPACE OR A ROOM ON A SEPARATE
 MEZZANINE-TYPE LEVEL.
  
 10. M-6.0: ROOF-TOP A/C UNIT SCHEDULE, NONE OF THE
 RTU?S ARE SHOWN ON ENERGY CALCULATIONS IN THE INPUT
 DATA REPORT (FURTHER REFERENCED AS IDR) UNDER THE
 ?SYSTEMS? PORTION. DATA SHALL BE INPUT INTO FLA/COM FOR
 EACH ZONE BY EQUIPMENT TYPE, SIZE AND EFFICIENCY IN
 ACCORDANCE WITH FBC 13-407.2.A. ALSO, NEITHER COOLING
 LOAD CALCULATIONS NOR SYSTEM SIZING SUMMARIES WERE
 INCLUDED WITH THE ENERGY CALCULATIONS. THESE
 CALCULATIONS SHALL BE ATTACHED TO THE CODE COMPLIANCE
 FORM SUBMITTED TO THE BUILDING DEPARTMENT AT TIME OF
 PERMIT APPLICATION IN ACCORDANCE WITH FBC
 13-407.1.ABC.1. PROVIDE ALL MISSING
 INFORMATION/CALCULATIONS/SUMMARIES AND MAKE THEM PART
 OF A COMPLETE METHOD A CODE COMPLIANCE FORM AS REQUIRED
 BY THESE SECTIONS.
  
 11. M-6.0: RTU SCHEDULE NOTES, AUXILIARY DRAIN
 PROTECTION IS REQUIRED ON DOWNDRAFT RTU?S AS ANY
 OVERFLOW OF CONDENSATE FROM THE PRIMARY DRAIN PAN WOULD
 INEVITABLY LEAK INTO THE BUILDING. THIS MAY BE
 ACCOMPLISHED WITH A WATER LEVEL DETECTION DEVICE (SUCH
 AS A FLOAT SWITCH) LOCATED INTERNALLY ON THE PRIMARY
 DRAIN PAN IN ACCORDANCE WITH FBC,M 307.2.3(2).
  
 12. M-6.0 SUPPLY AIR UNIT SCHEDULE:MUCH OF THE
 INFORMATION IN THE COOLING LOAD CALCULATIONS DOES NOT
 CORRESPOND WITH THIS SCHEDULE. EXAMPLE (A): AIR HANDLER
 #3 IS SHOWN WITH 95 TOTAL CFM IN CALCULATIONS BUT SHOWS
 1300 CFM ON SCHEDULE. EXAMPLE (B): AIR HANDLER #4 IS
 SHOWN WITH 14,839 CFM AND 38.57 TONS OF TOTAL COOLING
 IN CALCULATIONS BUT SHOWS 1300 CFM AND A LITTLE OVER 3
 TONS OF TOTAL COOLING ON SCHEDULE. PLEASE VERIFY THAT
 ALL INFORMATION IN SYSTEM SIZING CALCULATIONS AND THE
 IDR CORRESPONDS WITH THE EQUIPMENT SHOWN ON SCHEDULE.
  
 13. M-6.0: FAN SCHEDULE, EF-1 THROUGH EF-11 SHOW THEY
 ARE TO BE CONTROLLED BY WALL SWITCH. THESE AREAS ARE
 REQUIRED TO HAVE MECHANICAL EXHAUST IN ACCORDANCE WITH
 FBC,M TABLE 403.3 AND AS SUCH, ALL AIR SUPPLIED TO SUCH
 SPACES SHALL BE EXHAUSTED IN ACCORDANCE WITH FBC,M
 403.2.1(3). PLEASE SHOW HOW THESE FANS ARE TO BE
 CONTROLLED IN WAY THAT ASSURES THAT THEY WILL OPERATE
 WHENEVER AIR IS BEING SUPPLIED TO THESE SPACES (BY AHU
 OR RTU) AS WELL AS WHENEVER THESE SPACES ARE OCCUPIED
 IN ACCORDANCE WITH FBC,M 401.3 AND 403.2.1(3).
  
 14. M-6.0: FAN SCHEDULE, EF-14 AND EF-15 HAVE A NOTE
 (NOTE 5) INDICATING THEY ARE TO BE PROVIDED WITH
 WEATHER HOODS AND 2 INCH ALUMINUM MESH FILTERS. PLEASE
 CLARIFY AS IT APPEARS THIS NOTE SHOULD ONLY APPLY TO
 SF-1 AND SF-2. ALSO, SF-1 AND SF-2 HAVE A NOTE (NOTE 6)
 INDICATED THEY ARE TO HAVE GREASE DRAINS, HINGED CURBS
 CAPS, ETC. PLEASE CLARIFY AS IT APPEARS THIS NOTE
 SHOULD ONLY APPLY TO EF-14 AND EF-15. EQUIPMENT AND
 APPLIANCES SHALL BE INSTALLED AS REQUIRED BY THE TERMS
 OF THEIR APPROVAL, IN ACCORDANCE WITH THE CONDITIONS OF
 THE LISTING, THE MANUFACTURER?S INSTALLATION
 INSTRUCTIONS AND THIS CODE. FBC 304.1
  
 15. M-6.0 OUTDOOR AIR SCHEDULE: NOTE (1) INDICATES 50%
 DIVERSITY USED IN SEVERAL AREAS. THIS IS ASSUMED TO BE
 A REDUCTION OF THE OUTDOOR AIR RATE BASED ON A LIMITED
 DURATION OF THE TIME OF OCCUPANCY. THIS IS NOT OFFERED
 AS AN ADJUSTMENT UNDER FBC,M TABLE 403.3. THERE IS ALSO
 A NOTE IN THE RTU SCHEDULE INDICATING OUTDOOR AIRFLOW
 IS TO BE CONTROLLED BY CO2 SENSORS AND MODULATING
 DAMPERS. IF THE INTENT IS TO DESIGN THE SYSTEM BASED ON
 ASHRAE 62.1-2004 THEN THAT SHALL BE DECLARED ON PLANS.
 THE O.A. SCHEDULE INDICATES OA RATES ARE BASED ON TABLE
 403.3. IN LIEU OF COMPLIANCE WITH SECTION 403.1 THROUGH
 SECTION 403.3, MECHANICAL VENTILATION MAY BE
 IMPLEMENTED IN COMPLIANCE WITH ASHRAE 62.1-2004
 INCLUDING APPROVED ADDENDA IN ACCORDANCE WITH FBC,M
 403.4. PLEASE INDICATE WHICH METHOD IS TO BE USED AND
 PROVIDE FULL COMPLIANCE WITH THE METHOD CHOSEN.
  
 16. M-6.0 O.A. SCHEDULE: NOTE (2) INDICATES ?OCCUPANCY
 PROVIDED BY OWNER.? THE OCCUPANT LOAD IS NOT REQUIRED
 TO BE DETERMINED, BASED ON THE ESTIMATED MAXIMUM
 OCCUPANT LOAD RATE INDICATED IN TABLE 403.3 WHERE
 APPROVED STATISTICAL DATA DOCUMENT THE ACCURACY OF AN
 ALTERNATE ANTICIPATED OCCUPANT DENSITY (SEE FBC,M 403.3
 EXCEPTION). NO SUCH STATISTICAL DATA HAS BEEN PROVIDED
 TO JUSTIFY THESE OCCUPANT LOADS. ALSO, PG A-2.4
 INDICATES THAT THE SOCIAL HALL HAS A POTENTIAL OCCUPANT
 LOAD OF 711 PERSONS, NOT THE 300 SHOWN ON O.A.
 SCHEDULE. SELECT THE CORRECT OCCUPANT LOAD FOR THIS
 AREA AND DESIGN THE VENTILATION SYSTEM TO PROVIDE
 ADEQUATE VENTILATION IN ACCORDANCE WITH THE METHOD
 CHOSEN. FBC,M 403.3 AND FBC 106.1.2.
  
 17. M-9.0: PROVIDE MANUFACTURER?S SUBMITTAL DATA
 SHOWING OUTDOOR EQUIPMENT SUCH AS CONDENSING UNITS,
 RTU?S, ROOFTOP EXHAUST FANS AND VENTILATORS DESIGNED TO
 WITHSTAND WIND LOADS IN ACCORDANCE WITH FBC,M 301.13
 AND FBC 1609. MANUFACTURER?S INSTRUCTIONS SHALL ONLY BE
 USED FOR STRAPPING AND CURB ATTACHMENT IF THE DESIGN IS
 ENGINEERED TO MEET WIND LOAD REQUIREMENTS IN ACCORDANCE
 WITH THESE SECTIONS. PROVIDE ATTACHMENT DETAIL WIT WIND
 LOAD CALCULATIONS IF DIFFERENT FROM OR NOT INCLUDED IN
 MANUFACTURER?S INSTRUCTIONS. FBC 106.1.2.
  
 18. M-9.0 CONDENSER SUPPORT DETAIL: IS THIS TO BE A
 FIELD-FABRICATED SUPPORT OR A PRE-ENGINEERED A/C STAND?
 IF A PRE-ENGINEERED STAND IS TO BE USED, PRODUCT
 APPROVAL IS REQUIRED AS A/C STANDS ARE CLASSIFIED AS
 STRUCTURAL COMPONENTS BY FAC RULE 9B-72. ALSO, EXTERIOR
 WALL LOUVERS REQUIRE PRODUCT APPROVAL AS THEY ARE
 CLASSIFIED AS PANEL WALLS BY RULE 9B-72. PROVIDE ALL
 SUPPORTING DOCUMENTATION. FOR MORE INFORMATION ON THE
 FLORIDA PRODUCT APPROVAL SYSTEM PLEASE VISIT
 WWW.FLORIDABUILDING.ORG. ALSO, THE CLEARANCE UNDER THE
 A/C SUPPORTS SHALL BE DETERMINED BY THE WIDTH OF THE
 EQUIPMENT BEING SUPPORTED IN ACCORDANCE WITH FBC TABLE
 1509.7. THE 18 INCHES AS STATED ON THE DETAIL MAY OR
 MAY NOT BE ADEQUATE PER THIS SECTION.
  
 19. M-10.0: IF O.A. DAMPERS ON RTUS ARE TO BE MODULATED
 BY CO2 SENSORS, THEY SHOULD BE INCLUDED IN THE CONTROL
 DIAGRAM. FBC 106.1.1.
  
 20. M-11.0: LOCATIONS OF FIRE DAMPERS IS NOT SHOWN ON
 PLANS. THE SPECIFIC LOCATION AND INSTALLATION DETAILS
 OF EACH FIRE DOOR, FIRE DAMPER, CEILING DAMPER AND
 SMOKE DAMPER SHALL BE SHOWN AND PROPERLY IDENTIFIED ON
 THE BUILDING PLANS BY THE DESIGNER IN ACCORDANCE WITH
 FBC,M 607.8.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-06-04 Cont ID  
Sent By kstevens Date 2008-06-04 Time 14:45 Rev Time 0.00
Received By kstevens Date 2008-06-03 Time 12:52 Sent To  
Notes
2008-06-04 14:50:20 
  
  
 PASSED/PROVISO
  
 REVISION REQUIRED FOR SHT P-14.0.
  
 REVISE CONDENSATE RISER C/1 TO SHOW RELIEF VENT LINE
 FOR CONDENSATE RISER AS INDICATED ON THE FLOOR PLAN.
 (SHT P-1.0).
  
 REVISE CONDENSATE RISER C/5 TO INCLUDE CONDENSATE FROM
 AHU-15 AS INDICATED ON THE FLOOR PLAN. (SHT P-3.0).
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-03-15 Cont ID  
Sent By kstevens Date 2008-03-15 Time 08:40 Rev Time 0.00
Received By kstevens Date 2008-03-14 Time 18:52 Sent To  
Notes
2008-03-15 09:25:28DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
 CITY WPB MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
 2. OK
 3. OK
 4. OK
 5. OK
 6. OK
 7. OK
 8. OK
 9. OK
 10. OK
 11. OK
 12. OK
 13. OK
 14. OK
 15. OK
 16. OK
 17. OK
 18. OK
  
 19. SHT P1.0 SHOWS CONDENSATE TO DISCHARGE 6" ABOVE THE
 SIDEWALK. THIS IS NOT APPROVED. CONDENSATE SHALL
 CONNECT TO A DRYWELL, STORM CATCH BASIN, PLANTED AREA
 OR CONNECT TO A STORM DRAINAGE LINE OUTSIDE THE
 BUILDING. IF CONNECTING TO A STORM LINE, A RELIEF VENT,
 (GOOSENECK), SHALL BE REQUIRED AS THE CONDENSATE EXITS
 THE BUILDING. CONDENSATE DRAINAGE CAN NOT CREATE A
 HAZARD OR NUISANCE. SECTION 314.2.1.
 ****RESPONSE NOTED, BUT THE RELIEF VENT, (GOOSENECK),
 IS NOT INDICATED ON THE PLANS. THE RELIEF VENT WILL
 KEEP ANY STORM/CONDENSATE FROM ENTERING THE BUILDING
 AND MAKES THE REQUIREMENT FOR A BACKWATER VALVE MOOT.
  
 20. OK
 21. OK
  
 22. SUBMIT A WATER ISOMETRIC WATER RISER DIAGRAM FROM
 METER, THRU RPZV BACKFLOW, TO THE MOST REMOTE FIXTURE
 SHOWING ALL PIPE SIZES, VALVES, OFFSETS, & WATER HAMMER
 ARRESTORS REQUIRED BY SECTION 604.9. WATER HAMMER
 ARRESTORS SHALL BE LOCATED NEAR THE FIXTURES IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING. PDI-WH 201 AND
 MANUF. INSTALLATION INSTRUCTIONS. SECTION
 106.3.5.1.3(3)(10)(13).
 ****RESPONSE NOTED, BUT SHEET P-12 STATES "CONT. ON SHT
 P-13.0, BUT NO WATER ISOMETRIC WAS FOUND ON SHE P-13.0.
 PLEASE CLARIFY.
  
 23. OK
 24. OK
  
 25. SHT P-3.0 CONDENSATE LINES SHOW BACKWATER VALVES.
 PER SECTION 715.1 FIXTURES ABOVE THE ELEVATION OF THE
 MANHOLE SHALL NOT DISCHARGE THRU A BACKWATER VALVE.
 WHERE THE POSSIBILITY OF A BACKUP MAY OCCUR, A RELIEF
 VENT, (GOOSENECK) , SHALL BE INSTALLED AS THE
 CONDENSATE EXITS THE BUILDING.
 ****RESPONSE NOTED, BUT THE RELIEF VENT WILL KEEP ANY
 STORM/CONDENSATE FROM ENTERING THE BUILDING AND MAKES
 THE REQUIREMENT FOR A BACKWATER VALVE MOOT.
  
 26. OK
 27. OK
 28. OK
 29. OK
 30. OK
  
 31. SUBMIT STORM ISOMETRIC RISER DIAGRAMS FOR ALL ROOF
 DRAINS AND SECONDARY ROOF DRAINS THAT REFLECT THE FLOOR
 PLAN. SHOW ALL PIPE SIZES, OFFSETS AND INDICATE SQUARE
 FOOTAGE BEING DRAINED BY EACH ROOF DRAIN. SECTION
 106.3.5.1.3(7)(13).--SHOW CLEANOUTS REQUIRED BY
 SECTION 1101.8.
 ****RESPONSE NOTED, BUT ISOMETRIC RISER DIAGRAMS FOR
 RISERS 12 THRU 22 HAVE NOT BEEN SUBMITTED. PLEASE SHOW
 ALL PIPE SIZES AND INDICATE THE SQUARE FOOTAGE IN THE
 RISER DIAGRAM AS IT ACCUMULATES IN THE SYSTEM ON THE
 NEW RISERS AS WELL AS THOSE RISERS SUBMITTED
 PREVIOUSLY.
  
 32. SUBMIT CONDENSATE ISOMETRIC RISER DIAGRAMS FOR ALL
 CONDENSATE RISERS THAT REFLECT THE FLOOR PLAN. SHOW
 PIPE SIZES. OFFSETS AND INDICATE MATERIAL FOR SYSTEM.
 NO PVC IN PLENUMS.
 ****RESPONSE NOTED, BUT CONDENSATE RISERS WERE NOT
 FOUND.
  
 33. OK
 34. OK
 35. OK
 36. OK
 37. OK
  
 38. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING
 INFORMATION IS REQUIRED TO SECURE A PERMIT.
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.-- SHOW ALL PIPING FROM THE METER TO
 THE MOST REMOTE APPLIANCE.
 ****RESPONSE NOTED, BUT THE LENGTHS OF PIPE FROM THE
 METER TO AND INCLUDING THE FIRST DROP, THE FIRST RISE
 AND SECTION OVER TO THE FIRST RISER, (12FT). ALSO THE
 DROP OUT OF THE CEILING IS ONLY SHOWN AS 2FT. PLEASE
 CLARIFY AND SHOW ALL CUT SECTION LENGHTS.
  
 B. OK
 C. OK
  
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). --TOTAL DISTANCE FROM
 THE METER TO THE MOST REMOTE OUTLET IS NOT INDICATED ON
 THE PLANS. GAS APPLIANCE SCHEDULE NOTE #4 INDICATES
 80FT DEVELOPED LENGTH FROM THE REGULATOR, BUT ADDING
 ALL CUT SECTION LENGTHS PROVIDED ON THE ISOMETRIC
 SUBMITTED ON SHT P-11.0 197FT IS INDICATED. PLEASE
 CLARIFY.
 ****RESPONSE NOTED, BUT ADDITION OF CUT SECTION LENGHTS
 SHOWN TOTALS 127FT, THIS IS WITH THE SECTIONS FROM THE
 METER TO AND INCLUDING THE FIRST DROP, AS WELL AS THE
 FIRST RISE FROM THE PE PIPE AND SECTION TO THE FIRST
 RISER (12FT) NOT ADDED. A CLARIFICATION FOR THE DROP
 DOWNSTREAM OF THE SOLINOID VALVE, (2FT),WILL BE
 REQUIRED TO BE VERIFIED.
  
 E. OK
  
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, BUT THE LOCATION OF THE INFORMATION
 ON THE ARCHITECTURAL SHEETS IS NOT INDICATED. ALSO THE
 LISTING INFORMATION AS WELL AS THE BTU LOAD OF EACH GAS
 APPLIANCE IS REQUIRED. WILL THIS INFORMATION BE
 AVAILABLE ON THE ARCHITECTURAL SHEETS? IF NOT SUBMIT
 MANUF. SPECIFICATION SHEETS TO VERIFY LISTING & BTU
 LOAD.
  
 G. N/A
 H. N/A
  
 I. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 ****RESPONSE NOTED, BUT THE MANUAL SHUT OFF VALVE IS
 NOT INDICATED, NOR IS THE UNION. ALSO NO INDICATION
 THAT THE VALVES/UNION ARE BELOW THE CEILING.
  
 J. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE
 SECOND STAGE REGULATOR. INDICATE THE MODEL NUMBER. THE
 REGULATOR SHALL BE LISTED & INDICATE TOTAL BTU OUTPUT
 THAT CORRELATES TO THE TOTAL BTU LOAD DOWNSTREAM OF THE
 REGULATOR.
 ****RESPONSE NOTED, PLEASE SUBMIT PRIOR TO INSTALLATION
 TO PREVENT REMOVAL/REPLACEMENT IN CASE REGULATOR IS NOT
 APPROVED.
  
 K. A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR. SECTION 409.4.
 --ALSO A UNION WILL BE REQUIRED DOWNSTREAM OF THE
 SHUT OFF VALVE.PLEASE SHOW ON RISER DIAGRAM.
 ****RESPONSE NOTED, BUT THE UNION IS NOT INDICATED.
  
 **********NEW COMMENT**********
  
 1B. SHT P-11.1 THE UNIT NUMBERS FROM THE GAS APPLIANCE
 SCHEDULE DO NOT REFLECT THE NUMBERS INDICATED ON THE
 GAS ISOMETRIC RISER DIAGRAM. PLEASE CORRELATE. SECTION
 106.1.1 & TABLE 402.4(2).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-11-09 Cont ID  
Sent By kstevens Date 2007-11-09 Time 15:31 Rev Time 0.00
Received By kstevens Date 2007-11-03 Time 08:06 Sent To  
Notes
2007-11-09 18:49:38DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
 CITY WPB MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHTS L-1, L-2, I-1, I-2 & I-3 THE ADDRESS OF RECORD
 ON THE FLORIDA STATE DBPR WEBSITE FOR THE LANDSCAPE
 ARCHITECT DOES NOT REFLECT THE ADDRESS ON THE TITLE
 BLOCK. PLEASE UPDATE THE DPBR WEBSITE OR THE TITLE
 BLOCKS PRIOR TO RESUBMITTING FOR REVIEW. FAC
 61G1-16.004(1) & FS 481.306.
  
 2. SHT A-1.0 THE COMPLETE FIRM NAME IS REQUIRED IN THE
 TITLE BLOCK. FAC 61G1-16.004(1) & FS 481.2055.
  
 3. SHT A-1.0 BECAUSE OF MULTIPLE OCCUPANCIES,
 (BUSINESS, ASSEMBLY, MERCANTILE, & POSSIBLY EDUCATION,
 (DEPENDING ON THE AGE OF THE STUDENTS & TYPE OF CLASS
 ROOM EDUCATION), CALCULATIONS FOR MINIMUM FACILITIES IS
 REQUIRED. TABLES 1004.1.2 & 104.3.1 & SECTION 302.2.1.
 ALSO POTTY PARITY SHALL BE ADDRESSED AND REQUIRED PER
 SECTION 403.1.1.
  
 4. SHT A-1.0 SHOWS A SECONDARY KITCHEN. THE GREASE
 INTERCEPTOR SHALL BE SIZED BY THE UTILITY DEPT.,
 INDUSTRIAL PRETREATMENT, ENVIRONMENTAL COMPLIANCE.
 PLEASE CONTACT RODNEY COMPO, (561) 822-2272, E-MAIL
 [email protected] OR CALVIN WILLIAMS (561) 822-2284,
 E-MAIL [email protected]. THEIR FAX NUMBER IS (561)
 822-2287. THEY WILL ISSUE A WRITTEN DETERMINATION FOR
 THE SIZE & LOCATION OF THE GREASE INTERCEPTOR OF WHICH
 A COPY WILL BE SUBMITTED WITH THE PLANS WHEN
 RESUBMITTING FOR REVIEW.
  
 5. SHT A-2.0 WHERE SIX OR MORE STALLS ARE PROVIDED, IN
 ADDITION TO THE STALL COMPLYING WITH SECTION 11-4.17.3,
 AT LEAST ONE STALL 36 INCHES WIDE WITH AN OUTWARD
 SWINGING, SELF-CLOSING DOOR AND PARALLEL GRAB BARS
 COMPLYING WITH FIG. 30(D)AND SECTION 11-4.26 SHALL BE
 PROVIDED. SECTION 11-4.22.4.
  
 6. SHT A-2.1 TOILET ROOMS 208 & 209. AN UNOBSTRUCTED
 TURNING SPACE COMPLYING WITH SECTION 11-4.2.3 SHALL BE
 PROVIDED WITHIN AN ACCESSIBLE TOILET ROOM. SECTION
 11-4.22.3.
  
 7. SHT A-2.1 THE TOILET ROOM ADJACENT TO THE BRIDAL
 ROOM SHALL BE ACCESSIBLE. PLEASE SHOW COMPLIANCE WITH
 SECTION 11-4.22 WITH ALL SUBSECTIONS.
  
 8. SHT A-1.0 SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS PER SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS & TABLES. SHOW THE SQUARE FOOTAGE AREA OF
 EACH ROOF DRAIN, PLUS 1/2 AREA OF ALL VERTICAL WALLS
 INCLUDING PARAPETS, AS WELL AS ANY AREA OF A ROOF THAT
 DRAINS ONTO THE ROOF FROM ABOVE, (IF APPLICIABLE).
  
 9. SHT A-7.0 DETAILS 1 & 2 SHOW COMPLIANCE WITH THE
 FOLLOWING:
 ___FOR W/C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.3 HEIGHT
 C. 11-4.16.4 GRAB BARS
 D. 11-4.16.5 FLUSH CONTROLS
 E. 11-4.16.6 DISPENSERS
 ___FOR LAVS:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 B. 11-4.19.4 EXPOSED PIPES & CLEARANCES
 C. 11-4.19.5 FAUCETS
 WATER CLOSETS SHALL BE 18" OFF THE WALL TO THE
 CENTERLINE OF THE FIXTURE. FIGURE 28.
  
 10. SHT A-7.0 DETAIL 3, BATHROOM SHALL BE ACCESSIBLE.
 PLEASE SHOW COMPLIANCE WITH 11-4.16, 11-4.19, 11-4.21 &
 11-4.23 WITH ALL SUBSECTIONS AND FIGURES.
  
 11. SHT A-7.0 DETAIL 5. THE TOILET ROOMS SHALL BE
 ACCESSIBLE. PLEASE SHOW COMPLIANCE WITH SECTIONS
 11-4.16, 11-4.17,11-4.19 & 11-4.22 WITH ALL
 SUBSECTIONS AND FIGURES. W/C'S TO BE 18" OFF THE WALL
 TO THE CENTERLINE OF THE FIXTURE. FIGURE 28.
  
 12. SHT A-7.0 ALL DETAILS 1 THRU 5. SHOW COMPLIANCE
 WITH SECTION 1210.2. THE WALLS WITHIN 2FT OF THE W/C'S
 AND URINALS SHALL HAVE A SMOOTH, HARD, NONABSORBENT
 SURFACE UP TO 4FT ABOVE THE FLOOR.LEGEND TOILET ROOM
 ACCESSORIES W-1 INDICATES WAINSCOAT 36" HIGH BUT DETAIL
 4 SHOWS TILE TO CEILING. PLEASE CLAIRFY AND CORRELATE.
  
 13. SHT A-7.1 DETAIL 1 SHOW THE TURNING AREA IN THE
 TOILET ROOM. (NOT REQUIRED IN THE STALL). SECTION
 11-4.22.3.--SHOW COMPLIANCE WITH THE FOLLOWING:
 ___FOR W/C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.3 HEIGHT
 C. 11-4.16.4 GRAB BARS
 D. 11-4.16.5 FLUSH CONTROLS
 E. 11-4.16.6 DISPENSERS
 ___FOR URINALS:
 A. 11-4.18.2 HEIGHT
 B. 11-4.18.3 CLEAR FLOOR SPACE
 C. 11-4.18.4 FLUSH CONTROLS
 DETAILS 1 & 2 SHOW THE FOLLOWING:
 ___FOR LAVS:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 B. 11-4.19.4 EXPOSED PIPES & CLEARANCES
 C. 11-4.19.5 FAUCETS
 D. 11-4.19.6 MIRRORS
  
 14. SHT A-7.1 ALL DETAILS. SHOW COMPLIANCE WITH SECTION
 1210.2. WALLS WITHIN 2FT OF WATERCLOSETS AND URINALS
 SHALL HAVE A SMOOTH, HARD, NONABSORBENT SURFACE.
  
 15. SHT A-7.1 DETAILS 2 & 5 SHOW COMPLIANCE WITH THE
 FOLLOWING:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 B. 11-4.19.4 EXPOSED PIPES & CLEARANCES
 C. 11-4.19.5 FAUCETS
 D. 11-4.19.6 MIRRORS
  
 16. SHT A-7.1 DETAIL 6 TOILET ROOM SHALL BE ACCESSIBLE.
 PLEASE SHOW COMPLIANCE WITH SECTIONS 11-4.16, 11-4.19 &
 11-4.22 WITH ALL SUBSECTIONS AND FIGURES.
  
 17. SHT A-7.2 DETAILS 4 & 5 LOUNGE SINK SHALL BE
 ACCESSIBLE. SHOW COMPLIANCE WITH SECTION 11-4.24 WITH
 ALL SUBSECTIONS.
  
 18. SHTS S-1 THRU S-10 THE PRINTED NAME AND LICENSE
 NUMBER SHALL BE LEGIBLY PRINTED IN THE TITLE BLOCKS OF
 ALL SHEETS. FAC 61G15-23.002(2) & FS 471.025.
  
 19. SHT P1.0 SHOWS CONDENSATE TO DISCHARGE 6" ABOVE THE
 SIDEWALK. THIS IS NOT APPROVED. CONDENSATE SHALL
 CONNECT TO A DRYWELL, STORM CATCH BASIN, PLANTED AREA
 OR CONNECT TO A STORM DRAINAGE LINE OUTSIDE THE
 BUILDING. IF CONNECTING TO A STORM LINE, A RELIEF VENT,
 (GOOSENECK), SHALL BE REQUIRED AS THE CONDENSATE EXITS
 THE BUILDING. CONDENSATE DRAINAGE CAN NOT CREATE A
 HAZARD OR NUISANCE. SECTION 314.2.1.
  
 20. SHT P-1.0 STORM DRAINAGE IS SHOWN TO CONNECT TO
 STORMWATER DRAINAGE SYSTEM. "REFER TO CIVIL PLANS FOR
 CONT". PLESE CLARIFYAS THE STORMWATER DRAINAGE SYSTEM
 IS NOT SHOWN ON THE CIVIL PLANS. SECTION 106.1.1.
  
 21. SHT P-1.0 SHOW THE HOT AND COLD WATER PIPING ON THE
 FLOOR PLAN. SECTION 106.3.5.1.3(3)(10).
  
 22. SUBMIT A WATER ISOMETRIC WATER RISER DIAGRAM FROM
 METER, THRU RPZV BACKFLOW, TO THE MOST REMOTE FIXTURE
 SHOWING ALL PIPE SIZES, VALVES, OFFSETS, & WATER HAMMER
 ARRESTORS REQUIRED BY SECTION 604.9. WATER HAMMER
 ARRESTORS SHALL BE LOCATED NEAR THE FIXTURES IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING. PDI-WH 201 AND
 MANUF. INSTALLATION INSTRUCTIONS. SECTION
 106.3.5.1.3(3)(10)(13).
  
 23. SHT P-2.0 SHOW THE HOT & COLD WATER PIPING ON THE
 FLOOR PLAN. SECTION 106.3.5.1.3(3)(10).
  
 24. SHT P-3.0 BACKFLOW PROTECTION IS REQUIRED ON THE
 WATER LINES TO THE WATER FOUNTAINS. A VACUUM BREAKER AT
 THE HIGHEST POINT OF THE SUPPLY LINE TO THE FOUNTAINS
 WILL BE SUFFICIENT. SECTION 608.
  
 25. SHT P-3.0 CONDENSATE LINES SHOW BACKWATER VALVES.
 PER SECTION 715.1 FIXTURES ABOVE THE ELEVATION OF THE
 MANHOLE SHALL NOT DISCHARGE THRU A BACKWATER VALVE.
 WHERE THE POSSIBILITY OF A BACKUP MAY OCCUR, A RELIEF
 VENT, (GOOSENECK) , SHALL BE INSTALLED AS THE
 CONDENSATE EXITS THE BUILDING.
  
 26. SHT P-3.0 NOTE AT THE WATER HEATER INDICATES THE P
 & T RELIEF VALVE AND EM PAN DRAIN LINE TO BE ROUTED TO
 A FLOOR DRAIN VIA INDIRECT WASTE. FLOOR DRAINS ARE NOT
 APPROVED INDIRECT WASTE RECEPTORS. SECTION 802.3. SINCE
 AN EMERGENCY PAN IS NOT REQUIRED ON THE FIRST FLOOR PER
 SECTION 504.7 AND THE P & T CAN DISCHARGE ONTO THE
 FLOOR,THEY ARE NOT REQUIRED TO BE PIPED TO AN
 INDIRECT WASTE RECEPTOR SO A FLOOR DRAIN WILL BE OK IN
 THE ROOM BUT NOT AS AN INDIRECT WASTE RECEPTOR.
  
 27. SUBMIT A DETAIL FOR THE WATER HEATER. SHOW
 COMPLIANCE WITH SECTIONS 503.1, (SHUT OFF VALVE),
 SECTION 504.2, (IF BOTTOM FED W/H), 504.4, (RELIEF
 VALVE), 504.6.1, (DISCHARGE), 504.6.2, (MATERIALS) AND
 SECTION 607.3.2 (THERMAL EXPANSION CONTROL)
  
 28. SHT P-4.0 SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS. (SEE COMMENT # 8). A CHECK ON
 TWO ROOF AREAS, ROOF DRAINS #7 & #10 DO NOT SEEM TO
 INCLUDE ALL SQUARE FOOTAGE FOR THE ROOF AREAS AND/OR
 VERTICAL CONTRIBUTION. EXAMPLE ROOF DRAIN#7 AREA IS
 SHOWN AS 1,304SF, BUT A CHECK OF THE AREA INDICATES
 1,666SF AND THE ROOF DRAIN #10 AREA IS SHOWN AS 1,962SF
 BUT A CHECK OF THE AREA INDICATES 2,322SF. PLEASE
 SUBMIT THE CALCULATIONS SHOWING INFORMATION REQUESTED
 IN COMMENT #8. SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS AND TABLES.
  
 29. SHT P-5.0 SHOW THE GAS LINE UP TO THE MATCH LINE ON
 THE FLOOR PLAN. SECTION 106.1.1.
  
 30. SHT P-5.0 THE DISHWASHER, (P-49), SHALL DISCHARGE
 INTO THE SANITARY SYSTEM, NOT THE GREASE SYSTEM PER
 ARTICLE III SECTION 90-124(7)(B). PLEASE CONNECT
 DISHWASHER TO SANITARY.
  
 31. SUBMIT STORM ISOMETRIC RISER DIAGRAMS FOR ALL ROOF
 DRAINS AND SECONDARY ROOF DRAINS THAT REFLECT THE FLOOR
 PLAN. SHOW ALL PIPE SIZES, OFFSETS AND INDICATE SQUARE
 FOOTAGE BEING DRAINED BY EACH ROOF DRAIN. SECTION
 106.3.5.1.3(7)(13).--SHOW CLEANOUTS REQUIRED BY
 SECTION 1101.8.
  
 32. SUBMIT CONDENSATE ISOMETRIC RISER DIAGRAMS FOR ALL
 CONDENSATE RISERS THAT REFLECT THE FLOOR PLAN. SHOW
 PIPE SIZES. OFFSETS AND INDICATE MATERIAL FOR SYSTEM.
 NO PVC IN PLENUMS.
  
 33. SHT P-6.0 PLUMBING GENERAL SPECIFICATIONS 1509(G)
 AIR CHAMBERS ARE NOT APPROVED. PLEASE DELETE AIR
 CHAMBERS FROM REFLENCE. SECTION 604.9 AND PDI-WH 201.
  
 34. SUBMIT A WATER ISOMETRIC RISER DIAGRAM THAT
 REFLECTS THE FLOOR PLAN. SHOW ALL PIPE SIZES, VALVES,
 (FULL OPEN & SHUT OFF), SECTIONS 606.1 & 606.2,
 OFFSETS, AND WATER HAMMER ARRESTORS REQUIRED BY SECTION
 604.6, (DISHWASHER, WASH MACHINE, ICE MAKER ETC). WATER
 HAMMER ARRESTORS SHALL BE LOCATED NEAR THE FIXTURES IN
 AN "EFFECTIVE RANGE" NOT IN THE CEILING PER PDI-WH 201
 AND MANUF. INSTALLATION INSTRUCTIONS.
  
 35. SHT P-7.0 KITCHEN EQUIPMENT PLUMBING SCHEDULE ITEM
 P-58 INDICATES 1-1/2" SANITARY WASTE. A MINIMUM 2"
 P-TRAP IS REQUIRE PER TABLE 709.1. NOTE INDICATES FS-2
 AT THE WASH MACHINE, BUT SHOWS DIRECT CONNECTION TO THE
 SANITARY SYSTEM. PLEASE CLARIFY. SECTION 106.1.1.
  
 36. SHT P-10.0 THE VENTING FOR TOILET ROOMS 316 & 317
 DO NOT SHOW VENT THRU ROOF AS REQUIRED IN SECTION
 903.3. PLEASE CLARIFY.
  
 37. SHT P-11.0 SANITARY RISER DIAGRAM THE DISH WASHER
 SHALL DISCHARGE INTO THE SANITARY SYSTEM, NOT THE
 GREASE SYSTEM. ARTICLE III SECTION 90-124(7)(B). PLEASE
 CONNECT DISHWASHER TO SANITARY.
  
 38. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING
 INFORMATION IS REQUIRED TO SECURE A PERMIT.
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.-- SHOW ALL PIPING FROM THE METER TO
 THE MOST REMOTE APPLIANCE.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL). GAS APPLIANCE SCHEDULE
 NOTE #4 INDICATES TABLE 402.4(24) WHICH IS LP GAS.
  
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). --TOTAL DISTANCE FROM
 THE METER TO THE MOST REMOTE OUTLET IS NOT INDICATED ON
 THE PLANS. GAS APPLIANCE SCHEDULE NOTE #4 INDICATES
 80FT DEVELOPED LENGTH FROM THE REGULATOR, BUT ADDING
 ALL CUT SECTION LENGTHS PROVIDED ON THE ISOMETRIC
 SUBMITTED ON SHT P-11.0 197FT IS INDICATED. PLEASE
 CLARIFY.
  
 E. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304. -- FOR W/H.
  
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 G. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 H. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 I. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 J. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE
 SECOND STAGE REGULATOR. INDICATE THE MODEL NUMBER. THE
 REGULATOR SHALL BE LISTED & INDICATE TOTAL BTU OUTPUT
 THAT CORRELATES TO THE TOTAL BTU LOAD DOWNSTREAM OF THE
 REGULATOR.
  
 K. A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR. SECTION 409.4.
 --ALSO A UNION WILL BE REQUIRED DOWNSTREAM OF THE
 SHUT OFF VALVE.PLEASE SHOW ON RISER DIAGRAM.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date 2008-08-20 Cont ID  
Sent By kdfreema Date 2008-08-20 Time 16:28 Rev Time 0.00
Received By kdfreema Date 2008-08-20 Time 16:28 Sent To  
Notes
2008-08-20 16:28:34***PROVISO***
  
 SIDEWALK AND FIRE HYDRANT EASEMENTS, TO THE
 SATISFACTION OF THE CITY ENGINEERING SERVICES
 DEPARTMENT, SHALL BE RECORDED PRIOR TO THE ISSUANCE OF
 A CERTIFICATE OF OCCUPANCY.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT (561)
 822-1435 OR [email protected] WITH QUESTIONS.

Review Stop Z ZONING
Rev No 3 Status P Date 2008-06-02 Cont ID  
Sent By kdfreema Date 2008-06-02 Time 14:33 Rev Time 0.00
Received By kdfreema Date 2008-06-02 Time 14:33 Sent To  
Notes
2008-06-02 15:11:41***PROVISO***
  
 SIDEWALK AND FIRE HYDRANT EASEMENTS, TO THE
 SATISFACTION OF THE CITY ENGINEERING SERVICES
 DEPARTMENT, SHALL BE RECORDED PRIOR TO THE ISSUANCE OF
 A CERTIFICATE OF OCCUPANCY.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT (561)
 822-1435 OR [email protected] WITH QUESTIONS.

Review Stop Z ZONING
Rev No 2 Status F Date 2008-02-07 Cont ID  
Sent By kdfreema Date 2008-02-07 Time 15:51 Rev Time 0.00
Received By kdfreema Date 2008-02-07 Time 15:51 Sent To  
Notes
2008-02-07 15:57:28***FAILED***
  
 1. THE DUMPSTER SIZE SHOWN DOES NOT MEET THE MINIMUM
 SPECIFICATION REQUIRED BY THE CITY'S ZONING AND LAND
 DEVELOPMENT REGULATIONS. THE DUMPSTER ENCLOSURE SHOWN
 ON THE APPROVED SITE PLAN IS COMPLIANT. WE'D PREFER THE
 WOOD GATES OVER THE CHAIN LINK WITH SLATS.
  
 2. THE OFFICE WINDOWS SHALL BE OPERABLE AS SHOWN IN THE
 APPROVED SITE PLAN AND REQUIRED BY THE CURRIE MIXED USE
 DISTRICT REGULATIONS.
  
 3. PROVIDE DOCUMENTATION AS IT RELATES TO THE RECORDING
 OF THE FIRE HYDRANT AND SIDEWALK EASEMENTS AS REQUIRED
 BY THE ENGINEERING SERVICES DEPARTMENT.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT (561)
 822-1435 OR [email protected] WITH ANY QUESTIONS.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-09-12 Cont ID  
Sent By kdfreema Date 2007-09-12 Time 10:47 Rev Time 0.00
Received By kdfreema Date 2007-09-12 Time 10:47 Sent To  
Notes
2007-09-12 10:49:34***FAILED***
  
 THIS PROJECT HAS NOT RECEIVED SITE PLAN APPROVAL. NO
 ZONING REVIEW WILL BE PERFORMED UNTIL THE SITE PLAN HAS
 BEEN APPROVED.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 561-822-1435
 OR [email protected] WITH QUESTIONS.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved