 |
Plan Review Details - Permit 07090042
| Plan Review Stops For Permit 07090042 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2008-10-15 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-10-15 |
Time |
08:23 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-10-15 |
Time |
08:23 |
Sent To |
|
|
| Notes |
| 2008-10-15 08:25:40 | ***PROVISOS*** | | | | | | SEPARATE ROOF PERMIT REQUIRED | | | | | | SUBMIT PRODUCT APPROVAL FOR WINDSOR REPUBLIC DOORS, | | | SKYLIGHTS (-87PSF) AS A REVISION | | | | | | SUBMIT MECHANICAL EQUIPMENT ENGINEERING FBC1609 | | | | | | CORRELATE REFLECTED CEILING PLAN WITH ELECTRICAL | | | DRAWINGS PRIOR TO INSTALLATION | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2008-10-10 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-10-10 |
Time |
16:11 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-10-10 |
Time |
16:11 |
Sent To |
|
|
| Notes |
| 2008-10-10 16:13:24 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FS FLORIDA STATUTE | | | | | | COMMENTS FROM PREVIOUS LIST, NUMBERING REMAINS THE SAME | | | FOR CONSISTENCY | | | | | | 2.) IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY PRIOR | | | TO PERMIT ISSUANCE, 2300 N JOG RD. PLEASE CALL | | | 561-233-5025 FOR MORE INFORMATION. THE PLANS MUST BE | | | STAMPED AND THE RECEIPT IS TO BE INCLUDED WITH THE | | | PERMIT APPLICATION. | | | | | | PLEASE PROVIDE IMPACT FEE RECEIPT. THE BILL AND STAMPED | | | PLANS WERE PROVIDED, BUT A RECEIPT SHOWING THIS HAS | | | BEEN PAID MUST BE SUBMITTED (EITHER VIA FAX 805-6731 OR | | | EMAIL OR DELIVER TO FRONT COUNTER). | | | | | | PERMIT WILL BE ISSUED WITH PROVISOS: | | | | | | SEPARATE ROOF PERMIT REQUIRED | | | | | | SUBMIT PRODUCT APPROVAL FOR WINDSOR REPUBLIC DOORS, | | | SKYLIGHTS (-87PSF) AS A REVISION | | | | | | SUBMIT MECHANICAL EQUIPMENT ENGINEERING FBC1609 | | | | | | CORRELATE REFLECTED CEILING PLAN WITH ELECTRICAL | | | DRAWINGS PRIOR TO INSTALLATION | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2008-09-17 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-09-15 |
Time |
15:34 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-09-15 |
Time |
15:34 |
Sent To |
|
|
| Notes |
| 2008-09-17 13:24:24 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FS FLORIDA STATUTE | | | | | | COMMENTS FROM PREVIOUS LIST, NUMBERING REMAINS THE SAME | | | FOR CONSISTENCY | | | | | | 1.) A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO | | | PERMIT PICKUP, FS713.13. | | | | | | 2.) IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY PRIOR | | | TO PERMIT ISSUANCE, 2300 N JOG RD. PLEASE CALL | | | 561-233-5025 FOR MORE INFORMATION. THE PLANS MUST BE | | | STAMPED AND THE RECEIPT IS TO BE INCLUDED WITH THE | | | PERMIT APPLICATION. | | | | | | 3.) AS THIS IS A THRESHOLD BUILDING AS DEFINED IN | | | FS553.71(7), PLEASE ARRANGE WITH KEN CONRAD, | | | 561-805-6666, A MEETING INVOLVING THE OWNER, SPECIAL | | | INSPECTOR, JOB INSPECTOR, CONTRACTOR AND ENGINEER. THIS | | | MUST BE DONE PRIOR TO PERMIT ISSUANCE. THREE ORIGINAL | | | SETS OF ALL DOCUMENTS ARE REQUIRED FOR PERMITTING AND | | | FOR ALL SUBSEQUENT SUBMITTALS. SEE FBC*109.3.6. | | | | | | 4.) PLEASE KEEP THE THRESHOLD INSPECTION PLAN (AND | | | OTHER DOCUMENTS WHICH HAVE BEEN REVIEWED AND STAMPED) | | | AS A PART OF THE PERMIT PACKAGE. THE PLAN AND THE | | | PROPOSED SPECIAL INSPECTOR MUST BE APPROVED BY KEN | | | CONRAD (SEE OTHER COMMENTS, 561-805-6666) PRIOR TO | | | PERMIT ISSUANCE. | | | | | | 5-56.) ADDRESSED. | | | | | | PERMIT WILL BE ISSUED WITH PROVISOS: | | | | | | SEPARATE ROOF PERMIT REQUIRED | | | | | | SUBMIT PRODUCT APPROVAL FOR WINDSOR REPUBLIC DOORS, | | | SKYLIGHTS (-87PSF) AS A REVISION | | | | | | SUBMIT MECHANICAL EQUIPMENT ENGINEERING FBC1609 | | | | | | CORRELATE REFLECTED CEILING PLAN WITH ELECTRICAL | | | DRAWINGS PRIOR TO INSTALLATION | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2008-06-10 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-06-10 |
Time |
10:36 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-06-06 |
Time |
14:53 |
Sent To |
|
|
| Notes |
| 2008-06-10 10:36:32 | ****CORRECTIONS**** | | | ***REVISED 6/23/08*** | | | ***REVISED 7/22/08 (ITEM 54)** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC | | | FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | COMMENTS FROM PREVIOUS LIST, NUMBERING REMAINS THE SAME | | | FOR CONSISTENCY | | | | | | 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO | | | PERMIT PICKUP, FS713.13. | | | | | | 2.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY | | | PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.PLEASE CALL | | | 561-233-5025 FOR MORE INFORMATION.THE PLANS MUST BE | | | STAMPED AND THE RECEIPT IS TO BE INCLUDED WITH THE | | | PERMIT APPLICATION. | | | | | | 3.)AS THIS IS A THRESHOLD BUILDING AS DEFINED IN | | | FS553.71(7), PLEASE ARRANGE WITH HAROLD PISKURA | | | (INSPECTION SERVICES MANAGER - TEL:561 805 6711), A | | | MEETING INVOLVING THE OWNER, SPECIAL INSPECTOR, JOB | | | INSPECTOR, CONTRACTOR AND ENGINEER.THIS MUST BE DONE | | | PRIOR TO PERMIT ISSUANCE.THREE ORIGINAL SETS OF ALL | | | DOCUMENTS ARE REQUIRED FOR PERMITTING AND FOR ALL | | | SUBSEQUENT SUBMITTALS.SEE FBC*109.3.6. | | | | | | THREE COMPLETE COLLATED SETS OF PERMIT DOCUMENTS | | | REQUIRED FOR PERMIT ISSUANCE.ONLY TWO SETS OF THE | | | SUBMITTAL PREPARED BY WOJCIESZAK & ASSOCIATES (ROOFTOP | | | EQUIPMENT) WERE SUBMITTED, AND THE SUBMITTAL INCLUDED | | | PHOTOCOPIES OF ENGINEERING.SEE FAC61G15-23.002, | | | DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR | | | PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED | | | ORIGINALS.SEE OTHER COMMENT REGARDING THIS | | | SUBMITTAL. | | | | | | 4.)PLEASE KEEP THE THRESHOLD INSPECTION PLAN (AND | | | OTHER DOCUMENTS WHICH HAVE BEEN REVIEWED AND STAMPED) | | | AS A PART OF THE PERMIT PACKAGE.THE PLAN AND THE | | | PROPOSED SPECIAL INSPECTOR MUST BE APPROVED BY HAROLD | | | PISKURA (SEE OTHER COMMENTS, 561-805-6711) PRIOR TO | | | PERMIT ISSUANCE. | | | | | | 5.)ADDRESSED. | | | | | | 6.)ADDRESSED; THE PLANS WILL BE STAMPED WITH A5 FLOOD | | | ZONE DESIGNATION, FORM BOARD SURVEY REQUIRED | | | (INFORMATIONAL ONLY). | | | | | | 7-38.) ADDRESSED. | | | | | | 39.)SELECT THE APPROVED ASSEMBLY YOU ARE USING IN THE | | | ROOF PRODUCT APPROVAL. | | | | | | NOT ADDRESSED.THIS CAN BE DONE BY THE ROOFING | | | CONTRACTOR AT THE TIME OF ROOF PERMIT APPLICATION. THIS | | | WILL BE A PROVISO ITEM. | | | | | | 40.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL IN | | | ADDITION TO THE NOAS PROVIDED.IF A FLORIDA STATE | | | PRODUCT APPROVAL IS UNAVAILABLE, PLEASE ADVISE AND A | | | LOCAL PRODUCT APPROVAL WILL BE ISSUED USING THE NOA. | | | | | | PLEASE PRINT THE FLORIDA STATE PRODUCT APPROVALS IF | | | AVAILABLE, WWW.FLORIDABUILDING.ORG | | | | | | 41.)AN EVALUATION REPORT FOR WINDSOR REPUBLIC DOORS | | | WAS SUBMITTED.FLORIDA STATE OR LOCAL PRODUCT APPROVAL | | | REQUIRED.PLEASE SEE WWW.FLORIDABUILDING.ORG; THIS | | | COMPANY HAS FIVE DIFFERENT PRODUCT APPROVALS FOR SIDE | | | HINGED DOORS.IT IS LIKELY THAT THE INFORMATION | | | REQUIRED IS AVAILABLE ON THIS WEBSITE. | | | | | | 42-46.) ADDRESSED. | | | | | | 47.) THE GATE SWING WAS REVISED, BUT DOOR 323 NOW DOES | | | NOT COMPLY WITH FBC1007.2 (DOOR SWING CHANGED SINCE | | | LAST REVIEW), DOOR ENCROACHMENT, AS THE DOOR NOW OPENS | | | ONLY 90DEGREES (OBSTRUCTED BY THE GATE FROM OPENING | | | 180DEGREES).AS DISCUSSED, THIS CAN BE REDLINED WITH A | | | PROVISO THAT A REVISION BE SUBMITTED CHANGING DOOR | | | HINGE OR DOOR SWING. | | | | | | 48.)PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER | | | OF RECORD, (SHOP DRAWING REVIEW STAMP OR LETTER), | | | FBC*106.3.3.SHEET A9 SPECIFIES MOST OF THE COMPONENTS | | | AND CLADDING.HOWEVER, FOR OTHER ITEMS, PLEASE | | | REVIEW. | | | | | | 49.)PROVIDE PRODUCT APPROVAL FOR THE SKYLIGHTS SHOWN | | | ON A4.0, FAC9B72. | | | | | | 3RD REVIEW, THE NEGATIVE DESIGN PRESSURE FOR ROOF | | | COMPONENTS & CLADDING, ZONES 2 AND 3, IS -87.THE | | | SKYLIGHT SPECIFIED ON A4.0 HAS A DP LIMITATION OF -80. | | | THE PRODUCT APPROVAL SUBMITTED WAS A FLORIDA STATE | | | PRODUCT APPROVAL; THE PRODUCT SPECIFIED ON THE PLAN | | | REFERS TO A MIAMIDADE NOA.PLEASE RESOLVE THE DESIGN | | | PRESSURE ISSUE AND CORRELATE PAPERWORK. | | | | | | 50-53.) ADDRESSED. | | | | | | NEW COMMENTS: | | | | | | 54.) REGARDING THE SUBMITTAL PREPARED BY WOJCIESZAK & | | | ASSOCIATES: | | | | | | DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR | | | PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS | | | AND ARE TO INCLUDE ALL INFORMATION REQUIRED BY | | | FAC61G15-23.002, FS471 (CERTIFICATE OF AUTHORIZATION, | | | PRINTED NAME AND LICENSE NUMBER OF INDIVIDUAL SEALING | | | THE DOCUMENT, ETC.).THE ONLY EXCEPTION TO THIS | | | REQUIREMENT IS PRODUCT APPROVALS, WHICH HAVE AN | | | EXCEPTION TO THE REQUIREMENT FOR ORIGINAL DOCUMENTS | | | WITHIN THE FLORIDA STATUTE.ALSO, PLEASE NOTE THE | | | FOLLOWING: | | | | | | A. THE SUBMITTAL INCLUDES SPEC SHEETS (TOP RIGHT STATES | | | JOB: SARI, LOUVER, MARK 4 AND JOB: TEMPLE ISRAEL, FAN, | | | MARK SF 1 & 2) WHICH BOTH REFER TO NOA03-0422.05, | | | GREENHECK SEVERE DUTY LOUVERED ENCLOSURES FLORIDA STATE | | | PRODUCT APPROVAL 4825.1.PLEASE PRINT THE PRODUCT | | | APPROVAL, THREE SETS.BASED ON THE NOA WHICH I VIEWED | | | ONLINE, THIS PRODUCT APPEARS CODE COMPLIANT.SEE | | | COMMENT 48; HAVE THE DESIGNER REVIEW THE PRODUCT PRIOR | | | TO RESUBMITTAL (SHOP DRAWING REVIEW STAMP OR SIGNED AND | | | SEALED LETTER). | | | | | | B. THE SUBMITTAL INCLUDES AN UNSIGNED LETTER FROM RICE | | | ENGINEERING WHICH STATES THAT H-CUE 060-200 (EXHAUST | | | FAN, SPEC SHEET REFERS TO MARK EF 14 & 15), WILL | | | WITHSTAND WINDS UP TO 150MPH.BASED ON THE INFORMATION | | | FOUND AT | | | HTTP://WWW.GREENHECK.COM/PDF/FANS/PROMOHIGHWINDFANSNOVE | | | MBER2006.PDF, IT APPEARS THAT THIS PRODUCT MAY HAVE A | | | MIAMIDADE NOA OR FLORIDA STATE PRODUCT APPROVAL, BUT I | | | WAS UNABLE TO LOCATE.THE LETTER STATES THAT THIS | | | PRODUCT IS LIMITED TO -61 PSF.THEREFORE, THIS PRODUCT | | | IS ACCEPTABLE FOR USE IN ZONE 1 BUT NOT ZONES 2 OR 3. | | | PROVIDE THREE SETS OF PRODUCT APPROVALS, REVIEWED BY | | | DESIGNER OF RECORD, AND CLARIFY INSTALLATION LOCATIONS | | | OR APPLY FOR LOCAL PRODUCT APPROVAL IF AN EVALUATION | | | REPORT (MIAMIDADE NOA OR FLORIDA STATE PRODUCT | | | APPROVAL) IS NOT AVAILABLE.IT IS SUGGESTED THAT THE | | | LOCATIONS BE INCLUDED ON SHEET A4.0 WHICH SHOWS ROOFTOP | | | EQUIPMENT.NOTE THAT THE EDGE ZONE IS 14FEET, SEE | | | SHEET S7. | | | | | | C. THE SUBMITTAL INCLUDES AN UNSIGNED LETTER FROM RICE | | | ENGINEERING WHICH STATES THAT MODEL H-GB BELT DRIVE | | | ROOF DOWNBLAST CENTRIFUGAL EXHAUST FAN, (AKA SPUN | | | ALUMINUM ROOFTOP FAN, SPEC SHEET REFERS TO MARK EF 17), | | | WILL WITHSTAND WINDS UP TO 150MPH.BASED ON THE | | | INFORMATION FOUND AT | | | HTTP://GFCPORTAL.COM/PDF/FANS/SPECIFICATIONS/CSI_%20HGB | | | _%20SPEC_OCTOBER2007.RTF, IT APPEARS THAT THIS PRODUCT | | | IS INCLUDED IN MIAMIDADE NOA 07-0503.07.THIS PRODUCT | | | IS LIMITED TO -61 PSF.THEREFORE, THIS PRODUCT IS | | | ACCEPTABLE FOR USE IN ZONE 1 BUT NOT ZONES 2 OR 3. | | | PROVIDE THREE SETS OF PRODUCT APPROVALS, REVIEWED BY | | | DESIGNER OF RECORD, AND CLARIFY INSTALLATION LOCATIONS. | | | IT IS SUGGESTED THAT THE LOCATIONS BE INCLUDED ON SHEET | | | A4.0 WHICH SHOWS ROOFTOP EQUIPMENT.NOTE THAT THE EDGE | | | ZONE IS 14FEET, SEE SHEET S7. | | | | | | D. THE REPORTS FOR THE TRANE COMPANY ENTITLED SOUTH | | | FLORIDA HURRICANE WIND LOAD LOAD ANALYSIS & | | | CALCULATIONS PREPARED BY STAMOS & ASSOCIATES INC. ARE | | | REQUIRED TO BE ORIGINAL AND TO INCLUDE ALL INFORMATION | | | REQUIRED BY FAC61G15-23.002.CALCULATIONS ARE TO BE | | | EITHER SIGNED, SEALED AND DATED ON EACH SHEET OR | | | INCLUDE AN INDEX SHEET AS WELL AS ALL INFORMATION | | | REQUIRED BY FAC61G15-23.002.THE ENGINEERING IS DATED | | | 10/21/93; THE ASCE STANDARD FOR WIND HAS BEEN REVISED | | | THREE TIMES SINCE THAT DATE; THE CALCULATIONS WERE DONE | | | IN ACCORDANCE WITH SFBC (A CODE NO LONGER IN EFFECT) | | | AND SHOULD BE DONE IN ACCORDANCE WITH FBC/ASCE; PLEASE | | | UPDATE ENGINEERING.THE CALCULATIONS SUBMITTED REFER | | | TO SFBC AND APPLICABLE SFBC CODE REFERENCES; PLEASE | | | REVISE TO REFLECT THE CURRENT CODE.THE CALCULATIONS | | | USE P=37PSF FROM SFBC TABLE 2309.2; PLEASE USE | | | PRESSURES AS PER FBC2004 SECTION 1609 OR ASCE7-02. | | | DESIGN PRESSURES MUST BE CONSISTENT WITH PRESSURES | | | DECLARED BY THE STRUCTURAL ENGINEER.PLEASE SPECIFY | | | MINIMUM DISTANCE OF ROOFTOP UNIT TO EDGE OF ROOF | | | (LOCATION IN ZONE 1 OR ZONE 2); IT IS NOT CLEAR WHY | | | 37PSF HAS BEEN USED OR IF ROOFTOP EQUIPMENT LOCATION | | | WILL AFFECT DESIGN.THE CALCULATIONS STATE ON SHEET 3 | | | THAT REAR PANEL INFORMATION IS NOT AVAILABLE; PLEASE | | | REVISE CALCULATIONS TO INCLUDE ALL APPLICABLE | | | INFORMATION. THE CALCULATIONS STATE THAT SOME OF THE | | | SCREW FASTENER PATTERN CALCULATIONS WERE OMITTED DUE TO | | | ADEQUATE FASTENERS ILLUSTRATED, PLEASE REVISE TO | | | INCLUDE ALL APPLICABLE INFORMATION.THE DESIGN WAS FOR | | | 120MPH, MOST LIKELY SUSTAINED RATHER THAN 3SECOND GUST; | | | PLEASE CLARIFY DESIGN CRITERIA. | | | | | | E. A LETTER PREPARED BY KIRBY BICKNELL, PE AND REVIEWED | | | BY JOHN D. BUEROSSEE, PE REGARDING THE EXTREME | | | CONDITION MOUNTING KIT WAS SUBMITTED.DOCUMENTS | | | PREPARED BY AN ENGINEER AND SUBMITTED FOR PUBLIC RECORD | | | ARE TO BE SIGNED, SEALED, DATED ORIGINALS.PROVIDE THE | | | SPEC SHEETS FOR THIS PRODUCT ALONG WITH ORIGINAL | | | ENGINEERING IF A PRODUCT APPROVAL IS NOT AVAILABLE. | | | | | | F. ENGINEERING PREPARED BY BROMLEY COOK FOR PRECISION | | | ALUMINUM PRODUCTS WAS PROVIDED.THIS PRODUCT REQUIRES | | | FLORIDA STATE OR LOCAL PRODUCT APPROVAL, FAC9B72. | | | PLEASE VERIFY; A MIAMIDADE NOA MAY BE AVAILABLE. | | | | | | ** MECHANICAL EQUIPMENT ENGINEERING FOR WIND CAN BE A | | | PROVISO ITEM.ALL ITEMS 54A THROUGH F TO BE ADDRESSED | | | THROUGH PLAN REVIEW AS A REVISION PRIOR TO | | | INSTALLATION. ** (REVISED 7/22/8 | | | | | | 54.)PAYMENT OF IMPACT FEES AND APPROVAL OF THE | | | SPECIAL INSPECTOR BY HAROLD PISKURA ARE REQUIRED PRIOR | | | TO PERMIT ISSUANCE.ALL OTHER ISSUES IN THIS LIST CAN | | | BE PROVISO ITEMS (SUBMITTED PRIOR TO INSTALLATION, | | | AFTER PERMIT ISSUANCE). | | | | | | ***NEW COMMENTS 6/23/8*** | | | | | | 55.)SHEETS A3.0, A3.1, AND A3.2 WERE REMOVED FROM ONE | | | SET AND RETAINED BY ANOTHER REVIEWER.PLEASE PRINT | | | ANOTHER SET OF THESE SHEETS AND INSERT INTO THE SET | | | FROM WHICH THEY HAVE BEEN REMOVED. | | | | | | 56.)THIS PERMIT WILL BE ISSUED WITH THE PROVISO THAT | | | THE REFLECTED CEILING PLAN IS TO BE REVISED TO | | | CORRELATE WITH THE ELECTRICAL DRAWINGS PRIOR TO | | | INSTALLATION. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2008-03-18 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-03-18 |
Time |
08:51 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-03-07 |
Time |
17:53 |
Sent To |
|
|
| Notes |
| 2008-03-18 08:56:12 | ****CORRECTIONS**** | | | ****REVISED 3/18/8*** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC | | | FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | COMMENTS FROM PREVIOUS LIST, NUMBERING REMAINS THE SAME | | | FOR CONSISTENCY | | | | | | 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO | | | PERMIT PICKUP, FS713.13. | | | | | | 2.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY | | | PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.PLEASE CALL | | | 561-233-5025 FOR MORE INFORMATION.THE PLANS MUST BE | | | STAMPED AND THE RECEIPT IS TO BE INCLUDED WITH THE | | | PERMIT APPLICATION. | | | | | | 3.)AS THIS IS A THRESHOLD BUILDING AS DEFINED IN | | | FS553.71(7), PLEASE ARRANGE WITH HAROLD PISKURA | | | (INSPECTION SERVICES MANAGER - TEL:561 805 6711), A | | | MEETING INVOLVING THE OWNER, SPECIAL INSPECTOR, JOB | | | INSPECTOR, CONTRACTOR AND ENGINEER.THIS MUST BE DONE | | | PRIOR TO PERMIT ISSUANCE.THREE ORIGINAL SETS OF ALL | | | DOCUMENTS ARE REQUIRED FOR PERMITTING AND FOR ALL | | | SUBSEQUENT SUBMITTALS.SEE FBC*109.3.6. | | | | | | 4.)PROVIDE THE THRESHOLD INSPECTION PLAN.THE | | | APPROVED CONTRACT WITH THE THRESHOLD INSPECTOR WILL BE | | | REQUIRED IN THE PERMIT PACKAGE PRIOR TO PERMIT | | | ISSUANCE. | | | | | | 2ND REVIEW; I WAS UNABLE TO LOCATE THE COMPLIANCE | | | STATEMENT AS REQUIRED BY FS553.79(7)(D).THIS IS | | | REQUIRED FOR THE ARCHITECT AND ENGINEER.PLEASE ADVISE | | | AS TO LOCATION OF THIS STATEMENT. | | | | | | NOTE THAT THE THRESHOLD INSPECTION PLAN IS TYPICALLY | | | INCORPORATED INTO THE PLAN BY THE ARCHITECT IN ADDITION | | | TO BEING A PART OF THE CONTRACT BETWEEN THE OWNER, THE | | | INSPECTOR, AND THE CITY. | | | | | | 5.)ADDRESSED. | | | | | | 6.)ADDRESSED; THE PLANS WILL BE STAMPED WITH A5 FLOOD | | | ZONE DESIGNATION, FORM BOARD SURVEY REQUIRED | | | (INFORMATIONAL ONLY). | | | | | | 7.)ADDRESSED. | | | | | | 8.)FIRE SPRINKLER PLANS REQUIRED IF SPRINKLERS ARE | | | REQUIRED FOR CODE COMPLIANCE, FBC*106.3.5.1.1(5), | | | FS553.79 (2). | | | | | | SHEETS FS 1, 2, AND 3 WERE ADDED.HOWEVER, THEY DO NOT | | | SHOW SPRINKLER HEAD LAYOUT, ONLY HAZARD CLASSIFICATION | | | PER NFPA.PLEASE PROVIDE PLANS AS REQUIRED. | | | | | | 9-24.) ADDRESSED. | | | | | | 25.)THE GATES ARE REQUIRED TO BE ACCESSIBLE, | | | FBC11-4.1.3(9), ACCESSIBLE MEANS OF EGRESS.PROVIDE A | | | DETAIL TO SHOW COMPLIANCE. | | | | | | THE RESPONSE LETTER STATES THAT A10.1 SHOWS THIS | | | HARDWARE GROUP AS ACCESSIBLE.SEE HARDWARE GROUP 13 | | | AND 14; I AM UNABLE TO DISCERN FROM THE DESCRIPTION | | | THAT THIS IS ACCESSIBLE HARDWARE.PLEASE CLARIFY, | | | EITHER BY REVISING THE DESCRIPTION OR INCLUDING SPEC | | | SHEETS FOR THE GATE HARDWARE. | | | | | | 26-36.) ADDRESSED. | | | | | | 37.)SIGN THE OWNER/AGENT LINE OF THE ENERGY CALC, | | | FBC13-103.1. | | | | | | 38.)ADDRESSED. | | | | | | 39.)SELECT THE APPROVED ASSEMBLY YOU ARE USING IN THE | | | ROOF PRODUCT APPROVAL. | | | | | | NOT ADDRESSED.THIS CAN BE DONE BY THE ROOFING | | | CONTRACTOR AT THE TIME OF ROOF PERMIT APPLICATION. | | | | | | 40.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL IN | | | ADDITION TO THE NOAS PROVIDED.IF A FLORIDA STATE | | | PRODUCT APPROVAL IS UNAVAILABLE, PLEASE ADVISE AND A | | | LOCAL PRODUCT APPROVAL WILL BE ISSUED USING THE NOA. | | | | | | PLEASE PRINT THE FLORIDA STATE PRODUCT APPROVALS, | | | WWW.FLORIDABUILDING.ORG | | | | | | 41.)FOR THE EXCLUSIVE WOOD DOORS AND THE REPUBLIC | | | DOORS, PRINT THE FLORIDA STATE PRODUCT APPROVAL, | | | EVALUATION REPORT AND INSTALLATION INSTRUCTIONS FROM | | | THE INTERNET. | | | | | | NOT ADDRESSED.THE PAPERWORK PROVIDED SHOWS A DESIGN | | | PRESSURE OF +-47, SEE SHEET S10, 59.2 REQUIRED. | | | | | | 42.)FOR THE REPUBLIC DOORS, MARK WHICH PRODUCT(S) YOU | | | ARE INSTALLING. | | | | | | 2ND REVIEW, FL4304 WAS CIRCLED.PLEASE GO TO THE | | | WEBSITE, WWW.FLORIDABUILDING.ORG, AND PRINT THE PRODUCT | | | APPROVAL.CONFIRM THAT THE SUPPLEMENTARY DOCUMENTATION | | | (EVALUATION REPORT, INSTALLATION INSTRUCTIONS) MATCHES | | | THE ONES ON THE INTERNET.NOTE THAT FL4304 (CIRCLED ON | | | THE LIST OF MANUFACTURER?S PRODUCTS) HAS A DESIGN | | | PRESSURE OF 114, BUT THE PAPERWORK IS FOR A DOOR WITH A | | | DESIGN PRESSURE OF 60PSF.IT DOES NOT APPEAR TO BE THE | | | SAME DOOR. | | | | | | 43.)WHEN RESUBMITTING, PLEASE INCLUDE A RESPONSE | | | LETTER STATING HOW AND WHERE EACH ITEM WAS ADDRESSED. | | | | | | NEW COMMENTS: | | | | | | 44.)SHOW ALL REQUIRED DETECTABLE WARNINGS, | | | FBC11-4.29.5. | | | | | | 45.)A SECOND EXIT DOOR WAS ADDED TO THE CHAPEL.SEE | | | LANDSCAPE SHEETS.THE LANDSCAPE PLANS WERE NOT REVISED | | | TO REFLECT FLOOR PLAN CHANGES TO THE CHAPEL AND THE | | | OFFICE AREA.IT APPEARS THAT THIS DOOR OPENS ONTO AN | | | AREA WHICH IS NOT PAVED AND HAS AN IRRIGATION HEAD AT | | | THIS LOCATION.SEE FBC1008.1.5, DOOR LANDING REQUIRED, | | | AND FBC1003.4, FLOOR SURFACE. | | | | | | 46.)A1.1, SEE FBC 1024.10, AISLE ACCESSWAYS.SHOW | | | MINIMUM REQUIRED WIDTH. | | | | | | 47.)PLEASE SHOW OCCUPANT LOAD SERVED BY THE DOUBLE | | | GATES, ADJACENT TO CLASSROOM 331.SEE FBC1008.1.2. THE | | | PATH OF EGRESS IS SHOWN AS GOING TOWARDS THE ASSEMBLY | | | AREA RATHER THAN TOWARDS THE PARKING LOT. PLEASE | | | EXPLAIN THE LOGIC AS IT APPEARS THAT THE EGRESS PATH | | | WILL MOST LIKELY BE GOING TOWARDS THE PARKING LOT AREA. | | | IT ALSO APPEARS THAT, IF USED, OCCUPANT LOAD WHICH | | | THESE GATES SERVE MAY BE GREATER THAN 50.CAN THESE | | | GATES SWING BOTH DIRECTIONS (180 DEGREE SWING RATHER | | | THAN 90DEGREE AS SHOWN)? | | | | | | 48.)PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER | | | OF RECORD, (SHOP DRAWING REVIEW STAMP OR LETTER), | | | FBC*106.3.3.SHEET A9 SPECIFIES MOST OF THE COMPONENTS | | | AND CLADDING.HOWEVER, FOR OTHER ITEMS, PLEASE | | | REVIEW. | | | | | | 49.)PROVIDE PRODUCT APPROVAL FOR THE SKYLIGHTS SHOWN | | | ON A4.0, FAC9B72. | | | | | | 50.)PLEASE CORRELATE A9 AND S10.FOR INSTANCE, | | | OPENINGS 1 AND 2 ARE SHOWN AS 2X8 ON A9, 1FT8IN X | | | 7FT8IN ON S10.ARE THE OPENINGS THE SAME?IF NOT, | | | PLEASE CORRELATE. | | | | | | 51.)INFORMATIONAL ONLY; S10 HAS TWO SETS OF DESIGN | | | PRESSURES, ZONE 4 AND ZONE 5.ALL PRODUCT APPROVALS | | | WILL BE REVIEWED TO THE MOST STRINGENT.IF THIS IS NOT | | | ACCEPTABLE, PLEASE REVISE SO THAT ONLY ONE NEGATIVE | | | DESIGN PRESSURE IS INCLUDED FOR EACH OPENING. | | | | | | 52.ELECTRIC SHEETS ARE MISSING FROM THE SET WHICH WAS | | | REVIEWED FOR BUILDING.WHEN RESUBMITTING, PLEASE | | | CONFIRM THAT EACH SET IS COMPLETE AND IDENTICAL. | | | | | | 53.ON A1.1, THERE ARE DARK LINES ACROSS THE AREA | | | WHERE THE PEW AISLES CONVERGE, ADJACENT TO THE STAGE. | | | WHAT ARE THESE LINES? | | | | | | 54.)WHEN RESUBMITTING, PLEASE CLOUD ALL CHANGES. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-10-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-10-05 |
Time |
11:57 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-10-05 |
Time |
11:57 |
Sent To |
|
|
| Notes |
| 2007-10-05 11:57:44 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC | | | FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | | | | 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO | | | PERMIT PICKUP, FS713.13. | | | | | | 2.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY | | | PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.PLEASE CALL | | | 561-233-5025 FOR MORE INFORMATION.THE PLANS MUST BE | | | STAMPED AND THE RECEIPT IS TO BE INCLUDED WITH THE | | | PERMIT APPLICATION. | | | | | | 3.)AS THIS IS A THRESHOLD BUILDING AS DEFINED IN | | | FS553.71(7), PLEASE ARRANGE WITH HAROLD PISKURA | | | (INSPECTION SERVICES MANAGER - TEL:561 805 6711), A | | | MEETING INVOLVING THE OWNER, SPECIAL INSPECTOR, JOB | | | INSPECTOR, CONTRACTOR AND ENGINEER.THIS MUST BE DONE | | | PRIOR TO PERMIT ISSUANCE.THREE ORIGINAL SETS OF ALL | | | DOCUMENTS ARE REQUIRED FOR PERMITTING AND FOR ALL | | | SUBSEQUENT SUBMITTALS.SEE FBC*109.3.6. | | | | | | 4.)PROVIDE THE THRESHOLD INSPECTION PLAN.THE | | | APPROVED CONTRACT WITH THE THRESHOLD INSPECTOR WILL BE | | | REQUIRED IN THE PERMIT PACKAGE PRIOR TO PERMIT | | | ISSUANCE. | | | | | | 5.)THE PRINTED NAME OF THE PERSON SEALING THE | | | DOCUMENT IS TO BE ON EACH SHEET, SLIDER ENGINEERING, | | | FAC61G15-23.002. | | | | | | 6.)THIS PROJECT IS IN AN A5 HIGH HAZARD FLOOD ZONE. A | | | FORM BOARD ELEVATION CERTIFICATE AND FFE CERTIFICATE | | | WILL BE REQUIRED TO BE FILED WITH THIS OFFICE DURING | | | THE CONSTRUCTION PROCESS.ALL FFES, INCLUDING | | | MECHANICAL EQUIPMENT, ARE TO BE 6? ABOVE BASE FLOOD | | | ELEVATION, CITY OF WEST PALM BEACH MUNICIPAL CODE | | | 94-546(B).INCLUDE THIS REQUIREMENT ON THE PLAN. | | | | | | 7.)PROVIDE A CODE SUMMARY; HOW COMPLIANCE WITH FBC | | | TABLE 503, DECLARE MIXED OR NONSEPARATED USE, | | | INCIDENTAL OR ACCESSORY USES, FBC302.ALL AREA | | | INCREASE CALCULATIONS ARE TO BE ON THE PLAN.IF ANY | | | FIRE RATED WALLS ARE REQUIRED, SHOW ON THE PLAN AND | | | PROVIDE DETAILS. | | | | | | 8.)FIRE SPRINKLER PLANS REQUIRED IF SPRINKLERS ARE | | | REQUIRED FOR CODE COMPLIANCE, FBC*106.3.5.1.1(5), | | | FS553.79 (2). | | | | | | 9.)SEE CITY OF WEST PALM BEACH STANDARD FOR PARKING | | | STRIPING, SEE ATTACHED AND ZONING COMMENTS, SHEET | | | A1.0. | | | | | | 10.)PLEASE NOTE THAT THE ROOM DESIGNATION NUMBERS ARE | | | DIFFERENT ON SHEET A1.0 FROM OTHER SHEETS IN THE PLAN. | | | IT IS NOT A REQUIREMENT FOR THEM TO BE CONSISTENT, BUT | | | NOTE THAT SHEET A1.0 IS THE EASIEST SHEET TO USE FOR | | | REFERENCE AS IT SHOWS THE ENTIRE PLAN. | | | | | | 11.)SIMMONS & WHITE SHEET 2, RAMP SLOPE IS SHOWN AS | | | 12:1 MAX.DO YOU MEAN 1:12? | | | | | | 12.)NO ACCESS AISLE SHOWN FOR PARKING SPACE 55, | | | A1.0. | | | | | | 13.)THERE APPEARS TO BE AN UNNECESSARY ACCESS AISLE | | | BETWEEN TWO NON ACCESSIBLE SPACES, 58 AND 59, IS THIS | | | CORRECT?A1.0 | | | | | | 14.)SHOW THE PASSENGER LOADING ZONE FBC11-4.6.6. | | | | | | 15.)PROVIDE A DETAIL FOR THE RAMP HANDRAIL SHOWN ON | | | A1.0, EAST SIDE.FBC11-4.8.5. | | | | | | 16.)PROVIDE A DETAIL FOR THE STAIR HANDRAILS, | | | FBC11-4.9.4.THE HANDRAILS SHOWN DO NOT APPEAR TO HAVE | | | THE HANDRAIL EXTENSIONS AT THE BOTTOM FBC11-4.9.4(2) | | | (12INCHES PLUS WIDTH OF ONE TREAD). | | | | | | 17.)A LANDING IS REQUIRED AT THE BOTTOM OF THE RAMP, | | | A2.0 FBC11-4.8.4. | | | | | | 18.)HANDRAIL EXTENSIONS REQUIRED TOP AND BOTTOM OF | | | THE RAMP A2.0 FBC11-4.8.5. | | | | | | 19.)A2.0 SHOWS DETAIL INDICATOR 7-A7.5 IN THE | | | SANCTUARY AREA, BUT THIS DETAIL IS FOR A GATE.ALSO | | | SEE 2-A7.3, CHECK ALL. | | | | | | 20.)A2.0 DETAIL INDICATOR 3-A7.5 AT THE RAMP IS FOR | | | THE STAIR DETAIL; SHOULD THIS BE 4-A7.5?PROVIDE THE | | | HEIGHT, SEE FBC11-4.4. | | | | | | 21.)ON THE LIFE SAFETY PLAN, PLEASE SHOW EGRESS WIDTH | | | AND OCCUPANT LOAD SERVED FOR EACH COMPONENT, OCCUPANT | | | LOAD, TRAVEL DISTANCE, WIDTH OF COMPONENTS OF MEANS OF | | | EGRESS (HALLWAYS AND DOORS, ETC.), OVER ALL DIMENSIONS | | | FOR THE AREAS.THE EGRESS PLAN A2.3 SHOWS EXITING FROM | | | THE SANCTUARY, BUT EXIT DISCHARGE IS TO BE TO THE | | | PUBLIC WAY.THE LIFE SAFETY PLAN SHOULD CLEARLY SHOW | | | COMPLIANCE WITH FBC CHAPTER 10.TOTAL OCCUPANT LOAD | | | WAS SHOWN ON ANOTHER SHEET, BUT SOME OF THESE AREAS | | | SHARE THE EXIT ACCESS AND THIS NUMBER IS NOT SHOWN ON | | | THE PLAN.PLEASE LABEL ROOM NUMBERS.PLEASE CONTACT | | | ME IF YOU WISH TO DISCUSS. | | | | | | 22.)AREAS INCLUDED IN THE OCCUPANT LOAD ON A2-2 ARE | | | NOT ENTIRELY CLEAR.FOR INSTANCE, HOW WAS THE STAGE | | | AREA INCLUDED IN THIS CHART, OR ACCESSORY STORAGE | | | AREAS?SEE FBC TABLE 1004.1.2. | | | | | | 23.)AREA 201 DOES NOT APPEAR TO BE INCLUDED AS HAVING | | | AN OCCUPANT LOAD.SEE FBC1004.1.2, NUMBER OF OCCUPANTS | | | CANNOT BE LESS THAN FBC TABLE 1004.1.2.IT APPEARS | | | THAT THE OCCUPANT LOAD PROVIDED IS ACTUAL OCCUPANT | | | LOAD, FBC1004.1.1. | | | | | | 24.)TOTAL OCCUPANT LOAD GOING THROUGH EXIT DISCHARGE | | | 336A, 336D IS NOT SHOWN. | | | | | | 25.)THE GATES ARE REQUIRED TO BE ACCESSIBLE, | | | FBC11-4.1.3(9), ACCESSIBLE MEANS OF EGRESS.PROVIDE A | | | DETAIL TO SHOW COMPLIANCE. | | | | | | 26.)SHOW WHEELCHAIR AREAS AND SEATING, FBC11-4.33.3. | | | | | | 27.)IF TOILET ROOMS ARE PROVIDED, THEN EACH PUBLIC | | | AND COMMON USE TOILET ROOM SHALL COMPLY WITH | | | FBC11-4.22, FBC11-4.1.3(11).PRIVATE TOILET SPACES | | | SHALL BE ADAPTABLE, SEE BATHROOM ADJACENT TO AREA 103 | | | SHEET A2.1.PROVIDE A GRAB BAR BACKING DETAIL AND SHOW | | | TURNING RADIUS, DOOR MANEUVERING CLEARANCE FBC11 FIGURE | | | 25.ALSO SHOW DISTANCE REQUIRED FOR TWO DOORS IN A | | | SERIES, FBC11-4.13.7. | | | | | | 28.)LOUNGE SINKS ARE TO COMPLY WITH FBC11-4.2.4, | | | PROVIDE A DETAIL.THE SECTIONS SHOWN ON A7.2 SHOW | | | DOORS BLOCKING THE REQUIRED KNEE CLEARANCE. | | | FBC11-4.24.3. | | | | | | 29.)DOUBLE DOORS IN ROOMS 316 AND 317, ONE LEAF IS TO | | | MEET THE REQUIREMENTS OF FBC11-4.13, FBC11-4.13.4. | | | | | | 30.)PROVIDE A DETAIL AND SHOW LOCATION OF SEATING | | | COMPLYING WITH FBC11-4.1.3(18) AND (19). | | | | | | 31.)SHOW COMPLIANCE WITH FBC11-4.1.3(19)(B).IF YOU | | | FEEL THAT THIS (OR ANY OF THE ACCESSIBILITY | | | REQUIREMENTS) DOES NOT APPLY, PLEASE CONTACT ME AND | | | DOCUMENT THE EXEMPTION IN WRITING WITH THE | | | RESUBMITTAL. | | | | | | 32.)PROVIDE ROOF DRAINAGE CALCULATIONS, FBC1503.4. | | | SHOW LOCATION OF SCUPPERS AND HEIGHT OF SCUPPER IN THE | | | PARAPET WALL. | | | | | | 33.)A10.0, WALL FINISH W1 STATES TO SEE SHEET A- FOR | | | DETAILS.PLEASE COMPLETE REFERENCE. | | | | | | 34.)ROOM 316 AND 317 SHOW W1 ON THE FLOOR PLAN DETAIL | | | A7.0, W1* FOR FINISH.IT IS NOT CLEAR WHAT THE | | | ASTERISK DESIGNATES.PROVIDE THE DETAIL FBC1210.2. | | | CHECK ALL BATHROOM WALL FINISHES AND REVISE A10.0 | | | ACCORDINGLY. | | | | | | 35.)DETAIL 2 A6.0 HAD TEXT AT THE TOP RIGHT WHICH IS | | | ILLEGIBLE (CUT OFF).EITHER REMOVE THE PARTIAL TEXT OR | | | PROVIDE THE TEXT IN A LEGIBLE FORMAT. | | | | | | 36.)SHEET S10 STATES EDGE ZONE IS *'*", PLEASE | | | REVISE. | | | | | | 37.)SIGN THE OWNER/AGENT LINE OF THE ENERGY CALC, | | | FBC13-103.1. | | | | | | 38.)PROVIDE ROOF COMPONENTS AND CLADDING DESIGN | | | PRESSURE, FBC1603.1.4. | | | | | | 39.)SELECT THE APPROVED ASSEMBLY YOU ARE USING IN THE | | | ROOF PRODUCT APPROVAL. | | | | | | 40.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL IN | | | ADDITION TO THE NOAS PROVIDED.IF A FLORIDA STATE | | | PRODUCT APPROVAL IS UNAVAILABLE, PLEASE ADVISE AND A | | | LOCAL PRODUCT APPROVAL WILL BE ISSUED USING THE NOA. | | | | | | 41.)FOR THE EXCLUSIVE WOOD DOORS AND THE REPUBLIC | | | DOORS, PRINT THE FLORIDA STATE PRODUCT APPROVAL, | | | EVALUATION REPORT AND INSTALLATION INSTRUCTIONS FROM | | | THE INTERNET. | | | | | | 42.)FOR THE REPUBLIC DOORS, MARK WHICH PRODUCT(S) YOU | | | ARE INSTALLING. | | | | | | 43.)WHEN RESUBMITTING, PLEASE INCLUDE A RESPONSE | | | LETTER STATING HOW AND WHERE EACH ITEM WAS ADDRESSED. | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2008-09-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-09-30 |
Time |
11:21 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-09-30 |
Time |
11:21 |
Sent To |
|
|
| Notes |
| 2008-09-30 11:23:37 | | | | ** TEMPORARY DENIED REVIEW ** | | | | | | 1) NOTE: PLEASE SEE REVIEW NOTES FROM PREVIOUS REVIEW. | | | PROVISO IS SET FOR NOTES #2 AND 3 HOWEVER NO LETTER | | | SUBMITTED FOR NOTE #1 NOR FEE BALANCE PAID. | | | ** ELECTRICAL PLANS ARE ALREADY STAMPED AND REVIEW WILL | | | GO INTO A "P" STATUS ONCE REVIEW NOTE #1 IS ADDRESSED | | | FROM PREVIOUS REVIEW. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2008-08-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-08-27 |
Time |
16:04 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-08-27 |
Time |
16:04 |
Sent To |
|
|
| Notes |
| 2008-08-27 16:05:02 | | | | | | | | | | | | | | | | ** TEMPORARY DENIED ** | | | | | | *** NOTE #1 NEEDS TO BE ADDRESSED AT THIS TIME. COMMENT | | | #2 AND #3 CAN BE DONE AS A PROVISO. | | | | | | | | | 1) NOTE: THE LETTER OF UNDERSTANDING FROM OWNER NEEDS | | | TO BE SUBMITTED WITH REFERENCE TO THE 4X FEE WHICH WAS | | | NOT PAID. THE LETTER IS TO ACKNOWLEDGE THE FEE AMOUNT | | | AND UNDERSTAND THAT A HOLD WILL BE PLACED ON THE | | | CERTIFICATE OF OCCUPANCY UNTIL FEE IS PAID IN FULL. FOR | | | ANY TECHNICAL LEGAL QUESTIONS PLEASE CONTACT THE CITY | | | ATTORNEY?S OFFICE. | | | | | | 2) NOTE: LOCATION OF UPS IN HALL WITH THE SIZE AS | | | SPECIFIED ON THE MANUFACTURE CUT SHEETS NEEDS TO BE | | | VERIFIED. IN FACT BASED ON THE UNIT SPEC SHEETS THE | | | UNIT AS SUBMITTED IS TOO LARGE FOR LOCATION. | | | PLEASE REVISE AND SUBMIT DOCUMENTS AS NEEDED. | | | | | | 2) NOTE: SHEETS E-7.0 AND E-8.0 CONTAIN THE NOTES FOR | | | MINIMUM CD LEVELS FOR STROBE DEVICES TO MEET FBC | | | 11-4.28.3(4) HOWEVER PLANS STILL SHOW SEVERAL STROBE | | | LOCATIONS WITH CANDELA LEVELS BELOW THE MINIMUM OF 75. | | | (MANY AT 15) | | | | | | | | | | | | **IMPORTANT** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2008-06-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-06-18 |
Time |
12:07 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-06-18 |
Time |
12:07 |
Sent To |
|
|
| Notes |
| 2008-06-18 12:08:04 | ** DENIED3RD REVIEW ** | | | | | | ** PLEASE SEE THERE ARE SEVERAL COMMENTS FROM THE TWO | | | PREVIOUS REVIEWS WHICH ARE STILL IN NEED OF ADDRESSING. | | | THERE ARE ALSO SOME NEW COMMENTS DUE TO SOME CHANGES | | | MADE TO PREVIOUS PLANS, DESIGN ETC. | | | | | | 1) NOTE: THERE WAS A MEETING HELD AFTER THE LAST REVIEW | | | IN WHICH THE LIGHTING CONTROL SYSTEM WAS GOING TO BE | | | SUBSTANTIALLY CHANGED/REVISED. THIS REVIEWER MENTIONED | | | TO POSSIBLY HAVE AN ADDITIONAL MEETING BEFORE PLANS | | | WERE RESUBMITTED TO GO OVER ANY QUESTIONS FOR CHANGES | | | WHICH WERE GOING TO BE MADE. NO CONTACT WAS MADE TO | | | THIS REVIEWER. THE COMMENTS BELOW ARE BASED ON PLANS | | | AND SUPPORTING REQUIRED DOCUMENTS WHICH DO NOT SHOW * | | | MINIMUM* BUILDING CODE COMPLIANCE. | | | | | | ** THERE ARE EXTENSIVE EXAMPLES WHICH ARE LISTED BELOW | | | UNDER NOTES. THESE ARE GIVEN AS A BENEFIT IN AN EFFORT | | | FOR PLANS TO BE CORRECTED ON THE FOLLOWING REVIEW FOR | | | PERMIT ISSUANCE. THE EXAMPLES ARE GIVEN AS A BENEFIT | | | ONLY AND NOT AN EXHAUSTED LIST OF EVERY SPECIFIC ITEM. | | | THE CODE SECTIONS ARE ONCE AGAIN GIVEN. | | | | | | 2) NOTE: PLEASE SEE FBC 13-415.2.ABC.1.1, .1.2, .1.3, | | | 13-400, 13-400.3.A, 13-415.2 ETC AS THE SUBMITTED | | | ENERGY CALCULATIONS DO NOT CORRELATE WITH THE SUBMITTED | | | PLANS. PLEASE SEE THERE SEVERAL LIGHTING FIXTURES, | | | WATTAGES ETC ON PLANS WHICH ARE NOT SHOWN FOR THE | | | CORRECT NUMBER OF FIXTURES, WATTAGES OF FIXTURES IN THE | | | INPUT DATA REPORT OF THE SUBMITTED ENERGY CALCULATIONS. | | | THE INPUT DATA REPORT WILL BE NOTED AS IDR FOR THE | | | REMAINDER OF THIS COMMENT. | | | | | | FOR EXAMPLE: | | | PLEASE SEE FIXTURE M WHICH IS SHOWN FOR AN EXTERIOR | | | LIGHT FIXTURE ON PLANS AT THE FRONT ENTRANCE AND ON THE | | | FIXTURE LEGEND HOWEVER THESE ARE NOT SHOWN/LISTED ON | | | THE IDR FOR EXTERIOR LIGHT FIXTURES. | | | | | | FOR EXAMPLE: | | | PLEASE SEE PLANS WHICH SHOWS A TOTAL OF 50+ 35W | | | FIXTURES WHICH ARE LABELED WITH DIFFERENT ALPHA | | | DESIGNATIONS YET THE IDR ONLY SHOWS 22- TOTAL 35W | | | FIXTURES. PLANS CLEARLY SHOW A SUBSTANTIALLY HIGHER | | | AMOUNT OF FIXTURES. | | | | | | FOR EXAMPLE: | | | PLEASE SEE THE *H-1* FIXTURE SHOWN ON PLANS WHICH IS | | | LISTED ON THE FIXTURE LEGEND AS 2-26W BULBS WHICH IS | | | ABOUT 52WATTS/VA, YET THE IDR DOES NOT INCLUDE ANY 52W | | | FIXTURES. THE CLOSEST WATTAGE OR VA LISTED IS NOTED AS | | | THE STAIR FIXTURES. THE STAIR FIXTURES LISTED ON THE | | | FIXTURE LEGEND ARE SHOWN AS 28W AND TWO IN EACH RAIL | | | GIVES THE 56WATTS ALREADY ACCOUNTED FOR. | | | | | | ***** THIS IS ONLY A FEW EXAMPLES OF THE EXTERIOR | | | LIGHTS SHOWN ON PLANS WHICH DO NOT COORDINATE WITH THE | | | SUBMITTED ENERGY CALCULATIONS. THERE ARE OTHERS. | | | | | | PLEASE SEE THE SAME SECTIONS OF THE CODES ABOVE IN THIS | | | SAME NOTE FOR ALL FIXTURES ON THE INTERIOR OF THE | | | BUILDING WHICH IS REQUIRED TO BE PLACED INTO THE | | | SUBMITTED IDR/ENERGY CALCULATIONS. | | | SOME ADDITIONAL EXAMPLES OF FIXTURES ON THE INTERIOR | | | LIGHTS WILL ALSO BE GIVEN AS A BENEFIT. | | | | | | FOR EXAMPLE: | | | PLEASE SEE THE AREAS SUCH AS ROOM #100/SANCTUARY WHICH | | | ARE STILL SHOWING FIXTURES WHICH ARE NOT LISTED ON THE | | | IDR. | | | PLEASE SEE THE TRACK LIGHTING FIXTURES WHICH BASED ON | | | THE WATTAGE OF FIXTURE LEGEND IS NOT LISTED ON THE | | | IDR. | | | | | | FOR EXAMPLE: | | | PLEASE SEE THE *G1* FIXTURES IN SAME ROOM #100 ARE NOT | | | THE SAME AS ON IDR. | | | | | | FOR EXAMPLE: | | | PLEASE SEE THERE ARE STILL LIGHTING FIXTURES SHOWN IN | | | ROOM # 100 WHICH DO NOT DESIGNATIONS AND ARE NOT LISTED | | | ON THE IDR. THE SYMBOL IS SHOWING THESE TO BE LIGHTING | | | FIXTURES WHICH ARE A PENDANT TYPE BASED ON THE SYMBOL | | | LEGEND. THERE IS ROUGHLY AN 11 OF THESE FIXTURES NOT | | | ACCOUNTED FOR. PLEASE SEE COMMENTS WITH RESPECT TO | | | CONTROLS. | | | | | | FOR EXAMPLE: | | | PLEASE SEE AHU-1 ZONE. THESE FIXTURES ARE SHOWN IN THE | | | IDR AS 71W YET THE PLANS DO NOT SHOW THESE SAME TYPES | | | AND WATTAGES? | | | | | | FOR EXAMPLE: | | | PLEASE SEE FIXTURES SUCH AS Z-1 WHICH ARE NOT LISTED ON | | | THE LEGEND WITH ANY TYPE OF WATTAGE OR ALLOWANCE. | | | | | | FOR EXAMPLE: | | | PLEASE SEE FIXTURE *T* WHICH IS NOT LISTED WITH ANY | | | WATTAGE. THIS CAN NOT BE CONFIRMED IN ZONE RTU3B. IN | | | FACT THE PLANS CALL FOR *TBD* WHICH IS * TO BE | | | DETERMINED*. THE MINIMUM CODE COMPLIANCE IS REQUIRED ON | | | PLANS. FIXTURES DURING ANY PROJECT MAY BE REVISED. WHEN | | | FIXTURES ARE REVISED PLANS ALONG WITH REVISED ENERGY | | | CALCULATIONS ARE REQUIRED AND SUBMITTED BEFORE | | | INSPECTIONS/FINALS. PLANS AND CALCULATIONS ARE REQUIRED | | | TO SHOWN MINIMUM CODE COMPLIANCE BEFORE ISSUANCE. | | | | | | FOR EXAMPLE: | | | PLEASE SEE PLANS SHOW *TT* FIXTURES IN RTU5 ZONE. AS | | | THE FIXTURE LEGEND DOES NOT LIST ANY TYPE *TT* FIXTURE | | | ON ELECTRICAL OR ARCHITECTURAL PLANS IT IS NOT KNOWN | | | WHAT THESE ARE GOING TO BE? NEED TO COMPLETE MINIMUM AT | | | THIS TIME. | | | | | | FOR EXAMPLE: | | | PLEASE SEE SAME ZONE RTU-5 WHICH DOES NOT INCLUDE ANY | | | *F1* FIXTURE AS SHOWN ON PLANS AND LISTED ON THE | | | FIXTURE LEGEND. | | | | | | FOR EXAMPLE: | | | PLEASE SEE SAME ZONE RTU-5 WHICH DOES NOT LIST ANY TYPE | | | *C* FIXTURES WHICH ARE LISTED ON PLANS AND ON FIXTURE | | | LEGEND. | | | | | | FOR EXAMPLE: | | | PLEASE SEE THIS SAME ZONE RTU-5 WHICH SHOWS A TOTAL OF | | | 24-8A WATT *B* FIXTURES YET PLANS CLEARLY SHOW 32-84W | | | FIXTURES. | | | | | | FOR EXAMPLE: | | | PLEASE SEE AHU11 WHICH SHOWS A 42W FIXTURE HOWEVER | | | PLANS SHOW ALL 84 WATT FIXTURES. | | | | | | FOR EXAMPLE: | | | PLEASE SEE FIXTURES NOW ADDED IN CHAPEL NOT IN THE IDR. | | | (A2) | | | | | | FOR EXAMPLE: | | | PLEASE SEE THERE ARE SEVERAL FIXTURES LISTED ON PLANS | | | YET THEY ARE NOT LISTED ON THE FIXTURE LEGEND WITH ANY | | | TYPE OF WATTAGE. THESE ARE REQUIRED TO BE COMPLETE AT | | | THIS TIME WITH MINIMUM DESIGN ALLOWANCES. | | | SEE Z1, TT, T, ETC. SOME ALREADY NOTED ABOVE. | | | SEE CHAPEL FOR SYMBOLS SHOWN BUT NOT ANY DESIGNATIONS. | | | | | | *** THESE ARE SOME EXAMPLES AS A BENEFIT TO THE DESIGN | | | TEAM TO SEE THE TYPES OF ITEMS WHICH ARE STILL IN NEED | | | OF CORRECTIONS. THIS IS IN NO WAY AN EXHAUSTED LIST. ** | | | THIS REVIEWER CAN NOT EMPHASIZE ENOUGH TO PLEASE BE | | | SURE ALL COMPONENTS SHOWN AND LISTED IN BUILDING ARE | | | PLACED INTO THE INPUT DATA REPORT. (IDR). THIS IS | | | REQUIRED FOR ALL TRADE COMPONENTS. | | | **** | | | THERE WILL BE COMMENTS BELOW WHICH MAY VERY WELL AFFECT | | | ENERGY CALCULATIONS. | | | | | | 3) NOTE: PLEASE SEE AS NOTED ON PREVIOUS REVIEW | | | LIGHTING CONTROLS FOR ALL FIXTURES IN ALL AREAS ARE NOT | | | SHOWN TO BE COMPLETE/COMPLIANT AT THIS TIME. PLEASE SEE | | | 13-415.1.ABC.1.1, .1.2, .1.3, AND .1.4. | | | | | | FOR EXAMPLE: | | | PLEASE SEE FIXTURES AS NOTED ABOVE IN NOTES WHICH ARE | | | LOCATED IN ROOM #100. THESE SHOW A NUMBER IN A ROUND | | | CIRCLE HOWEVER THERE IS NOT LEGEND OR NOTES ON WHAT | | | THESE NUMBERS REPRESENT. AS THE FIXTURES ARE NOT | | | LABELED IT IS NOT POSSIBLE TO GIVE EXACT LOCATION. | | | THESE ARE THE FIXTURES (BASED ON SYMBOL LEGEND) THAT | | | HAVE THE CIRCLE NUMERICAL DESIGNATIONS, 10, 11, 13 AND | | | 14. THESE ARE NOTED AS PENDANT FIXTURES ON SYMBOL | | | LEGEND. THERE ARE OTHER FIXTURES SUCH AS THE *G1* WHICH | | | ARE SHOWING A FIXTURE DESIGNATION HOWEVER THE ONLY A | | | NUMBER 12 IN A CIRCLE. | | | PLEASE CLARIFY. | | | | | | FOR EXAMPLE: | | | PLEASE SEE SOME OUTSIDE EXTERIOR LIGHTS WHICH ARE NOTED | | | TO TIME CLOCK YET THE TIME CLOCK SCHEDULE DOES NOT LIST | | | ANY OF THESE CIRCUITS. SEE THE TC SCHEDULE IS MISSING | | | #22, #37. | | | | | | ** PLEASE SEE COMMENTS BELOW WITH RESPECT TO EGRESS | | | LIGHTING WHICH WILL HAVE AN AFFECT ON CIRCUITING, | | | LIGHTS ETC. | | | | | | 4) NOTE: PLEASE SEE THERE ARE CIRCUITS LISTED ON THE | | | PLANS TO NOW GO TO A NEW UPS FOR EMERGENCY BACK UP | | | FIXTURES YET THE SCHEDULE SHOWN ON E-12.0 DOES NOT SHOW | | | THESE FIXTURES. | | | | | | FOR EXAMPLE: | | | PLEASE SEE MISSING CIRCUITS, 1L3-1, 1L3-22 AND 1L3-37. | | | THE PLANS SHOW LIGHT FIXTURES *H* AT FRONT ENTRANCE TO | | | THIS UNIT, THE FIXTURES *H* AT REAR ENTRY/COVERED ARE | | | ALSO BUT NOT LISTED. | | | | | | FOR EXAMPLE: | | | PLEASE VERIFY FIXTURES *W-2* WHICH ARE LISTED AS THE | | | WATER FEATURE LIGHTS ON THE UPS. | | | | | | NFPA-101 2003 7.8, 7.9, | | | FBC 106.1.2 FOR COORDINATION. | | | | | | 5) NOTE: PLEASE SEE THAT COMPLIANCE WITH THE MINIMUM | | | LIFE SAFETY CODE HAS NOT BEEN SHOWN AT THIS TIME. THERE | | | ARE ALSO SEVERAL COMMENTS WITH RESPECT TO COORDINATION | | | OF PLANS. | | | PLEASE SEE NFPA-101 7.8, 7.9, 7.8.1.3, 7.9.2. AS THE | | | SUBMITTED PHOTO-METRICS DO NOT COORDINATE WITH PLANS IN | | | MANY LOCATIONS THERE IS THE NEED FOR MANY ITEMS TO BE | | | ADJUSTED AND REVISED. | | | | | | FOR EXAMPLE: | | | PLEASE SEE ELECTRICAL LIGHTING PLANS CLEARLY SHOW | | | FIXTURES A AND AE IN OUTSIDE CORRIDORS YET THE | | | SUBMITTED PHOTO-METRICS CLEARLY DO NOT SHOW THESE SAME | | | FIXTURES. IN FACT IN THE SOUTH OUTSIDE CORRIDORSHOWN | | | ON THE PHOTO-METRICS SHOWS A EM-2 FIXTURE. THIS | | | FIXTURES HAS A LISTED 2000 LUMENS ON PHOTO-METRIC | | | SHEETS YET THE FIXTURES WHICH ARE ACTUALLY SHOWN ON | | | PLANS ARE 1400 LUMEN FIXTURES. HOW IS THIS POSSIBLE? | | | | | | FOR EXAMPLE: | | | PLEASE SEE PLATFORM EGRESS AREA ON THE EAST SIDE OF | | | BUILDING WHICH BASED ON THE PHOTO-METRICS SHOWN ON | | | SHEET E-16.0 IS BLANK. | | | | | | FOR EXAMPLE: | | | PLEASE SEE AREAS SUCH AS ROOM 334 WHICH DOES NOT MATCH | | | WITH ELECTRICAL PLANS. | | | | | | FOR EXAMPLE: | | | PLEASE SEE LIBRARY WHICH SHOWS EMERGENCY FIXTURES ON | | | ELECTRICAL BUT NOT THE SAME AS PHOTO-METRICS. | | | | | | FOR EXAMPLE: | | | PLEASE SEE SEVERAL OF THE FIXTURE TYPES ON PHOTO-METRIC | | | PLANS DO NOT CORRELATE WITH THE LIGHTING WHICH IS SHOWN | | | ONE ELECTRICAL PLANS OR ELECTRICAL FIXTURE LEGEND. | | | PLEASE ALSO SEE FIXTURE HR AS LISTED ON PHOTO-METRICS | | | YET THIS FIXTURE IS NOT LISTED ON ELECTRICAL PLANS | | | FIXTURE LEGEND OR SHOWN ON PLANS. | | | PLEASE SEE SITE PLANS WHICH SHOW COMPLETELY DIFFERENT | | | FIXTURES THAN ON FIXTURE LEGEND FOR THE SAME FIXTURES. | | | | | | PLEASE BE SURE TO COORDINATE ALL FIXTURES ON SITE PLAN | | | AS LISTED, ELECTRICAL PLANS AND PHOTO-METRICS. | | | | | | ** AS SOME AREAS ARE NOT COMPLETE, NOT SAME FIXTURES, | | | SAME WATTAGE, LEVELS ETC COMPLIANCE HAS NOT BEEN | | | SHOWN. | | | | | | 6) NOTE: PLEASE SEE CIRCUITS ON E-4.0 WHICH SHOWS FRONT | | | DOOR J-BOXES WITH P1-22,24 AND 26, YET THE PANEL | | | SCHEDULE FOR P1 SHOWS OTHER LOCATIONS AND CIRCUITS | | | BEING SERVED. | | | | | | 7) NOTE: THE RISER NOW SHOWS TWO NEW MAINS INSTEAD OF | | | THE PREVIOUS MLO MAIN DISTRIBUTION BOARD. PLEASE BE | | | SURE TO SHOW A BOND FROM EACH MAIN ON RISER TO EACH | | | GROUNDING ELECTRODE AS SHOWN. 250.58 | | | | | | 8) NOTE: AS THE RISER HAS NOW BEEN REVISED TO SHOW TO | | | MAINS INSIDE BUILDING. PLEASE SEE THE SITE ELECTRICAL | | | PLANS E-000 IS STILL SHOWING A MAIN OUTSIDE. | | | | | | 9) NOTE: PLEASE SEE REVISED LAYOUT OF LIGHTING ON E-6.0 | | | IS NOT THE SAME AS E-3.0. | | | PLEASE ALSO SEE THE ARCHITECTURAL PLANS WHICH ARE ALSO | | | REQUIRED TO SHOW MINIMUM LIGHTING FOR LIFE SAFETY CODE/ | | | NFPA-101 2003 DO NOT CORRELATE WITH THE ELECTRICAL | | | PLANS. | | | | | | FOR EXAMPLE: | | | IN FACT PLEASE SEE SHEET A-3.0 FOR EXAMPLE WHICH DOES | | | NOT SHOW ANY EMERGENCY EGRESS LIGHTS IN ROOM #100. THIS | | | ROOM ON THE ELECTRICAL PLANS HAS SEVERAL EMERGENCY | | | LIGHTS WHICH ARE SHOWN. | | | | | | FOR EXAMPLE: | | | PLEASE SEE ROOM #105 WHICH DOES NOT SHOW ANY EMERGENCY | | | LIGHT FIXTURES. | | | | | | FOR EXAMPLE: | | | PLEASE SEE THE OUTSIDE CORRIDORS, LIBRARY, ETC. THESE | | | ARE SOME EXAMPLES, BUT THERE ARE TOO NUMEROUS TO LIST. | | | | | | ** IT IS IMPORTANT TO KNOW THE LIGHTING REQUIRED TO BE | | | SHOWN BY THE ARCHITECT FOR LIFE SAFETY PLANS NEED TO | | | COORDINATE. THESE CORRECTIONS ARE REQUIRED WHETHER OR | | | NOT COMMENT IS MADE BY ANY OTHER TRADE OR REVIEWER. | | | PLEASE ALSO KNOW EVEN IF ANY OF THESE SHEETS CONTAIN | | | STAMPS FROM OTHER TRADES, THEY NEED TO BE REVISED AND | | | CORRECTED. | | | | | | 10) NOTE: PLEASE BE SURE TO SUBMIT THREE COMPLETE SETS, | | | SIGNED DATED AND SEALED BY THE DESIGNERS OF RECORD AS | | | REQUIRED BY FAC 61G15-23.002. IT HAS NO BEARING ON | | | WHETHER OR NOT THE SET IS THE PLANS WHICH REMAIN ON | | | FILE. THE FLORIDA ADMINISTRATIVE CODE SECTION GIVEN | | | REQUIRES ALL SETS AND DOCUMENTS DONE BY ANY LICENSED | | | PROFESSIONAL ENGINEER TO CONTAIN AN ORIGINAL SIGNATURE | | | DATE AND RAISED SEAL. | | | PLEASE SEE SHEET(S) WHICH ARE IN FACT PHOTO-COPIES OF | | | SIGNED AND SEALED PLANS WHICH ARE IN ONE OF THESE SETS | | | SUBMITTED. | | | PLEASE BE SURE TO GO THROUGH ALL SHEETS, PLANS AND | | | DOCUMENTS. | | | | | | 11) NOTE: PLEASE TAKE A LOOK AT THE SIZE AND SPECS FOR | | | THE NEW UPS FOR EMERGENCY LIGHT FIXTURES WHICH IS BEING | | | SHOWN TO BE INSTALLED FLASH INSIDE THE CORRIDOR WALL. | | | PLEASE BE SURE THIS CAN BE INSTALLED INSIDE THE WALL AS | | | SHOWN WITH TEMPERATURE AND HEAT CONSIDERATIONS PER | | | LISTING. | | | PLEASE ALSO SEE THE DIMENSIONS APPEAR TO BE LARGER THAN | | | THE AREA IN WHICH IS SHOWN ON PLANS. | | | THIS IS NOT SOMETHING THAT WANTS TO BE FOUND OUT AT A | | | LATER DATE CAUSING WALLS ETC TO BE MOVED OR | | | RE-DESIGNED. IF THIS IS VERIFIED THEN WILL BE AN | | | ON-SITE ITEM. THIS IS ONLY NOTED FOR LISTING, | | | INSTALLATION ETC AT THIS TIME. | | | 110.3,90.7. | | | | | | 12) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO AIC | | | RATING HAS PANELS AND RISER NOW REVISED SHOWING RATINGS | | | FOR PANELS AND BRANCH BREAKERS. ALL BRANCH BREAKERS | | | SHOWN WITH 42K RATING. | | | NO RESPONSE NEEDED. | | | | | | 13) NOTE: PLEASE SEE THE PREVIOUS REVIEW GAVE NOTICE TO | | | FLORIDA STATUTES 553.80(2)(B) WITH RESPECT TO REPEAT | | | COMMENTS FOR CODE COMPLIANCE. THE SECOND REVIEW THE | | | SECTION OF THE STATUTE WAS GIVEN AS THERE WERE CODE | | | SECTIONS REPEATED FOR THE SAME CODE COMPLIANCE REQUIRED | | | ON PLANS AND SUPPORTING DOCUMENTS. THERE WERE ONCE | | | AGAIN REPEATED CODE SECTIONS NOT IN COMPLIANCE. PLEASE | | | KNOW AS REQUIRED UNDER THE ABOVE STATUE AS GIVEN THE | | | FEE OF FOUR TIMES THE PERMIT FEE ATTRIBUTED TO PLAN | | | REVIEW HAS BEEN ASSESSED. THIS FEE IS ASSESSED UNDER A | | | STATUTORY REQUIREMENT AND IS NOT A REQUIRED FEE ON A | | | LOCAL LEVEL. THE FLORIDA STATUTES ALSO REQUIRES THIS | | | FEE TO BE PAID BEFORE PLANS ARE TO BE RESUBMITTED.THE | | | FEE WHICH IS NOW ASSESSED AND REQUIRED TO BE PAID IS | | | $46,097.90. | | | ** PLEASE KNOW ONE SET OF ELECTRICAL PLANS AND | | | SUPPORTING ENERGY CALCULATIONS WILL BE RETAINED BY THIS | | | OFFICE AND PLACED WITH PREVIOUS RETAINED PLANS. | | | ** IT IS RECOMMENDED THAT A MEETING BE HELD TO GO OVER | | | COMMENTS BEFORE PLANS ARE RESUBMITTED FOR THE FOURTH | | | REVIEW. | | | | | | | | | ** IMPORTANT** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF | | | THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT | | | HESITATE IN CONTACTING THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2008-02-16 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-02-16 |
Time |
12:32 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-02-14 |
Time |
19:24 |
Sent To |
|
|
| Notes |
| 2008-02-16 12:32:53 | *** DENIED 2ND REVIEW *** | | | | | | ** PLEASE SEE THERE ARE SEVERAL ITEMS FROM PREVIOUS | | | REVIEW WHICH ARE STILL IN NEED OF ADDRESSING. AS | | | MENTIONED ON PREVIOUS REVIEW AS THERE WAS ALSO | | | INFORMATION NOT YET SUBMITTED THERE MAY ALSO BE NEW | | | COMMENTS. | | | ** PLEASE SEE NOTES BELOW AS THERE IS INFORMATION NOT | | | YET SUBMITTED WHICH MAY GENERATE NEW COMMENTS ON THE | | | FOLLOWING REVIEW WHICH CAN NOT POSSIBLY BE MADE AT THIS | | | TIME. | | | | | | 1) NOTE: ** IMPORTANT** WHEN CALLING THIS | | | OFFICE/REVIEWER AND LEAVING VOICEMAIL PLEASE BE SURE TO | | | LEAVE A RETURN PHONE NUMBER. | | | | | | 2) NOTE: ** IMPORTANT** PLEASE SEE PREVIOUS REVIEW NOTE | | | AT THE END OF REVIEW WHICH WAS ** AND LABELED AS | | | IMPORTANT** WHICH SPECIFICALLY REQUESTED FOR ALL | | | OLD/VOIDED SHEETS TO BE COMPLETELY REMOVED FROM SETS. | | | THIS WOULD CREATE SETS WHICH DO NOT CONTAIN ANY OF THE | | | OLD SHEETS AND ONLY NEW SHEETS FOR REVIEW. ANY OLD AND | | | VOIDED SHEETS WOULD BE SUBMITTED ALONG WITH NEW SETS | | | SEPARATELY AND ONLY NEED ONE SET OF THE OLD SHEETS. | | | PLANS SUBMITTED CONTAIN ALL THE OLD AND ALL THE NEW | | | SHEETS CREATING SETS WHICH ARE TWICE AS LARGE AS NEED | | | BE. | | | ** THIS WILL HELP THE REVIEW PROCESS AND EXPEDITE THE | | | REVIEWS. THANKING YOU IN ADVANCE FOR ATTENTION TO | | | THIS. | | | | | | 3) NOTE:** THIS COMMENT WITH RESPECT TO LIFE SAFETY | | | EGRESS LIGHTING WILL BE BROKEN UP INTO SUB-SECTIONS. | | | PLEASE ALSO KNOW THAT SOME EXAMPLES WILL BE GIVEN BUT | | | ARE NO ALL LOCATIONS IN QUESTION. | | | PLEASE SEE NOTE #3 FROM PREVIOUS REVIEW WITH RESPECT TO | | | MINIMUM LIGHTING LEVELS FOR ALL DESIGNATED EGRESS | | | PATHS. | | | PLEASE SEE THERE ARE SEVERAL AREAS ON PLANS WHERE NO | | | EMERGENCY BATTERY BACK UP LIGHT FIXTURES IS SHOWN. THE | | | PREVIOUS REVIEW GAVE SOME AREAS OF EXAMPLES AND MANY | | | LIGHTING FIXTURE TYPES IN SOME OF THOSE AREAS WERE | | | ADJUSTED HOWEVER MANY AREAS WERE STILL NOT CHANGE OR | | | THE FIXTURES WERE NOT ADJUSTED. | | | | | | A) PLEASE SEE THE PREVIOUS REVIEW MENTIONED TO PROVIDE | | | PHOTO-METRICS FOR EGRESS PATHS HOWEVER NONE WERE | | | SUBMITTED. PLEASE SEE THE AREAS OF STAIRS REQUIRE A | | | LEVEL OF 10FT CANDLES UNDER NORMAL AND IS PERMITTED | | | DOWN TO 1FT CANDLE UNDER EMERGENCY CONDITIONS. NFPA-101 | | | 7.8.1.3, 7.9.2.2. | | | THERE ARE NO SUBMITTED PHOTO-METRICS LEVELS FOR ANY | | | EGRESS PATHS. PLEASE SUBMIT. PLANS NOW INCLUDE A NEW | | | BATTERY BACK UNIT WAS NOW ADDED TO RISER FOR MOST OF | | | THE CIRCUITS BUT NOT ALL. ONLY CIRCUITS 1L3, 23, 29, | | | AND 33 ARE SHOWN YET THERE ARE OTHER CIRCUITS FOR | | | OUTSIDE EGRESS LIGHTS WHICH ARE NOT SHOWN. PLEASE | | | SUBMIT THE NEW SPECS/CUT SHEETS ON THIS PROPOSED UNIT. | | | PLEASE INDICATE TIME IN EMERGENCY UNDER LOAD OF | | | CIRCUITS. | | | FAC 61G15-33.004. | | | | | | B) PLEASE SEE SOME EGRESS PATH HAD ALL LIGHT FIXTURES | | | CHANGED TO BATTERY BACK UP FIXTURES. THIS WAS NOT THE | | | REQUEST HOWEVER THIS IS NOT A CODE ISSUE. PLEASE SEE | | | THERE ARE SEVERAL OTHER AREAS IN WHICH NO EMERGENCY | | | LIGHTING FIXTURES WERE LOCATED. | | | PLEASE SEE SOCIAL HALL, BASED ON THE FIXTURE LEGEND | | | NONE OF THESE FIXTURES IN AREAS OF EGRESS ARE BATTERY | | | BACK UP. | | | PLEASE SEE SANCTUARY, BASED ON THE FIXTURE LEGEND NONE | | | OF THESE FIXTURES IN EGRESS AREAS ARE BATTERY BACK UP. | | | PLEASE SEE LOBBY AREAS, BASED ON FIXTURE LEGEND NONE OF | | | THESE FIXTURES IN EGRESS AREAS ARE BATTERY BACK UP. | | | PLEASE SEE CHAPEL, NONE OF THESE FIXTURES AREA BATTERY | | | BACK UP BASED ON FIXTURE LEGEND AND THE OCCUPANCY LOAD | | | OF THE ROOM CERTAINLY REQUIRES THIS. | | | PLEASE SEE SOME HANDRAILS WHICH DO NOT SHOW ANY LIGHTS | | | (NE CORNER) | | | PLEASE SEE CHAPEL WHICH BASED ON LIFE SAFETY PLANS | | | INDICATES EGRESS INTO COURTYARD AREA WHICH COULD NOT | | | LOCATE BACK UP LIGHTING TO OUTDOOR EGRESS HALLWAYS. | | | ONCE THE PHOTO-METRICS ARE SUBMITTED THE LIGHTING | | | LEVELS IN THAT ARE MAY BE SUFFICIENT WITH THE BATTERY | | | BACK UP OF THE *A* FIXTURES WHICH ARE ALL SHOWN AS | | | BATTERY BACK UP. | | | PLEASE SEE LIBRARY, NONE OF THESE FIXTURES BASED ON THE | | | FIXTURE LEGEND INDICATES ANY OF THESE AS BATTERY BACK | | | UP. BASED ON OCCUPANCY AND LOAD OF ROOM, THIS IS | | | REQUIRED. | | | PLEASE SEE EGRESS PATHS FROM BUILDING TO STAIRS, NO | | | FIXTURES COULD BE LOCATED FOR ILLUMINATION OF PLATFORM | | | AREAS. | | | ** PLEASE SEE THERE ARE OTHER AREAS ON PLANS SHOW WHERE | | | EVERY SINGLE FIXTURE WAS CHANGED TO BATTERY BACK UP. | | | THIS OFFICE ONLY REQUESTED TO MEET THE LIFE SAFETY | | | CODE. | | | WAS THE INTENT ON PLANS FOR ALL *B* FIXTURES WHICH ARE | | | IN CLASSROOMS, OFFICES, STORAGE ROOMS, CLOSETS ETC TO | | | ALL BE BATTERY BACK UP? | | | WAS IT INTENDED FOR ALL *A* FIXTURES TO BE BATTERY | | | BACK? SOME LOCATIONS ARE CLEAR AS TO WHY THESE WOULD BE | | | CHANGED HOWEVER IS IT NOT UNDERSTOOD WHY MOST AREAS | | | WHICH REQUIRE BATTERY BACK UP FIXTURES DO NOT CONTAIN | | | ANY AND THEN OTHER AREAS WHICH DO NOT REQUIRE ANY | | | CONTAIN ALL FIXTURES AS BATTERY BACK UP. SOME OF THE | | | *A* FIXTURES WERE CHANGED TO *AE* FIXTURES. | | | ** THERE IS NOTHING IN THE CODE WHICH PROHIBITS | | | DESIGNER TO DESIGN ALL FIXTURES IN A BUILDING BEING | | | BATTERY BACK UP HOWEVER THE REQUIRED EGRESS PATHS MUST | | | CONTAIN THE MINIMUM TO MEET THE 1FT CANDLE LEVEL. | | | | | | C) PLEASE SEE COMMENTS BELOW IN NOTE #5E WITH RESPECT | | | TO OCCUPANCY SENSORS ON EGRESS LIGHTING. FBCAND LS | | | CODE. | | | | | | AS THERE ARE STILL MANY QUESTIONS AND SOME ITEMS ARE | | | MISSING CAN NOT REVIEW ALL FOR CODE COMPLIANCE AT THIS | | | TIME. REVIEW CAN ONLY BE BASED ON PLANS SUBMITTED. | | | | | | 4) NOTE: PLEASE SEE THERE ARE SEVERAL SYMBOLS ON PLANS | | | WHICH ARE NOT IN LEGEND FOR SYMBOLS, ARE NOT IN FIXTURE | | | LEGEND AND DO NOT CONTAIN ANY CIRCUITING ETC. IT IS | | | UNCLEAR WHAT MANY OF THESE ARE. | | | PLEASE SEE SANCTUARY AREA WHICH CONTAINS A D IN A | | | SQUARE BOX WHICH INDICATE 1INCH CONDUIT TO ER? PLEASE | | | SEE LOBBY AREA WHICH ANOTHER CIRCLE SYMBOL WITH SQUARE | | | BOX WHICH INDICATES TO ER, TO WPD? | | | PLEASE SEE SOCIAL AREA WHICH CONTAINS THE SAME WHICH | | | STATES TO ER, WPB? | | | PLEASE BE SURE ALL SYMBOLS ON PLANS ARE ON LEGEND FOR | | | WHAT THESE ARE. | | | PLEASE SEE LIGHTING FIXTURES ON THE ELECTRICAL PLANS | | | WHICH ARE NOT THE SAME AS THE FIXTURES SHOWN ON | | | ARCHITECTURAL PLANS.(EXAMPLE: EXTERIOR) PLEASE KNOW | | | AS THERE ARE OTHER COMMENTS ON ELECTRICAL PLANS AND | | | WILL HAVE ADJUSTMENTS ON FIXTURES ETC PLEASE BE SURE | | | THE INFORMATION IS FORWARDED TO THE ARCHITECT FOR | | | COORDINATION. | | | FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION. | | | | | | 5) NOTE: PLEASE SEE PREVIOUS NOTE WITH RESPECT TO FBC | | | AND CHAPTER 13. | | | PLEASE SEE THE COMMENTS BELOW WILL BE IN SECTIONS AS | | | PREVIOUS REVIEW AND THE INPUT DATA REPORT WILL BE NOTED | | | AS IDR. | | | | | | A) PLEASE SEE THAT NOT ENOUGH DETAILS WERE SUBMITTED | | | FOR MAIN AREAS FOR LIGHTING CONTROLS. NO DETAILS ON THE | | | DEVICES, POWER PACKS, SCHEDULING OF PROPOSED, ZONES | | | ETC. PLANS SHOW SOME NEW OCCUPANCY SENSOR TYPE DEVICES | | | YET NOT ENOUGH INFORMATION ON THESE WAS PROVIDED. HOW | | | WILL ALL AREAS BE CONTROLLED? | | | FOR EXAMPLE: LOBBY AREAS, OVER RIDES, OCCUPANCY | | | SENSORS, ACCENT LIGHTING, DISPLAY LIGHTING ETC. PLEASE | | | SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. | | | | | | B) PLEASE SEE THAT NOT ENOUGH INFORMATION IS PROVIDED | | | FOR EXTERIOR LIGHTING CONTROLS. PLANS SHOW A LIGHTING | | | CONTACTOR AND SOME LOCATIONS NOTE THERE WILL BE A | | | ASTRONOMICAL TIME CLOCK HOWEVER PLEASE SEE THE REQUIRED | | | BATTERY BACK UP OF 10HRS IF PROPOSING A TC COULD NOT BE | | | LOCATED. | | | PLEASE SEE 13-415.1.ABC.1.4 ALSO 13-415.1.ABC.2 | | | | | | C) PLEASE SEE THE INFORMATION ON THE IDR DOES NOT | | | CORRELATE WITH PLANS. PLEASE SEE THE EXTERIOR LIGHTING | | | FOR EXAMPLE WHICH STATES ALL FIXTURES AS ONLY BEING 1. | | | THIS IS NOT POSSIBLE WHEN THE ARE DOZENS OF FIXTURES ON | | | PLANS FOR EACH TYPE. THE IDR REQUIRES EACH FIXTURE, | | | EACH TYPE, AND METHOD OF CONTROL TO COORDINATE WITH | | | PLANS. AT THIS TIME AS FIXTURES ARE ONLY INDICATE AS 1 | | | (ONE) AT EACH LOCATION ON THE IDR,THE SPECIFIC | | | FIXTURES, COUNTS ETC CAN NOT BE DETERMINED. | | | | | | D) PLEASE SEE THE IDR FOR ALL INTERIOR LIGHTS DOES NOT | | | COORDINATE. PLEASE SEE THAT ALL LIGHTING IS REQUIRED TO | | | BE FIGURED PER 13-415.2.ABC.1.1 AND .1.2 | | | PLEASE SEE 13-415.2, 13-400 | | | PLEASE KNOW AS THERE ARE FIXTURES ON THE IDR WHICH ARE | | | NOT ON FIXTURE LEGEND AND FIXTURES ON THE FIXTURE | | | LEGEND WHICH ARE NOT ON THE IDR. | | | FOR EXAMPLE: | | | 500W COMPACT FLUORESCENT FIXTURES ON IDR, NOT ON | | | LEGEND. | | | 250W ON FIXTURE LEGEND NOT ON IDR. | | | PLEASE SEE FIXTURE COUNTS ON PLANS COMPARED TO FIXTURES | | | IN AREAS ON THE IDR. | | | ** PLEASE KNOW THERE ARE SEVERAL MORE WHICH DO NOT | | | CORRELATE AND ONLY A COUPLE OF EXAMPLES ARE GIVEN. | | | | | | E) PLEASE SEE CORRIDOR 335 WHICH INDICATES ONE WALL | | | DEVICE AT EACH END OF THIS LONG EGRESS PATH. PLEASE SEE | | | FBC 1006.1.2 AND NFPA-101 7.8.1.2.2 WITH RESPECT TO | | | AUTOMATED DEVICES IN EGRESS PATHS. THIS IS PERMITTED BY | | | BOTH CODES HOWEVER THE COVERAGE OF SUCH UNITS SHALL BE | | | SUFFICIENT FOR ENTIRE LENGTH, THE DEVICES ARE REQUIRED | | | TO BE 15MINS OF TIME AND PLANS SHOW 10MINS. | | | PLEASE ALSO SEE THE DEVICES SHALL ALSO BE FAIL-SAFE ON | | | DEVICES. THIS WOULD ALSO BE FOR OTHER AREAS WHERE | | | OCCUPANCY SENSORS ARE BEING USED FOR EGRESS LIGHTING. | | | | | | F) PLEASE INCLUDE NOTES ON PLANS ARE REQUIRED PER | | | 13-413.1.ABC.2, .2.1 AND .2.2 | | | | | | G) PLEASE BE SURE THE OWNER AGENT HAS FILLED OUT | | | SECTION ON CERTIFICATION SHEET AND SIGNED WHEN NEW | | | CALCULATIONS ARE SUBMITTED. | | | 13-103.1.1.1 | | | | | | 6) NOTE: PLEASE BE SURE ALL EMERGENCY AND EXIT LIGHTS | | | ARE CIRCUITED PER 700.12F. AS MOST FIXTURES IN MANY | | | AREAS ARE ALL BATTERY BACK UP THIS IS OK, HOWEVER THIS | | | NOTE REMAINS BASE DON THE FACT THERE ARE OTHER AREAS | | | WHERE THERE ARE NO BATTERY BACK UP FIXTURES. | | | | | | 7) NOTE: PLEASE SEE FAC 61G15-33.004 WHICH REQUIRES ALL | | | LIGHTING AND ILLUMINATION DESIGN TO BE PART OF THE | | | RESPONSIBILITY OF THE DESIGN PROFESSIONAL. IF THERE ARE | | | OTHER SHEETS WHICH WILL BE PART OF THE LIGHTING BEING | | | SUBMITTED FOR SCOPE OF WORK REQUIRED BY A DESIGN | | | PROFESSIONAL PLEASE BE SURE ALL SHEETS CONTAINS THE | | | INFORMATION FROM THAT DESIGN PROFESSIONAL AND ARE | | | SIGNED, DATED AND SEALED ACCORDINGLY. | | | PLEASE SEE LIGHTING PLANS SUBMITTED BY LD INC. | | | THE PREVIOUS REVIEW REQUESTED PHOTO-METRICS TO BE | | | SUBMITTED FOR ALL EXTERIOR LIGHTING AREAS. HOWEVER | | | PLEASE SEE PLANS WHICH SHOWS AREAS WITH 0.0 (NO) LEVELS | | | OF LIGHTING. HOW IS THIS POSSIBLE WHEN THERE ARE DOZENS | | | OF EXTERIOR LIGHTS ON PLANS? | | | PLEASE COORDINATE ALL. | | | FBC 106.1.2, 106.3.5.1.2 FOR COORDINATION AND | | | ADDITIONAL INFORMATION. | | | | | | 8) NOTE: PLEASE SEE THE PREVIOUS REVIEW MENTIONED THE | | | CONCERN OF THE MAIN ELECTRICAL EQUIPMENT AND OTHER | | | ELECTRICAL PANELS IN A REQUIRED EGRESS HALLWAY. REVIEW | | | COMMENT MENTIONED TO SEE POSSIBLE BUILDING AND FIRE | | | REVIEW COMMENTS. | | | THE RESPONSE MENTIONS NO CODES WERE LOCATED WHICH | | | PREVENTED THIS. AT THIS TIME INFORMATION AND SCENARIOS | | | WILL BE TURNED OVER TO THE BUILDING REVIEWER AND | | | BUILDING OFFICIAL FOR CLARIFICATION ON WHETHER OR NOT | | | THIS IS PERMITTED AND MOST OF ALL IF THIS IS SAFE FOR | | | THE OCCUPANTS IN AN EMERGENCY SITUATION. THIS REVIEWER | | | CAN NOT SEE HOW THIS IS NOT A HAZARD AND NEEDS | | | DETERMINATION ON THIS SCENARIO. | | | THE 1600AMP MDP PROTRUDES INTO A REQUIRED EGRESS HALL | | | WAY. | | | FBC 1001.3, 1001.4 | | | | | | 9) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #4 WHICH | | | MENTIONED TO CLARIFY THE MDP1 AS SHOWN ON RISER AND | | | SCHEDULE. | | | PLEASE SEE THE RISER STILL CONTAINS NOTE WHICH STATES | | | *MAIN DISCONNECT PANEL*. THIS PANEL BY THE SCHEDULE IS | | | SHOWN AS A MAIN LUG ONLY SWITCHBOARD. | | | PLEASE SEE THE CIRCUITING ON THIS PANEL WAS ALSO NOT | | | UPDATED. FOR EXAMPLE: AS NOTED PREVIOUSLY: EXAMPLE; 1) | | | PANEL 1L1 | | | 3) | | | 5) | | | 7) PANEL 1L2 | | | 9) | | | 11) | | | THIS IS AN EXAMPLE ONLY AS THIS IS STILL THREE PHASE | | | EQUIPMENT. | | | 408.4, FBC 106.3.5.1.2, 106.1.2 FOR ADDITIONAL | | | INFORMATION AND COORDINATION. | | | | | | 10) NOTE: PLEASE COORDINATE RISER AND PANELS. PLEASE | | | SEE KITCHEN PANELS 1K1 AND 1K2 WHICH ARE BOTH SHOWN AS | | | 400AMP ON RISER AND BEING FED FROM THE MAIN | | | DISTRIBUTION BOARD WITH A 400AMP BREAKER. YET PLEASE | | | SEE EACH OF THESE PANELS ARE SHOWN AS 200AMP MLO ON | | | THEIR SCHEDULES WITH ONLY A SINGLE FEED OF 3/0 | | | CONDUCTORS. | | | PLEASE COORDINATE AND ADJUST. | | | PLEASE ALSO SEE THE POWER PLANS DO NOT SHOW THE | | | LOCATION OF THESE PANELS. SHEET E-5.0 MENTIONS TO SEE | | | SHEET E-11.0 FOR THE ENLARGED KITCHEN PLANS. IT WAS | | | BEING ASSUMED THESE PANEL WERE IN THE KITCHEN HOWEVER | | | COULD NOT LOCATE THESE ANYWHERE ON PLANS. | | | SHEET E-6.0 ALSO DOES NOT SHOW THESE K PANELS. 240.24, | | | 110.26, 408.17, 240.4, 310.16, ETC | | | FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION AND | | | COORDINATION. | | | | | | | | | 11) NOTE: PLEASE SEE PREVIOUS NOTE WITH RESPECT TO AIC | | | RATINGS FOR ALL PANELS, BREAKER AND SERVICE EQUIPMENT. | | | THE MAIN SWITCH BOARD DOES NOW INDICATE THE BRANCH | | | CIRCUIT RATINGS AS 65K RATED AND MAIN AT 100K. HOWEVER | | | PLEASE SEE OTHER PANELS WHICH SHOW ONE AIC RATING FOR | | | BOARD AND BREAKERS STILL. | | | PLEASE VERIFY FOR EXAMPLE ALL PANELS SHOWING A 65K | | | RATING FOR PANELS AND BRANCH BREAKERS THIS IS WITH THE | | | EXCEPTION OF PANEL 1K1 WHICH SHOWS A 10K RATING. 110.9, | | | 110.3 | | | FBC106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION AND | | | COORDINATION. | | | | | | 12) NOTE: PLEASE KNOW THE SIGNED AND SEALED STRUCTURAL | | | WIND LOAD CALCULATIONS SHOWING THE EPA (EFFECTIVE | | | PROJECTED AREAS) OF LIGHT FIXTURES ON POLES WILL BE | | | REVIEWED BY THE BUILDING REVIEWER. | | | | | | 13) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO | | | REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A | | | NOTICE GIVEN AT THIS TIME. | | | PLEASE BE SURE TO GO OVER ALL COMMENTS AND ONCE AGAIN | | | PLEASE CALL. PLEASE LEAVE PHONE NUMBER WHEN LEAVING A | | | MESSAGE. | | | ** PLEASE ALSO KNOW THAT AT THIS TIME ONE SET OF | | | ELECTRICAL PLANS AND ENERGY CALCULATIONS ARE BEING | | | RETAINED BY THIS OFFICE. | | | | | | ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY | | | QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR | | | NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN | | | CONTACTING THIS REVIEWER. | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | | DELAYS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | | DELAYS. | | | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | | | 2008-02-16 07:59:23 | 2008-02-16 07:059:23 | | | | | | IN REVIEW | | 2008-02-15 19:34:00 | | | | 2008-02-15 15:35:24 | | | REVIEW COMMENCED | | | | | | 2008-02-15 19:34:00 | | | REVIEW STOPPED. WILL CONTINUE ON 2/16, NOTES WILL | | | FOLLOW AND PLANS WILL BE IN A *FAILED STATUS* | | | | | | | | 2008-02-14 19:24:52 | 2008-02-14 19:24:52 | | | | | | IN ELEC FOR REVIEW |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-10-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-10-07 |
Time |
12:23 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-10-06 |
Time |
18:46 |
Sent To |
|
|
| Notes |
| 2007-10-07 13:20:24 | NOTE ADDED: | | | | | | PLEASE KNOW THAT ALL LOW VOLTAGE SYSTEMS ARE REQUIRED | | | TO BE UNDER SEPARATE PERMITS. IF THE LV IS SHOWN ON | | | PLANS, THEN THE SUB CONTRACTOR WOULD ONLY NEED TO | | | REFERENCE PLANS FOR TURN AROUND PERMIT. | | | FEES ARE SEPARATE FOR VALUE OF THE SCOEP OF WORK AS | | | SHWON. | | 2007-10-07 12:24:26 | 2007-10-07 12:24:26 | | | | | | | | | *** DENIED *** | | | | | | 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH | | | ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS | | | UNDER THE NEW CODES ADOPTED BY THE STATE. | | | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO | | | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. | | | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY | | | AFFECT DESIGNS FOR ALL TRADES. | | | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS | | | REVIEWER AT A MINIMUM. | | | 2004 FBC W/ 2006 REVISIONS | | | 2005 NFPA-70 | | | 2002 NFPA-72 | | | 2003 NFPA-101 | | | | | | ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED | | | FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS | | | NOT MADE BY OTHER TRADE(S). | | | | | | 2) NOTE: PLEASE SEE THAT COMPLIANCE WITH NFPA-101 7.8 | | | AND 7.9 NEEDS TO BE MET. | | | PLEASE SEE THERE ARE SEVERAL AREAS IN WHICH BATTERY | | | BACK UP TYPE OF LIGHTING FIXTURES ARE MISSING. PLEASE | | | KNOW THAT LIGHTING IS REQUIRED FOR ALL EGRESS PATHS | | | INCLUDING THAT TO THE EXIT DISCHARGE AREAS/PATHS. FOR | | | EXAMPLE: PLEASE SEE THE STAIR AREAS OUTSIDE WHICH ARE | | | PART OF THE EXIT DISCHARGE WHICH DO NOT CONTAIN BATTERY | | | BACK UP LIGHTING. | | | PLEASE SEE THE HALL WHICH DOES NOT INDICATE ANY | | | EMERGENCY LIGHTING FIXTURES. | | | PLEASE SEE COURTYARD AREAS AS THESE ARE EXIT PATHS | | | HOWEVER AS THEY ARE NOT CONSIDERED THE PUBLIC RIGHT OF | | | WAY OR SAFE DISTANCE FROM THE BUILDING, EMERGENCY | | | LIGHTING FIXTURES WILL BE REQUIRED. | | | PLEASE SEE ANY TOILETS WHICH ARE NOT A SINGLE POINT OF | | | USE WILL ALSO REQUIRE A BATTERY BACK UP FIXTURES OF | | | SOME TYPE. | | | PLEASE SEE THERE ARE OTHER AREAS ALSO HOWEVER NOT ALL | | | ARE LISTED. | | | PLEASE SUBMIT AND PROVIDE LIGHTING PHOTO-METRICS FOR | | | ALL EGRESS PATHS TO THE PUBLIC RIGHT OF WAY. PLEASE SEE | | | THE LEVELS UNDER NORMAL FOR STAIRS SHALL MEET THE | | | MINIMUM OF 10FT CANDLES PER 7.8.1.3 AND IS PERMITTED TO | | | GO DOWN TO 1FT CANDLE UNDER EMERGENCY CONDITIONS. FBC | | | 106.1.2, FAC 61G15-33.004 | | | NFPA-101 7.8, 7.9 | | | | | | 3) NOTE: PLEASE SEE THERE ARE SOME LOCATIONS IN WHICH | | | EXIT SIGNS APPEAR TO BE MISSING. PLEASE SEE CHAPEL AND | | | LIBRARY FOR EXAMPLE. IF THE OCCUPANT LOAD EXCEEDS THAT | | | OF THE FBC FOR THESE AREAS AN EXIT SIGN WILL BE | | | REQUIRED. | | | PLEASE SEE BUILDING AND FIRE MARSHAL REVIEW COMMENTS | | | FOR THESE POSSIBLE LOCATIONS. | | | PLEASE SEE FBC 1006.3.8.2, .3, LS-101 7.10.1.6 AND | | | 12.4.7.7.2 AS FLOOR PROXIMITY EXIT LIGHTING IS REQUIRED | | | IN ASSEMBLY AREAS. | | | PLEASE PROVIDE LOCATIONS ALONG WITH HEIGHT/LOCATION | | | REQUIREMENTS. | | | | | | 4) NOTE: PLEASE SEE THE MDP/ MAIN AS SHOWN INDICATES | | | MORE THAN 42 SPACES. PLEASE SEE 408.5 AS THIS IS NOT | | | PERMITTED IN THIS ENCLOSURE AS SHOWN. | | | PLEASE LABEL ALL WITH COORDINATION OF CIRCUITING/PHASES | | | ON PANELS. | | | FOR EXAMPLE: 1,3,5 WOULD BE 1L1, | | | | | | 5) NOTE: PLEASE CLARIFY AIC RATING AS STATED ON THE | | | PANEL-BOARD. THIS STATES 100K, WHICH IS OK, HOWEVER IS | | | THIS THE RATING FOR ALL BREAKERS IN THIS SAME | | | ENCLOSURE? | | | IF EACH IS RATED AT 100K, PLEASE FIRST VERIFY ALL | | | BREAKERS AS SHOWN ARE AVAILABLE AT THIS 100K RATING. | | | THERE IS NO CODE VIOLATION, HOWEVER THE 100K RATING FOR | | | ALL BREAKERS AS SHOWN IS HIGH AND IF SHOWN AS 100K | | | RATING FOR EACH, THEN THAT?S WHAT WILL BE REQUIRED TO | | | BE INSTALLED. | | | THIS IS ONLY A SUGGESTION TO VERIFY THIS. | | | | | | 6) NOTE: PLEASE SEE THE LOCATION OF THE MDP ON E-6.0 IS | | | NOT THE SAME AS E-000. | | | PLEASE CORRELATE AND SEE OTHER COMMENTS. | | | FBC 106.1.2. | | | NEC 110.26 ETC. | | | | | | 7) NOTE: PLEASE SEE THE LOCATIONS OF THE PANELS ALL | | | APPEAR TO BE IN A EGRESS HALLWAY? | | | PLEASE VERIFY THIS AS RATED EXIT PASSAGE WAYS MAY NOT | | | HAVE THESE ELECTRICAL PANELS AS SHOWN. | | | IF THIS IS NOT A EXIT/HALL WAY, THEN PLEASE ADJUST | | | IDENTIFICATION OF THIS AREA. | | | PLEASE SEE FBC CHAPTER 10, 1006.3.1, THIS WILL BE | | | REVIEWED BY BUILDING, FIRE MARSHAL REVIEW COMMENTS. | | | THIS IS BEING NOTED ON ELECTRICAL REVIEW AS THIS MAY | | | AFFECT ELECTRICAL PANELS AND LOCATIONS. | | | | | | 8) NOTE: PLEASE INDICATE MINIMUM WIND LOAD DESIGNS FOR | | | LIGHT POLES ON ELECTRICAL PLANS. | | | PLEASE SUBMIT WIND LOAD CALCULATIONS WHICH WILL BE | | | REVIEWED BY THE BUILDING REVIEWER. | | | PLEASE KNOW THAT ANY RE-LOCATED POLES AS SHOWN WILL BE | | | REQUIRED TO MEET CURRENT WIND LOADS. | | | FBC 106.1.2 | | | | | | 9) NOTE: PLEASE SUBMIT SITE LIGHTING PHOTO-METRICS FOR | | | VERIFICATION OF ZONING COMPLIANCE. | | | THERE ARE NO MINIMUMS FOR ELECTRICAL REVIEW HOWEVER | | | ZONING DOES HAVE REGULATIONS FOR MAXIMUM LIGHTING | | | LEVELS ACROSS PROPERTY LINES. | | | PLEASE SEE COMMENTS BELOW WITH RESPECT TO LIGHTING FOR | | | CHAPTER 13 OF THE FBC. | | | FBC 106.1.2 | | | | | | 10) NOTE: PLEASE SEE THAT COMPLIANCE WITH FBC CHAPTER | | | 13 IS NEEDED FOR ALL LIGHTING CONTROLS IN ALL AREAS. | | | | | | A) PLEASE PROVIDE INFORMATION/DESIGN/TIME SCHEDULING | | | ETC ON HOW LIGHTING IS BEING CONTROLLED IN COMMON | | | AREAS. | | | PLEASE BE SURE TO PROVIDE ZONES BASED ON MAXIMUM SQ FT | | | FOR CONTROLS. | | | PLEASE SEE THE OCCUPANCY DEVICES AS SHOWN IN MANY OF | | | THE ROOMS AND LOCATIONS NEED TO STATE THE MAXIMUM | | | TIMES. 13-415.1.ABC.1.1, .1.2 AND .1.3. | | | | | | B) PLEASE SEE THERE ARE SOME AREAS IN WHICH A OCCUPANCY | | | SWITCH IS LOCATED IN ANOTHER ROOM THAN THE ROOM IN | | | WHICH THE LIGHTING IS BEING CONTROLLED. | | | FOR EXAMPLE: PLEASE SEE THE LOCATION OF THE DEVICE FOR | | | FINANCIAL MANGERS OFFICE WHICH SEEMS TO CONTAIN A | | | DEVICE IN THE TOILET AREA (313). | | | PLEASE ALSO SEE THE SAME FM OFFICE 314 WHICH HAS A | | | DEVICE WHICH FEEDS LIGHTING IN THE ROOM TO THE EAST? | | | 13-415.1.ABC.1.1, .1.2 | | | | | | C) PLEASE PROVIDE MORE INFORMATION ON THE TYPES OF | | | DEVICES BEING INSTALLED. PLEASE SEE THE BATHROOM/TOILET | | | AREAS WHICH INDICATE A SINGLE WALL OCCUPANCY DEVICE. IF | | | THIS IS A MOTION DEVICE ONLY THEN COVERAGE NEEDED IS | | | NOT PROVIDED. | | | PLEASE CLARIFY THESE. 13-415.1.ABC.1.1 | | | | | | D) PLEASE SEE THAT NO LIGHTING CONTROLS COULD BE FOUND | | | FOR ACCENT/DISPLAY LIGHTING. 13-415.1.ABC.1.3 | | | | | | E) PLEASE SEE PLANS INDICATES A *S* IN A BOX WITH A TD | | | DESIGNATION NEXT TO THIS, HOWEVER THE DEVICE LEGEND ON | | | E-12.0 DOES NOT CONTAIN THIS DEVICE. | | | PLEASE PROVIDE INFORMATION. | | | 13-415.1.ABC.1.1 | | | | | | F) PLEASE PROVIDE DETAIL FOR EXTERIOR LIGHTING CONTROLS | | | PER 13-415.1.ABC.1.4, 13-415.1.ABC.2 | | | | | | G) PLEASE SEE THAT ALL SEPARATE SPACES PER | | | 13-415.1.ABC.1.2 ARE REQUIRED TO CONTAIN LIGHTING | | | CONTROL. EXAMPLE: TOILET 316, HALL, ETC | | | **PLEASE SEE LS 101 7.8.1.2.2 AND CHAPTER 10 OF THE FBC | | | AS AUTOMATED OCCUPANCY DEVICES ARE PERMITTED HOWEVER | | | THE SET UP/SCENARIO WILL NEED TO BE GONE OVER WITH THIS | | | OFFICE. | | | | | | | | | ** PLEASE KNOW AS THERE ARE MANY ITEMS WHICH HAVE NOT | | | YET BEEN PROVIDED FOR LIGHTING CONTROLS, IT IS NOT | | | POSSIBLE TO PROVIDE A COMPLETE REVIEW FOR CODE | | | COMPLIANCE. THERE VERY WELL MAY BE NEW COMMENTS ON THE | | | FOLLOWING REVIEW WHICH CAN NOT BE MADE AT THIS TIME. | | | PLEASE CALL TO GO OVER ANY OF THESE ITEMS. | | | | | | 11) NOTE: PLEASE SEE COMPLIANCE WITH FBC CHAPTER 13 FOR | | | ENERGY CALCULATIONS/LIGHTING PERFORMANCE CALCULATIONS | | | NEEDS TO BE MET. | | | PLEASE SEE THE FOLLOWING WHICH WILL HAVE REFERENCE TO | | | THE INPUT DATA REPORT AS IDR. | | | | | | A) PLEASE CORRELATE ALL LIGHTING WHICH IS ON PLANS AND | | | CONSUMES ENERGY WITH THAT OF THE IDR. | | | FOR EXAMPLE: | | | PLEASE SEE THE EXTERIOR LIGHTING WHICH INDICATES A | | | *PASSED* STATUS. PLEASE SEE THE IDR SHOWS ONLY *1-ONE* | | | FIXTURE AND THIS FIXTURE AS SHOWN CONTAINS NO POWER | | | USAGE. THIS IS NOT POSSIBLE WHEN THE PLANS INDICATE | | | OVER 100 FIXTURES WHICH HAVE NOT BEEN PLACED ON THE | | | IDR. | | | PLEASE BE SURE THE FIXTURE LEGEND COORDINATES WITH THE | | | LIGHTING IN THE IDR. | | | PLEASE ALSO SEE FOR EXAMPLE THE INTERIOR LIGHTING WHICH | | | NEEDS TO COORDINATE WITH PLANS. | | | PLEASE SEE THE AREAS DO NOT MATCH. | | | PLEASE SEE THE NUMBER OF FIXTURES ON EACH AND EACH | | | AREA/ROOM DESIGNATION DOES NOT CORRELATE. | | | PLEASE SEE SEVERAL WHICH ONLY INDICATES *ONE* FIXTURE | | | WHICH IS NOT POSSIBLE. | | | PLEASE SEE THE METHOD OF CONTROLS INDICATES *MANUAL | | | ON/OFF* WHICH IS ALSO NOT POSSIBLE WHEN LIGHTING | | | CONTROLS ARE AUTOMATED ETC. | | | | | | ** PLEASE BE SURE TO COORDINATE ALL FIXTURES ON PLANS | | | WITH THE IDR. | | | PLEASE SEPARATE TO ROOMS AND AREAS ON THE IDR. REVIEW | | | OF MANY ITEMS CAN NOT BE DONE. | | | | | | PLEASE BE SURE TO SEE 13-415.2.ABC.1.2 FOR TRACK | | | LIGHTING. | | | PLEASE SEE 13-415.2.ABC.1.3 FOR EXTERIOR ALLOWANCES | | | PLEASE SEE 13-415.1.A, 13-415.2 ETC. | | | | | | ** PLEASE SEE 2004 FBC CHAPTER 13 FOR ALL ELECTRICAL | | | LIGHTING CONTROLS AND CALCULATIONS REQUIRED. | | | | | | 12) NOTE: PLEASE CLARIFY THE GROUNDING ELECTRODE SYSTEM | | | AS NOTED. | | | CALLS FOR *BUILDING STEEL*, IS THIS MEANT TO BE *FOOTER | | | STEEL*? IF THE STRUCTURE CONTAINS BOTH FOOTER AND | | | BUILDING STEEL PLEASE SEE 250.50 AS BOTH ARE REQUIRED | | | TO BE PART OF THE SYSTEM. | | | PLEASE VERIFY ANY COLD WATER PIPING PER 250.50 **PLEASE | | | PLACE NOTE ON PLANS FOR FBC 2704 WHICH REQUIRES METAL | | | FRAMING MEMBERS TO BE BONDED. | | | | | | 13) NOTE: PLEASE SEE KITCHEN (207) WHICH STATES A NOTE | | | TO SEE E-13 FOR ELECTRICAL FOR THAT AREA HOWEVER E-13.0 | | | DOES NOT CONTAIN THIS. | | | THIS ARE WAS HOWEVER FOUND ON E-11 | | | A) PLEASE SEE NEC 210.8B2 AS GFI PROTECTION IS REQUIRED | | | FOR ALL 15 AND 20AMP 120V IN KITCHEN AREA WHETHER OR | | | NOT THESE ARE COUNTER SPACE OUTLETS. | | | PLEASE SEE THERE ARE CIRCUITS WHICH DO NOT CONTAIN THE | | | REQUIRED PROTECTION. | | | FOR EXAMPLE: | | | PLEASE SEE 1K2-17, 1K2-19 ETC. | | | B) PLEASE SEE THERE ARE WHAT APPEAR TO BE EQUIPMENT | | | DESIGNATIONS ON THIS SAME LAYOUT ON E-11 WHICH ARE NOT | | | ON THE EQUIPMENT LIST AS PROVIDED. PLEASE SEE FOR | | | EXAMPLE: | | | E-901, E-902, E49B ETC THERE ARE OTHERS. | | | | | | 14) NOTE: PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4) | | | AND STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR | | | ADA REQUIRED AREAS. DEVICES ARE BEING SHOWN ON | | | PLANS/LEGEND. PLEASE CORRELATE WITH PLANS, AND FA | | | SHEETS SUBMITTED. | | | ** PLEASE KNOW THAT THE FIRE ALARM WILL BE UNDER A | | | SEPARATE PERMIT HOWEVER THE BASE LIFE SAFETY SYSTEM IS | | | REQUIRED ON BASE PLANS AS SHOWN. DO NOT REMOVE FROM | | | SETS. | | | FBC 106.3.5.1.2 | | | | | | 15) NOTE: PLEASE CLARIFY SPACE ABOVE LINE #1 ON THE MDP | | | AS THIS NOTES 2000AMP MAIN? | | | PLEASE CORRELATE AS THE RISER SHOWS A MDP1, THE | | | PANEL-BOARD IS MDP AND THE PLANS DO NOT INDICATE | | | EITHER. | | | PLEASE CORRELATE AND PLEASE SHOW LOCATION OF THE MDP ON | | | PLANS. | | | PLEASE SEE 110.26, 408.36 | | | | | | 16) NOTE: PLEASE CLARIFY ALL CONTINUOUS AND LARGEST | | | MOTOR LOADS AT 125%. | | | PLEASE SHOW. 215.3, 230.42 (SOME ARE SHOWN) | | | | | | 17) NOTE: PLEASE SEE THAT PANEL SCHEDULES ARE TO BE | | | SPECIFIC TO THE ROOMS AND AREAS IN WHICH THEY FEED. | | | PLEASE SEE 408.4. | | | | | | *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE | | | THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A | | | PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE | | | THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. | | | CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED | | | AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE | | | BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, | | | DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE | | | CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT | | | ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS | | | ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR | | | RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT | | | OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE | | | ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT | | | PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS | | | SECTION.* | | | 408.4, 310.16, 240.4 ETC | | | FBC 106.3.5.1.2, 106.5, 106.1.2 | | | | | | ** PLEASE KNOW AS THERE WILL SEVERAL CHANGES TO PLANS, | | | THERE MAY BE NEW COMMENTS WHICH ARE NOT MADE ON THIS | | | REVIEW. | | | | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | | DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | 2007-10-07 09:16:44 | 2007-10-07 09:16:44 | | | | | | | | | REVIEW IN PROGRESS | | 2007-10-06 18:46:42 | 2007-10-06 18:46:42 | | | | | | IN ELECTRICAL FOR REVIEW. |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
4 |
Status |
P |
Date |
2008-08-28 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2008-08-28 |
Time |
13:57 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2008-08-28 |
Time |
13:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
F |
Date |
2008-06-04 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2008-06-04 |
Time |
14:25 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2008-06-04 |
Time |
14:05 |
Sent To |
|
|
| Notes |
| 2008-06-04 14:24:53 | ***FAILED**** PLEASE PROVIDE THE FOLLOWING: | | | | | | 1. CIVIL DRAWING SETS PREPARED BY SIMMONS & WHITE | | | REVISIONS NOT CONSISTENT.FOR EXAMPLE, SHEET #2 OF ONE | | | SET HAS 1 REVISION,AND OTHER SET SAME SHEET # 2 HAS 4 | | | REVISIONS. SAME WAY ONE SET SHEET #3HAS NO REVISION | | | OTHER SET SAME SHEEET #3 HAS ONE REVISION ETC, ETC. | | | EACH SHEET OF ALL SETS MUST HAVE CONSISTENTREVISIONS | | | AND UPTO LAST REVISION.ALL 3 SETS MUST BE SAME. | | | | | | 2. STORM WATER QUALITY CALCULATIONS MUST BE APPROVED | | | FROM 100045TH STREET ENGINEERING SERVICES BEFORE WE | | | APPROVED. | | | | | | 3. WATER & SEWER PLANS MUST BE APPROVED &STAMPED | | | FROM 45TH STREET (MANNY G.), UTILITY DEPT BEFORE WE | | | APPROVED. | | | | | | PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR | | | PERMITTING PROCESS | | | | | | RASIK CHOKSHI805-6723 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
F |
Date |
2008-02-27 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2008-02-27 |
Time |
09:39 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2008-02-27 |
Time |
09:39 |
Sent To |
|
|
| Notes |
| 2008-02-27 09:47:08 | ***FAILED**** PLEASE PROVIDE THE FOLLOWING: | | | | | | 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI). | | | PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR | | | NOI. | | | YOU CAN GET NOI INFO FROM | | | WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/ | | | NOTICE OF INTENT DEP FORM 62-621.300(4)(B), | | | EFFECTIVE MAY 1, 2003 | | | 2. STORM WATER QUALITY CALCULATIONS MUST BE APPROVED | | | FROM 100045TH STREET ENGINEERING SERVICES BEFORE WE | | | APPROVED. | | | 3. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH | | | STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED. | | | | | | PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR | | | PERMITTING PROCESS | | | | | | RASIK CHOKSHI805-6723 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2007-10-30 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2007-10-30 |
Time |
09:18 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2007-10-30 |
Time |
08:49 |
Sent To |
|
|
| Notes |
| 2007-10-30 09:14:34 | ***FAILED**** PLEASE PROVIDE THE FOLLOWING: | | | | | | | | | 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI). | | | PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR | | | NOI. | | | YOU CAN GET NOI INFO FROM | | | WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/ | | | NOTICE OF INTENT DEP FORM 62-621.300(4)(B), | | | EFFECTIVE MAY 1, 2003 | | | 2. PLEASE SHOW ON DRAWING ALL CITY STANDARDS NOTES FOR | | | SIDEWALK, DRIVEWAY, APPROACH, PARKINGS, HANDICAP | | | PARKINGS, DUMPSTER ENCLOSURE, YOU CAN GET A C D FROM | | | 1000, 45 STREET FOR ALL THESE CITY STANDARDS NOTES. | | | PHONE# 494-1040 | | | 3. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE | | | DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION | | | MUST BE ACCESSIBLE FOR PICKUP TRUCK. | | | 4. PLEASE SHOW ON CALCULATION THAT YOU HAVE CONSIDERED | | | FLOOD ZONE AREA, & 5,10, 25, 100 YEAR FLOOD CRITERIA | | | AND CROWN OF THE ROAD WHEN YOU DETERMINE THE FIRST | | | FLOOR ELEVATION. | | | 5. PLEASE SHOW ON DRAINAGE DRAWINGTHE SITE AREA, | | | GREEN, LAKE,PARKING AREA, IMPERVIOUS,PERVIOUS AREAYOU | | | ARE DEVELOPING FOR THIS PROJECT . PLEASEMAKE SURE | | | THESE AREAS SHOWN ON DRAINAGE DRAWINGS MUST MATCH WITH | | | AND USED IN STORM WATER QUALITY CALCULATIONS. PLEASE | | | PROVIDE A COPY OF THESE CALCULATIONS. | | | 6. PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE | | | SO, WE CANSEE THE LAYOUT OF STORM WATER PIPES FROM | | | ALL OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF THE | | | CONTROL STRUCTURESWITH ELEVATIONS, NOTCHES, BLEEDING | | | ELEVATION, ETC ON DRAWINGS, CALCULATION FOR | | | EXFILTRATION TRENCHES, PLEASE SHOW DRY DETENTION/WET | | | DETENTION AREAS IN STORM WATER CALS IF YOU HAVE ALL | | | THESE. | | | 7. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND | | | YOUR SITE FOR STORM WATER DRAIN SO YOUR SITE DO NOT GET | | | FLOODED AND HAVE ENOUGH DRAINS. | | | 8. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, &STORM | | | WATER QUALITY CALCULATIONS. STORM WATER CALS MUST BE | | | APPROVED FROM 100045TH STREET ENGINEERING SERVICES. | | | 9. PLEASE SHOW ON DRAWINGS THE POLLUTION PREVENTION | | | DETAILS,CLOTHES USED FOR SILT ETC., PLANS SHOWING SILT | | | FENCE AROUND THE SITE & CATCH BASINS DURING | | | CONSTRUCTION AND ALL DEMOLITION PHASE.HEIGHT OF FENCE | | | SHOULD BE HIGH ENOUGH PER FDEP TO STOP DUST PARTICLES. | | | YOU HAVE SHOWN SILT FENCE DURING CONSTRUCTION PHASE BUT | | | NOT DURING DEMOLITION PHASE. | | | 10. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH | | | STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED. | | | | | | PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR | | | PERMITTING PROCESS | | | | | | RASIK CHOKSHI805-6723 | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2008-09-16 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-09-16 |
Time |
11:07 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-09-16 |
Time |
10:43 |
Sent To |
|
|
| Notes |
| 2008-09-16 11:07:21 | *****APPROVED***** | | | | | | PLAN SHEETS A-1.1, A-5.1, A-10.0 & A-10.1, E-1.0 & | | | E-2.0 & E-3.0, E-7.0 & E-8.0 & E-9.0, AND FS-1.0 & FS-2 | | | & FS-3.0 & FS-4.0 WERE STAMPED, INITIALED, AND DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2008-06-25 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-06-25 |
Time |
12:27 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-06-24 |
Time |
15:34 |
Sent To |
|
|
| Notes |
| 2008-06-25 12:22:58 | *****PROVISO***** | | | | | | | | | THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE | | | BEEN ADDRESSED;HOWEVER THE APPROPIATE PLAN SHEETS TO | | | BE FIRE-STAMPED WHEN THE OTHER PLAN REVIEWERS HAVE BEEN | | | SATISFIED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 5610805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2008-03-27 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2008-03-27 |
Time |
09:50 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2008-03-27 |
Time |
09:36 |
Sent To |
|
|
| Notes |
| 2008-03-27 09:49:47 | 1. TACTILE SIGNAGE REQUIRED AT ALL EXIT DOOR | | | LOCATIONS. | | | | | | 2. THIS OFFICE PICKED UP ON THE EMERGENCY LIGHT | | | FIXTURES IDENTIFIED AS A, A1, H, AND Q, HOWEVER IT | | | APPEARS THAT ALL AREAS ARE NOT DIPLAYED. EMERGENCY | | | LIGHTING EQUIPMENT SHALL BE DISPLAYED FOR ALL AREAS OF | | | THE BUILDING. PLEASE REVIEW ALL LARGE ROOMS TO | | | DETERMINE IF EMERGENCY LIGHTING EQUIPMENT EXISTS FOR | | | THESE AREAS. PLEASE PROVIDE DRAWINGS. | | | | | | 3. THE FABRIC TRACK CEILING DISPLAYED ON PAGE A-6.0 | | | SHALL NOT INTERFERE WITH THE SPRAY PATTERN OF ANY | | | AUTOMATIC FIRE SPRINKLER HEADS. THE FIRE SPRINKLER | | | HEADS IN THIS AREA SHALL BE PROPERLY INSTALLED WITH | | | CONSIDERATION FOR THE FABRIC TRACK CEILING. | | | | | | 4. HOW IS THE COOK TOP GOING TO BE PROTECTED THAT IS | | | DISPLAYED ON PAGE A-7.2. THERE APPEARS TO BE NO HOOD, | | | DUCT OR FIRE SUPPRESSION SYSTEM ABOVE IT, ONLY A | | | MICROWAVE OVEN. | | | | | | 5. ANOTHER EXIT SIGN APPEARS TO BE NEEDED IN CORRIDOR | | | 300 TO DIRECT PERSONS TO WAITNG ROOM AREA EXIT 308 | | | NOTED ON PAGE E-3.0. | | | | | | 6. KEYPADS NOTED AT DOORS ON ELECTRICAL SHEETS | | | ILLUSTRATING FIRE ALARM EQUIPMENT. HOW DO THESE KEYPADS | | | WORK. HOW DOES SOMEONE EXIT IF THEY DO NOT KNOW THE | | | NUMBERS TO PUNCH. EVERY EMERGENCY DOES NOT ACTIVATE THE | | | FIRE ALARM SYSTEM. SOME EMERGENCIES COULD OCCUR THAT | | | DOES NOT IMMEDIATELY ACTIVATE THE FIRE SPRINKLER OR | | | FIRE ALARM SYSTEM. PLEASE EXPLAIN KEYPAD AND HOW DOES | | | IT WORK. | | | | | | 7. PLEASE PROVIDE DOCUMENTATION ON THERMAL BLANKET THAT | | | PROVIDES A TWO HOUR FIRE RATING ON PAGE M-2.3. | | | | | | 8. PLEASE INDICATE EXIT ROUTES AND EXIT LOCATIONS FROM | | | PARKING AREA. | | | | | | 9. ANY FIRE EXTINGUISHERS PLANNED FOR ACCESS TO PARKING | | | AREA. | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION | | | 804-4709 PHONE | | | 804-4776 FAX |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2007-10-23 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2007-10-23 |
Time |
16:42 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2007-10-23 |
Time |
14:12 |
Sent To |
|
|
| Notes |
| 2007-10-23 14:34:20 | 1. WET FIRE HYDRANTS ARE REQUIRED PRIOR TO, DURING, AND | | | AFTER CONSTRUCTION. | | | | | | 2. CONSTRUCTION, RENOVATION, AND DEMOLITION SHALL | | | COMPLY WITH NFPA 241. | | | | | | 3. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. | | | | | | 4. ANY CUTTING AND WELDING OPERATIONS TO COMPLY WITH | | | NFPA 51B. | | | | | | 5. EXITS ARE TO REMAIN CLEAR AND UNOBSTRUCTED. | | | | | | 6. IT APPEARS THAT SOME ILLUMINATED EXIT SIGNS ARE | | | MISSING FROM THE ELECTRICAL DRAWINGS. ALL EXIT ACCESS | | | AND EXITS ARE TO BE PROPERLY IDENTIFIED BY ILLUMINATED | | | EXIT SIGNS. | | | | | | 7. SEPARATE PLANS AND PERMITS REQUIRED FOR AUTOMATIC | | | FIRE SPRINKLER SYSTEM INSTALLATION. | | | | | | 8. SEPARATE PLANS AND PERMITS REQUIRED FOR THE | | | INSTALLATION OF THE FIRE ALARM SYSTEM. | | | | | | 9. KNOX-BOX WILL BE REQUIRED FOR THE BUILDING. | | | | | | 10. KNOX-BOX LOCKING CAPS WILL BE REQUIRED FOR THE FIRE | | | DEPARTMENT CONNECTION CONNECTED TO THE SPRINKLER | | | SYSTEM. | | | | | | 11. THE REQUIRED FIRE ALARM SYSTEM SHALL BE MONITORED | | | BY A LICENSED UL LISTED CENTRAL STATION APPROVED FOR | | | CENTRAL STATION SERVICE. | | | | | | 12. PLEASE EXPLAIN KEY PAD NOTES THAT ARE LISTED ON THE | | | PLANS. HOW DO THESE DEVICES IMPACT EXITING FROM THE | | | BUILDING. | | | | | | 13. PLEASE PROVIDE INTERIOR FINISH CLASSIFICATIONS FOR | | | ALL WALLS. CEILING INFORMATION LOCATED. | | | | | | 14. SEPARATE PLANS AND PERMITS REQUIRED FOR THE | | | HOOD,DUCT, AND FIRE SUPPRESSION SYSTEM PLANNED FOR THE | | | BUILDING. | | | | | | 15. ALL WALK-IN COOLERS AND FREEZERS ARE TO BE | | | PROTECTED BY AUTOMATIC FIRE SPRINKLER PROTECTION. | | | | | | 16. HANDRAILS AND GUARDRAILS TO COMPLY WITH APPLICABLE | | | BUILDING AND FIRE CODE REQUIREMENTS. | | | | | | 17. BUILDING ADDRESS REQUIRED. A MINIMUM OF AT LEAST 6" | | | HIGH AND AT LEAST 1" NUMBERS ARE REQUIRED. | | | | | | 18. PLEASE PROVIDE A COMPLETE LIFE SAFETY PLAN | | | ILLUSTRATING PROPOSED OCCUPANT LOADS, TRAVEL DISTANCES, | | | EXIT ROUTES, EXITS AND ALL OTHER RELATED INFORMATION. | | | | | | 19. ANY ARCHITECTURAL SOFFITS SHALL NOT INTERFERE WITH | | | THE OPERATION OF ANY FIRE SPRINKLER HEADS. | | | | | | 20. PLEASE PROVIDE EGRESS CAPACITIES FOR DOORS ON PAGE | | | A-2.3. | | | | | | 21. EGRESS SCHEMES NEED TO BE FURTHER DEFINED. | | | | | | 22. FLAME SPREAD DETAILS NEEDED FOR FABRIC CEILING | | | ILLUSTRATED ON PAGE A-3.0. INFORMATION LOCATED ON PAGE | | | A-6.0 | | | | | | 23. PLEASE ILLUSTRATE SEATING AREAS PLANNED FOR THE | | | HANDICAPPED IN THE ASSEMBLY AREAS. | | | | | | 24. PLEASE DISPLAY ALL PROPOSED FIRE EXTINGUISHER | | | LOCATIONS. | | | | | | 25. ACCORDING TO THE DOOR SCHEDULE ON PAGE A-10.1 THE | | | GROUP SEVEN HARDWARE HAS A DEADBOLT AND AN EXIT PANIC | | | DEVICE. WHEN PANIC DEVICES ARE INSTALLED ON EXIT DOORS | | | NO OTHER LOCKS OR HANDWARE IS PERMITTED. | | | | | | 26. THE DOOR SCHEDULE DECLARES ON PAGE A-10.1 THAT ONLY | | | TWO TYPES OF DOORS WILL HAVE PANIC HARDWARE. IS THIS | | | TRUE AND CORRECT. | | | | | | 27. COULD NOT LOCATE AN EMERGENCY LIGHT FIXTURE TYPES | | | ON PAGE E-15.0. | | | | | | 28. ANY OCCUPIED AREA SHALL BE EQUIPPED WITH EMERGENCY | | | LIGHTING EQUIPMENT. PLEASE ILLUSTRATE EMERGENCY LIGHT | | | FIXTURES. | | | | | | 29. PLEASE DESCRIBE WHAT THE CLASSROOMS WILL BE USED | | | FOR. IF CHILDREN WILL USE THESE FACILITIES, PLEASE | | | PROVIDE AGES, STAFFING COUNTS, AND NUMBER OF HOURS. | | | | | | 30. PLEASE INDICATE WHAT THE VOICE EVACUATION MESSAGE | | | FOR THE FIRE ALARM SYSTEM WILL DESCRIBE TO THE | | | OCCUPANTS. | | | | | | 31. WHAT HARDWARE IS EXPECTED ON THE GATES USED TO EXIT | | | THE ENCLOSED COURTYARD AREA. | | | | | | 32. THE LARGE MONUMENTAL STAIRS LOCATED ON THE EXTERIOR | | | SHALL COMPLY WITH THE APPLICABLE STAIR SECTIONS OF THE | | | CODE. | | | | | | 33. IF THE OCCUPANT LOAD DECLARED ON PAGE A-2.1 CAN BE | | | EXPECTED TO BE IN THE BUILDING AT ONE TIME, CROWD | | | MANAGERS MAY BE NECESSARY AND SHALL RECEIVE THE PROPER | | | TRAINING. | | | | | | 34. NO SMOKING SIGNS SHALL BE INSTALLED SINCE SMOKING | | | IS ASSEMBLY OCCUPANCIES CAN BE REGULATED BY THE | | | AUTHORITY HAVING JURISDICTION. | | | | | | 35. ALL ELECTRICAL EQUIPMENT INSTALLATION TO COMPLY | | | WITH NFPA 70, THE NATIONAL ELECTRICAL CODE. | | | | | | 36. PLEASE ILLUSTRATE ON THE PLANS THE ONE THIRD | | | DIAGONAL DIMENSION FOR EXITING TO REACH EXITS IN FIRE | | | SPRINKLER PROTECTED BUILDINGS. | | | | | | 37. THE COVERED AREA AND AC AREA DOES NOT REFLECT THE | | | TOTAL DISPLAYED ON PAGE A-1.0 | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | 804-4709 PHONE | | | 804-4774 FAX |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2008-06-04 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-06-04 |
Time |
14:53 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-06-03 |
Time |
12:52 |
Sent To |
|
|
| Notes |
| 2008-06-04 14:56:45 | | | | | | | PASSED/PROVISO | | | | | | A REVISION IS REQUIRED FOR SHT P-11.0. | | | | | | SUBMIT A REVISION FOR THE GAS RISER DIAGRAM SHOWING THE | | | BRANCH LINE AND SHUT OFF VALVE FOR APPLIANCE INDICATED | | | AS OVEN UNIT NUMBER G3 AND DELETE SHUT OFF VALVE AND | | | UNION IN THE CEILING. | | | | | | THE MANUF. SPECIFICATION SHEETS FOR THE G3 OVEN AND THE | | | SECOND STAGE REGULATOR ARE REQUIRED AT THE TIME OF GAS | | | PERMIT APPLICATION. | | | | | | | | | | | | | | | . |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2008-03-15 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-03-15 |
Time |
08:39 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-03-15 |
Time |
08:39 |
Sent To |
|
|
| Notes |
| 2008-04-04 08:07:05 | DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | | | | ****FROM PREVIOUS REVIEW: | | | | | | 1. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING | | | INFORMATION IS REQUIRED TO SECURE A PERMIT. | | | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE.-- SHOW ALL PIPING FROM THE METER TO | | | THE MOST REMOTE APPLIANCE. | | | ****RESPONSE NOTED, BUT THE LENGTHS OF PIPE FROM THE | | | METER TO AND INCLUDING THE FIRST DROP, THE FIRST RISE | | | AND SECTION OVER TO THE FIRST RISER, (12FT). ALSO THE | | | DROP OUT OF THE CEILING IS ONLY SHOWN AS 2FT. PLEASE | | | CLARIFY AND SHOW ALL CUT SECTION LENGHTS. | | | | | | B. OK | | | C. OK | | | | | | D. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). --TOTAL DISTANCE FROM | | | THE METER TO THE MOST REMOTE OUTLET IS NOT INDICATED ON | | | THE PLANS. GAS APPLIANCE SCHEDULE NOTE #4 INDICATES | | | 80FT DEVELOPED LENGTH FROM THE REGULATOR, BUT ADDING | | | ALL CUT SECTION LENGTHS PROVIDED ON THE ISOMETRIC | | | SUBMITTED ON SHT P-11.0 197FT IS INDICATED. PLEASE | | | CLARIFY. | | | ****RESPONSE NOTED, BUT ADDITION OF CUT SECTION LENGHTS | | | SHOWN TOTALS 127FT, THIS IS WITH THE SECTIONS FROM THE | | | METER TO AND INCLUDING THE FIRST DROP, AS WELL AS THE | | | FIRST RISE FROM THE PE PIPE AND SECTION TO THE FIRST | | | RISER (12FT) NOT ADDED. A CLARIFICATION FOR THE DROP | | | DOWNSTREAM OF THE SOLINOID VALVE, (2FT),WILL BE | | | REQUIRED TO BE VERIFIED. | | | | | | E. OK | | | | | | F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | ****RESPONSE NOTED, BUT THE LOCATION OF THE INFORMATION | | | ON THE ARCHITECTURAL SHEETS IS NOT INDICATED. ALSO THE | | | LISTING INFORMATION AS WELL AS THE BTU LOAD OF EACH GAS | | | APPLIANCE IS REQUIRED. WILL THIS INFORMATION BE | | | AVAILABLE ON THE ARCHITECTURAL SHEETS? IF NOT SUBMIT | | | MANUF. SPECIFICATION SHEETS TO VERIFY LISTING & BTU | | | LOAD. | | | | | | G. N/A | | | H. N/A | | | | | | I. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. | | | ****RESPONSE NOTED, BUT THE MANUAL SHUT OFF VALVE IS | | | NOT INDICATED, NOR IS THE UNION. ALSO NO INDICATION | | | THAT THE VALVES/UNION ARE BELOW THE CEILING. | | | | | | J. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE | | | SECOND STAGE REGULATOR. INDICATE THE MODEL NUMBER. THE | | | REGULATOR SHALL BE LISTED & INDICATE TOTAL BTU OUTPUT | | | THAT CORRELATES TO THE TOTAL BTU LOAD DOWNSTREAM OF THE | | | REGULATOR. | | | ****RESPONSE NOTED, PLEASE SUBMIT PRIOR TO INSTALLATION | | | TO PREVENT REMOVAL/REPLACEMENT IN CASE REGULATOR IS NOT | | | APPROVED. | | | | | | K. A LISTED SHUTOFF VALVE SHALL BE INSTALLED | | | IMMEDIATELY AHEAD OF EACH MP REGULATOR. SECTION 409.4. | | | --ALSO A UNION WILL BE REQUIRED DOWNSTREAM OF THE | | | SHUT OFF VALVE.PLEASE SHOW ON RISER DIAGRAM. | | | ****RESPONSE NOTED, BUT THE UNION IS NOT INDICATED. | | | | | | **********NEW COMMENT********** | | | | | | 1B. SHT P-11.1 THE UNIT NUMBERS FROM THE GAS APPLIANCE | | | SCHEDULE DO NOT REFLECT THE NUMBERS INDICATED ON THE | | | GAS ISOMETRIC RISER DIAGRAM. PLEASE CORRELATE. SECTION | | | 106.1.1 & TABLE 402.4(2). | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | | FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2007-11-09 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-11-09 |
Time |
08:37 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-11-09 |
Time |
08:37 |
Sent To |
|
|
| Notes |
| 2008-03-15 08:39:36 | DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | | | | 1. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING | | | INFORMATION IS REQUIRED TO SECURE A PERMIT. | | | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE.-- SHOW ALL PIPING FROM THE METER TO | | | THE MOST REMOTE APPLIANCE. | | | | | | B. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE IF BEING USED. | | | | | | C. TYPE OF GAS, (LP OR NATURAL). GAS APPLIANCE SCHEDULE | | | NOTE #4 INDICATES TABLE 402.4(24) WHICH IS LP GAS. | | | | | | D. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). --TOTAL DISTANCE FROM | | | THE METER TO THE MOST REMOTE OUTLET IS NOT INDICATED ON | | | THE PLANS. GAS APPLIANCE SCHEDULE NOTE #4 INDICATES | | | 80FT DEVELOPED LENGTH FROM THE REGULATOR, BUT ADDING | | | ALL CUT SECTION LENGTHS PROVIDED ON THE ISOMETRIC | | | SUBMITTED ON SHT P-11.0 197FT IS INDICATED. PLEASE | | | CLARIFY. | | | | | | E. SUBMIT CALCULATIONS FOR COMBUSTION | | | AIR (IF APPLICABLE) PER FBC-2004 FUEL | | | GAS CODE SECTION 304. -- FOR W/H. | | | | | | F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | | | | G. CLEARLY SHOW THE LOCATION AND CAP- | | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | | OR ASME), THE DISTANCE OF THE TANK FROM | | | THE BUILDING AND ADJACENT PROPERTY LINES | | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | | CES OF IGNITION, OTHER CONTAINERS, BUILD | | | INGS, AND THE LOCATION OF ANY BUILDING | | | OPENINGS BELOW THE RELIEF VALVE OF THE | | | TANK PER NFPA 58, TABLE 3-2.2.2. | | | | | | H. CLEARLY INDICATE ON THE PLAN IF THE | | | LP TANK IS ABOVE OR BELOW GROUND, AND | | | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES | | | PER NFPA 58. IF THE TANK | | | IS BELOW GROUND THE CONTAINER SHALL BE | | | SECURILY ANCHORED PER NFPA 58 SECTION | | | 3-2.2.7(H). | | | | | | I. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. | | | | | | J. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE | | | SECOND STAGE REGULATOR. INDICATE THE MODEL NUMBER. THE | | | REGULATOR SHALL BE LISTED & INDICATE TOTAL BTU OUTPUT | | | THAT CORRELATES TO THE TOTAL BTU LOAD DOWNSTREAM OF THE | | | REGULATOR. | | | | | | K. A LISTED SHUTOFF VALVE SHALL BE INSTALLED | | | IMMEDIATELY AHEAD OF EACH MP REGULATOR. SECTION 409.4. | | | --ALSO A UNION WILL BE REQUIRED DOWNSTREAM OF THE | | | SHUT OFF VALVE.PLEASE SHOW ON RISER DIAGRAM. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | | FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2008-09-29 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-09-29 |
Time |
08:42 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-09-29 |
Time |
08:42 |
Sent To |
|
|
| Notes |
| 2008-09-29 08:43:11 | TO"COMM" BD#49--PLANS ON RACK 3 ROLLS/PAPERWORK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2008-08-12 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-08-12 |
Time |
11:49 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-08-12 |
Time |
11:49 |
Sent To |
|
|
| Notes |
| 2008-08-12 11:51:40 | TO "COMM" BD#43/PLANS ON RACK/4 ROLLS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2008-05-20 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-05-20 |
Time |
12:52 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-05-20 |
Time |
12:52 |
Sent To |
|
|
| Notes |
| 2008-06-19 08:56:47 | 6/19/08--PLANS TAKEN FROM "COMM" BD#35, AND ROUTED TO | | | MIKE WILLIAMS DESK FOR FIRE REVIEW.FIRE IS THE LAST | | | REVIEW ON THIS RESUB. | | 2008-05-20 12:56:33 | TO "COMM" BD#35/PLANS ON RACK/4 ROLLS AND PAPERWORK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-02-05 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-02-05 |
Time |
08:45 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-02-05 |
Time |
08:45 |
Sent To |
|
|
| Notes |
| 2008-02-05 08:46:26 | TO "COMM" BD#21/PLANS ON RACK/3 ROLLS AND PAPERWORK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-11-09 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-11-09 |
Time |
18:49 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-09-06 |
Time |
12:10 |
Sent To |
|
|
| Notes |
| 2007-10-01 09:15:15 | TO "COMM" BD#62 | | 2007-09-06 12:11:25 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2008-08-27 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-08-27 |
Time |
09:09 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-08-26 |
Time |
16:31 |
Sent To |
|
|
| Notes |
| 2008-08-27 09:02:53 | *************PROVISO************** | | | | | | DOCUMENTATION FROM APPLIANCE MANUFACTURER SHALL BE | | | PROVIDED SHOWING ALL OUTDOOR APPLIANCES WHICH ARE | | | EXPOSED TO WIND ARE DESIGNED TO RESSIST WIND PRESSURES | | | IN ACCORDANCE WITH FBCM SECTION 301.13. THIS | | | INFORMATION (FOR RTU'S ONLY, OTHER APPLIANCES ALREADY | | | DOCUMENTED) SHALL BE SUBMITTED FOR PLAN REVIEW PRIOR TO | | | INSTALLATION OF OUTDOOR APPLIANCES. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2008-06-03 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-06-03 |
Time |
16:06 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-06-03 |
Time |
13:09 |
Sent To |
|
|
| Notes |
| 2008-06-03 16:06:46 | ALL PREVIOUS PLAN REVIEW COMMENTS HAVE BEEN ADEQUATELY | | | ADDRESSED RELATED TO THE PLANS. PLANS HAVE BEEN STAMPED | | | AS REVIEWED FOR CODE COMPLIANCE. THE FOLLOWING ISSUES | | | ARE OUTSTANDING: | | | | | | 1. THIS IS A THRESHOLD BUILDING AND AS SUCH, THREE | | | COMPLETE SETS OF PLANS, SPECIFICATIONS AND SUBMITTALS | | | ARE REQUIRED FOR PERMIT. PLEASE COLLATE AND SUBMIT | | | THREE COMPLETE SETS OF ALL PERMIT DOCUMENTATION | | | (INCLUDING PRODUCT APPROVALS, SUCH AS FOR THE | | | PRE-ENGINEERED A/C STANDS) FOR PERMIT. | | | | | | 2. THE WINDLOAD REPORT SUBMITTED BY THE MECHANICAL | | | DESIGNER HAS NOT SUCCESSFULLY PASSED A BUILDING PLAN | | | REVIEW. THE INFORMATION ON FANS, GRAVITY VENTS AND | | | CONDENSING UNITS IS SUFFICIENT, BUT THERE ARE NOT THREE | | | COPIES SUBMITTED. THE INFORMATION PROVIDED FOR THE | | | ROOFTOP PACKAGE UNITS IS NOT ADEQUATE AS IT IS A REPORT | | | FROM 1993. THERE HAVE BEEN MANY CHANGES TO THE CODES | | | AND RELATED REFERENCE STANDARDS SINCE THAT TIME. | | | | | | BASED ON THE LANGUAGE IN FBCM 301.13, THE MANUFACTURER | | | OF THE APPLIANCES, WHO IS RESPONSIBLE FOR THE DESIGN OF | | | THE APPLIANCES, SHALL CERTIFY THAT THE APPLIANCES ARE | | | DESIGNED TO WITHSTAND ANTICIPATED WIND PRESSURES IN | | | ACCORDANCE WITH FBCB CHAPTER 16. ONCE THIS BECOMES THE | | | ONLY OUTSTANDING ISSUE RELATED TO MECHANICAL. A PASSED | | | STATUS WILL BE ENTERED AND THE MISSING WIND LOAD | | | INFORMATION WILL BE COVERED IN A PROVISO IN ORDER TO | | | ALLOW THE PROJECT TO MOVE FORWARD WHILE MISSING | | | INFORMATION IS OBTAINED AND SUBMITTED. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2008-03-03 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-03-03 |
Time |
17:30 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-02-27 |
Time |
09:53 |
Sent To |
|
|
| Notes |
| 2008-03-03 17:30:44 | REVIEW #: 2ND | | | ACTION: DENIED | | | | | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH | | | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN | | | RESPONSES FOR THE PURPOSE OF CONTINUITY. | | | | | | 1. OK EXCEPT: | | | PG M-1.1: IT APPEARS THAT SEVERAL SG-2 LINEAR DIFFUSERS | | | ARE INCORRECTLY LABELED 20 INCHES BY 1 INCH WHEN THEY | | | SHOULD BE LABELED FOR 20 FEET BY 1 INCH. ALSO, THE | | | RETURN GRILL FOR RTU 1C DOES NOT HAVE A SIZE OR CFM | | | DESIGNATION. | | | | | | 2. PG M-1.1 AND M-1.2: AIR BALANCES STILL DO NOT | | | REFLECT THE INTRODUCTION OF OUTDOOR AIR. EXAMPLE: RTU | | | 1A AND RTU 1B ON EQUIPMENT SCHEDULE EACH SHOW 6400 CFM | | | OF SUPPLY. THE FLOOR PLAN ON PG M-1.1 SHOWS EACH UNIT | | | RETURNING 6400 CFM FROM THE SPACE. IF THESE UNITS ARE | | | RETURNING 100% OF THE AIR BEING SUPPLIED, HOW WILL THEY | | | BE ABLE TO INTRODUCE THE 1300 CFM OF OUTDOOR AIR THAT | | | EACH UNIT CALLS FOR ON THE EQUIPMENT SCHEDULE? A | | | SIMILAR CONFIGURATION AND PROBLEM OCCURS FOR RTU 2A AND | | | RTU 2B. IF THE INTENTION IS FOR THE RETURN AIR FLOW TO | | | BE REDUCED AS THE OUTSIDE AIR DAMPER MODULATES, WOULD | | | THERE NOT BE A NEED FOR A CORRESPONDING MODULATING | | | DAMPER IN THE RETURN DUCTS? ADDITIONALLY, IT IS UNCLEAR | | | HOW THE GRAVITY RELIEF VENTILATORS WILL SERVE TO | | | RELIEVE POSITIVE PRESSURE IN THE SPACES BEING SERVED IF | | | THEY ARE TIED INTO THE RETURN AIR DUCT SYSTEM. THIS | | | WOULD PUT THE GRAVITY RELIEF UNDER CONSTANT NEGATIVE | | | PRESSURE. PLEASE CLARIFY. | | | | | | 3. A-6.1: ELEVATION DRAWINGS STILL DO NOT SHOW A | | | PERMANENT MEANS OF ACCESS WHICH STARTS AT GRADE LEVEL | | | AS REQUIRED BY FBCM 306.5. PLEASE SHOW COMPLIANCE AND | | | RESUBMIT. | | | | | | 4. DEFERRED TO BUILDING PLAN REVIEW. PLEASE COORDINATE | | | WITH ARCHITECT SHOULD BUILDING PLAN REVIEW INDICATE THE | | | NEED FOR RATED ASSEMBLIES IN ANY AREAS. | | | | | | 5. PG M-2.1: PLEASE SEE COMMENT #2 ABOVE REGARDING AIR | | | BALANCE AND GRAVITY VENTILATOR DESIGN FOR RTU 3A. | | | AHU-14: FLOOR PLAN SHOWS 640 CFM OF SUPPLY WHILE | | | SCHEDULE ON PG M-6.0 SHOWS 450 CFM OF SUPPLY. ALSO, | | | SUPPLY AND RETURN ARE BOTH SHOWN AT 640 CFM, HOW WILL | | | OUTSIDE AIR BE INTRODUCED? | | | AHU-13: DH-2, WHICH IS ATTACHED TO THIS AHU, DOES NOT | | | APPEAR IN THE EQUIPMENT SCHEDULE ON PG M-6.0. PLEASE | | | CLARIFY. SEE COMMENT ABOVE REGARDING OA INTRODUCTION. | | | PLEASE CHECK ALL AIR HANDLING SYSTEMS FOR SIMILAR | | | CIRCUMSTANCES ON M-2.1, M-2.2, M-3.1 AND M-3.2. | | | PG M-2.2: EXHAUST GRILLS FOR EF-3 ARE MISSING | | | DESIGNATIONS, SIZES AND CFM. PLEASE CORRECT. | | | PG M-3.2: THERE ARE DUCTS COMING DOWN FROM ROOF IN ROOM | | | 322 WHICH APPEAR TO BE FROM OAU-1. THIS UNIT IS SHOWN | | | ON PG M-11.0 AS A 100% OUTSIDE AIR UNIT. IT IS UNCLEAR | | | AS TO WHY A 100% OUTSIDE AIR UNIT HAS A RETURN DUCT | | | SYSTEM SINCE IT IS PROVIDING 100% OUTSIDE AIR. PLEASE | | | CLARIFY THE DESIGN INTENT. FBC 106.1.1. | | | | | | 6. PLEASE SEE COMMENT #2 REGARDING DESIGN OF GRAVITY | | | RELIEF DAMPERS. | | | | | | 7. OK | | | | | | 8. OK, EXCEPT PG M-2.3: KITCHEN GREASE EXHAUST DUCT, | | | VERTICAL DUCTS UNDER EF-14 AND EF-15 ARE SHOWN ON PLAN | | | TO BE 16X16. EACH OF THESE FANS IS SHOWN ON EQUIPMENT | | | SCHEDULE TO BE RATED AT 1912 CFM. THIS MEANS THE AIR | | | VELOCITY IN THE 16X16 DUCT WOULD BE APPROXIMATELY 1074 | | | FEET PER MINUTE. GREASE DUCT SYSTEMS SERVING A TYPE I | | | HOOD SHALL BE DESIGNED AND INSTALLED SO AS TO PROVIDE | | | AN AIR VELOCITY WITHIN THE DUCT SYSTEM OF NOT LESS THAN | | | 1,500 FEET PER MINUTE AND NOT GREATER THAN 2,500 FEET | | | PER MINUTE IN ACCORDANCE WITH FBCM 506.3.4. THE 16X16 | | | DUCT MAY FALL UNDER THE EXCEPTION IN THIS SECTION IF IT | | | IS FOR THE PURPOSE OF TRANSITIONING TO THE SIZE OF THE | | | FANS AND IT IS LESS THAN 3 FEET IN LENGTH BUT THAT CAN | | | NOT BE DETERMINED FROM THESE DRAWINGS. | | | | | | 9. OK | | | | | | 10. OK | | | | | | 11. M-6.0: PLEASE INCLUDE THIS NOTE ON THE OARTU | | | SCHEDULE. | | | | | | 12. OK | | | | | | 13. OK | | | | | | 14. OK | | | | | | 15. OK | | | | | | 16. OK | | | | | | 17. WIND LOAD SUBMITTAL DATA FOR ROOFTOP EQUIPMENT WILL | | | BE REVIEWED BY THE BUILDING PLAN REVIEWER. | | | | | | 18. EQUIPMENT HEIGHT OK, PRODUCT APPROVAL SUBMITTALS | | | WILL BE REVIEWED BY THE BUILDING PLAN REVIEWER. | | | | | | 19. OK | | | | | | 20. TO BE DETERMINED BY SUBSEQUENT BUILDING PLAN | | | REVIEW. | | | | | | PLEASE RESPOND TO ALL REVIEW COMMENTS IN WRITING WITH | | | INFORMATION ON HOW COMMENTS HAVE BEEN ADDRESSED AND | | | WHERE THE REQUESTED INFORMATION CAN BE FOUND IN ORDER | | | TO SPEED THE REVIEW PROCESS. ADDITIONALLY, PLEASE | | | RETURN ONE SET OF OLD PLANS FOR REFERENCE. ROMOVE | | | OLD/VOIDED SHEETS FROM THE PLANS BEING SUBMITTED FOR | | | PERMIT PRIOR TO RESUBMITTAL. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2007-11-03 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-11-03 |
Time |
15:08 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-11-01 |
Time |
17:16 |
Sent To |
|
|
| Notes |
| 2007-11-03 15:08:32 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. M-1.0: GIVEN THE CONGESTED NATURE OF THE DUCT LAYOUT | | | IN THE ROOM 101 SANCTUARY AREA, IT IS NOT POSSIBLE TO | | | REVIEW THIS AREA OF THE PLANS. WHILE IT IS UNDERSTOOD | | | THAT THE PLANS ARE DRAWN AT THE MINIMUM ALLOWED 1/8IN. | | | SCALE, THE NATURE OF THE WORK AND THE VOLUME OF | | | INFORMATION INCLUDED IN THIS SMALL AREA MAKES IT | | | DIFFICULT TO ASCERTAIN THE NATURE AND SCOPE OF WORK IN | | | THIS AREA. IT IS REQUESTED THAT, UPON RESUBMITTAL, THIS | | | AREA BE REPRESENTED IN A MANNER WHICH MORE CLEARLY | | | DELINEATES THE SIZES, ROUTING, LOCATIONS AND | | | DESIGNATIONS OF EQUIPMENT, DUCTS AND DIFFUSERS. ONE | | | SUGGESTION WOULD BE TO SHOW THIS AREA (ROOM 101 | | | SANCTUARY) AT A LARGER SCALE. FBC 106.1.1 AND 106.1.3. | | | | | | 2. M-1.0: ROOM 102 SOCIAL HALL, THE AIR QUANTITIES IN | | | THIS AREA DO NOT APPEAR IN BALANCE. GRILL DESIGNATIONS | | | CALL FOR 8000 TOTAL CFM OF SUPPLY AND 12,800 CFM OF | | | RETURN. ALSO, THE OUTDOOR AIR SCHEDULE CALLS FOR 2400 | | | CFM OF O.A. IN THIS AREA. HOW WILL THIS O.A. BE | | | INTRODUCED IF THE RTUS ARE RETURNING MORE AIR THAN THEY | | | ARE SUPPLYING? WILL ANY AIR BE EXHAUSTED TO BE REPLACED | | | BY THE 2400 CFM OF O.A.? THE AMOUNT OF SUPPLY AIR SHALL | | | BE APPROXIMATELY EQUAL TO THE AMOUNT OF RETURN AND | | | EXHAUST AIR IN ACCORDANCE WITH FBC,M 403.1 AND THE | | | MECHANICAL SYSTEM SHALL BE DESIGNED TO ASSURE THAT THE | | | BUILDING IS PRESSURIZED WITH RESPECT TO OUTDOORS IN | | | ACCORDANCE WITH FBC 13-409.1.ABC.2. | | | NOTE: THESE COMMENTS APPLY TO ALL AREAS WHICH ARE | | | REQUIRED TO BE PROVIDED WITH OUTSIDE AIR IN ACCORDANCE | | | WITH FBC,M 403.3. VERIFY AIR BALANCES FOR ALL SYSTEMS | | | IN ALL AFFECTED AREAS AND MAKE CORRECTIONS AS NEEDED | | | PRIOR TO RESUBMITTAL. | | | | | | 3. A-6.1: ELEVATION DRAWINGS SHOW ACCESS LADDERS FROM | | | LOWER ROOF TO HIGHER ROOF AREAS. WHERE EQUIPMENT AND | | | APPLIANCES REQUIRING ACCESS ARE INSTALLED ON ROOFS OR | | | ELEVATED STRUCTURES AT A HEIGHT EXCEEDING 16 FEET, SUCH | | | ACCESS SHALL BE PROVIDED BY A PERMANENT APPROVED MEANS | | | OF ACCESS, THE EXTENT OF WHICH SHALL BE FROM GRADE OR | | | FLOOR LEVEL TO THE EQUIPMENT AND APPLIANCES? LEVEL | | | SERVICE SPACE. SUCH ACCESS SHALL NOT REQUIRE CLIMBING | | | OVER OBSTRUCTIONS GREATER THAN 30 INCHES HIGH IN | | | ACCORDANCE WITH FBC,M 306.5. PLEASE SHOW THE PERMANENT | | | MEANS OF ACCESS TO BE FROM FLOOR OR GRADE TO THE ROOF | | | LEVEL. | | | PERMANENT LADDERS INSTALLED TO PROVIDE THE REQUIRED | | | ACCESS SHALL COMPLY WITH THE FOLLOWING MINIMUM DESIGN | | | CRITERIA: | | | 1) THE SIDE RAILING SHALL EXTEND ABOVE THE PARAPET OR | | | ROOF EDGE NOT LESS THAN 30 INCHES. | | | 2) LADDERS SHALL HAVE RUNG SPACING NOT TO EXCEED 14 | | | INCHES ON CENTER. | | | 3) LADDERS SHALL HAVE A TOE SPACING NOT LESS THAN 6 | | | INCHES DEEP. | | | 4) THERE SHALL BE A MINIMUM OF 18 INCHES BETWEEN | | | RAILS. | | | 5) RUNGS SHALL HAVE A MINIMUM 0.75-INCH DIAMETER AND BE | | | CAPABLE OF WITHSTANDING A 300-POUND LOAD. | | | THERE ARE MULTIPLE LEVELS OF ROOF WHICH APPEAR TO BE | | | SEPARATED BY PARAPETS SHOWN ON PG M-4.0. SHOW A MEANS | | | OF PERMANENT ACCESS AS REQUIRED BY THIS SECTION ON EACH | | | OF THESE LEVELS WHERE EQUIPMENT REQUIRING SERVICE | | | ACCESS IS LOCATED. | | | | | | 4. NO WALL SCHEDULE OR FLOOR PLAN COULD BE FOUND IN | | | ARCHITECTURAL PLANS SHOWING LOCATIONS OF | | | FIRE-RESISTANCE RATED WALL ASSEMBLIES. PLANS COULD NOT | | | BE REVIEWED FOR POTENTIAL REQUIRED OPENING PROTECTIVES | | | IN DUCT PENETRATIONS OF WALLS. PLEASE INCLUDE THE | | | LOCATION OF ALL FIRE RESISTANCE RATED ASSEMBLIES IN THE | | | ARCHITECTURAL PLANS TO DETERMINE WHERE OPENING | | | PROTECTIVES MAY BE REQUIRED. PLEASE COORDINATE BETWEEN | | | MECHANICAL AND ARCHITECTURAL DESIGNERS TO ENSURE ALL | | | REQUIRED OPENING PROTECTIVES ARE SHOWN ON PLANS PRIOR | | | TO RESUBMITTAL. FBC,M 607.5 AND 607.8. | | | | | | 5. M-2.0 AND M-3.0: PLEASE SEE COMMENT #1 REGARDING | | | CLARITY OF PLANS AND SCOPE OF WORK. IT IS NOT POSSIBLE | | | BASED ON THE LAYOUT ON THE PLANS TO DETERMINE WHICH | | | DESIGNATION SYMBOL GOES WITH WHICH GRILL, DIFFUSER OR | | | FAN ON THIS FLOOR PLAN. PLEASE CLARIFY. FBC 106.1.1. | | | | | | 6. M-4.0: WHAT IS THE FUNCTION OF THE GRAVITY RELIEF | | | VENTILATORS? THERE IS NO INDICATION ON FLOOR PLANS THAT | | | THESE VENTILATORS COMMUNICATE WITH ANY INTERIOR | | | PORTIONS OF THE BUILDING. ARE THESE FOR THE RELIEF OF | | | POSITIVE PRESSURE CREATED BY THE INTRODUCTION OF | | | OUTDOOR AIR? PLEASE SEE COMMENT #2 REGARDING AIR | | | BALANCES. | | | | | | 7. M-4.0: WHAT IS THE ELEVATION OF KITCHEN EXHAUST FANS | | | IN RELATION TO THE PARAPET WALL TO THE SOUTH OF THE | | | FANS? NO ELEVATION IS GIVEN ON THE KITCHEN ROOF | | | EXHAUSTER DETAIL SHOWN ON M-9.0. EXHAUST OUTLETS THAT | | | TERMINATE ABOVE THE ROOF SHALL HAVE THE DISCHARGE | | | OPENING LOCATED NOT LESS THAN 40 INCHES ABOVE THE ROOF | | | SURFACE IN ACCORDANCE WITH FBC,M 506.3.12.1. ALSO, | | | EXHAUST OUTLETS SHALL BE LOCATED NOT LESS THAN 10 FEET | | | HORIZONTALLY FROM PARTS OF THE SAME OR CONTIGUOUS | | | BUILDINGS. EXCEPTION: THE MINIMUM HORIZONTAL DISTANCE | | | BETWEEN VERTICAL DISCHARGE FANS AND PARAPET-TYPE | | | BUILDING STRUCTURES SHALL BE 2 FEET PROVIDED THAT SUCH | | | STRUCTURES ARE NOT HIGHER THAN THE TOP OF THE FAN | | | DISCHARGE OPENING IN ACCORDANCE WITH FBC,M 506.3.12.3 | | | AND 506.5.5. CURRENTLY THE EXHAUST FANS ARE SHOWN LESS | | | THAN 10 FEET FROM THE PARAPET. SHOW COMPLIANCE WITH | | | THESE SECTIONS. | | | | | | 8. KITCHEN EXHAUST: NO INFORMATION WAS PROVIDED IN | | | THESE PLANS REGARDING THE COMMERCIAL KITCHEN EXHAUST | | | SYSTEM OTHER THAN THAT SHOWN ON FAN SCHEDULE. THIS | | | SYSTEM CAN NOT BE REVIEWED FOR CODE COMPLIANCE AT THIS | | | TIME. PROVIDE SUFFICIENT DETAIL AND DOCUMENTATION TO | | | DEMONSTRATE COMPLIANCE WITH FBC,M SEC. 506, 507 AND 508 | | | PRIOR TO PERMIT ISSUANCE AS THESE ARE CODE REQUIRED | | | SYSTEMS FOR COMMERCIAL KITCHENS. SEE FBC,M 507.2. | | | PROVIDE A KITCHEN LAYOUT SHOWING THE LOCATION OF ALL | | | COOKING EQUIPMENT IN RELATION TO THE KITCHEN HOOD. FBC | | | 106.1.2. ALSO, PG A-1.0 INDICATES THAT THE YOUTH CENTER | | | ROOM 213 IS TO CONTAIN A ?SECONDARY KITCHEN.? PLEASE | | | SHOW ON PLANS THE LAYOUT OF THIS KITCHEN ALONG WITH | | | COOKING EQUIPMENT AND REQUIRED EXHAUST SYSTEMS. | | | | | | 9. M-5.0: PROVIDE DETAILED INFORMATION SHOWING ACCESS | | | FOR SERVICE AND REPLACEMENT FOR AHU?S 12A AND 12B IN | | | THE CHAPEL. SHOW COMPLIANCE WITH FBC,M 306.1 AND EITHER | | | 306.2 OR 306.3, WHICHEVER IS MORE APPROPRIATE FOR | | | CONDITIONS. IT IS UNCLEAR WHETHER THESE UNITS ARE | | | HOUSED IN AN ATTIC SPACE OR A ROOM ON A SEPARATE | | | MEZZANINE-TYPE LEVEL. | | | | | | 10. M-6.0: ROOF-TOP A/C UNIT SCHEDULE, NONE OF THE | | | RTU?S ARE SHOWN ON ENERGY CALCULATIONS IN THE INPUT | | | DATA REPORT (FURTHER REFERENCED AS IDR) UNDER THE | | | ?SYSTEMS? PORTION. DATA SHALL BE INPUT INTO FLA/COM FOR | | | EACH ZONE BY EQUIPMENT TYPE, SIZE AND EFFICIENCY IN | | | ACCORDANCE WITH FBC 13-407.2.A. ALSO, NEITHER COOLING | | | LOAD CALCULATIONS NOR SYSTEM SIZING SUMMARIES WERE | | | INCLUDED WITH THE ENERGY CALCULATIONS. THESE | | | CALCULATIONS SHALL BE ATTACHED TO THE CODE COMPLIANCE | | | FORM SUBMITTED TO THE BUILDING DEPARTMENT AT TIME OF | | | PERMIT APPLICATION IN ACCORDANCE WITH FBC | | | 13-407.1.ABC.1. PROVIDE ALL MISSING | | | INFORMATION/CALCULATIONS/SUMMARIES AND MAKE THEM PART | | | OF A COMPLETE METHOD A CODE COMPLIANCE FORM AS REQUIRED | | | BY THESE SECTIONS. | | | | | | 11. M-6.0: RTU SCHEDULE NOTES, AUXILIARY DRAIN | | | PROTECTION IS REQUIRED ON DOWNDRAFT RTU?S AS ANY | | | OVERFLOW OF CONDENSATE FROM THE PRIMARY DRAIN PAN WOULD | | | INEVITABLY LEAK INTO THE BUILDING. THIS MAY BE | | | ACCOMPLISHED WITH A WATER LEVEL DETECTION DEVICE (SUCH | | | AS A FLOAT SWITCH) LOCATED INTERNALLY ON THE PRIMARY | | | DRAIN PAN IN ACCORDANCE WITH FBC,M 307.2.3(2). | | | | | | 12. M-6.0 SUPPLY AIR UNIT SCHEDULE:MUCH OF THE | | | INFORMATION IN THE COOLING LOAD CALCULATIONS DOES NOT | | | CORRESPOND WITH THIS SCHEDULE. EXAMPLE (A): AIR HANDLER | | | #3 IS SHOWN WITH 95 TOTAL CFM IN CALCULATIONS BUT SHOWS | | | 1300 CFM ON SCHEDULE. EXAMPLE (B): AIR HANDLER #4 IS | | | SHOWN WITH 14,839 CFM AND 38.57 TONS OF TOTAL COOLING | | | IN CALCULATIONS BUT SHOWS 1300 CFM AND A LITTLE OVER 3 | | | TONS OF TOTAL COOLING ON SCHEDULE. PLEASE VERIFY THAT | | | ALL INFORMATION IN SYSTEM SIZING CALCULATIONS AND THE | | | IDR CORRESPONDS WITH THE EQUIPMENT SHOWN ON SCHEDULE. | | | | | | 13. M-6.0: FAN SCHEDULE, EF-1 THROUGH EF-11 SHOW THEY | | | ARE TO BE CONTROLLED BY WALL SWITCH. THESE AREAS ARE | | | REQUIRED TO HAVE MECHANICAL EXHAUST IN ACCORDANCE WITH | | | FBC,M TABLE 403.3 AND AS SUCH, ALL AIR SUPPLIED TO SUCH | | | SPACES SHALL BE EXHAUSTED IN ACCORDANCE WITH FBC,M | | | 403.2.1(3). PLEASE SHOW HOW THESE FANS ARE TO BE | | | CONTROLLED IN WAY THAT ASSURES THAT THEY WILL OPERATE | | | WHENEVER AIR IS BEING SUPPLIED TO THESE SPACES (BY AHU | | | OR RTU) AS WELL AS WHENEVER THESE SPACES ARE OCCUPIED | | | IN ACCORDANCE WITH FBC,M 401.3 AND 403.2.1(3). | | | | | | 14. M-6.0: FAN SCHEDULE, EF-14 AND EF-15 HAVE A NOTE | | | (NOTE 5) INDICATING THEY ARE TO BE PROVIDED WITH | | | WEATHER HOODS AND 2 INCH ALUMINUM MESH FILTERS. PLEASE | | | CLARIFY AS IT APPEARS THIS NOTE SHOULD ONLY APPLY TO | | | SF-1 AND SF-2. ALSO, SF-1 AND SF-2 HAVE A NOTE (NOTE 6) | | | INDICATED THEY ARE TO HAVE GREASE DRAINS, HINGED CURBS | | | CAPS, ETC. PLEASE CLARIFY AS IT APPEARS THIS NOTE | | | SHOULD ONLY APPLY TO EF-14 AND EF-15. EQUIPMENT AND | | | APPLIANCES SHALL BE INSTALLED AS REQUIRED BY THE TERMS | | | OF THEIR APPROVAL, IN ACCORDANCE WITH THE CONDITIONS OF | | | THE LISTING, THE MANUFACTURER?S INSTALLATION | | | INSTRUCTIONS AND THIS CODE. FBC 304.1 | | | | | | 15. M-6.0 OUTDOOR AIR SCHEDULE: NOTE (1) INDICATES 50% | | | DIVERSITY USED IN SEVERAL AREAS. THIS IS ASSUMED TO BE | | | A REDUCTION OF THE OUTDOOR AIR RATE BASED ON A LIMITED | | | DURATION OF THE TIME OF OCCUPANCY. THIS IS NOT OFFERED | | | AS AN ADJUSTMENT UNDER FBC,M TABLE 403.3. THERE IS ALSO | | | A NOTE IN THE RTU SCHEDULE INDICATING OUTDOOR AIRFLOW | | | IS TO BE CONTROLLED BY CO2 SENSORS AND MODULATING | | | DAMPERS. IF THE INTENT IS TO DESIGN THE SYSTEM BASED ON | | | ASHRAE 62.1-2004 THEN THAT SHALL BE DECLARED ON PLANS. | | | THE O.A. SCHEDULE INDICATES OA RATES ARE BASED ON TABLE | | | 403.3. IN LIEU OF COMPLIANCE WITH SECTION 403.1 THROUGH | | | SECTION 403.3, MECHANICAL VENTILATION MAY BE | | | IMPLEMENTED IN COMPLIANCE WITH ASHRAE 62.1-2004 | | | INCLUDING APPROVED ADDENDA IN ACCORDANCE WITH FBC,M | | | 403.4. PLEASE INDICATE WHICH METHOD IS TO BE USED AND | | | PROVIDE FULL COMPLIANCE WITH THE METHOD CHOSEN. | | | | | | 16. M-6.0 O.A. SCHEDULE: NOTE (2) INDICATES ?OCCUPANCY | | | PROVIDED BY OWNER.? THE OCCUPANT LOAD IS NOT REQUIRED | | | TO BE DETERMINED, BASED ON THE ESTIMATED MAXIMUM | | | OCCUPANT LOAD RATE INDICATED IN TABLE 403.3 WHERE | | | APPROVED STATISTICAL DATA DOCUMENT THE ACCURACY OF AN | | | ALTERNATE ANTICIPATED OCCUPANT DENSITY (SEE FBC,M 403.3 | | | EXCEPTION). NO SUCH STATISTICAL DATA HAS BEEN PROVIDED | | | TO JUSTIFY THESE OCCUPANT LOADS. ALSO, PG A-2.4 | | | INDICATES THAT THE SOCIAL HALL HAS A POTENTIAL OCCUPANT | | | LOAD OF 711 PERSONS, NOT THE 300 SHOWN ON O.A. | | | SCHEDULE. SELECT THE CORRECT OCCUPANT LOAD FOR THIS | | | AREA AND DESIGN THE VENTILATION SYSTEM TO PROVIDE | | | ADEQUATE VENTILATION IN ACCORDANCE WITH THE METHOD | | | CHOSEN. FBC,M 403.3 AND FBC 106.1.2. | | | | | | 17. M-9.0: PROVIDE MANUFACTURER?S SUBMITTAL DATA | | | SHOWING OUTDOOR EQUIPMENT SUCH AS CONDENSING UNITS, | | | RTU?S, ROOFTOP EXHAUST FANS AND VENTILATORS DESIGNED TO | | | WITHSTAND WIND LOADS IN ACCORDANCE WITH FBC,M 301.13 | | | AND FBC 1609. MANUFACTURER?S INSTRUCTIONS SHALL ONLY BE | | | USED FOR STRAPPING AND CURB ATTACHMENT IF THE DESIGN IS | | | ENGINEERED TO MEET WIND LOAD REQUIREMENTS IN ACCORDANCE | | | WITH THESE SECTIONS. PROVIDE ATTACHMENT DETAIL WIT WIND | | | LOAD CALCULATIONS IF DIFFERENT FROM OR NOT INCLUDED IN | | | MANUFACTURER?S INSTRUCTIONS. FBC 106.1.2. | | | | | | 18. M-9.0 CONDENSER SUPPORT DETAIL: IS THIS TO BE A | | | FIELD-FABRICATED SUPPORT OR A PRE-ENGINEERED A/C STAND? | | | IF A PRE-ENGINEERED STAND IS TO BE USED, PRODUCT | | | APPROVAL IS REQUIRED AS A/C STANDS ARE CLASSIFIED AS | | | STRUCTURAL COMPONENTS BY FAC RULE 9B-72. ALSO, EXTERIOR | | | WALL LOUVERS REQUIRE PRODUCT APPROVAL AS THEY ARE | | | CLASSIFIED AS PANEL WALLS BY RULE 9B-72. PROVIDE ALL | | | SUPPORTING DOCUMENTATION. FOR MORE INFORMATION ON THE | | | FLORIDA PRODUCT APPROVAL SYSTEM PLEASE VISIT | | | WWW.FLORIDABUILDING.ORG. ALSO, THE CLEARANCE UNDER THE | | | A/C SUPPORTS SHALL BE DETERMINED BY THE WIDTH OF THE | | | EQUIPMENT BEING SUPPORTED IN ACCORDANCE WITH FBC TABLE | | | 1509.7. THE 18 INCHES AS STATED ON THE DETAIL MAY OR | | | MAY NOT BE ADEQUATE PER THIS SECTION. | | | | | | 19. M-10.0: IF O.A. DAMPERS ON RTUS ARE TO BE MODULATED | | | BY CO2 SENSORS, THEY SHOULD BE INCLUDED IN THE CONTROL | | | DIAGRAM. FBC 106.1.1. | | | | | | 20. M-11.0: LOCATIONS OF FIRE DAMPERS IS NOT SHOWN ON | | | PLANS. THE SPECIFIC LOCATION AND INSTALLATION DETAILS | | | OF EACH FIRE DOOR, FIRE DAMPER, CEILING DAMPER AND | | | SMOKE DAMPER SHALL BE SHOWN AND PROPERLY IDENTIFIED ON | | | THE BUILDING PLANS BY THE DESIGNER IN ACCORDANCE WITH | | | FBC,M 607.8. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2008-06-04 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-06-04 |
Time |
14:45 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-06-03 |
Time |
12:52 |
Sent To |
|
|
| Notes |
| 2008-06-04 14:50:20 | | | | | | | | | | PASSED/PROVISO | | | | | | REVISION REQUIRED FOR SHT P-14.0. | | | | | | REVISE CONDENSATE RISER C/1 TO SHOW RELIEF VENT LINE | | | FOR CONDENSATE RISER AS INDICATED ON THE FLOOR PLAN. | | | (SHT P-1.0). | | | | | | REVISE CONDENSATE RISER C/5 TO INCLUDE CONDENSATE FROM | | | AHU-15 AS INDICATED ON THE FLOOR PLAN. (SHT P-3.0). | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2008-03-15 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-03-15 |
Time |
08:40 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-03-14 |
Time |
18:52 |
Sent To |
|
|
| Notes |
| 2008-03-15 09:25:28 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 FUEL GAS | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | FBC-2004 BUILDING | | | CITY WPB MUNICIPAL CODE | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | ****FROM PREVIOUS REVIEW: | | | | | | 1. OK | | | 2. OK | | | 3. OK | | | 4. OK | | | 5. OK | | | 6. OK | | | 7. OK | | | 8. OK | | | 9. OK | | | 10. OK | | | 11. OK | | | 12. OK | | | 13. OK | | | 14. OK | | | 15. OK | | | 16. OK | | | 17. OK | | | 18. OK | | | | | | 19. SHT P1.0 SHOWS CONDENSATE TO DISCHARGE 6" ABOVE THE | | | SIDEWALK. THIS IS NOT APPROVED. CONDENSATE SHALL | | | CONNECT TO A DRYWELL, STORM CATCH BASIN, PLANTED AREA | | | OR CONNECT TO A STORM DRAINAGE LINE OUTSIDE THE | | | BUILDING. IF CONNECTING TO A STORM LINE, A RELIEF VENT, | | | (GOOSENECK), SHALL BE REQUIRED AS THE CONDENSATE EXITS | | | THE BUILDING. CONDENSATE DRAINAGE CAN NOT CREATE A | | | HAZARD OR NUISANCE. SECTION 314.2.1. | | | ****RESPONSE NOTED, BUT THE RELIEF VENT, (GOOSENECK), | | | IS NOT INDICATED ON THE PLANS. THE RELIEF VENT WILL | | | KEEP ANY STORM/CONDENSATE FROM ENTERING THE BUILDING | | | AND MAKES THE REQUIREMENT FOR A BACKWATER VALVE MOOT. | | | | | | 20. OK | | | 21. OK | | | | | | 22. SUBMIT A WATER ISOMETRIC WATER RISER DIAGRAM FROM | | | METER, THRU RPZV BACKFLOW, TO THE MOST REMOTE FIXTURE | | | SHOWING ALL PIPE SIZES, VALVES, OFFSETS, & WATER HAMMER | | | ARRESTORS REQUIRED BY SECTION 604.9. WATER HAMMER | | | ARRESTORS SHALL BE LOCATED NEAR THE FIXTURES IN AN | | | "EFFECTIVE RANGE" NOT IN THE CEILING. PDI-WH 201 AND | | | MANUF. INSTALLATION INSTRUCTIONS. SECTION | | | 106.3.5.1.3(3)(10)(13). | | | ****RESPONSE NOTED, BUT SHEET P-12 STATES "CONT. ON SHT | | | P-13.0, BUT NO WATER ISOMETRIC WAS FOUND ON SHE P-13.0. | | | PLEASE CLARIFY. | | | | | | 23. OK | | | 24. OK | | | | | | 25. SHT P-3.0 CONDENSATE LINES SHOW BACKWATER VALVES. | | | PER SECTION 715.1 FIXTURES ABOVE THE ELEVATION OF THE | | | MANHOLE SHALL NOT DISCHARGE THRU A BACKWATER VALVE. | | | WHERE THE POSSIBILITY OF A BACKUP MAY OCCUR, A RELIEF | | | VENT, (GOOSENECK) , SHALL BE INSTALLED AS THE | | | CONDENSATE EXITS THE BUILDING. | | | ****RESPONSE NOTED, BUT THE RELIEF VENT WILL KEEP ANY | | | STORM/CONDENSATE FROM ENTERING THE BUILDING AND MAKES | | | THE REQUIREMENT FOR A BACKWATER VALVE MOOT. | | | | | | 26. OK | | | 27. OK | | | 28. OK | | | 29. OK | | | 30. OK | | | | | | 31. SUBMIT STORM ISOMETRIC RISER DIAGRAMS FOR ALL ROOF | | | DRAINS AND SECONDARY ROOF DRAINS THAT REFLECT THE FLOOR | | | PLAN. SHOW ALL PIPE SIZES, OFFSETS AND INDICATE SQUARE | | | FOOTAGE BEING DRAINED BY EACH ROOF DRAIN. SECTION | | | 106.3.5.1.3(7)(13).--SHOW CLEANOUTS REQUIRED BY | | | SECTION 1101.8. | | | ****RESPONSE NOTED, BUT ISOMETRIC RISER DIAGRAMS FOR | | | RISERS 12 THRU 22 HAVE NOT BEEN SUBMITTED. PLEASE SHOW | | | ALL PIPE SIZES AND INDICATE THE SQUARE FOOTAGE IN THE | | | RISER DIAGRAM AS IT ACCUMULATES IN THE SYSTEM ON THE | | | NEW RISERS AS WELL AS THOSE RISERS SUBMITTED | | | PREVIOUSLY. | | | | | | 32. SUBMIT CONDENSATE ISOMETRIC RISER DIAGRAMS FOR ALL | | | CONDENSATE RISERS THAT REFLECT THE FLOOR PLAN. SHOW | | | PIPE SIZES. OFFSETS AND INDICATE MATERIAL FOR SYSTEM. | | | NO PVC IN PLENUMS. | | | ****RESPONSE NOTED, BUT CONDENSATE RISERS WERE NOT | | | FOUND. | | | | | | 33. OK | | | 34. OK | | | 35. OK | | | 36. OK | | | 37. OK | | | | | | 38. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING | | | INFORMATION IS REQUIRED TO SECURE A PERMIT. | | | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE.-- SHOW ALL PIPING FROM THE METER TO | | | THE MOST REMOTE APPLIANCE. | | | ****RESPONSE NOTED, BUT THE LENGTHS OF PIPE FROM THE | | | METER TO AND INCLUDING THE FIRST DROP, THE FIRST RISE | | | AND SECTION OVER TO THE FIRST RISER, (12FT). ALSO THE | | | DROP OUT OF THE CEILING IS ONLY SHOWN AS 2FT. PLEASE | | | CLARIFY AND SHOW ALL CUT SECTION LENGHTS. | | | | | | B. OK | | | C. OK | | | | | | D. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). --TOTAL DISTANCE FROM | | | THE METER TO THE MOST REMOTE OUTLET IS NOT INDICATED ON | | | THE PLANS. GAS APPLIANCE SCHEDULE NOTE #4 INDICATES | | | 80FT DEVELOPED LENGTH FROM THE REGULATOR, BUT ADDING | | | ALL CUT SECTION LENGTHS PROVIDED ON THE ISOMETRIC | | | SUBMITTED ON SHT P-11.0 197FT IS INDICATED. PLEASE | | | CLARIFY. | | | ****RESPONSE NOTED, BUT ADDITION OF CUT SECTION LENGHTS | | | SHOWN TOTALS 127FT, THIS IS WITH THE SECTIONS FROM THE | | | METER TO AND INCLUDING THE FIRST DROP, AS WELL AS THE | | | FIRST RISE FROM THE PE PIPE AND SECTION TO THE FIRST | | | RISER (12FT) NOT ADDED. A CLARIFICATION FOR THE DROP | | | DOWNSTREAM OF THE SOLINOID VALVE, (2FT),WILL BE | | | REQUIRED TO BE VERIFIED. | | | | | | E. OK | | | | | | F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | ****RESPONSE NOTED, BUT THE LOCATION OF THE INFORMATION | | | ON THE ARCHITECTURAL SHEETS IS NOT INDICATED. ALSO THE | | | LISTING INFORMATION AS WELL AS THE BTU LOAD OF EACH GAS | | | APPLIANCE IS REQUIRED. WILL THIS INFORMATION BE | | | AVAILABLE ON THE ARCHITECTURAL SHEETS? IF NOT SUBMIT | | | MANUF. SPECIFICATION SHEETS TO VERIFY LISTING & BTU | | | LOAD. | | | | | | G. N/A | | | H. N/A | | | | | | I. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. | | | ****RESPONSE NOTED, BUT THE MANUAL SHUT OFF VALVE IS | | | NOT INDICATED, NOR IS THE UNION. ALSO NO INDICATION | | | THAT THE VALVES/UNION ARE BELOW THE CEILING. | | | | | | J. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE | | | SECOND STAGE REGULATOR. INDICATE THE MODEL NUMBER. THE | | | REGULATOR SHALL BE LISTED & INDICATE TOTAL BTU OUTPUT | | | THAT CORRELATES TO THE TOTAL BTU LOAD DOWNSTREAM OF THE | | | REGULATOR. | | | ****RESPONSE NOTED, PLEASE SUBMIT PRIOR TO INSTALLATION | | | TO PREVENT REMOVAL/REPLACEMENT IN CASE REGULATOR IS NOT | | | APPROVED. | | | | | | K. A LISTED SHUTOFF VALVE SHALL BE INSTALLED | | | IMMEDIATELY AHEAD OF EACH MP REGULATOR. SECTION 409.4. | | | --ALSO A UNION WILL BE REQUIRED DOWNSTREAM OF THE | | | SHUT OFF VALVE.PLEASE SHOW ON RISER DIAGRAM. | | | ****RESPONSE NOTED, BUT THE UNION IS NOT INDICATED. | | | | | | **********NEW COMMENT********** | | | | | | 1B. SHT P-11.1 THE UNIT NUMBERS FROM THE GAS APPLIANCE | | | SCHEDULE DO NOT REFLECT THE NUMBERS INDICATED ON THE | | | GAS ISOMETRIC RISER DIAGRAM. PLEASE CORRELATE. SECTION | | | 106.1.1 & TABLE 402.4(2). | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | | FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-11-09 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-11-09 |
Time |
15:31 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-11-03 |
Time |
08:06 |
Sent To |
|
|
| Notes |
| 2007-11-09 18:49:38 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 FUEL GAS | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | FBC-2004 BUILDING | | | CITY WPB MUNICIPAL CODE | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. SHTS L-1, L-2, I-1, I-2 & I-3 THE ADDRESS OF RECORD | | | ON THE FLORIDA STATE DBPR WEBSITE FOR THE LANDSCAPE | | | ARCHITECT DOES NOT REFLECT THE ADDRESS ON THE TITLE | | | BLOCK. PLEASE UPDATE THE DPBR WEBSITE OR THE TITLE | | | BLOCKS PRIOR TO RESUBMITTING FOR REVIEW. FAC | | | 61G1-16.004(1) & FS 481.306. | | | | | | 2. SHT A-1.0 THE COMPLETE FIRM NAME IS REQUIRED IN THE | | | TITLE BLOCK. FAC 61G1-16.004(1) & FS 481.2055. | | | | | | 3. SHT A-1.0 BECAUSE OF MULTIPLE OCCUPANCIES, | | | (BUSINESS, ASSEMBLY, MERCANTILE, & POSSIBLY EDUCATION, | | | (DEPENDING ON THE AGE OF THE STUDENTS & TYPE OF CLASS | | | ROOM EDUCATION), CALCULATIONS FOR MINIMUM FACILITIES IS | | | REQUIRED. TABLES 1004.1.2 & 104.3.1 & SECTION 302.2.1. | | | ALSO POTTY PARITY SHALL BE ADDRESSED AND REQUIRED PER | | | SECTION 403.1.1. | | | | | | 4. SHT A-1.0 SHOWS A SECONDARY KITCHEN. THE GREASE | | | INTERCEPTOR SHALL BE SIZED BY THE UTILITY DEPT., | | | INDUSTRIAL PRETREATMENT, ENVIRONMENTAL COMPLIANCE. | | | PLEASE CONTACT RODNEY COMPO, (561) 822-2272, E-MAIL | | | [email protected] OR CALVIN WILLIAMS (561) 822-2284, | | | E-MAIL [email protected]. THEIR FAX NUMBER IS (561) | | | 822-2287. THEY WILL ISSUE A WRITTEN DETERMINATION FOR | | | THE SIZE & LOCATION OF THE GREASE INTERCEPTOR OF WHICH | | | A COPY WILL BE SUBMITTED WITH THE PLANS WHEN | | | RESUBMITTING FOR REVIEW. | | | | | | 5. SHT A-2.0 WHERE SIX OR MORE STALLS ARE PROVIDED, IN | | | ADDITION TO THE STALL COMPLYING WITH SECTION 11-4.17.3, | | | AT LEAST ONE STALL 36 INCHES WIDE WITH AN OUTWARD | | | SWINGING, SELF-CLOSING DOOR AND PARALLEL GRAB BARS | | | COMPLYING WITH FIG. 30(D)AND SECTION 11-4.26 SHALL BE | | | PROVIDED. SECTION 11-4.22.4. | | | | | | 6. SHT A-2.1 TOILET ROOMS 208 & 209. AN UNOBSTRUCTED | | | TURNING SPACE COMPLYING WITH SECTION 11-4.2.3 SHALL BE | | | PROVIDED WITHIN AN ACCESSIBLE TOILET ROOM. SECTION | | | 11-4.22.3. | | | | | | 7. SHT A-2.1 THE TOILET ROOM ADJACENT TO THE BRIDAL | | | ROOM SHALL BE ACCESSIBLE. PLEASE SHOW COMPLIANCE WITH | | | SECTION 11-4.22 WITH ALL SUBSECTIONS. | | | | | | 8. SHT A-1.0 SUBMIT CALCULATIONS FOR PRIMARY AND | | | SECONDARY ROOF DRAINS PER SECTIONS 1106 & 1107 WITH ALL | | | SUBSECTIONS & TABLES. SHOW THE SQUARE FOOTAGE AREA OF | | | EACH ROOF DRAIN, PLUS 1/2 AREA OF ALL VERTICAL WALLS | | | INCLUDING PARAPETS, AS WELL AS ANY AREA OF A ROOF THAT | | | DRAINS ONTO THE ROOF FROM ABOVE, (IF APPLICIABLE). | | | | | | 9. SHT A-7.0 DETAILS 1 & 2 SHOW COMPLIANCE WITH THE | | | FOLLOWING: | | | ___FOR W/C'S: | | | A. 11-4.16.2 CLEAR FLOOR SPACE | | | B. 11-4.16.3 HEIGHT | | | C. 11-4.16.4 GRAB BARS | | | D. 11-4.16.5 FLUSH CONTROLS | | | E. 11-4.16.6 DISPENSERS | | | ___FOR LAVS: | | | A. 11-4.19.2 HEIGHT & CLEARANCES | | | B. 11-4.19.4 EXPOSED PIPES & CLEARANCES | | | C. 11-4.19.5 FAUCETS | | | WATER CLOSETS SHALL BE 18" OFF THE WALL TO THE | | | CENTERLINE OF THE FIXTURE. FIGURE 28. | | | | | | 10. SHT A-7.0 DETAIL 3, BATHROOM SHALL BE ACCESSIBLE. | | | PLEASE SHOW COMPLIANCE WITH 11-4.16, 11-4.19, 11-4.21 & | | | 11-4.23 WITH ALL SUBSECTIONS AND FIGURES. | | | | | | 11. SHT A-7.0 DETAIL 5. THE TOILET ROOMS SHALL BE | | | ACCESSIBLE. PLEASE SHOW COMPLIANCE WITH SECTIONS | | | 11-4.16, 11-4.17,11-4.19 & 11-4.22 WITH ALL | | | SUBSECTIONS AND FIGURES. W/C'S TO BE 18" OFF THE WALL | | | TO THE CENTERLINE OF THE FIXTURE. FIGURE 28. | | | | | | 12. SHT A-7.0 ALL DETAILS 1 THRU 5. SHOW COMPLIANCE | | | WITH SECTION 1210.2. THE WALLS WITHIN 2FT OF THE W/C'S | | | AND URINALS SHALL HAVE A SMOOTH, HARD, NONABSORBENT | | | SURFACE UP TO 4FT ABOVE THE FLOOR.LEGEND TOILET ROOM | | | ACCESSORIES W-1 INDICATES WAINSCOAT 36" HIGH BUT DETAIL | | | 4 SHOWS TILE TO CEILING. PLEASE CLAIRFY AND CORRELATE. | | | | | | 13. SHT A-7.1 DETAIL 1 SHOW THE TURNING AREA IN THE | | | TOILET ROOM. (NOT REQUIRED IN THE STALL). SECTION | | | 11-4.22.3.--SHOW COMPLIANCE WITH THE FOLLOWING: | | | ___FOR W/C'S: | | | A. 11-4.16.2 CLEAR FLOOR SPACE | | | B. 11-4.16.3 HEIGHT | | | C. 11-4.16.4 GRAB BARS | | | D. 11-4.16.5 FLUSH CONTROLS | | | E. 11-4.16.6 DISPENSERS | | | ___FOR URINALS: | | | A. 11-4.18.2 HEIGHT | | | B. 11-4.18.3 CLEAR FLOOR SPACE | | | C. 11-4.18.4 FLUSH CONTROLS | | | DETAILS 1 & 2 SHOW THE FOLLOWING: | | | ___FOR LAVS: | | | A. 11-4.19.2 HEIGHT & CLEARANCES | | | B. 11-4.19.4 EXPOSED PIPES & CLEARANCES | | | C. 11-4.19.5 FAUCETS | | | D. 11-4.19.6 MIRRORS | | | | | | 14. SHT A-7.1 ALL DETAILS. SHOW COMPLIANCE WITH SECTION | | | 1210.2. WALLS WITHIN 2FT OF WATERCLOSETS AND URINALS | | | SHALL HAVE A SMOOTH, HARD, NONABSORBENT SURFACE. | | | | | | 15. SHT A-7.1 DETAILS 2 & 5 SHOW COMPLIANCE WITH THE | | | FOLLOWING: | | | A. 11-4.19.2 HEIGHT & CLEARANCES | | | B. 11-4.19.4 EXPOSED PIPES & CLEARANCES | | | C. 11-4.19.5 FAUCETS | | | D. 11-4.19.6 MIRRORS | | | | | | 16. SHT A-7.1 DETAIL 6 TOILET ROOM SHALL BE ACCESSIBLE. | | | PLEASE SHOW COMPLIANCE WITH SECTIONS 11-4.16, 11-4.19 & | | | 11-4.22 WITH ALL SUBSECTIONS AND FIGURES. | | | | | | 17. SHT A-7.2 DETAILS 4 & 5 LOUNGE SINK SHALL BE | | | ACCESSIBLE. SHOW COMPLIANCE WITH SECTION 11-4.24 WITH | | | ALL SUBSECTIONS. | | | | | | 18. SHTS S-1 THRU S-10 THE PRINTED NAME AND LICENSE | | | NUMBER SHALL BE LEGIBLY PRINTED IN THE TITLE BLOCKS OF | | | ALL SHEETS. FAC 61G15-23.002(2) & FS 471.025. | | | | | | 19. SHT P1.0 SHOWS CONDENSATE TO DISCHARGE 6" ABOVE THE | | | SIDEWALK. THIS IS NOT APPROVED. CONDENSATE SHALL | | | CONNECT TO A DRYWELL, STORM CATCH BASIN, PLANTED AREA | | | OR CONNECT TO A STORM DRAINAGE LINE OUTSIDE THE | | | BUILDING. IF CONNECTING TO A STORM LINE, A RELIEF VENT, | | | (GOOSENECK), SHALL BE REQUIRED AS THE CONDENSATE EXITS | | | THE BUILDING. CONDENSATE DRAINAGE CAN NOT CREATE A | | | HAZARD OR NUISANCE. SECTION 314.2.1. | | | | | | 20. SHT P-1.0 STORM DRAINAGE IS SHOWN TO CONNECT TO | | | STORMWATER DRAINAGE SYSTEM. "REFER TO CIVIL PLANS FOR | | | CONT". PLESE CLARIFYAS THE STORMWATER DRAINAGE SYSTEM | | | IS NOT SHOWN ON THE CIVIL PLANS. SECTION 106.1.1. | | | | | | 21. SHT P-1.0 SHOW THE HOT AND COLD WATER PIPING ON THE | | | FLOOR PLAN. SECTION 106.3.5.1.3(3)(10). | | | | | | 22. SUBMIT A WATER ISOMETRIC WATER RISER DIAGRAM FROM | | | METER, THRU RPZV BACKFLOW, TO THE MOST REMOTE FIXTURE | | | SHOWING ALL PIPE SIZES, VALVES, OFFSETS, & WATER HAMMER | | | ARRESTORS REQUIRED BY SECTION 604.9. WATER HAMMER | | | ARRESTORS SHALL BE LOCATED NEAR THE FIXTURES IN AN | | | "EFFECTIVE RANGE" NOT IN THE CEILING. PDI-WH 201 AND | | | MANUF. INSTALLATION INSTRUCTIONS. SECTION | | | 106.3.5.1.3(3)(10)(13). | | | | | | 23. SHT P-2.0 SHOW THE HOT & COLD WATER PIPING ON THE | | | FLOOR PLAN. SECTION 106.3.5.1.3(3)(10). | | | | | | 24. SHT P-3.0 BACKFLOW PROTECTION IS REQUIRED ON THE | | | WATER LINES TO THE WATER FOUNTAINS. A VACUUM BREAKER AT | | | THE HIGHEST POINT OF THE SUPPLY LINE TO THE FOUNTAINS | | | WILL BE SUFFICIENT. SECTION 608. | | | | | | 25. SHT P-3.0 CONDENSATE LINES SHOW BACKWATER VALVES. | | | PER SECTION 715.1 FIXTURES ABOVE THE ELEVATION OF THE | | | MANHOLE SHALL NOT DISCHARGE THRU A BACKWATER VALVE. | | | WHERE THE POSSIBILITY OF A BACKUP MAY OCCUR, A RELIEF | | | VENT, (GOOSENECK) , SHALL BE INSTALLED AS THE | | | CONDENSATE EXITS THE BUILDING. | | | | | | 26. SHT P-3.0 NOTE AT THE WATER HEATER INDICATES THE P | | | & T RELIEF VALVE AND EM PAN DRAIN LINE TO BE ROUTED TO | | | A FLOOR DRAIN VIA INDIRECT WASTE. FLOOR DRAINS ARE NOT | | | APPROVED INDIRECT WASTE RECEPTORS. SECTION 802.3. SINCE | | | AN EMERGENCY PAN IS NOT REQUIRED ON THE FIRST FLOOR PER | | | SECTION 504.7 AND THE P & T CAN DISCHARGE ONTO THE | | | FLOOR,THEY ARE NOT REQUIRED TO BE PIPED TO AN | | | INDIRECT WASTE RECEPTOR SO A FLOOR DRAIN WILL BE OK IN | | | THE ROOM BUT NOT AS AN INDIRECT WASTE RECEPTOR. | | | | | | 27. SUBMIT A DETAIL FOR THE WATER HEATER. SHOW | | | COMPLIANCE WITH SECTIONS 503.1, (SHUT OFF VALVE), | | | SECTION 504.2, (IF BOTTOM FED W/H), 504.4, (RELIEF | | | VALVE), 504.6.1, (DISCHARGE), 504.6.2, (MATERIALS) AND | | | SECTION 607.3.2 (THERMAL EXPANSION CONTROL) | | | | | | 28. SHT P-4.0 SUBMIT CALCULATIONS FOR PRIMARY AND | | | SECONDARY ROOF DRAINS. (SEE COMMENT # 8). A CHECK ON | | | TWO ROOF AREAS, ROOF DRAINS #7 & #10 DO NOT SEEM TO | | | INCLUDE ALL SQUARE FOOTAGE FOR THE ROOF AREAS AND/OR | | | VERTICAL CONTRIBUTION. EXAMPLE ROOF DRAIN#7 AREA IS | | | SHOWN AS 1,304SF, BUT A CHECK OF THE AREA INDICATES | | | 1,666SF AND THE ROOF DRAIN #10 AREA IS SHOWN AS 1,962SF | | | BUT A CHECK OF THE AREA INDICATES 2,322SF. PLEASE | | | SUBMIT THE CALCULATIONS SHOWING INFORMATION REQUESTED | | | IN COMMENT #8. SECTIONS 1106 & 1107 WITH ALL | | | SUBSECTIONS AND TABLES. | | | | | | 29. SHT P-5.0 SHOW THE GAS LINE UP TO THE MATCH LINE ON | | | THE FLOOR PLAN. SECTION 106.1.1. | | | | | | 30. SHT P-5.0 THE DISHWASHER, (P-49), SHALL DISCHARGE | | | INTO THE SANITARY SYSTEM, NOT THE GREASE SYSTEM PER | | | ARTICLE III SECTION 90-124(7)(B). PLEASE CONNECT | | | DISHWASHER TO SANITARY. | | | | | | 31. SUBMIT STORM ISOMETRIC RISER DIAGRAMS FOR ALL ROOF | | | DRAINS AND SECONDARY ROOF DRAINS THAT REFLECT THE FLOOR | | | PLAN. SHOW ALL PIPE SIZES, OFFSETS AND INDICATE SQUARE | | | FOOTAGE BEING DRAINED BY EACH ROOF DRAIN. SECTION | | | 106.3.5.1.3(7)(13).--SHOW CLEANOUTS REQUIRED BY | | | SECTION 1101.8. | | | | | | 32. SUBMIT CONDENSATE ISOMETRIC RISER DIAGRAMS FOR ALL | | | CONDENSATE RISERS THAT REFLECT THE FLOOR PLAN. SHOW | | | PIPE SIZES. OFFSETS AND INDICATE MATERIAL FOR SYSTEM. | | | NO PVC IN PLENUMS. | | | | | | 33. SHT P-6.0 PLUMBING GENERAL SPECIFICATIONS 1509(G) | | | AIR CHAMBERS ARE NOT APPROVED. PLEASE DELETE AIR | | | CHAMBERS FROM REFLENCE. SECTION 604.9 AND PDI-WH 201. | | | | | | 34. SUBMIT A WATER ISOMETRIC RISER DIAGRAM THAT | | | REFLECTS THE FLOOR PLAN. SHOW ALL PIPE SIZES, VALVES, | | | (FULL OPEN & SHUT OFF), SECTIONS 606.1 & 606.2, | | | OFFSETS, AND WATER HAMMER ARRESTORS REQUIRED BY SECTION | | | 604.6, (DISHWASHER, WASH MACHINE, ICE MAKER ETC). WATER | | | HAMMER ARRESTORS SHALL BE LOCATED NEAR THE FIXTURES IN | | | AN "EFFECTIVE RANGE" NOT IN THE CEILING PER PDI-WH 201 | | | AND MANUF. INSTALLATION INSTRUCTIONS. | | | | | | 35. SHT P-7.0 KITCHEN EQUIPMENT PLUMBING SCHEDULE ITEM | | | P-58 INDICATES 1-1/2" SANITARY WASTE. A MINIMUM 2" | | | P-TRAP IS REQUIRE PER TABLE 709.1. NOTE INDICATES FS-2 | | | AT THE WASH MACHINE, BUT SHOWS DIRECT CONNECTION TO THE | | | SANITARY SYSTEM. PLEASE CLARIFY. SECTION 106.1.1. | | | | | | 36. SHT P-10.0 THE VENTING FOR TOILET ROOMS 316 & 317 | | | DO NOT SHOW VENT THRU ROOF AS REQUIRED IN SECTION | | | 903.3. PLEASE CLARIFY. | | | | | | 37. SHT P-11.0 SANITARY RISER DIAGRAM THE DISH WASHER | | | SHALL DISCHARGE INTO THE SANITARY SYSTEM, NOT THE | | | GREASE SYSTEM. ARTICLE III SECTION 90-124(7)(B). PLEASE | | | CONNECT DISHWASHER TO SANITARY. | | | | | | 38. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING | | | INFORMATION IS REQUIRED TO SECURE A PERMIT. | | | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE.-- SHOW ALL PIPING FROM THE METER TO | | | THE MOST REMOTE APPLIANCE. | | | | | | B. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE IF BEING USED. | | | | | | C. TYPE OF GAS, (LP OR NATURAL). GAS APPLIANCE SCHEDULE | | | NOTE #4 INDICATES TABLE 402.4(24) WHICH IS LP GAS. | | | | | | D. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). --TOTAL DISTANCE FROM | | | THE METER TO THE MOST REMOTE OUTLET IS NOT INDICATED ON | | | THE PLANS. GAS APPLIANCE SCHEDULE NOTE #4 INDICATES | | | 80FT DEVELOPED LENGTH FROM THE REGULATOR, BUT ADDING | | | ALL CUT SECTION LENGTHS PROVIDED ON THE ISOMETRIC | | | SUBMITTED ON SHT P-11.0 197FT IS INDICATED. PLEASE | | | CLARIFY. | | | | | | E. SUBMIT CALCULATIONS FOR COMBUSTION | | | AIR (IF APPLICABLE) PER FBC-2004 FUEL | | | GAS CODE SECTION 304. -- FOR W/H. | | | | | | F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | | | | G. CLEARLY SHOW THE LOCATION AND CAP- | | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | | OR ASME), THE DISTANCE OF THE TANK FROM | | | THE BUILDING AND ADJACENT PROPERTY LINES | | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | | CES OF IGNITION, OTHER CONTAINERS, BUILD | | | INGS, AND THE LOCATION OF ANY BUILDING | | | OPENINGS BELOW THE RELIEF VALVE OF THE | | | TANK PER NFPA 58, TABLE 3-2.2.2. | | | | | | H. CLEARLY INDICATE ON THE PLAN IF THE | | | LP TANK IS ABOVE OR BELOW GROUND, AND | | | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES | | | PER NFPA 58. IF THE TANK | | | IS BELOW GROUND THE CONTAINER SHALL BE | | | SECURILY ANCHORED PER NFPA 58 SECTION | | | 3-2.2.7(H). | | | | | | I. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. | | | | | | J. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE | | | SECOND STAGE REGULATOR. INDICATE THE MODEL NUMBER. THE | | | REGULATOR SHALL BE LISTED & INDICATE TOTAL BTU OUTPUT | | | THAT CORRELATES TO THE TOTAL BTU LOAD DOWNSTREAM OF THE | | | REGULATOR. | | | | | | K. A LISTED SHUTOFF VALVE SHALL BE INSTALLED | | | IMMEDIATELY AHEAD OF EACH MP REGULATOR. SECTION 409.4. | | | --ALSO A UNION WILL BE REQUIRED DOWNSTREAM OF THE | | | SHUT OFF VALVE.PLEASE SHOW ON RISER DIAGRAM. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | | FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2008-08-20 |
|
|
Cont ID |
|
| Sent By |
kdfreema |
Date |
2008-08-20 |
Time |
16:28 |
Rev Time |
0.00 |
| Received By |
kdfreema |
Date |
2008-08-20 |
Time |
16:28 |
Sent To |
|
|
| Notes |
| 2008-08-20 16:28:34 | ***PROVISO*** | | | | | | SIDEWALK AND FIRE HYDRANT EASEMENTS, TO THE | | | SATISFACTION OF THE CITY ENGINEERING SERVICES | | | DEPARTMENT, SHALL BE RECORDED PRIOR TO THE ISSUANCE OF | | | A CERTIFICATE OF OCCUPANCY. | | | | | | PLEASE CONTACT KELLY FREEMAN, PLANNER, AT (561) | | | 822-1435 OR [email protected] WITH QUESTIONS. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2008-06-02 |
|
|
Cont ID |
|
| Sent By |
kdfreema |
Date |
2008-06-02 |
Time |
14:33 |
Rev Time |
0.00 |
| Received By |
kdfreema |
Date |
2008-06-02 |
Time |
14:33 |
Sent To |
|
|
| Notes |
| 2008-06-02 15:11:41 | ***PROVISO*** | | | | | | SIDEWALK AND FIRE HYDRANT EASEMENTS, TO THE | | | SATISFACTION OF THE CITY ENGINEERING SERVICES | | | DEPARTMENT, SHALL BE RECORDED PRIOR TO THE ISSUANCE OF | | | A CERTIFICATE OF OCCUPANCY. | | | | | | PLEASE CONTACT KELLY FREEMAN, PLANNER, AT (561) | | | 822-1435 OR [email protected] WITH QUESTIONS. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2008-02-07 |
|
|
Cont ID |
|
| Sent By |
kdfreema |
Date |
2008-02-07 |
Time |
15:51 |
Rev Time |
0.00 |
| Received By |
kdfreema |
Date |
2008-02-07 |
Time |
15:51 |
Sent To |
|
|
| Notes |
| 2008-02-07 15:57:28 | ***FAILED*** | | | | | | 1. THE DUMPSTER SIZE SHOWN DOES NOT MEET THE MINIMUM | | | SPECIFICATION REQUIRED BY THE CITY'S ZONING AND LAND | | | DEVELOPMENT REGULATIONS. THE DUMPSTER ENCLOSURE SHOWN | | | ON THE APPROVED SITE PLAN IS COMPLIANT. WE'D PREFER THE | | | WOOD GATES OVER THE CHAIN LINK WITH SLATS. | | | | | | 2. THE OFFICE WINDOWS SHALL BE OPERABLE AS SHOWN IN THE | | | APPROVED SITE PLAN AND REQUIRED BY THE CURRIE MIXED USE | | | DISTRICT REGULATIONS. | | | | | | 3. PROVIDE DOCUMENTATION AS IT RELATES TO THE RECORDING | | | OF THE FIRE HYDRANT AND SIDEWALK EASEMENTS AS REQUIRED | | | BY THE ENGINEERING SERVICES DEPARTMENT. | | | | | | PLEASE CONTACT KELLY FREEMAN, PLANNER, AT (561) | | | 822-1435 OR [email protected] WITH ANY QUESTIONS. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2007-09-12 |
|
|
Cont ID |
|
| Sent By |
kdfreema |
Date |
2007-09-12 |
Time |
10:47 |
Rev Time |
0.00 |
| Received By |
kdfreema |
Date |
2007-09-12 |
Time |
10:47 |
Sent To |
|
|
| Notes |
| 2007-09-12 10:49:34 | ***FAILED*** | | | | | | THIS PROJECT HAS NOT RECEIVED SITE PLAN APPROVAL. NO | | | ZONING REVIEW WILL BE PERFORMED UNTIL THE SITE PLAN HAS | | | BEEN APPROVED. | | | | | | PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 561-822-1435 | | | OR [email protected] WITH QUESTIONS. |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |