Plan Review Details - Permit 07090017
Plan Review Stops For Permit 07090017
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-10-19 Cont ID  
Sent By shill Date 2007-10-19 Time 15:11 Rev Time 0.00
Received By shill Date 2007-10-19 Time 15:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-25 Cont ID  
Sent By shill Date 2007-09-25 Time 09:30 Rev Time 0.00
Received By shill Date 2007-09-25 Time 09:30 Sent To  
Notes
2007-09-25 09:31:32****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.)THE POOL IS TO COMPLY WITH SAFETY REQUIREMENTS OF
 FBC4101.17.REVISE THE PLAN TO SHOW COMPLIANCE.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-10-11 Cont ID  
Sent By btrobaug Date 2007-10-11 Time 15:05 Rev Time 0.00
Received By btrobaug Date 2007-10-11 Time 14:55 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-09-17 Cont ID  
Sent By btrobaug Date 2007-09-11 Time 14:57 Rev Time 0.00
Received By btrobaug Date 2007-09-11 Time 14:56 Sent To P
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2007-10-17 Cont ID  
Sent By mperson Date 2007-10-17 Time 12:14 Rev Time 0.00
Received By mperson Date 2007-10-17 Time 12:13 Sent To B
Notes
2007-10-17 12:14:53NOTE: THERE IS NO POOL HEATER ON PLANS.

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2007-09-25 Cont ID  
Sent By mperson Date 2007-09-25 Time 09:15 Rev Time 0.00
Received By mperson Date 2007-09-25 Time 09:16 Sent To B
Notes
2007-09-25 09:17:10NOTE: THERE IS NO POOL HEATER ON PLANS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-05 Cont ID  
Sent By adarroug Date 2007-10-05 Time 16:12 Rev Time 0.00
Received By adarroug Date 2007-10-05 Time 16:12 Sent To Z
Notes
2007-10-05 16:12:28TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-09-25 Cont ID  
Sent By shill Date 2007-09-25 Time 09:31 Rev Time 0.00
Received By shill Date 2007-09-06 Time 08:47 Sent To  
Notes
2007-09-06 08:47:32TO "Z" BOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-10-17 Cont ID  
Sent By mperson Date 2007-10-17 Time 12:13 Rev Time 0.00
Received By mperson Date 2007-10-17 Time 12:13 Sent To G
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-09-25 Cont ID  
Sent By mperson Date 2007-09-25 Time 08:35 Rev Time 0.00
Received By mperson Date 2007-09-25 Time 08:35 Sent To G
Notes
2007-09-25 09:15:33DENIED
 REFERENCE:
 ** FBC-2004 WITH 2006 REVISIONS SECTIONS 424.2 AND
 R4101 SWIMMING POOLS.
 ** FBC-2004 WITH 2006 REVISIONS, PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 1. THE EQUIPMENT LAYOUT AND LEGEND ITEM NUMBERS TWO
 (2) AND FIVE (5) ARE INDICATING A TOTAL OF FOUR (4)
 1-1/2" WALL FOUNTAIN SUPPLY LINES BUT THE POOL PLAN IS
 ONLY INDICATING THREE (3) 1-1/2" WALLFEATURES. ARE
 THE WALL FEATURES THE SAME AS THE WALL FOUNTAIN SUPPLY
 LINE? PLEASE CLARIFY AND CORRELATE THE PLANS ON THE
 RESUBMITTAL PER FBC-2004 CHAPTER 1, SECTION 106.1.1
 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS,
 AS DETERMINED BY THE
 BUILDING OFFICIAL.
  
 2. INDICATE THAT THE AUTO FILL LINE IS TO BE PROTECTED
 FROM CROSS CONNECTION PER FBC-2004 W/2006 REV. PLUMBING
 SECTION 608.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2007-10-25 Cont ID  
Sent By choops Date 2007-10-25 Time 15:34 Rev Time 0.00
Received By choops Date 2007-10-25 Time 15:34 Sent To E
Notes
2007-10-25 15:35:52***APPROVED - RESUB #1***

Review Stop Z ZONING
Rev No 1 Status F Date 2007-09-10 Cont ID  
Sent By choops Date 2007-09-10 Time 10:09 Rev Time 0.00
Received By choops Date 2007-09-10 Time 10:09 Sent To E
Notes
2007-09-10 10:11:27***FAILED***
  
  
 1)AS THE SURVEY DOES NOT SHOW AN EXISTING PERMANENT
 FENCE COMPLETELY SURROUNDING THE POOL, A FENCE PERMIT
 SHALL BE SUBMITTED CONCURRENTLY AND SHALL CONFORM TO
 THE MINIMUM STANDARDS PROVIDED BELOW.
  
 PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND LAND
 DEVELOPMENT REGULATIONS, SECTION, 94-304(D)(2)(B)+(C):
  
 B.EVERY SWIMMING POOL SHALL BE ENCLOSED BY A FENCE
 OR SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT
 ACCESS BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF
 THE RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED.
 BARRIERS OR FENCES SHALL BE AT LEAST FOUR FEET IN
 HEIGHT ABOVE GRADE.
 C.ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE
 THROUGH A BUILDING OR THROUGH A SELF-CLOSING AND
 SELF-LATCHING GATE OR THROUGH A SCREEN ENCLOSURE DOOR
 WITH LATCHES PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF
 GATE. AT LEAST 90 PERCENT OF THE SURFACE AREA OF ALL
 SCREEN ENCLOSURES SHALL BE SCREENING MATERIAL THROUGH
 WHICH AIR SHALL FLOW. ALL POOLS LOCATED ON A CORNER LOT
 SHALL BE SCREENED AT THE CORNER LOT LINE BY AT LEAST A
 42-INCH HIGH LANDSCAPE BUFFER, AS MEASURED FROM GRADE,
 AT THE PROPERTY LINE, TO ENSURE PRIVACY.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720