Plan Review Details - Permit 07090014
Plan Review Stops For Permit 07090014
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-10-23 Cont ID  
Sent By shill Date 2007-10-23 Time 08:37 Rev Time 0.00
Received By shill Date 2007-10-23 Time 08:37 Sent To  
Notes
2007-10-23 08:38:36****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.THE PURPOSE OF THE PAPERWORK IS NOT CLEAR.IF YOU
 ARE CHANGING PRODUCTS, COMPLETE A NEW INSTALLATION
 SCHEDULE AND SUBMIT TWO SETS (INSTALL. SCHEDULE AND
 PRODUCT APPROVALS) AS A REVISION.THIS IS NOT A
 SUBMITTAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-09-18 Cont ID  
Sent By shill Date 2007-09-18 Time 17:58 Rev Time 0.00
Received By shill Date 2007-09-18 Time 17:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-11 Cont ID  
Sent By shill Date 2007-09-11 Time 07:52 Rev Time 0.00
Received By shill Date 2007-09-11 Time 07:52 Sent To  
Notes
2007-09-11 07:53:31****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
  
 SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY
  
 ____1.PROVIDE BUILDING HEIGHT ON THE PLAN.DESIGN
 PRESSURES FOR BUILDINGS OVER 60FEET ARE REQUIRED TO BE
 DESIGNED USING ASCE7, FBC1609.1.1 AND MUST BE DONE BY A
 DESIGN PROFESSIONAL. DOCUMENTS PREPARED BY AN ARCHITECT
 OR ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED SEALED ORIGINALS FAC61G15, FAC61G1 16.
  
 ____2.PROVIDE A COPY OF THE CONDO ASSOCIATION
 APPROVAL.
  
 _XX_3.COMPLETE THE ATTACHED INSTALLATION SCHEDULE
 OR PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN
 ANOTHER FORMAT, FBC*106.
  
 ____4.FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED, FAC9B72, WWW.FLORIDABUILDING.ORG.
  
 ____5.SHOW THE EMERGENCY MEANS OF ESCAPE, FBC
 R310.
  
 _XX_6.PROVIDE A FLOOR PLAN SHOWING WHERE THE
 SHUTTERS WILL BE INSTALLED AND PANEL SIZES WHICH
 CORRELATES WITH THE INSTALLATION SCHEDULE, ITEM 3
 ABOVE.
  
 ____8.REVISE EXPOSURE CATEGORY FBC1609.6.2.1(2),
 FBC R301.2.1.4.NOTE THAT THE DEFINITION FOR EXPOSURE
 C HAS CHANGED EFFECTIVE DECEMBER 8, 2006 FBC1609.4, FBC
 R301.2.1.4.
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-10-24 Cont ID  
Sent By adarroug Date 2007-10-24 Time 14:27 Rev Time 0.00
Received By adarroug Date 2007-10-24 Time 14:27 Sent To B
Notes
2007-10-24 14:28:14TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-10-15 Cont ID  
Sent By adarroug Date 2007-10-15 Time 16:09 Rev Time 0.00
Received By adarroug Date 2007-10-15 Time 16:09 Sent To B
Notes
2007-10-15 16:10:07TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-09-14 Cont ID  
Sent By adarroug Date 2007-09-14 Time 14:04 Rev Time 0.00
Received By adarroug Date 2007-09-14 Time 14:04 Sent To B
Notes
2007-09-14 14:05:04TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-09-11 Cont ID  
Sent By shill Date 2007-09-11 Time 07:53 Rev Time 0.00
Received By shill Date 2007-09-06 Time 08:53 Sent To  
Notes
2007-09-06 08:53:53TO "MISC" BOX#1