Plan Review Details - Permit 07080957
Plan Review Stops For Permit 07080957
Review Stop AD ADDRESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By jjohnsto Date 2007-09-27 Time 08:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-27 Cont ID  
Sent By jjohnsto Date 2007-09-27 Time 09:40 Rev Time 1.75
Received By jjohnsto Date 2007-09-27 Time 08:00 Sent To  
Notes
2007-09-27 09:39:48CONSTRUCTION SERVICES DEPARTMENT
 200 SECOND STREET, 3RD FLOOR, WEST PALM BEACH,
 FLORIDA33401
 TEL:561-805-6713FAX:
 561-805-6731
  
 JAMES JOHNSTON, PERMIT NO 07080957
 BUILDING PLAN EXAMINERII
 PROJECT HOBBS RESIDENCE
 E-MAIL:JJOHNSTON @WPB.ORG ADDRESS
 4100 BROADWAY
  DATE SEPTEMBER 26, 2007
  
 STRUCTURALPLANREVIEW
  
  
  
 REVISION SUBMITTAL
 WHEN RE-SUBMITTING PERMITTED PLANS PLEASE INDICATE BY
 CLOUDING THE REVISION. REMOVE AND REPLACE ANY SHEETS AS
 NECESSARY.INCLUDE A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE. ALSO IDENTIFY THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND AND
 INCLUDE THE OLD SHEETS IN THE RE-SUBMITTAL PACKAGE FOR
 THE PLAN REVIEWER?S REFERENCE.
 THIS SHALL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
 COMMENT-FOR YOUR INFORMATION
  
 F.S.713.13NOTICE OF COMMENCEMENT
 FILE NOTICE WITH THE CLERK OF COURT RECORDING DIVISION.
 IF THE WORK DESCRIBED IN THE NOTICE IS NOT COMMENCED
 WITHIN 90 DAYS OF FILING THE NOTICE WILL BECOME NULL
 AND VOID. SUBMIT THE NOTICE AT THE TIME OF PERMIT
 ISSUANCE AND POST A COPY AT THE JOB SITE BEFORE THE
 FIRST INSPECTION.
 COMMENT-FOR YOUR INFORMATION
  
 NOTE ON COVER SHEET
 FBC2004 BUILDING RESIDENTIALW 2006 REVISIONS
 FBC2004 BUILDING EXISTING
 FBC2004 BUILDING W/ 2006 REVISIONS
 LEVEL OF ALTERATION
 TYPE OF CONSTRUCTION / SPRINKLED / UN-SPRINKLED
 TYPE OF CONSTRUCTION
 WIND SPEED AND EXPOSURE
 WIND IMPORTANCE FACTOR
 TYPE OF OCCUPANCY
 OCCUPANT LOAD
 GROSS LOAD
 NET LOAD
  
  
  
 DOCUMENTS SIGNED AND SEALED
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL
 AND BEING FILED FOR PUBLIC RECORD SHALL HAVE THE
 SIGNATURE AND SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT WITH THE DATE.
 COMMENT-DESIGNEROF RECORD MUST SIGN PRODUCT
 APPROVALS FOR ACCEPTANCE OF USE ON THIS PROJECT
  
 M& I DESIGN INC.
 THIS FIRM IS NOT A REGISTERED DESIGN FIRM
 481.2131INTERIOR DESIGN; PRACTICE REQUIREMENTS;
 DISCLOSURE OF COMPENSATION FOR PROFESSIONAL SERVICES.--
  
 (1)A REGISTERED INTERIOR DESIGNER IS AUTHORIZED TO
 PERFORM "INTERIOR DESIGN" AS DEFINED IN S. 481.203.
 INTERIOR DESIGN DOCUMENTS PREPARED BY A REGISTERED
 INTERIOR DESIGNER SHALL CONTAIN A STATEMENT THAT THE
 DOCUMENT IS NOT AN ARCHITECTURAL OR ENGINEERING STUDY,
 DRAWING, SPECIFICATION, OR DESIGN AND IS NOT TO BE USED
 FOR CONSTRUCTION OF ANY LOAD-BEARING COLUMNS,
 LOAD-BEARING FRAMING OR WALLS OF STRUCTURES, OR
 ISSUANCE OF ANY BUILDING PERMIT, EXCEPT AS OTHERWISE
 PROVIDED BY LAW. INTERIOR DESIGN DOCUMENTS THAT ARE
 PREPARED AND SEALED BY A REGISTERED INTERIOR DESIGNER
 MAY, IF REQUIRED BY A PERMITTING BODY, BE SUBMITTED FOR
 THE ISSUANCE OF A BUILDING PERMIT FOR INTERIOR
 CONSTRUCTION EXCLUDING DESIGN OF ANY STRUCTURAL,
 MECHANICAL, PLUMBING, HEATING, AIR-CONDITIONING,
 VENTILATING, ELECTRICAL, OR VERTICAL TRANSPORTATION
 SYSTEMS OR THAT MATERIALLY AFFECT LIFE SAFETY SYSTEMS
 PERTAINING TO FIRE SAFETY PROTECTION SUCH AS FIRE-RATED
 SEPARATIONS BETWEEN INTERIOR SPACES, FIRE-RATED
 VERTICAL SHAFTS IN MULTISTORY STRUCTURES, FIRE-RATED
 PROTECTION OF STRUCTURAL ELEMENTS, SMOKE EVACUATION AND
 COMPARTMENTALIZATION, EMERGENCY INGRESS OR EGRESS
 SYSTEMS, AND EMERGENCY ALARM SYSTEMS.
 WINDOWS / DOORS PRODUCT APPROVALS
 WPB ADMINISTRATIVE CODE 106.3 REGULATED BY DCA RULE
 9B-72FLORIDA PRODUCT APPROVAL
 SUBMIT TWO COPIES OF EACH APPROVAL WITH FLORIDA PRODUCT
 APPROVAL COVER SHEET THE ARCHITECT?S / ENGINEER?S
 SIGNATURE AS APPLICABLE, STATING ?TO THE BEST OF THEIR
 KNOWLEDGE THE PRODUCT APPROVAL COMPLIES WITH THE PLANS
 AND SPECIFICATIONS.SEE:WEB SITE
 WWW.FLORIDABUILDING.COM
 NOTE: SEE DIVISION FACTOR TO BE USED IN DESIGN PRESSURE
 BY LEGACYFPA
 COMMENT-FOR YOUR INFORMATION
  
  
 SUBMIT PRODUCT APPROVALS WITH FLORIDA PRODUCT APPROVAL
 COVER
 PAGE FOR THE FOLLOWING
 FIXED GLASS
 MULLION TUBES
 WINDOWS
 EXTERIOR DOORS
 SLIDING GLASS DOORS
 HOLLOW METAL DOORS
 WOOD DOORS
 TRUSS ANCHORS
 STORE FRONT GLAZING SYSTEM
 COMMENT-FOR YOUR INFORMATION
  
  
 1. THE STATE OF FLORIDA CONTRACTOR QUALIFIED BUSINESS
 LICENSE NUMBER QB 23968EXPIRED2005
 YOU CAN RENEW THIS LICENSE NUMBER ON LINE AT
 WWW.MYFLORIDALICENSE.COM
 THEN BRING RENEWED LICENSE TO WPB DEPT. TO REMOVE HOLD
  
 2. DEMOLITION SHEET
  DESCRIBE THE SCOPE OF WORK BEING COMPLETED AND THE
 INTENT.ARE YOU CHANGING THE OCCUPANCY FROM A
 RESIDENCE TO A BUSINESS, OR TO A RESIDENCE AND A
 BUSINESS?
  
 THE PLANS MUST COMPLY WITH ALL CODES RELATING TO THIS
 PROJECT INCLUDING BUT NOT LIMITED TO DESIGN PRESSURES
 ON THE BUILDING ZONES, WINDOW PRESSURES,FIRE RATINGS
 AS THEY APPLY TO BUILDING COMPONENTS, CHAPTER 13 ENERGY
 CALCULATIONS, CHAPTER 11 HANDICAP ACCESSIBILITY CODES,
 PARKING AS IT WILL APPLY, AND A TOTAL DESIGN OF
 EXISTING CONDITIONS, DIMENSIONS AND ALL OTHER RELATED
 COMPONENTS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-09-23 Cont ID  
Sent By dpalmer Date 2007-09-23 Time 11:16 Rev Time 0.00
Received By dpalmer Date 2007-09-23 Time 10:52 Sent To I
Notes
2007-09-23 11:17:362007-09-23 11:17:36
  
 PLANS REMOVED FROM INCOMING FOR REVIEW. ROUTED BACK TO
 INCOMING WHERE PLANS ARE WAITING FOR COMM BOARD.
2007-09-23 11:16:532007-09-23 11:16:53
  
 ** DENIED**
  
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED
 FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS
 NOT MADE BY OTHER TRADE(S).
  
 2) NOTE: PLEASE SEE THE ADDRESS FOR UNIT/SUITE SHALL BE
 STATED ON PERMIT APPLICATION AND TITLE BLOCKS FOR
 PLANS.
 A COPY OF PERMIT APPLICATION WAS ROUTED TO ADDRESSING
 REVIEWER. PLEASE BE AWARE OF ANY DESIGNATIONS WHICH MAY
 BE ASSIGNED.
  
 3) NOTE: PLEASE PROVIDE LICENSE INFORMATION FOR MI
 DESIGN. PLEASE SEE FS 481.229, 471.003 AS A
 DESIGNER/DRAFTSMAN MAY NOT PERFORM SCOPE OF WORK AS
 SHOWN ON PLANS.
  
 4) NOTE: PLEASE SEE THE NEW ELECTRICAL SERVICE BEING
 PROPOSED IS NOT PERMITTED OR GRANTED PER 230.2. PLEASE
 SEE THIS WILL BE REVIEWED BY ZONING AND BUILDING WHICH
 MAY PERMIT THIS AS A TENANT SPACE WHICH WOULD STILL
 REQUIRE ELECTRICAL TO BE FED FROM THE EXISTING SERVICE
 OR UPGRADE THE EXISTING SERVICE IF NOT SUFFICIENT.
 PLEASE ALSO SEE COMMENTS BELOW AS A REVIEW OF PLANS
 SUBMITTED WILL BE DONE EVEN AS SERVICE AS SHOWN IS NOT
 PERMITTED.
  
 5) NOTE: PLEASE SEE PLANS INDICATE PANEL AS 200AMPS,
 YET RISER SHOWS THIS PANEL AS 150AMPS.
 PLEASE CORRELATE, HOWEVER SEE NOTE ABOVE AS SERVICE
 RISER WILL REQUIRE A COMPLETE CHANGE.
 FBC 106.3.5.1.2, 106.1.2
  
 6) NOTE: PLEASE SEE THE CALCULATIONS AS SUBMITTED ARE
 SHOWN FOR A RESIDENTIAL UNIT. THIS IS FOR COMMERCIAL
 AND CALCULATIONS ARE NOT THE SAME.
 PLEASE BE SURE TO SEE THAT ALL CONTINUOUS LOADS ARE TO
 BE FIGURED AT 125%.
 PLEASE SEE 220.12,220.14,220.42,220.43,220.44, ETC
 215.3, 230.42
 PLEASE SEE 422.13 UNDER THE 2005 NEC WHICH NOW REQUIRES
 WATER HEATER LOADS TO BE FIGURED AT 125%.
  
 7) NOTE: PLEASE SEE MISSING DEDICATED SIGN CIRCUIT PER
 600.5 AND LOADS ON LOAD CALCULATIONS REQUIRED FOR SIGN
 CIRCUIT.
  
 8) NOTE: PLEASE SEE MISSING SHOW WINDOW RECEPTACLES PER
 210.62 AND LOADS TO BE FIGURED PER 220.43
  
 9) NOTE: PLEASE SEE 700.12FFOR CIRCUITING OF
 EMERGENCY AND EXIT LIGHTS. THE CIRCUITING AS SHOWN IS
 NOT CODE COMPLIANT.
  
 10) NOTE: PLEASE SEE MISSING GFI RECEPTACLE FOR OUTSIDE
 CU. PER 210.63, 210.8B
  
 11) NOTE: PLEASE SEE THE OVER CURRENT PROTECTION FOR
 THE AHU/AIR HANDLER UNIT HEAT IS TOO LOW. PLEASE SEE
 424.3B FOR MINIMUM OCP.
  
 12) NOTE: PLEASE SEE FBC CHAPTER 13 FOR LIGHTING
 CALCULATIONS AND PERFORMANCE CALCULATIONS.
 PLEASE SEE 13-415.1.B, 13-415.1.C, 13-415.2
 PLEASE SEE AS NO DESIGN WAS SUBMITTED FOR CHAPTER 13
 COMPLIANCE, NO REVIEW CAN BE DONE.
 PLEASE SEE MISSING ENERGY CALCULATIONS.
  
 13) NOTE: PLEASE SEE THE LOCATIONS OF EXIT AND
 EMERGENCY LIGHTING FIXTURES NEED TO BE GONE OVER WITH
 THE LS CODE, NFPA-101 7.8 AND 7.9.
 PLEASE SEE POSSIBLE COMMENTS FROM THE FIRE MARSHAL
 AND/OR BUILDING REVIEWER.
  
 ** PLEASE KNOW AS THERE ARE NUMEROUS ITEMS WHICH NEED
 TO BE CORRECTED AND/OR ARE NOT SUBMITTED YET FOR
 REVIEW, THERE MAY VERY WELL BE NEW NOTES ON THE NEXT
 REVIEW.
 PLEASE BE SURE TO SEE COMMENT #3 AS NOTED ABOVE.
 LICENSED PROFESSIONALS WITH KNOWLEDGE OF WORK BEING
 PERFORMED MAY ONLY SIGN AND SEAL PLANS.
 PLEASE SEE FS 471.025 FOR ENGINEERS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-10-23 Cont ID  
Sent By mwennerg Date 2007-10-23 Time 12:49 Rev Time 0.00
Received By mwennerg Date 2007-10-23 Time 12:49 Sent To  
Notes
2007-10-23 13:06:36***DENIED***
  
 1) PLEASE ADVISE OCCUPANCY TYPE FOR ENTIRE BUILDING.
  
 2) 2A-10B,C RATED FIRE EXTINGUISHERS ARE REQUIRED.
 PLEASE SHOW LOCATIONS.
  
 3) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION.
  
 4) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 5) A COMBINATION EXIT/EMERGENCY SIGN IS SHOWN WITH NO
 DOOR PRESENT. IS THAT A DIRECTIONAL SIGN?
  
 6) SMOKE DETECTORS ARE SHOWN ON THE ELECTRICAL PLAN. IS
 THAT EQUIPMENT REQUIRED?
  
 7) EMERGENCY LIGHTS ON ONE OF THE EXIT SIGNS ARE
 POSITIONED TOWARD THE EXTERIOR OF THE BUILDING.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By adarroug Date 2007-09-04 Time 09:52 Sent To  
Notes
2007-09-24 16:27:41TO "COMM" BD#44
2007-09-04 09:55:16WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-10-24 Cont ID  
Sent By hmoser Date 2007-10-24 Time 18:15 Rev Time 0.00
Received By hmoser Date 2007-10-24 Time 18:15 Sent To  
Notes
2007-10-24 18:29:15PLAN DENIED
 1- PLEASE INDICATE ON PLANS WHERE THE 24X12 RTG IS
 GOING.
 2- PLEASE REFER TO SECTION 602.2.1 MATERIALS EXPOSED
 WITHIN PLENUMS 2004 FBC (M) ( CONDENSATE MUST BE COPPER
 )
 3- PLEASE REFER TO TABLE 403.3 REQUIRED OUTDOOR
 VENTILATION . 2004 FBC(M)
 4-PLEASE INDICATE ON PLANS THE TERMINATION OF THE
 CONDENSATE LINE.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2007-10-01 Cont ID  
Sent By bpowell Date 2007-10-01 Time 17:35 Rev Time 0.00
Received By bpowell Date 2007-10-01 Time 17:35 Sent To  
Notes
2007-10-01 17:47:331.PLEASE PROVIDE TWO COPIES OF A SURVEY OF THE
 PROPERTY.
  
 2. THE SITE PLAN SHALL INDICATE THE DIRECTION WITH A
 NORTH ARROW.
  
 FOR ANY QUESTIONS OR COMMENTS PLEASE CALL;
 BOBBY POWELL JR.
 PLANNER, 822-1435