Plan Review Details - Permit 07080952
Plan Review Stops For Permit 07080952
Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2008-09-12 Cont ID  
Sent By mjacobs Date 2008-09-12 Time 11:19 Rev Time 0.00
Received By mjacobs Date 2008-09-12 Time 10:33 Sent To Z
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2008-08-08 Cont ID  
Sent By mjacobs Date 2008-08-08 Time 11:17 Rev Time 0.00
Received By mjacobs Date 2008-08-08 Time 10:22 Sent To PC
Notes
2008-08-08 11:17:46 
  
 106.1.3* THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. AS REQUESTED PREVIOUSLY, ALL
 CHANGES TO EACH SHEET SHALL BE IDENTIFIED BY CLOUDS,
 DATE AND A REVISION NUMBER FOR THE CHANGE. SHEET A.1
 REVISION CHANGES SHOWS REVISIONS 1-6, BUT THE SHEET
 SHOWS REVISIONS #5 WHICH IS NOT CLOUDED AND REVISION #7
 WHICH IS NOT ON THE REVISION LIST. ONLY THE REVISIONS
 WHICH AFFECT THIS PAGE SHALL BE INDICATED; THE ONES
 WHICH DO NOT AFFECT THIS PAGE SHALL BE REMOVED, AND BE
 INDICATED ON THE APPROPRIATE PAGE. THIS GOES FOR ALL
 SHEETS. THE CHANGES TO THE BATHROOM ARE NOT INDICATED
 ON THE NEW SHEETS.
  
 NOTED: HOWEVER, THE MECHANICAL PLANS SHOW FOUR NEW
 OPENINGS FOR INTAKE LOUVERS: THE ARCHITECTURAL PLANS
 SHALL REFLECT THE OPENINGS SHOWN ON THE MECHANICAL
 PLANS. DETAILED ELEVATION DRAWINGS SHALL BE SUBMITTED
 INDICATING HOW THE LOUVERS AND MOTORIZE DAMPER WILL BE
 ATTATCH TO THE OPENINGS. SHOW ALL DIMENSIONS ON THE
 ELEVATION DRAWINGS. TWO SETS OF PRODUCT APPROVALS ARE
 REQUIRED FOR THE LOUVERS.
 1)THE REVISED SHEET NEEDS TO INDICATE ALL THE CHANGES
 WITH THE CLOUDED SYMBOL AND THE REVISION NUMBER NEXT TO
 IT AROUND THE CHANGED AREA. THE ADDITIONAL PLUMBING
 SYSTEMS SHALL BE INDICATED ALONG WITH THE RELOCATION OF
 THE DOORS AND WALLS ETC. AGAIN PLEASE SHOW ALL CHANGES
 WITH IDENTIFIABLE SYMBOLS AND THE REVISION NUMBER.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED. 106.1.1
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2008-07-11 Cont ID  
Sent By mjacobs Date 2008-07-11 Time 13:50 Rev Time 0.00
Received By mjacobs Date 2008-07-11 Time 10:28 Sent To PC
Notes
2008-07-11 13:46:54BUILDING PLAN REVIEW
 PERMIT: 07080952
 ADD: 310 FLAMINGO RD.
 CONT: ISLAND CONSTRUCTION
 TEL: (561)804-9376
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: REVISION
 ACTION: DENIED
  
 NOTED: HOWEVER, THE MECHANICAL PLANS SHOW FOUR NEW
 OPENINGS FOR INTAKE LOUVERS: THE ARCHITECTURAL PLANS
 SHALL REFLECT THE OPENINGS SHOWN ON THE MECHANICAL
 PLANS. DETAILED ELEVATION DRAWINGS SHALL BE SUBMITTED
 INDICATING HOW THE LOUVERS AND MOTORIZE DAMPER WILL BE
 ATTATCH TO THE OPENINGS. SHOW ALL DIMENSIONS ON THE
 ELEVATION DRAWINGS. TWO SETS OF PRODUCT APPROVALS ARE
 REQUIRED FOR THE LOUVERS.
 1)THE REVISED SHEET NEEDS TO INDICATE ALL THE CHANGES
 WITH THE CLOUDED SYMBOL AND THE REVISION NUMBER NEXT TO
 IT AROUND THE CHANGED AREA. THE ADDITIONAL PLUMBING
 SYSTEMS SHALL BE INDICATED ALONG WITH THE RELOCATION OF
 THE DOORS AND WALLS ETC. AGAIN PLEASE SHOW ALL CHANGES
 WITH IDENTIFIABLE SYMBOLS AND THE REVISION NUMBER.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED. 106.1.1
  
 2)OK
  
 NOTE: THE GENERATOR SHALL BE SUBMITTED UNDER 'A
 SEPERATE PERMIT.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2008-06-24 Cont ID  
Sent By mjacobs Date 2008-06-24 Time 11:17 Rev Time 0.00
Received By mjacobs Date 2008-06-24 Time 09:40 Sent To P
Notes
2008-06-24 11:17:21BUILDING PLAN REVIEW
 PERMIT: 07080952
 ADD: 310 FLAMINGO RD.
 CONT: ISLAND CONSTRUCTION
 TEL: (561)804-9376
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: REVISION
 ACTION: DENIED
  
 1)THE REVISED SHEET NEEDS TO INDICATE ALL THE CHANGES
 WITH THE CLOUDED SYMBOL AND THE REVISION NUMBER NEXT TO
 IT AROUND THE CHANGED AREA. THE ADDITIONAL PLUMBING
 SYSTEMS SHALL BE INDICATED ALONG WITH THE RELOCATION OF
 THE DOORS AND WALLS ETC. AGAIN PLEASE SHOW ALL CHANGES
 WITH IDENTIFIABLE SYMBOLS AND THE REVISION NUMBER.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED. 106.1.1
  
 2)THE DRAWINGS NEED TO INDICATE THE TYPE OF FLOOR AND
 WALL FINISHES FOR THE NEW SHOWER AND MOP SINK/ LAUNDRY
 TUB AREAS PER R307. THE TYPE OF GLAZING, IF ANY, SHALL
 MEET THE REQUIREMENTS OF R308. (ROOMS 105 AND 105A)
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status N Date 2008-04-18 Cont ID  
Sent By mjacobs Date 2008-04-18 Time 10:45 Rev Time 0.00
Received By mjacobs Date 2008-04-17 Time 15:28 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-03-13 Cont ID  
Sent By mjacobs Date 2008-03-13 Time 07:41 Rev Time 0.00
Received By mjacobs Date 2008-03-13 Time 06:57 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-02-21 Cont ID  
Sent By mjacobs Date 2008-02-21 Time 07:53 Rev Time 0.00
Received By mjacobs Date 2008-02-20 Time 11:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-12-18 Cont ID  
Sent By jwitmer Date 2007-12-18 Time 13:02 Rev Time 3.33
Received By jwitmer Date 2007-12-18 Time 13:02 Sent To  
Notes
2007-12-18 13:30:12BUILDING PLAN REVIEW
 PERMIT: 07080952
 ADD: 310 FLAMINGO DRIVE
 CONT: ISLAND CONSTRUCTION
 TEL: (561)236-9983
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 2-3) COMPLIED.
  
 4) PARTIALLY COMPLIED. PLANS DO INDICATE A LEVEL II
 ALTERATION, THE APPLICABLE CODES ARE 2004 FBC WITH 2007
 REVISIONS ORSUPPLEMENTS 2004 EXISTING BUILDING CODE,
 AND THE 2004 RESIDENTIAL CODE WITH 2007 REVISIONS OR
 SUPPLEMENTS.
 THE PLANS CURRENTLY INDICATE THIS TO BE A R3 RESIDENCE
 AND THE GARAGE A ACCESSORY USEAGE. THE PLANS DO MEET
 THIS CRITERIA FOR A ONE & TWO FAMILY RESIDENCE AND THIS
 REVIEW WILL BE COMPLETED AS SUCH.
 FOR THE BUILDING DEPARTMENTS OCCUPANCY CLASSIFICATION
 IT WILL NEED TO REPRESENT A R3 OCCUPANCY ON THE SHEET
 A.0. WE HAVE NO SUCH CLASSIFICATION AS COMMERCIAL LIVE/
 WORKIF THIS IS A ZONING CLASSIFICATION PLEASE SESIGNATE
 AS SUCH.
  
 5) SEMI-COMPLIED, THE RESPONCE INDICATES AS WELL AS THE
 PLANS THIS IS TO BE A R3 RESIDENCE AND THE RESPONCE
 LETTER INDICATES THE STORAGE PORTION TO BE USED AS A
 GARAGE.WITH THIS NEW KNOWLEDGE OF WHAT TYPE OF
 OCCUPANCY CLASSIFICATION WILL BE USED FOR THIS
 STRUCTURE THE DESIGNER NEEDS TO COMPLY WITH R 309.1
 OPENINGS FROM A PRIVATE GARAGE DIRECTLY INTO A ROOM
 USED FOR SLEEPING SHALL NOT BE PERMITTED. SEE THE REST
 OF THE SECTION AS TO FIRE RATINGS REQUIRED.
  
 6-11) COMPLIED.
  
 12-13) BOTH COMMENTS DEAL WITH THE ENERGY CALCS, THE
 ENERGY CALCULATIONS ARE COMPLETED ON FORM 400A, THIS
 PLAN NOW STATES THIS IS A R-3 OCCUPANCY WITH THE GARAGE
 BEING A ACCESSORY OCCUPANCY, THERE ARE NO LONGER WALLS
 WITH SEPERATION BETWEEN BAYS. PLEASE REVISE THE ENERGY
 CALCULATIONS. NOTE THE ENERGY CALCULATIONS NEED TO
 ACCURATELY DEPICT THE FIXTURES LISTED ON SHEET E-2.
  
 14) THIS PLAN APPEARS TO HAVE A CHANGE IN OCCUPANCY
 REQUIRING PALM BEACH COUNTY IMPACT FEE ASSESSMENT.
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-26 Cont ID  
Sent By jwitmer Date 2007-09-26 Time 19:56 Rev Time 3.33
Received By jwitmer Date 2007-09-26 Time 19:56 Sent To  
Notes
2007-09-26 20:30:19BUILDING PLAN REVIEW
 PERMIT: 07080952
 ADD: 310 FLAMINGO DRIVE
 CONT: ISLAND CONSTRUCTION
 TEL: (561)236-9983
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 2) PLLEASE SEE NOTES FROM JOHN ROACH IN ZONING THAT A
 WORK LIVE LOFT CAN ONLY USE 20% OF THE GROSS FLOOR
 AREA, THE PLAN ON SHEET A.1 INDICATES THAT 80 % OF THE
 STRUCTURE WOULD BE
 STORAGE NOT THE ALLOWABLE 20%. THE OTHER ISSUE FOR A
 WORK LIVE LOFT IS THAT IT NEEDS TO MEET THE DEFINITION
 OF DWELLING UNIT. DWELLING UNIT . A SINGLE UNIT
 PROVIDING COMPLETE, INDEPENDENT LIVING FACILITIES FOR
 ONE OR MORE PERSONS, INCLUDING PERMANENT PROVISIONS FOR
 LIVING, SLEEPING, EATING, COOKING AND SANITATION. THIS
 PLAN LACKS SLEEPING QUARTERS, MAKING IT NOT A DWELLING
 UNIT.
 PLANS ALSO FAIL TO INDICATE WHICH WINDOWS WILL QUALIFY
 AS THE EMERGENCY EGRESS OPENINGS FOR THE SLEEPING
 QUARTERS.1025.1/ 1025.2.
  
 3) PLEASE CORRECT THE A.0 COVERSHEET WITH REGARDS TO
 FLOOD ZONE INFORMATION, THIS IS NOT IN A "AH" FLOOD
 ZONE.
  
 4) PLEASE PROVIDE TO WHAT LEVEL OF ALTERATION WILL BE
 COMPLETED UNDER THIS PERMIT. PROVIDE INFORMATION
 ADDITIONAL INFORMATION TO THE APPLICABLE ODES, 2004 FBC
 BUILDING W/ 2007 REVISONS
 2004 EXISTING BUILDING CODE W/ 2006 REVISIONS
  
 5A) PLANS INDICATE A PROPOSED STORAGE OCCUPANCY, WHAT
 TYPE OF MATERIALS WOULD BE STORED THERE?PROVIDE IF
 S1, S2 OR HAZARDOUS MATERIALS, AND QUANITIES.SEE TABLE
 302.3.2 FOR HR RATING, NOT A 1 HR WALL IF S1 THEN 3HR
 RATED WALL, S2 THEN A 2HR RATED WALL BETWEEN THE
 STORAGE OCCUPANCY AND R3 OCCUPANCY.
  
 5B) UNDER THE STORAGE OCCUPANCY, IS THIS A SINGLE
 TENANT OCCUPANCY OR MULTIPLE TENANT OCCUPANCY? PLANS DO
 NOT SHOW EGRESS DOORS IF MULTIPLE STORAGE TENANT.
  
 6)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR)
 OF PRODUCT TESTING REPORTS ,MISSING REPORTS ARE AS
 FOLLOWS:
 6A) ROOFING ASSEMBLIES W/INSULATION
  
 7) THIS ROOF IS MISSING OR NOT INCOMPLIANCE WITH
 THE FOLLOW ITEMS:
 _X__ CONTRACTOR DID NOT PROVIDE THE MEAN ROOF HEIGHT.
 _X__ CONTRACTOR DID NOT INDICATE THE ROOF PITCH. _X__
 CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO BE USED.
 NO REPORT SUBMITTED.
 _X__ THE SYSTEM PROVIDED HAS A LOWPRESSURE FOR ZONE
 2&3___ .
 X___ THE SYSTEM PROVIDED STATESLIMITATION# 7, SHOULD
 THE FASTENER
 RESISTANCE BE LESS THAN THAT REQUIRED, AS
 DETERMINED BY THE
 BUILDING OFFICIAL, A REVISEDFASTENER SPACING,
 PREPARED , SIGNED
 AND SEALED BY A FLORIDA REGISTERED PROFESSIONAL
 ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF
 CONSULTANT MAY BE SUBMITTED.
 ___THE SYSTEM PROVIDED INDICATES LIMITATION# 9, NO
 ENHANCED FASTENING ALLOWED.
  
 8) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 9)THE STORAGE OCCUPANCIES INDICATE A FUTURE TOILET
 IN EACH OF THREE BAYS, AT WHAT TIME IS THE FUTURE
 TOILET TO BE INSTALLED, IF SHOWN ON THESE PLANS ARE
 THEY TO BE PART OF THIS PERMIT.
 THEY WILL NEED TO MEET THE REQUIREMENTS FOR
 ACCESSIBILITY FOR HANDICAPPED RESTROOMS IF SEPERATE
 TENANTS. 11-4.22 AND OR 11-4.16.
  
 10) DISCREPANCIES, A-1 VS E -1 SHEET E-1 IS MISSING THE
 REQUIRED EGRESS DOORS FORT HE STORAGE OCCUPANCIESTHAT
 ARE SHOWN ON A-1. SHEET A-2 ALSO DOESN'T INDICATE THE
 EGRESS DOORS.
 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 11)A.1 TOLIET ROOMS DO NOT INDICATE ANY WINDOWS NOR
 DO THEY SHOW ON E2 ANY LIGHT FIXTURES WITHIN THE
 RESTROOM FACILITIES1205.3 ARTIFICIAL LIGHT.
  
 12)THE ENERGY CALCS INPUT DATA REPORT SHEET 3
 &INDICATES THERE TO BE LIGHTS WITHIN THEWAREHOUSE
 RESTROOM A 50 WATT FIXTURE WHERE AS THE E2 SHEET
 DOESN'T INDICATE ANY 50 WATT FIXTURES NOR DOES THE
 LIGHTING PLAN CORRELATE WITH THE LIGHTING LEGEND.
 13-415.2
  
 13) WHEN REVIEWING THE ENERGY CALCS FOR THE LIGHTING
 SHEETS 2& 3 OF THE INPUT DATA REPORT NONE OF THE
 FIXTURES MATCH THE FIXTURE LEGEND FOUND ON SHEET E-2
 SEE 13-415.2.
  
 14) SHEET E-2 IS MISSING THE EGRESS DOORSSHOEN ON A-2
 AND EXIT LIGHTING FOR THE (3) STORAGE BAYS. 2004 FBC
 SECTION 1006.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-06-17 Cont ID  
Sent By btrobaug Date 2008-06-17 Time 11:52 Rev Time 0.00
Received By btrobaug Date 2008-06-17 Time 07:46 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-01-24 Cont ID  
Sent By btrobaug Date 2008-01-24 Time 15:59 Rev Time 0.00
Received By btrobaug Date 2008-01-24 Time 15:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-12-10 Cont ID  
Sent By btrobaug Date 2007-12-10 Time 15:30 Rev Time 0.00
Received By btrobaug Date 2007-12-10 Time 06:50 Sent To  
Notes
2007-12-10 15:39:26 
  
 APPLICATION #07080952
 ELECTRICAL PLAN REVIEW
 310 FLAMINGO DRIVE
 12/10/07
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE
 NOTED.
  
 ALTHOUGH THE ELECTRICAL REVIEW WAS PASSED ON 9/12/07,
 THESE COMMENTS COME FROM NEW INFORMATION AND DRAWINGS
 SUBMITTED ON 11/28/07.
  
 1} ELECTRICAL SPECIFICATIONS, SHEET E-0, PART 3 (A),
 INDICATES THE COLOR CODING FOR A SINGLE PHASE, 120/240
 VOLT SYSTEM. THE RISER DIAGRAM INDICATES THE SERVICE
 BEING 3 PHASE 120/208 SYSTEM, CORRELATE SAME.
  
 2} THE PANEL SCHEDULES INDICATE THE PANELS ARE ?FED
 FROM UTILITY?, CORRECT TO INDICATE FED FROM MAIN
 DISCONNECT.106.1.3 FBC AS AMENDED.
  
 3} INDICATE THE BRANCH CIRCUIT CONDUCTOR SIZES ON THE
 PANEL SCHEDULE SO THAT COMPLIANCE WITH 310.16 CAN BE
 REVIEWED.
  
 4} CIRCUIT LPA-5 HAS TWO RECEPTACLES LOCATED ON A
 KITCHEN COUNTERTOP AND MUST COMPLY WITH SMALL APPLIANCE
 BRANCH CIRCUIT ARTICLES. SEE 210.52(A), 210.52(C), AND
 210.8(A)(6) GFI.
  
 5} SEE 210.52(C)(2) FOR ISLAND RECEPTACLE REQUIREMENT,
 LOCATE SAME ON PLAN.
  
 6} THE MOCP FOR AIR HANDLERS 1,2 AND 4, ON SHEET M.2,
 AND THE OCP IN THE PANEL SCHEDULES, SHEET E-0, FOR
 THOSE UNITS ARE IN CONFLICT. CORRELATE SAME.
  
 7}210.52(E) OUTDOOR OUTLETS FOR A ONE-FAMILY DWELLING
 AND EACH UNIT OF A TWO-FAMILY DWELLING THAT IS AT GRADE
 LEVEL, AT LEAST ONE RECEPTACLE OUTLET ACCESSIBLE AT
 GRADE LEVEL AND NOT MORE THAN 2.0 M (6 1/ 2 FT) ABOVE
 GRADE SHALL BE INSTALLED AT THE FRONT AND BACK OF THE
 DWELLING. LOCATE SAME ON PLANS.
  
 8} CIRCUIT LPA-35 AND LPA-17 MUST BE AFCI PROTECTED PER
 210.12.
  
 9} THE ENERGY CERTIFICATIONS SUBMITTED ARE FOR A
 WAREHOUSE, SHEET A.1 INDICATES AN R3 BUILDING TYPE. THE
 APPLICATION STATES NO CHANGE OF OCCUPANCY. THE GARAGE
 IS LABELED ?ACCESSORY TO RESIDENCE?.CORRELATE THESE
 DOCUMENTS, DECLARE OCCUPANCY TYPE, IF R3 CHECK THE
 CHANGE OF OCCUPANCY BOX ON THE APPLICATION, SUBMIT
 ENERGY CALCULATIONS PER 13-600.
  
 THE ELECTRICAL REVIEW WAS DONE FOR R3 AS INDICATED ON
 THE PLAN. PLEASE REMOVE ALL OLD OR VOIDED SHEETS AND
 REPLACE WITH CORRECTED ONES WHEN RESUBMITTING. INCLUDE
 THEM SEPARATELY TO EXPEDITE THE REVIEW PROCESS. RESPOND
 TO REVIEW COMMENTS IN WRITING.
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-09-12 Cont ID  
Sent By btrobaug Date 2007-09-12 Time 14:59 Rev Time 0.00
Received By btrobaug Date 2007-09-12 Time 06:46 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-02-21 Cont ID  
Sent By mawillia Date 2008-02-21 Time 16:56 Rev Time 0.00
Received By mawillia Date 2008-02-21 Time 16:33 Sent To  
Notes
2008-02-21 16:56:37****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED;PLAN SHEETS A.1, A.3 AND E-2 WERE
 STAMPED, INITIALED, AND DATED.
  
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-12-26 Cont ID  
Sent By mawillia Date 2007-12-26 Time 14:26 Rev Time 0.00
Received By mawillia Date 2007-12-26 Time 13:46 Sent To  
Notes
2007-12-26 14:26:36*****UNSAT*****
  
 THE FOLLOWING COMMENTS (OF 9) TAKEN FROM THE PREVIOUS
 FIRE PLAN REVIEW STILL NEED TO BE ADDRESSED:
  
  
 5.PAGE A-5 DOES NOT MATCH ELECTRICAL DRAWINGS AS THEY
 RELATE TO EXIT LIGHTS AND EMERGENCY LIGHTS.
  
 7.PLEASE DECLARE MATERIALS PLANNED TO BE STORED IN
 STORAGE AREAS.IS ANY FLAMMABLE, COMBUSTIBLE, TOXIC,
 POISONOUS, OR EXPLOSIVE SOLIDS, LIQUIDS, OR GASES
 PLANNED TO BE STORED?
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-10-22 Cont ID  
Sent By mcarsill Date 2007-10-22 Time 14:05 Rev Time 0.00
Received By mcarsill Date 2007-10-22 Time 13:43 Sent To  
Notes
2007-10-22 14:05:071. BUILDING ADDRESS IS REQUIRED ON THE PROPER BUILDING
 ELEVATION. A MINIMUM OF AT LEAST 6" HIGH 1" WIDE
 NUMBERS ARE REQUIRED.
  
 2. DEMOLITION, RENOVATION, AND CONSTRUCTION TO COMPLY
 WITH NFPA 241.
  
 3. ELECTRIC POWERED SMOKE DETECTORS ARE REQUIRED WITHIN
 THE RESIDENTIAL PORTION OF THE BUILDING. WHEN
 ACTIVATED, THE DETECTOR(S) SHALL BE AUDIBLE TO ALERT
 PERSONS OF A FIRE EMERGENCY.
  
 4. ON M-1 PLANS MAKE REFERENCE TO CARBON DIOXIDE
 DETECTORS AND IN OTHER INSTANCES IT CALLS OUT THE
 SYMBOL FOR CARBON MONOXIDE DETECTORS. PLEASE CORRECT
 PLANS.
  
 5. PAGE A-5 DOES NOT MATCH ELECTRICAL DRAWINGS AS THEY
 RELATE TO EXIT SIGNS AND EMERGENCY LIGHTING.
  
 6. PLANS CALL CLASS C FLAMESPREAD BUT THE PLANS
 INDICATE THAT THE BUILDING IS NON FIRE SPRINKLER
 PROTECTED. PLEASE CORRECT PLANS AS NECESSARY.
  
 7. PLEASE DECLARE MATERIALS PLANNED TO BE STORED IN
 STORAGE AREAS. IS ANY FLAMMABLE, COMBUSTIBLE, TOXIC,
 POSIONOUS, OR EXPLOSIVE SOLIDS, LIQUIDS, OR GASES
 PLANNED TO BE STORED.
  
 8. VEHICLES IF PLANNED TO BE STORED IN THESE AREAS, THE
 VEHICLES SHALL CONTAIN VERY LITTLE FUEL AND HAVE THE
 BATTERY TERMINALS DISCONNECTED.
  
 9. PLEASE ILLUSTRATE ANY PORTABLE FIRE EXTINGUISHING
 EQUIPMENT PLANNED FOR THE SPACE.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 804-4709 PHONE
 804-4774 FAX

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2008-09-16 Cont ID  
Sent By adarroug Date 2008-09-16 Time 14:44 Rev Time 0.00
Received By adarroug Date 2008-09-16 Time 14:44 Sent To Z
Notes
2008-09-16 14:46:54TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2008-09-05 Cont ID  
Sent By adarroug Date 2008-09-05 Time 10:20 Rev Time 0.00
Received By adarroug Date 2008-09-05 Time 10:20 Sent To M
Notes
2008-09-05 10:20:42TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2008-08-08 Cont ID  
Sent By adarroug Date 2008-08-08 Time 13:19 Rev Time 0.00
Received By adarroug Date 2008-08-08 Time 13:19 Sent To P
Notes
2008-08-08 13:19:56TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2008-07-28 Cont ID  
Sent By adarroug Date 2008-07-28 Time 10:11 Rev Time 0.00
Received By adarroug Date 2008-07-28 Time 10:11 Sent To M
Notes
2008-07-28 10:11:46TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2008-07-28 Cont ID  
Sent By adarroug Date 2008-07-28 Time 10:09 Rev Time 0.00
Received By adarroug Date 2008-07-28 Time 10:09 Sent To M
Notes
2008-07-28 10:09:34TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2008-07-03 Cont ID  
Sent By adarroug Date 2008-07-03 Time 11:20 Rev Time 0.00
Received By adarroug Date 2008-07-03 Time 11:20 Sent To P
Notes
2008-07-03 11:21:01TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2008-07-03 Cont ID  
Sent By adarroug Date 2008-07-03 Time 11:20 Rev Time 0.00
Received By adarroug Date 2008-07-03 Time 11:17 Sent To M
Notes
2008-07-03 11:17:40TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2008-07-03 Cont ID  
Sent By adarroug Date 2008-07-03 Time 11:05 Rev Time 0.00
Received By adarroug Date 2008-07-03 Time 11:05 Sent To Z
Notes
2008-07-03 11:06:08TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-06-25 Cont ID  
Sent By adarroug Date 2008-06-25 Time 13:43 Rev Time 0.00
Received By adarroug Date 2008-06-25 Time 13:43 Sent To M
Notes
2008-06-25 13:43:43TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-06-16 Cont ID  
Sent By adarroug Date 2008-06-16 Time 14:11 Rev Time 0.00
Received By adarroug Date 2008-06-16 Time 14:11 Sent To B
Notes
2008-06-16 14:14:48TO "MJACOBS" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-06-11 Cont ID  
Sent By adarroug Date 2008-06-11 Time 08:31 Rev Time 0.00
Received By adarroug Date 2008-06-11 Time 08:30 Sent To E
Notes
2008-06-11 08:31:24TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-04-16 Cont ID  
Sent By adarroug Date 2008-04-16 Time 13:16 Rev Time 0.00
Received By adarroug Date 2008-04-16 Time 13:16 Sent To B
Notes
2008-04-16 13:16:44TO "MJACOBS" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-03-04 Cont ID  
Sent By adarroug Date 2008-03-04 Time 10:45 Rev Time 0.00
Received By adarroug Date 2008-03-04 Time 10:45 Sent To B
Notes
2008-03-04 10:46:17TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-02-27 Cont ID  
Sent By adarroug Date 2008-02-27 Time 09:50 Rev Time 0.00
Received By adarroug Date 2008-02-27 Time 09:50 Sent To M
Notes
2008-02-27 09:51:10TO "TGORDON" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-01-23 Cont ID  
Sent By adarroug Date 2008-01-23 Time 17:11 Rev Time 0.00
Received By adarroug Date 2008-01-23 Time 17:11 Sent To  
Notes
2008-01-23 17:11:48TO "COMM" BD#53

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-28 Cont ID  
Sent By adarroug Date 2007-11-28 Time 14:39 Rev Time 0.00
Received By adarroug Date 2007-11-28 Time 14:39 Sent To  
Notes
2007-12-03 08:35:07TO "COMM" BD#14
2007-11-28 14:39:36WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-11-02 Cont ID  
Sent By kstevens Date 2007-11-02 Time 18:23 Rev Time 0.00
Received By kstevens Date 2007-09-04 Time 10:35 Sent To  
Notes
2007-09-22 10:37:10TO COMM BOARD SPACE #3.DVP
2007-09-04 10:36:07WAITING FOR "COMM" BD--CHANGED FROM "RES-REMOD" TO
 "COM-REMOD"

Review Stop M MECHANICAL (A/C)
Rev No 9 Status N Date 2008-09-08 Cont ID  
Sent By tgordon Date 2008-09-08 Time 15:49 Rev Time 0.15
Received By tgordon Date 2008-09-08 Time 15:49 Sent To B
Notes
2008-09-08 15:49:43BUILD. REVISION NOT MECH.

Review Stop M MECHANICAL (A/C)
Rev No 8 Status N Date 2008-07-28 Cont ID  
Sent By tgordon Date 2008-07-28 Time 11:16 Rev Time 0.15
Received By tgordon Date 2008-07-28 Time 11:16 Sent To B
Notes
2008-07-28 11:16:53REVISION TO BUILDING PLANS NOT MECH. PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2008-07-03 Cont ID  
Sent By tgordon Date 2008-07-03 Time 16:33 Rev Time 0.45
Received By tgordon Date 2008-07-03 Time 16:33 Sent To  
Notes
2008-07-03 16:36:11REVISION TO MECH. PLANS PAGE M.1, M.2, M.3, ENERGY
 CAL'S. AND COOLING LOAD CAL'S.

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2008-06-26 Cont ID  
Sent By tgordon Date 2008-06-26 Time 11:50 Rev Time 1.30
Received By tgordon Date 2008-06-26 Time 11:50 Sent To  
Notes
2008-06-26 12:27:46PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 REVISION TO MECHANICAL PLANS
 *** DENIED ***
 1) MECHANICAL PLANS ON FILE WERE SIGNED AND SEALED BY
 AN ENGINEER (MICHAEL M. BASSFORD) SO ONLY HE CAN MAKE
 REVISIONS TO THEM, PER FAC 61G15-23.002.
  
 2) PLEASE HAVE THE ENGINEER ALSO REVISE THE ENERGY
 CALCULATIONS AND COOLING LOAD CALCULATIONS AS THEY HAVE
 BEEN SIGNED AND SEALED BY HIM ALSO AND WILL NEED TO BE
 REVISED AS A RESULT OF THE CHANGES IN THE MECHANICAL
 PLANS, PER 2004 FBC 13-600.3.ABC.2.
  
 3) PLEASE SHOW THE OUTSIDE AIR CALCULATIONS ON THE
 MECHANICAL PLAN AND PROVIDE OUTSIDE AIR WERE REQUIRED
 BY 2004 FBC/R R303 AND FBC/M TABLE 403.3.
  
 4) PLEASE SUBMIT MANUFACTURER'S SPECIFICATION'S AND
 INSTALLATION INSTRUCTIONS FOR THE 26X26 MOTORIZED
 DAMPERS, AND 30" WEATHER HOOD FOR THE EXHAUST FAN,
 SHOWING COMPLIANCE WITH 2004 FBC 1609 WIND LOADS.
 PLEASE SUBMIT PRODUCT APPROVAL OR AN NOA FOR LOUVERS IF
 BEING USED, SEE FS 553.842(1) AND FAC RULE 9B-72,
 9B-72.005, AND FAC 9B-72.010(31)(C).
  
 5) THE BUILDING PLANS WILL NEED TO BE REVISED SHOWING
 THE NEW OUTDOOR AIR OPENINGS AND EXHAUST OPENING, PER
 2004 FBC 1609.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 5 Status N Date 2008-06-26 Cont ID  
Sent By tgordon Date 2008-06-26 Time 13:30 Rev Time 0.00
Received By tgordon Date 2008-06-26 Time 11:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-02-27 Cont ID  
Sent By tgordon Date 2008-02-27 Time 11:51 Rev Time 1.30
Received By tgordon Date 2008-02-27 Time 11:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2008-01-25 Cont ID  
Sent By tgordon Date 2008-01-25 Time 08:04 Rev Time 0.25
Received By tgordon Date 2008-01-25 Time 08:04 Sent To  
Notes
2008-01-25 08:28:27PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS ARE CALLING FOR 14 SEER A/C
 SYSTEMS, THE PLANS PAGE M.2 A/C SCHEDULE IS CALLING FOR
 13 SEER A/C SYSTEMS. THE PLANS CAN NOT CALL FOR LESS
 THAN THE ENERGY CALCULATIONS. PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-12-12 Cont ID  
Sent By tgordon Date 2007-12-12 Time 09:30 Rev Time 0.30
Received By tgordon Date 2007-12-12 Time 09:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-10-11 Cont ID  
Sent By hmoser Date 2007-10-11 Time 19:19 Rev Time 0.00
Received By hmoser Date 2007-10-11 Time 19:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 6 Status P Date 2008-08-11 Cont ID  
Sent By mperson Date 2008-08-11 Time 10:19 Rev Time 0.00
Received By mperson Date 2008-08-11 Time 10:19 Sent To PC
Notes
2008-08-11 10:30:21REVISION SHEET P.1 AND ADDED SHEET P.2: "OK" MOVED
 FIXTURES AND ADDED SHOWER IN BACK BATHROOM. ADDED SINK
 IN UTILITY ROOM. ADDED HOSE BIBBS. STUBBED FOR FUTURE
 UTILTY SINK AND ADDED WATER FOR FUTURE ICE MACHINE.
  
 ****************PROVISO****************
 A} WATER HAMMER ARRESTORS SHALL BE INSTALLED WHERE
 QUICK CLOSING VALVES ARE UTILIZED. (DISHWASHER, FUTURE
 ICE MACHINE). PER FBC- PLUMBING SECTION 604.9 WATER
 HAMMER.
 B} A TWO-WAY CLEANOUT SHALL BE INSTALLED AT THE
 JUNCTION OF THE BUILDING DRAIN AND BUILDING SEWER. PER
 FBC- PLUMBING SECTION 708.3.5. BUILDING DRAIN AND
 BUILDING SEWER JUNCTION.
 C} SHEET P.1 PLUMBING FIXTURES: SEE RED LINE
 CORRECTION TO WASHING MACHINE WASTE (3").
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 5 Status F Date 2008-07-23 Cont ID  
Sent By kstevens Date 2008-07-23 Time 14:15 Rev Time 0.00
Received By kstevens Date 2008-07-23 Time 14:15 Sent To  
Notes
2008-07-23 14:52:40REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA STATUTES
  
 1. SHT P.1 OF 1 REVISIONS TO PLANS SIGNED AND SEALED BY
 A PROFESSIONAL ENGINEER SHALL BE SIGNED AND SEALED BY
 THE ENGINEER OF RECORD. FS 471.--PREVIOUS REVIEWED
 SHEET SHOWED REVISIONS 1 & 2. NEW REVISIONS 3, 4 & 5
 ARE NOT INDICATED WITH CLOUDS OR REVISION NUMBERS. MUCH
 OF THE INFORMATION ON THE REVIEWED/STAMPED PLANS HAS
 BEEN DELETED SUCH AS THE WATER RISER DIAGRAM ETC. SHT
 NOW IS INDICATED AS P.1 OF 7. PLEASE CLARIFY. SECTION
 106.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 4 Status F Date 2008-06-24 Cont ID  
Sent By mperson Date 2008-06-24 Time 15:50 Rev Time 0.00
Received By mperson Date 2008-06-24 Time 15:50 Sent To PC
Notes
2008-06-24 16:12:12PLUMBING PLAN REVIEW:
 REVISION DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET A.1 FLOOR PLAN ROOM 105 & 105A: ALL CHANGES
 TO THE PLAN ARE TO BE CLOUDED WITH REVISION
 NUMBERS/DATES PER FBC-2004 CHAPTER 1, SECTION 106.1.3
 THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM.
 NOTE: A TRANSMITTAL LETTER IS HELPFUL.
  
 2. SHEET A.1 FLOOR PLAN ROOM 105 & 105A: CLEARLY
 IDENTIFY ALL FIXTURES IN THESE ROOMS. PER FBC- PLUMBING
 SECTION 401.1 SCOPE.
  
 3. PLEASE PROVIDE A REVISED SHEET P.1 SANITARY AND
 WATER RISER DIAGRAMS CLEARLY INDICATING THE NEW LAYOUT
 OF ROOMS 105 & 105A PLUMBING FIXTURES WITH THE ADDED
 FIXTURES. PER (W.P.B. AS AMENDED) SECTION 106.3.5.4 (9)
 PLUMBING.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-02-21 Cont ID  
Sent By mperson Date 2008-02-21 Time 15:09 Rev Time 0.00
Received By mperson Date 2008-02-21 Time 15:09 Sent To  
Notes
2008-02-21 15:14:13****************PROVISO****************
 PER FBC PLUMBING SECTION *406.3 WASTE CONNECTIONS.THE
 TRAP AND FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES WASHER
 SHALL BE A MINIMUM OF 2 INCHES (51MM) IN DIAMETER. THE
 AUTOMATIC CLOTHES WASHER FIXTURE DRAIN SHALL CONNECT TO
 A BRANCH DRAIN OR DRAINAGE STACK A MINIMUM OF 3 INCHES
 (76MM) IN DIAMETER. (REVISION REQUIRED)
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-12-15 Cont ID  
Sent By kstevens Date 2007-12-15 Time 07:10 Rev Time 0.00
Received By kstevens Date 2007-12-15 Time 07:10 Sent To  
Notes
2007-12-15 07:39:06DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
  
 2. DECLARE THE OCCUPANCY. IT APPEARS THAT THESE ARE
 WAREHOUSES AND THE RESIDENTIAL AREA DOES NOT MEET THE
 DEFINITION OF DWELLING IN AS IT DOES NOT HAVE SLEEPING
 PROVISIONS. SECTION 310.2. COMMERCIAL LIVE/WORK DOES
 NOT INDICATE THE OCCUPANCY OF THE COMMERCIAL SECTION.
 SECTION 106.1.1.
 ****RESPONSE NOTED, BUT THE COMMENT WAS NOT ADDRESSED.
 JOHN ROACH IS NOT A BUILDING OR PLUMBING PLAN REVIEWER
 AND HAS NO KNOWLEDGE OF OUR REQUIREMENTS. THERE HAS
 BEEN PLAN DEVELOPMENT BETWEEN THE FIRST REVIEW AND THE
 PRESENT REVIEW. AS SUCH NEW COMMENTS WILL BE INDICATED.
 THE OCCUPANCY STILL IS NOT INDICATED.
  
 3. SHT A-1 THE STORAGE OCCUPANCIES REQUIRES DRINKING
 FOUNTAINS AND SERVICES SINKS IF, AS INDICATED ON THE
 ENERGY CALCULATIONS, THERE WILL BE FOUR WAREHOUSE BAYS.
 PLEASE ALSO INDICATE THE TYPE OF MATERIAL & THE AMOUNT
 THAT WILL BE STORED IN THE STORAGE BAYS. MSDS SHEETS
 MAY BE REQUIRED AS WELL AS AN EYE WASH/EMERGENCY SHOWER
 DEPENDING ON THE RESPONSE OF THIS COMMENT AND THE MSDS
 SHEETS. SECTION 106.1.2 & TABLE 403.1.
 ****RESPONSE NOTED, BUT THE COMMENT WAS NOT ADDRESSED.
 JOHN ROACH IS NOT A BUILDING OR PLUMBING PLAN REVIEWER
 AND HAS NO KNOWLEDGE OF OUR REQUIREMENTS. THERE IS A 2
 HRFIRE SEPARATION WALL INDICATED, BUT THE SPACE IS
 INDICATED AS AN ACCESSORY TO RESIDENCE. MORE
 INFORMATION IS STILL REQUIRED.
  
 4. SUBMIT AN EXISTING FLOOR PLAN SO THE EXTENT OF THE
 WORK CAN BE ESTABLISHED. SECTION 106.1.2, MORE
 INFORMATION REQUIRED.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. THE DEMO
 SHOWS NOT EXISTING TOILET ROOMS, KITCHEN, WASH MACHINE
 CONNECTIONS, SLEEPING PROVISIONS ETC THAT ARE REQUIRED
 IN A RESIDENCE. IF THIS IS AN EXISTING RESIDENCE, WHERE
 ARE ALL OF THE EXISTING REQUIRED ELEMENTS? A
 PRE-INSPECTION MAY BE REQUIRED TO VERIFY INFORMATION
 INDICATED IN THE PLANS.
  
 5. SHT A.1 THE FUTURE TOILET ROOMS SHALL BE ACCESSIBLE.
 SHOW COMPLIANCE WITH SECTIONS 11-4.15, 11-4.16, 11-4.19
 & 11-4.22 WITH ALL SUBSECTIONS AS WELL AS SECTION
 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING.--SUBMIT DETAILS IN
 BOTH A FLOOR PLAN AND ELEVATIONS.
 ****RESPONSE NOTED, BUT THE "COMMERCIAL" INDICATION ON
 SHT A.0 REQUIRES THAT ALL TOILET ROOMS PROVIDED SHALL
 BE ACCESSIBLE AND SHALL BE ON AN ACCESSIBLE ROUTE.
 SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTIONS
 11-4.16, 11-4.19 & 11-4.22 WITH ALL SUBSECTIONS. ALSO
 SUBMIT A DETAIL FOR THE REQUIRED DRINKING FOUNTAIN
 SHOWING COMPLIANCE WITH SECTION 11-4.15 WITH ALL
 SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A).
  
 6. OK
  
 7. N/A PLAN DEVELOPMENT.
  
 8. OK
  
 9. SHT P.1 NO SANITARY OR WATER PIPING ARE SHOWN TO THE
 WASH MACHINE. TABLE 403.1.
 ****RESPONSE NOTED, BUT WATER HAMMER ARRESTORS ARE
 REQUIRED AT THE WASH MACHINE PER SECTION 604.9.
  
 **********NEW COMMENT**********
  
 1B. SEE ATTACHED SHEET CONCERNING THE DESIGN
 PROFESSIONAL AND FS 553.80(2)(B). THIS IS GIVEN AS A
 NOTICE AT THIS TIME.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-11-02 Cont ID  
Sent By kstevens Date 2007-11-02 Time 17:52 Rev Time 0.00
Received By kstevens Date 2007-11-02 Time 17:52 Sent To  
Notes
2007-11-02 18:23:39DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. PLANS SHALL BE SUBMITTED IN A MINIMUM OF TWO
 COMPLETE SETS. LOOSE SHEETS ARE NOT ACCEPTABLE. SECTION
 106.1.
  
 2. DECLARE THE OCCUPANCY. IT APPEARS THAT THESE ARE
 WAREHOUSES AND THE RESIDENTIAL AREA DOES NOT MEET THE
 DEFINITION OF DWELLING IN AS IT DOES NOT HAVE SLEEPING
 PROVISIONS. SECTION 310.2. COMMERCIAL LIVE/WORK DOES
 NOT INDICATE THE OCCUPANCY OF THE COMMERCIAL SECTION.
 SECTION 106.1.1.
  
 3. SHT A-1 THE STORAGE OCCUPANCIES REQUIRES DRINKING
 FOUNTAINS AND SERVICES SINKS IF, AS INDICATED ON THE
 ENERGY CALCULATIONS, THERE WILL BE FOUR WAREHOUSE BAYS.
 PLEASE ALSO INDICATE THE TYPE OF MATERIAL & THE AMOUNT
 THAT WILL BE STORED IN THE STORAGE BAYS. MSDS SHEETS
 MAY BE REQUIRED AS WELL AS AN EYE WASH/EMERGENCY SHOWER
 DEPENDING ON THE RESPONSE OF THIS COMMENT AND THE MSDS
 SHEETS. SECTION 106.1.2 & TABLE 403.1.
  
 4. SUBMIT AN EXISTING FLOOR PLAN SO THE EXTENT OF THE
 WORK CAN BE ESTABLISHED. SECTION 106.1.2, MORE
 INFORMATION REQUIRED.
  
 5. SHT A.1 THE FUTURE TOILET ROOMS SHALL BE ACCESSIBLE.
 SHOW COMPLIANCE WITH SECTIONS 11-4.15, 11-4.16, 11-4.19
 & 11-4.22 WITH ALL SUBSECTIONS AS WELL AS SECTION
 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING.--SUBMIT DETAILS IN
 BOTH A FLOOR PLAN AND ELEVATIONS.
  
 6. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE TO
 THE BUILDING. SECTION 608.13.2.
  
 7. SHT P.1 2 WATER CLOSETS ARE NOT INDICATED AS FUTURE
 FIXTURES. PLEASE CLARIFY. SECTION 106.1.1.
  
 8. SHT P.1 KEY PLAN NOTES #1 IS NOT SHOWN ON THE FLOOR
 PLAN. PLEASE INDICATED NOTE #1. SECTION 106.1.2.
  
 9. SHT P.1 NO SANITARY OR WATER PIPING ARE SHOWN TO THE
 WASH MACHINE. TABLE 403.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 5 Status P Date 2008-09-21 Cont ID  
Sent By mcruz Date 2008-09-21 Time 15:27 Rev Time 0.00
Received By mcruz Date 2008-09-21 Time 15:27 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status F Date 2008-09-12 Cont ID  
Sent By mcruz Date 2008-09-12 Time 16:11 Rev Time 0.00
Received By mcruz Date 2008-09-12 Time 16:10 Sent To  
Notes
2008-09-12 16:11:30***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO ALL PROPERTY LINES. AS PER SECTION
 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 3 Status F Date 2008-07-08 Cont ID  
Sent By choops Date 2008-07-08 Time 08:26 Rev Time 0.00
Received By choops Date 2008-07-08 Time 08:26 Sent To B
Notes
2008-07-08 08:26:39***FAILED - REVISION - A/C LOCATION CHANGE AND PAD
 DETAIL, CHANGES TO INTERIOR FRAMING.***
  
  
 1)AS THE MECHANICAL EQUIPMENT LOCATION HAS CHANGED
 FROM WHAT WAS ORIGINALLY APPROVED, THE A/C EQUIPMENT
 AND GENERATOR PAD DO NOT MEET THE MINIMUM REQUIRED
 SETBACK DIMENSIONS.AS PER SECTION 94-305(B)(4) OF THE
 ZLDRS: MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN 4
 FEET INTO A REQUIRED SETBACK.
  
 SECTION 94-148.PROFESSIONAL OFFICE RESIDENTIAL (POR)
 DISTRICT.
 (2)MINIMUM SETBACKS:
 A.FRONT: 25 FEET.
 B.CORNER: 15 FEET.
 C.SIDE: TEN FEET.
 D.INTERIOR SIDE: TEN FEET.
 E.REAR: 15 FEET.
  
 THE MINIMUM REQUIRED REAR SETBACK IS 11' TO ANY
 MECHANICAL EQUIPMENT.THE MINIMUM REQUIRED SIDE
 SETBACK IS 6' TO ANY MECHANICAL EQUIPMENT.REVISE
 PLANS ACCORDINGLY.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
 [email protected]
  
  
  
  
 SENT TO "B" - MJ

Review Stop Z ZONING
Rev No 2 Status P Date 2007-12-04 Cont ID  
Sent By choops Date 2007-12-04 Time 12:36 Rev Time 0.00
Received By choops Date 2007-12-04 Time 12:36 Sent To  
Notes
2007-12-04 12:37:26***APPROVED - RESUB #1***

Review Stop Z ZONING
Rev No 1 Status F Date 2007-09-07 Cont ID  
Sent By choops Date 2007-09-07 Time 17:30 Rev Time 0.00
Received By choops Date 2007-09-07 Time 17:30 Sent To  
Notes
2007-09-07 17:50:26***FAILED***
  
  
 1)PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS: AS THE VALUE OF THE
 PROPOSED WORK EXCEEDS 50% OF THE BUILDING'S VALUE, ALL
 LANDSCAPING SHALL BE REQUIRED TO MEET ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS.
  
 2)THIS SPACE APPEARS TO BE SETUP TO BE RENTED AS
 WAREHOUSING SPACE, WHICH IS NOT A PERMITTED USE IN THE
 POR ZONING DISTRICT.
  
 3)GATE/FENCE EXCEED MAXIMUM HEIGHT ALLOWABLE WITHIN
 FRONT SETBACK.PURSUANT TO SECTION 94-302(C)(1):
 MAXIMUM HEIGHT.IN NONRESIDENTIAL DISTRICTS, NO FENCE,
 HEDGE OR WALL SHALL EXCEED EIGHT FEET IN HEIGHT WITHIN
 THE REQUIRED SIDE AND REAR SETBACKS. FENCES AND WALL
 SHALL NOT EXCEED 48 INCHES IN HEIGHT WITHIN THE
 REQUIRED FRONT SETBACK.
  
 4)ANY NEW WALL/FENCE REQUIRES AN EASEMENT CONSENT
 FORM FROM THE CITY OF WEST PALM BEACH DEPARTMENT OF
 PUBLIC UTILITIES.
  
 5)SHOW SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO THE PROPERTY LINES.
  
 6)THE SITE PLAN (A.0) SHOWS A BOX STRUCTURE ON THE
 SOUTHEAST CORNER OF THE LOT.WHAT IS THIS?PROVIDE
 DIMENSIONS, HEIGHT, ETC...
  
 7)PROVIDE A PHOTOMETRIC PLAN SHOWING THE PROJECTED
 FOOT CANDLES OF THE EXTERIOR LIGHTING AT THE
 NEIGHBORING RESIDENTIAL LINES.AS PER SECTION
 94-310(D): GLARE.ANY OPERATION OR ACTIVITY PRODUCING
 GLARE SHALL BE CONDUCTED SO THAT DIRECT OR INDIRECT
 LIGHT FROM THE SOURCE SHALL NOT CAUSE ILLUMINATION IN
 EXCESS OF 0.5 FOOT CANDLES WHEN MEASURED IN A
 RESIDENTIAL DISTRICT.
  
 8)PROVIDE ALL DIMENSIONS ON SITE PLAN (A.0):
 DIMENSION OF PROPOSED AWNINGS TO PROPERTY LINES,
 DIMENSION AWNINGS PROTRUDE FROM BUILDING, ETC...
  
 9)REMOVE EXCESS PLANS FROM PACKET THAT ARE NO LONGER
 VALID.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720