| 2007-09-23 10:30:58 | 2007-09-23 10:30:58 |
| | |
| | ** DENIED** |
| | |
| | |
| | 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS |
| | WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES |
| | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED |
| | FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS |
| | NOT MADE BY OTHER TRADE(S). |
| | |
| | 2) NOTE: PLEASE SEE THE ADDRESS FOR UNIT/SUITE SHALL BE |
| | STATED ON PERMIT APPLICATION AND TITLE BLOCKS FOR |
| | PLANS. |
| | A COPY OF PERMIT APPLICATION WAS ROUTED TO ADDRESSING |
| | REVIEWER. PLEASE BE AWARE OF ANY DESIGNATIONS WHICH MAY |
| | BE ASSIGNED. |
| | |
| | 3) NOTE: PLEASE CLARIFY THE PANEL HL, IS THIS A *HOUSE |
| | PANEL*? PLEASE ALSO BE SURE TO CONTACT CITY ENGINEERING |
| | DEPARTMENT FOR ANY LIGHTING WHICH ACTUALLY MAY BE |
| | LOCATED IN THE *RIGHT OF WAY*. THIS MAY NOT BE |
| | PERMITTED AND ONLY LIGHTING LOCATED ON THE LEGAL |
| | PROPERTY MAY BE FED FROM BUILDING ELECTRICAL SERVICE. |
| | RIGHT OF WAY LIGHTING IS TYPICALLY FED FROM THE CITY |
| | POWER LOCATED IN RIGHT OF WAYS. |
| | |
| | 4) NOTE: PLEASE SEE THE LIGHTING IN THE NEW *FUTURE |
| | RETAIL* IS BEING SHOWN ON CIRCUITS TO PANEL *HB*> THIS |
| | IS A 277/480V PANEL FOR TRACK LIGHTING. |
| | PLEASE SEE PANEL *HB* DOES NOT CONTAIN ANY LIGHTING |
| | CIRCUITS AND THE CIRCUITS AS REFERENCED ARE INDICATING |
| | OTHER CIRCUITS. |
| | THIS APPEARS THAT THESE SHOULD HAVE BEEN TO PANEL |
| | *LB*?? |
| | PLEASE ADJUST AND COORDINATE CIRCUITS WITH PANEL |
| | SCHEDULE. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 5) NOTE: PLEASE SEE THE RISER INDICATES THE TRANSFORMER |
| | IN THE RETAIL SPACE AS *THB* ALONG WITH THE TRANSFORMER |
| | LEGEND HOWEVER PLEASE SEE PANEL *HB* AS THIS PANEL |
| | INDICATES A TRANSFORMER *T1B*. |
| | PLEASE CORRELATE AND ADJUST. PLEASE ALSO SEE NEXT |
| | COMMENT. |
| | |
| | 6) NOTE: PLEASE SEE THE TRANSFORMER WHICH IS BEING |
| | SHOWN AS 45KVA UNIT IS BEING SHOWN WITH 110AMP OVER |
| | CURRENT PROTECTION IN PANEL *HB* WHICH IS NOT |
| | PERMITTED. PLEASE SEE 450.3 AS THE OCP IS TO BE A |
| | MAXIMUM OF 125%.(UNLESS MEETING EXCEPTION WHICH THIS |
| | TRANSFORMER DOES NOT INDICATE). |
| | PLEASE CORRELATE AND ADJUST. |
| | THIS COMMENT IS BEING *ASSUMED* AS THE TRANSFORMER AS |
| | LISTED ON PANEL *HB* DOES NOT HAVE THE SAME |
| | DESIGNATIONS AS SHOWN ON RISER AND TRANSFORMER LEGEND. |
| | FBC 106.1.2. |
| | |
| | 7) NOTE: PLEASE CLARIFY WHERE CONTINUOUS LOADS ARE |
| | SHOWN. |
| | 215.3, 230.42, 220 ETC |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 8) NOTE: PLEASE CLARIFY THE USE OF AN *E-MON* METER. IF |
| | THIS IS GOING TO BE A NEW RETAIL TENANT SPACE, WOULD |
| | NOT A METER FROM FPL BE INSTALLED? |
| | PLEASE KNOW THE PLANS WILL BE ROUTED TO ZONING FOR |
| | DIVISION OF SPACES AND TENANTS. |
| | PLEASE CONTACT THE FPL SERVICE REPRESENTATIVE. PLEASE |
| | BE SURE TO INDICATE ANY *FLOATING NEUTRAL* KITS WHICH |
| | ARE TO BE INSTALLED AFTER THE FIRST MEANS OF DISCONNECT |
| | PER 250.6, 250.24. |
| | |
| | 9) NOTE: PLEASE SEE THAT LIGHTING PERFORMANCE |
| | CALCULATIONS FOR NEW LIGHTING BEING ADDED TO EXISTING |
| | PER 13-415.2.ABC.1.2, 13-415.2 |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-09-23 09:48:00 | 2007-09-23 09:48:00 |
| | |
| | PLANS REMOVED FROM INCOMING WILL BE RETURNED TO |
| | INCOMING WAITING FOR COMM BOARD ONCE ELECTRICLA REVIEW |
| | IS COMPLETED. |