Plan Review Details - Permit 07080894
Plan Review Stops For Permit 07080894
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-12-26 Cont ID  
Sent By lmartine Date 2008-12-26 Time 13:56 Rev Time 0.00
Received By lmartine Date 2008-12-26 Time 13:56 Sent To  
Notes
2008-12-26 13:57:49METAL ROOF REVISION APPROVED LM

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-03-01 Cont ID  
Sent By amorse Date 2008-03-01 Time 12:27 Rev Time 0.00
Received By amorse Date 2008-03-01 Time 12:27 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-02-21 Cont ID  
Sent By amorse Date 2008-02-21 Time 16:06 Rev Time 0.00
Received By amorse Date 2008-02-21 Time 16:06 Sent To PC
Notes
2008-02-21 16:08:30 
  
 DENIED
  
 THE FOLLOWING COMMENTS WERE NOT ADDRESSED IN THE 1ST OR
 2ND REVIEWS:
  
 1ST REVIEW COMMENTS
  
 COMMENT # 5(IN AN EXISTING BUILDING WHERE ALTERATIONS
 ARE BEING MADE A DESIGN PROFESSIONAL MUST ELECT THE
 LEVEL OF ALTERATION PER 301.5 OF EXISTING BUILDING CODE
 AND STATE ALONG WITH THE TYPE OF CONSTRUCTION ON THE
 DRAWINGS)
 ********PLEASE SEE NOTICE WITH RESPECT TO A 4X THE FEE
 IF COMMENTS ARE NOT CORRECTED AFTER THE 3RD
 REVIEW**********
  
 COMMENT # 6 (SUBMIT TWO COPIES OF ENERGY CALC'S PER
 13-101.2.2 FBC. BE SURE THAT THEY ARE SIGNED AND DATED
 BY PREPARER AND OWNER/AGENT PRIOR TO SUBMITTAL)
 *********PLEASE PROVIDE CORRECT R VALUES AND AREA SIZES
 FOR CONCRETE WALL INSULATION, 2 X 4 WOOD FRAME WALLS, 2
 X 6 WOOD FRAME WALLS, RAISED WOOD FLOOR AREA BETWEEN
 CONDITIONED AND NON CONDITIONED SPACES AND DUCT
 INSULATION
  
  
 2ND REVIEW COMMENTS
  
 COMMENT # 7( PLEASE CLARIFY TYPE OF DOOR ON WEST
 ELEVATION, PLAN STATES FRENCH DOOR BUT SCHEDULE SHOWS
 PANEL DOOR, IF DOOR IS METAL PANEL PROVIDE PRODUCT
 APPROVAL)
  
 COMMENT # 8 (PER 713.13(2) F.S. IF THE IMPROVEMENT
 DESCRIBED IN THE NOC HAS NOT COMMENCED WITHIN 90 DAYS
 OF RECORDING, THE NOTICE IS VOID)
  
  
 3RD REVIEW COMMENTS
  
 1)TYPICAL WOOD SHEARWALL FRAMING DETAIL AT OPENINGS
 THAT WAS ASKED FOR ON FIRST REVIEW AND PROVIDED HAS
 BEEN DELETED FROM SHEET A-4 FOR NEW HIGH ROOF FRAMING
 PLAN AND DETAIL WAS NOT ADDED TO ANOTHER SHEET, PLEASE
 CORRECT
  
 NOTE: FBC = FLORIDA BUILDING CODE 2004 W/2006
 AMENDMENTS
 FBC* = WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS TO FBC
 FAC = FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
 FBC RES. = FLORIDA BUILDING CODE
 RESIDENTIAL 2004 W/2006 AMENDMENTS
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-12-15 Cont ID  
Sent By amorse Date 2007-12-15 Time 09:31 Rev Time 0.00
Received By amorse Date 2007-12-15 Time 09:31 Sent To PC
Notes
2007-12-15 09:31:53 
  
 DENIED
 THE FOLLOWING COMMENTS WERE NOT ADDRESSED ON THE 1ST
 REVIEW:
  
 2)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
 *******ADJUSTED VALUE FOR REMODELLED FIRST FLOOR AREA,
 VALUE STILL EXCEEDS AMOUNT STATED ON PERMIT
 APPLICATION******
  
 3)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON
 SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER
 ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE
 ADDED TO THE PERMIT APPLICATION FEES
 *******THESE FEES ARE BASED ON NEW UNDER ROOF SQUARE
 FOOTAGE******
  
 NOTE: FEES ARE DUE IN THE AMOUNT OF $773.37FOR
 INCREASED VALUE AND STATE RADON FEES THIS AMOUNT IS
 REQUIRED TO BE PAID PRIOR TO FURTHER PLAN REVIEW
  
 5)IN AN EXISTING BUILDING WHERE ALTERATIONS ARE BEING
 MADE A DESIGN PROFESSIONAL MUST ELECT THE LEVEL OF
 ALTERATION PER 301.5 OF EXISTING BUILDING CODE AND
 STATE ALONG WITH THE TYPE OF CONSTRUCTION ON THE
 DRAWINGS
  
 6)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND DATED BY PREPARER
 AND OWNER/AGENT PRIOR
 TO SUBMITTAL ********ENERGY CALC'S NOT CORRECT,
 DRAWINGS SHOW ATTIC INSULATION AS R30 AND CALC'S ARE
 R19, NO DESIGNATION FOR BLOCK WALLS AND WOOD FRAME
 WALLS ON SECOND FLOOR WAS MADE*******
  
 11)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF
 EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. THESE
 SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER PAGES.
 ALL CAN BE FOUND ON WWW.FLORIDABUILDING.ORG
  
 12)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
 *******ALL PRODUCT APPROVALS/SHOP DRAWINGS, ETC ARE
 REQUIRED TO BE REVIEWED AND APPROVED BY PERSONS
 RESPONSIBLE FOR DRAWINGS********
  
 13)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER
 SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON
 WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT
 SUBMITTED APPLICATIONS WILL BE DENIED.
  
 NEW REVIEW COMMENTS
  
 1)PROVIDE INFORMATION ON THE DRAWINGS FOR NEW ROOM
 ADDED TO ROOF DECK, DOES THIS COVER ROOF ACCESS HATCH?
 NO PLAN VIEW, STRUCTURAL ATTACHMENT METHOD, DOOR OR
 WINDOWS NOT IN SCHEDULES, ETC.
  
 2)PROVIDE ATTACHMENT METHOD FOR BILKO ROOF HATCH,
 SHOP DRAWING DOES NOT SPECIFY
  
 3) PROVIDE NOTE ON THE DRAWINGS FOR BUILDING
 PAPER/WATERPROOFING PER THE HARDIPLANK PRODUCT
 APPROVAL
  
 4)ELEVATIONS DEPICT A LOWER ROOF HEIGHT WITH NEW
 ALUMINUM RAILINGS, THESE CHANGES ARE NOT REFLECTED ON
 THE BUILDING SECTIONS OR DETAILS
  
 5)PROVIDE ATTACHMENT METHOD FOR RAILING SYSTEM AT
 ROOF AND BALCONY, NOA IS FOR EMBEDMENT INTO CONCRETE
 BLOCK/TIE BEAM
  
 6)CHOOSE SYSTEM THAT WILL BE USED FROM FLAT ROOF NOA,
 BE SURE THAT IT WILL MEET THE REQUIRED DESIGN PRESSURE
 FROM SHEET A-12 FOR THE PERIMETER AND CORNER ZONES OR
 PROVIDE ENHANCED FASTENING REQUIREMENTS AS OUTLINED IN
 LIMITATION #7 AT END OF NOA. PLEASE NOTE THAT THIS
 MIAMI-DADE REPORT HAS BEEN REVISED AND RENEWED BY
 REPORT #07-0228.06
  
 7)PLEASE CLARIFY TYPE OF DOOR ON WEST ELEVATION, PLAN
 STATES FRENCH DOOR BUT SCHEDULE SHOWS PANEL DOOR, IF
 DOOR IS METAL PANEL PROVIDE PRODUCT APPROVAL
  
 8)PER 713.13(2) F.S.
 IF THE IMPROVEMENT DESCRIBED IN THE NOC HAS NOT
 COMMENCED WITHIN 90 DAYS OF RECORDING, THE NOTICE IS
 VOID
  
  
 NOTE: FBC = FLORIDA BUILDING CODE 2004 W/2006
 AMENDMENTS
 FBC* = WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS TO FBC
 FAC = FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
 FBC RES. = FLORIDA BUILDING CODE
 RESIDENTIAL 2004 W/2006 AMENDMENTS
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-29 Cont ID  
Sent By amorse Date 2007-09-29 Time 13:04 Rev Time 0.00
Received By amorse Date 2007-09-29 Time 13:04 Sent To PC
Notes
2007-09-29 14:08:49 
  
 DENIED
  
 1)BEFORE A PERMIT TO CONSTRUCT, MAYBE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SETS OF PLANS MUST BE STAMPED BY THAT OFFICE,
 AND A COPY OF THE PAID RECEIPTATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION.
  
 2)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 3)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON
 SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER
 ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE
 ADDED TO THE PERMIT APPLICATION FEES
  
 NOTE: FEES ARE DUE IN THE AMOUNT OF $773.37FOR
 INCREASED VALUE AND STATE RADON FEES THIS AMOUNT IS
 REQUIRED TO BE PAID PRIOR TO FURTHER PLAN REVIEW
  
 4)PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL
 COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006
 AMENDMENTS PER 106.1.1 FBC*
  
 5)IN AN EXISTING BUILDING WHERE ALTERATIONS ARE BEING
 MADE A DESIGN PROFESSIONAL MUST ELECT THE LEVEL OF
 ALTERATION PER 301.5 OF EXISTING BUILDING CODE AND
 STATE ALONG WITH THE TYPE OF CONSTRUCTION ON THE
 DRAWINGS
  
 6)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND
 DATED BY PREPARER AND OWNER/AGENT PRIOR
 TO SUBMITTAL
  
 7)PROVIDE AT MINIMUM 1 ACCESSIBLE BATHROOM PER
 R322.1.1 FBC 29" CLEAR WITH DOOR OPEN 90 DEGREES
  
 8)PROVIDE SCHEDULE FOR PRECAST LINTEL THAT WILL BE
 USED AND OPENING SIZES TO COMPLY WITH 2104.1.5 FBC &
 703.7.3 FBC RES. FOR MIN BEARING
  
 9)PROVIDE ATTIC ACCESS ON DRAWINGS TO ALL AREAS AS
 REQUIRED PER R807.1 FBC RES.
  
 10)SUBMIT ENGINEERED TRUSS DRAWINGS THAT COMPLY WITH
 R802.10.1 FBC WITH PERMIT APPLICATION OR BEFORE
 INSTALLATION THAT HAVE BEEN REVIEWED AND APPROVED BY
 THE DESIGNER OF RECORD
  
 11)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF
 EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. THESE
 SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER PAGES.
 ALL CAN BE FOUND ON WWW.FLORIDABUILDING.ORG
  
 12)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 13)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER
 SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON
 WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT
 SUBMITTED APPLICATIONS WILL BE DENIED
  
 NOTE: PRODUCT APPROVALS ARE REQUIRED FOR ALL COMPONENT
 AND CLADDING PRODUCTS (FRENCH DOORS, WINDOWS, WINDOW
 MULLIONS, ROOFING (MODIFIED & SHINGLE), VINYL SOFFIT &
 SIDING, CONCRETE LINTELS, ROOF HATCH, ETC.
  
 14)PROVIDE SIMPSON TIE CONNECTOR SCHEDULE FOR ALL
 FRAMING CONNECTIONS THAT INCLUDES FLORIDA STATEWIDE
 PRODUCT APPROVAL #'S OR SUBMIT THE PRODUCT APPROVALS
 FOR THE REQUIRED CONNECTORS
  
 15)SUBMIT SHOP DRAWINGS FOR THE SPIRAL STAIRS THAT
 SHOW COMPLIANCE WITH R311.5.8.1 FBC RES.
  
 16)PROVIDE CORRECT SIZES FOR WINDOWS IN THE WINDOW
 SCHEDULE AS THEY DO NOT MATCH BUILDING ELEVATIONS, BE
 SURE TO NOTE OPENINGS THAT REQUIRE (2) UNITS TO BE
 MULLED TOGETHER. ALSO VERIFY WINDOW TYPES ELEVATION HAS
 SINGLE HUNG AND SCHEDULE HAS CASEMENT.
  
 17)PROVIDE ALL DOOR AND WINDOW DESIGN PRESSURES
  
 18)PROVIDE WOOD FRAME OPENING DETAIL C/W FRAMING
 CONNECTOR THAT WILL BE USED AT WINDOW OPENINGS.
  
 19)PROVIDE DETAIL FOR POST ATTACHMENT AT MASTER
 BEDROOM BALCONY, GUARDRAIL TO MEET CONCENTRATED LOAD
 REQUIREMENTS OF 200 POUNDS PER SQUARE FOOT APPLIED IN
 ANY DIRECTION PER R303.5 FBC RES.
  
 20)CLARIFY BB-1 ON FOUNDATION PLAN SHEET A-3, SECTION
 3/A-11 STATES THAT STEM WALL IS SOLID GROUT BELOW GRADE
 IS TOP OF STEM WALL A BOND BEAM AS IT IS NOT IN THE
 BEAM SCHEDULE. ALSO 3/A11 AND WALL SECTION C/A-5 SHOW
 DIFFERENT FLOOR JOIST CONNECTIONS
  
 21)REMOVE ALL OLD PAGES AND RESUBMIT 2 COMPLETE SETS
 OF NEW DRAWINGS AND INCLUDE 1 COPY OF THE OLD PAGES
 ONLY FOR REFERENCE
  
 NOTE: FBC = FLORIDA BUILDING CODE 2004 W/2006
 AMENDMENTS
 FBC* = WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS TO FBC
 FAC = FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
 FBC RES. = FLORIDA BUILDING CODE
 RESIDENTIAL 2004 W/2006 AMENDMENTS
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-11-21 Cont ID  
Sent By btrobaug Date 2007-11-21 Time 16:17 Rev Time 0.00
Received By btrobaug Date 2007-11-21 Time 15:02 Sent To M
Notes
2007-11-21 16:17:47 
  
 TOM'S DESK./WRT.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-09-07 Cont ID  
Sent By btrobaug Date 2007-09-07 Time 11:49 Rev Time 0.00
Received By btrobaug Date 2007-09-07 Time 07:22 Sent To M
Notes
2007-09-07 11:49:38 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE SERVICE LOCATION DOES NOT MEET THE CLEARANCE
 REQUIREMENTS OF 110.26. THE CLEAR SPACE (3?) BECAUSE OF
 THE STEPS, AND THE 30? WIDTH REQUIREMENT WITH REGARD TO
 THE CONDENSING UNIT, THE DISCONNECT AND THE METER.
  
 2} PROVIDE THE CONDUIT SIZE, CONDUCTOR NUMBER AND SIZE
 FROM THE METER TO THE DISCONNECT ON THE RISER. THIS
 COMMENT IS MADE TO INSURE THAT NO GROUNDING CONDUCTOR
 PARALLELS THE NEUTRAL PRIOR TO THE FIRST MEANS OF
 DISCONNECT.
  
 3} THE GROUNDING ELECTRODE SYSTEM MUST COMPLY WITH
 250.50. SEE 250.52(A)(3) FOR FOOTER STEEL.
  
 4}PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT. COMPLIANCE WITH THIS ARTICLE MUST
 BE CLEAR IN THE DESIGN STAGE AND THAT RATING INDICATED
 ON THE PLAN.
  
 5} INDICATE THE CODE CYCLES THIS PROJECT WAS DESIGNED
 UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES FOR CLARITY
 IN THE FIELD AND RECORD RETENTION PER 106.1.3 FBC AS
 AMENDED.
  
 6} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A),210.52(C) AND 210.8(A)(6) GFI. THIS APPLIES
 TO ALL COUNTERTOPS AND THE ISLAND.
  
 7} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1) AND
 210.52(A)(2). SEE BEDROOM #2 WALL AREA BETWEEN THE DOOR
 AND CLOSET.
  
 8} THE ENGINEER OF RECORD MUST PROVIDE A TITLE BLOCK
 WITH INFORMATION PER 61G15-23.002(2) FAC
  
  NOTE: REGARDING THE DISCONNECTING MEANS FOR THE WATER
 HEATER. SEE 422.16 NEC FOR CORD AND PLUG RESTRICTIONS,
 AND 422.31(B) FOR HARDWIRE REQUIREMENTS AND 422.17 FOR
 COMBUSTIBLE MATERIALS AND APPLIANCES.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-12-22 Cont ID  
Sent By adarroug Date 2008-12-22 Time 10:52 Rev Time 0.00
Received By adarroug Date 2008-12-22 Time 10:52 Sent To B
Notes
2008-12-22 10:52:57TO "LMARTINEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-02-28 Cont ID  
Sent By adarroug Date 2008-02-28 Time 11:14 Rev Time 0.00
Received By adarroug Date 2008-02-28 Time 11:14 Sent To Z
Notes
2008-02-28 11:15:09TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-02-14 Cont ID  
Sent By adarroug Date 2008-02-14 Time 14:00 Rev Time 0.00
Received By adarroug Date 2008-02-14 Time 14:00 Sent To B
Notes
2008-02-14 14:00:30TO "AMORSE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-02-14 Cont ID  
Sent By adarroug Date 2008-02-14 Time 10:25 Rev Time 0.00
Received By adarroug Date 2008-02-14 Time 10:25 Sent To Z
Notes
2008-02-14 10:25:23TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-15 Cont ID  
Sent By adarroug Date 2007-11-15 Time 11:52 Rev Time 0.00
Received By adarroug Date 2007-11-15 Time 11:52 Sent To Z
Notes
2007-11-15 11:53:11TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-09-29 Time   Rev Time 0.00
Received By adarroug Date 2007-08-30 Time 14:39 Sent To  
Notes
2007-08-30 14:39:36TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-11-26 Cont ID  
Sent By tgordon Date 2007-11-26 Time 11:16 Rev Time 0.35
Received By tgordon Date 2007-11-26 Time 11:16 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-09-11 Cont ID  
Sent By tgordon Date 2007-09-11 Time 12:12 Rev Time 0.40
Received By tgordon Date 2007-09-11 Time 12:11 Sent To P
Notes
2007-09-11 12:21:46PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA
 ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS).
  
 *** DENIED ***
 1) INFORMATION MISSING IN TITLE BLOCK FOR ARCHITECT
 BUSINESS 'GLACE & COMPANY INC.'(FIRM LICENSE NUMBER)
 ALL PAGES. SEE FAC 61G1-16.004 TITLE BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT. ("JOB
 ADDRESS" SEE CITY WPB AMEND. 106.1.1).
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON
 SEALING THE DOCUMENT.
  
 2) ENERGY CALCULATIONS NEED TO BE ON FORM 600A-2004R,
 SEE FBC 600.3.A. PLEASE CORRECT.
  
 3) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-12-12 Cont ID  
Sent By jleech Date 2007-12-12 Time 08:11 Rev Time 0.00
Received By jleech Date 2007-12-12 Time 08:11 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-09-15 Cont ID  
Sent By jleech Date 2007-09-15 Time 10:46 Rev Time  
Received By jleech Date   Time   Sent To B
Notes
2007-09-15 10:57:34DENIED;
 1.AUTOMATIC CLOTHES WASHER NOT SHOWN ON FLOOR PLAN PAGE
 A-2.
 2. TWO P-1'S SUBMITED, REMOVE THE SHEET DRAWN BY GLACE
 AND COMPANY.
 3. REVIEW OF RISER DIAGRAM BY BRUCE MILLER;
 A. AUTOMATIC CLOTHES WASHER NOT VENTED, ALSO
 CLEANOUT IS REQUIRED AT 48" OFF FINISH FLOOR.
 B. DISHWASHER TO DISCHARGE INDIRECTLY INTO THE
 TAIL PIECE OF THE KITCHEN SINK.
 C. BATHROOM # 1 CAN NOT BE INSTALLED AS DRAWN.
 A BATHROOM GROUP CAN NOT BE PART OF THE BUILDING DRAIN.
 SEE FBC-2004 PLUMBING SECTION 909.1
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 3 Status P Date 2008-02-28 Cont ID  
Sent By choops Date 2008-02-28 Time 14:31 Rev Time 0.00
Received By choops Date 2008-02-28 Time 14:31 Sent To B
Notes
2008-02-28 14:33:35***APPROVED - RESUB #2 - (RESTAMPED PLANS)***
  
 PROVISOS:
 1) LANDSCAPING MUST MEET MINIMUM REQUIREMENTS FOUND IN
 SECTION 94-442 OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS: FOR SINGLE-FAMILY DWELLING UNITS, AT LEAST
 ONE SHADE, FLOWERING OR FRUIT TREE SHALL BE PLANTED FOR
 EACH 1,200 SQUARE FEET OF OPEN SPACE OR PORTION
 THEREOF. FOR SINGLE-FAMILY DWELLING UNITS, AT LEAST ONE
 SHRUB SHALL BE PLANTED FOR EACH 500 SQUARE FEET OF OPEN
 SPACE OR PORTION THEREOF. NOTE: PALM TREES DO NOT COUNT
 AS SHADE OR FLOWERING TREES.
 2)ANY NEW OR RELOCATED MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4' INTO A REQUIRED SETBACK.
  
  
  
 SENT TO "B" - AM

Review Stop Z ZONING
Rev No 2 Status P Date 2007-11-20 Cont ID  
Sent By choops Date 2007-11-20 Time 09:14 Rev Time 0.00
Received By choops Date 2007-11-20 Time 09:14 Sent To E
Notes
2007-11-20 09:16:00***APPROVED - RESUB #1***
  
 PROVISOS:1) LANDSCAPING MUST MEET MINIMUM
 REQUIREMENTS FOUND IN SECTION 94-442 OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS: FOR SINGLE-FAMILY
 DWELLING UNITS, AT LEAST ONE SHADE, FLOWERING OR FRUIT
 TREE SHALL BE PLANTED FOR EACH 1,200 SQUARE FEET OF
 OPEN SPACE OR PORTION THEREOF. FOR SINGLE-FAMILY
 DWELLING UNITS, AT LEAST ONE SHRUB SHALL BE PLANTED FOR
 EACH 500 SQUARE FEET OF OPEN SPACE OR PORTION THEREOF.
 NOTE: PALM TREES DO NOT COUNT AS SHADE OR FLOWERING
 TREES.2)ANY NEW OR RELOCATED MECHANICAL
 EQUIPMENT MAY NOT PROJECT MORE THAN 4' INTO A REQUIRED
 SETBACK.
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 1 Status F Date 2007-08-31 Cont ID  
Sent By choops Date 2007-08-31 Time 18:08 Rev Time 0.00
Received By choops Date 2007-08-31 Time 18:08 Sent To E
Notes
2007-08-31 18:16:33***FAILED***
  
  
 1)DOES NOT MEET FRONT SETBACK REQUIREMENT OF 25
 FEET.THE EXISTING STRUCTURE IS A NONCONFORMING
 BUILDING.NEW CONSTRUCTION MUST MEET ALL CURRENT
 REGULATIONS.
  
 2)INDICATE REAR SETBACK DIMENSION FROM FLORIDA
 ROOM/PORCH TO THE PROPERTY LINE.
  
 3)SHOW ANY PROPOSED OR RELOCATED A/C EQUIPMENT, IF
 ANY, WITH SETBACK DIMENSIONS TO THE PROPERTY LINES.
  
 4)ELEVATIONS (SHEET A-5) SHALL BE SHOWN FROM GRADE
 TO THE MIDPOINT OF THE ROOF'S PITCH.
  
 5)PROVIDE ALL OVERHANG DIMENSIONS FROM THE WALL TO
 THE OUTERMOST POINT OF THE ROOF.
  
 6)AS THE VALUE OF THE PROPOSED WORK EXCEEDS 50% OF
 THE VALUE OF THE HOME, THE LANDSCAPING MUST MEET
 CURRENT REGLUATIONS.THE LANDSCAPE PLAN MUST SHOW TYPE
 AND SIZE OF EXISTING TREES/SHRUBS AND MUST BE IN
 CONFORMANCE WITH SECTION 94-442 OF THE CITY OF WEST
 PALM BEACH ZONING AND LAND DEVELOPMENT REGULATIONS.
  
 7)SHOW DISTANCE FROM CLOSEST POINT OF PRINCIPAL
 STRUCTURE (EITHER NEW WALL, OR FLORIDA ROOM) TO THE
 EXISTING COTTAGE HOUSE. (MUST MAINTAIN A MINIMUM OF 6
 FEET)
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720