| Plan Review Stops For Permit 07080846 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2007-08-30 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-08-30 |
Time |
17:39 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-08-30 |
Time |
17:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-08-28 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-08-28 |
Time |
16:48 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-08-28 |
Time |
16:48 |
Sent To |
|
|
| Notes |
| 2007-08-28 16:54:35 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.)THE ENGINEER'S LETTER STATES THAT THE SYSTEM HAS A | | | DESIGN PRESSURE OF -45, CONTRACTOR HIGHLIGHTED A SYSTEM | | | FOR -52.5.CONFIRM WHICH ASSEMBLY YOU'RE USING. | | | | | | 2.)ENGINEER'S LETTER STATES THAT 9"/9" IS TO BE USED | | | IN THE BALANCE OF THE ROOF (OTHER THAN CORNERS), BUT | | | THE PERIMETER REQUIREMENT IS -59.2, ENHANCED FASTENING | | | FOR ZONE 2 REQUIRED. |
|
|
|