| 2007-10-16 14:41:14 | RESIDENTIAL SHUTTERS BUILDING REVIEW SECOND CHECKLIST. |
| | |
| | REVIEW DONE UNDER 2004 FLORIDA RESIDENTIAL CODE AND BC |
| | 2004 WITH 2007 REVISIONS. |
| | |
| | 1- STORM SHUTTERS INSTALLATION SCHEDULE SUBMITTED: |
| | A) PROVIDE 2 COPIES.ONLY ONE WAS SUBMITTED.SEC. |
| | 106.1 CITY AMENDMENTS TO FBC 2004. |
| | |
| | B) THERE ARE 2 DIFFERENT PRODUCT APPROVALS |
| | SUBMITTED.FL 722-R1 AND NOA 06-0110.04ARE 2 |
| | DIFFERENT PRODUCT APPROVALS.SUBMIT ONLY ONE COMPLETE |
| | PACKAGE. EG: IF SUBMITTING THE FL722-R1, THEN PROVIDE |
| | DRAWINGS THAT WERE SUBMITTED TO GET THE FLORIDA PRODUCT |
| | APPROVAL.OTHERWISE, PROVIDE THE NOA ALONE. |
| | |
| | C) BUILDING HEIGHT CAN'TBE 8'-1".SEC. 106.1.2 |
| | CITY AMENDMENTS TO FBC 2004.REVISE AS REQUIRED. SEE |
| | PLANS. |
| | |
| | D) REVISE OPENING SIZE FOR OPENING #1. SEE KEY |
| | PLAN. |
| | |
| | E) INFORMATION SHOWN ON INSTALLATION SCHEDULE |
| | DOESN'T MATCH INFORMATION HIGHLIGHTED ON THE STORM |
| | SHUTTERS DRAWINGS. COORDINATE INFORMATIONAS REQUIRED |
| | TO MATCH. EG: CHECK ANCHOR TYPE AND SPACING, MOUNTING |
| | CONDITIONS (WALL MOUNTED, BUILD OUT, ETC.),SUBSTRATE |
| | (CONCRETE BLOCK OR CONCRETE), ETC. |
| | |
| | F) CLARIFY INFORMATION ON COLUMN 4. WHAT'S WALL |
| | B?.THIS COLUMN IS DESIGNED TO SPECIFY SHUTTER |
| | MOUNTING CONDITIONS. EG: WALL MOUNT, BUILD OUT, ETC. |
| | SEE SHUTTERS DRAWINGS FOR SPECIFICMOUNTING CONDITIONS |
| | TO BE USED.THIS HELPS TO IDENTIFY WHICH ANCHOR |
| | CONNECTION TYPE NEEDS TO BE USED IN THE ANCHOR SCHEDULE |
| | SHOWN ON PAGE 5 OF 7. |
| | |
| | G) SPECIFYBOTH DESIGN PRESSURES. POSITIVE AND |
| | NEGATIVE.SCHEDULE SUBMITTED ONLY IDENTIFIES THE |
| | POSITIVE DESIGN PRESSURES. SEC. 106.1.2 CITY AMENDMENTS |
| | TO FBC 2004. |
| | |
| | H) SPECIFY SHUTTER GLASS SEPARATION. SEE PAGE 4 OF |
| | DRAWINGS SUBMITTED. |
| | |
| | I) SPECIFY ANCHOR SPACING AT BOTTOM OF SHUTTER. ONLY |
| | TOP ONE WAS SPECIFIED. |
| | |
| | J) PROVIDE COMPLETE INFORMATION REGARDING CENTER |
| | BOLTS.SHUTTER DRAWINGS SUBMITTED DON'T SPECIFY ANY |
| | CENTER BOLTS. WHERE IS THIS INFORMATION TAKEN FROM?. |
| | SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | K) INSTALLATION SCHEDULESUBMITTED CALLS FOR |
| | CONCRETE BLOCK AS THE SUBSTRATE TO RECEIVE THE STORM |
| | PANELS, WHILEANCHOR SCHEDULE ON PAGE 5 OF 7 THE |
| | CONCRETE COLUMN WAS HIGHLIGHTED.REVISE INFORMATION AS |
| | REQUIRED TO MATCH.ANCHORSPACING IS DIFFERENT FOR |
| | CONCRETE AND FOR CONCRETE BLOCK. |
| | |
| | L) REVISE ANCHOR SPACING FOR OPENING #7 AND #12. SEE |
| | ANCHOR SCHEDULE ON SHEET 5 OF 7. |
| | |
| | 2- THERE IS A REVIEW AND APPROVED STAMP ON FLORIDA |
| | PRODUCT APPROVAL FL722-R1.DESIGNER OF RECORD WHO |
| | REVIEWED AND APPROVED THIS PRODUCT APPROVAL NEEDS TO |
| | PROVIDE HIS NAME. OTHERWISE, THERE IS NO WAY OF KNOWING |
| | WHO REVIEW AND APPROVED THE PRODUCT APPROVAL. AND , |
| | THIS DECEIVES THE PURPOSE OF HAVING THE DESIGNER OF |
| | RECORD APPROVING THE PRODUCT APPROVALS. |
| | ***NOTE:MAKE SURE SELECTED PRODUCT APPROVAL(SEE |
| | ITEM 1(B)ABOVEGETS REVIEWED AND APPROVED IN WRITING |
| | (NOT SIGNING AND SEALING)BY THE DESIGNER OF RECORD AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 3- VALUE DECLARED IN THE PERMIT APPLICATION IS TOO LOW. |
| | UPDATE VALUE AS REQUIRED. SEC. 108.3 CITY AMENDMENTS TO |
| | FBC 2004. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |