Plan Review Details - Permit 07080804
Plan Review Stops For Permit 07080804
Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2008-06-05 Cont ID  
Sent By amorse Date 2008-06-05 Time 18:52 Rev Time 0.00
Received By amorse Date 2008-06-05 Time 18:52 Sent To PC
Notes
2008-06-05 18:53:24 
  
 REVISION FOR AS BUILT CONDITION PASSED

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2008-05-22 Cont ID  
Sent By amorse Date 2008-05-22 Time 15:30 Rev Time 0.00
Received By amorse Date 2008-05-22 Time 15:30 Sent To PC
Notes
2008-05-22 15:31:30 
  
 BUILDING SUBMITTAL FOR SHUTTERS AS REQUESTED; PASSED

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2008-04-30 Cont ID  
Sent By amorse Date 2008-04-30 Time 16:20 Rev Time 0.00
Received By amorse Date 2008-04-30 Time 16:20 Sent To PC
Notes
2008-04-30 16:40:50 
  
 DENIED
  
 1)PROVIDE A KEY PLAN WITH THE OPENINGS NUMBERED TO
 COINCIDE WITH THE SHUTTER SCHEDULE OPENING NUMBERS,
 THIS IS REQUIRED FOR INSPECTIONS. PLEASE NOTE THAT THE
 OPENINGS ON THE SHUTTER SCHEDULE SEEM TO HAVE NO ORDER
 IN RELATION TO DRAWINGS
  
 2)PRESSURES FOR OPENINGS SHOULD MATCH THOSE ON SHEET
 1.3 OF DRAWINGS, IF LEFT AS IS, OPENING # 8 WILL NOT
 WORK AS MAX DESIGN PRESSURE ALLOWED FOR THIS SHUTTER
 SPAN IS -42 PSF PER SHEET # 2 OF PRODUCT APPROVAL
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-04-09 Cont ID  
Sent By lmartine Date 2008-04-09 Time 16:50 Rev Time 0.00
Received By lmartine Date 2008-04-09 Time 16:44 Sent To  
Notes
2008-04-09 16:50:40 
  
 "BUILDING PROVISO"
  
  
  
 A COMPLETED INSTALLATION SCHEDULE AND STORM SHUTTER
 PRODUCT APPROVAL SHALL BE SUBMITTED FOR REVIEW BEFORE
 C.O.
  
  
 LUIS MARTINEZ
 805-6710

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-04-05 Cont ID  
Sent By amorse Date 2008-04-05 Time 11:09 Rev Time 0.00
Received By amorse Date 2008-04-05 Time 11:09 Sent To E
Notes
2008-04-05 11:14:34 
  
 DENIED
  
 THE FOLLOWING COMMENTS WERE NOT ADDRESSED FROM THE 3RD
 REVIEW
  
 6)SHUTTERAPPLICATIONS REQUIRE A KEY PLAN (WITH
 EGRESS SHOWN), SHUTTER SCHEDULE AND THE PRODUCT
 APPROVALS. APPROVAL DRAWINGS SHALL BE MARKED FOR
 MOUNTING METHOD AND CONNECTION TYPE AND THE SCHEDULE
 FILLED OUT WITH ALL PERTINENT INFORMATION SPECIFIC TO
 THE SITE (TYPE OF CONSTRUCTION, MOUNTING CONNECTION
 METHOD, ANCHOR TYPE, SHUTTER SPAN (VERTICAL OR
 HORIZONTAL), ETC.)***************PLEASE SEE THE
 ATTACHED MEMO AND SCHEDULE.****************
  
 *******NOTE********
 SHUTTER INSTALLATION: FASTENERS FOR FILLED CELL
 BLOCK-WORK-CONTRACTOR CANNOT ASSUME THAT THERE IS A
 CONCRETE SUBSTRATE WHEN SELECTING FASTENERS (AND
 SPACING) UNLESS THEY CAN PROVIDE DOCUMENTATION TO
 VERIFY COMPRESSIVE STRENGTH OF 3,000 PSI, OR 3,500 PSI,
 ETC, AND THE REQUIRED FASTENER EMBEDMENT DEPTH,AS
 REQUIRED ON THE PRODUCT APPROVAL. IF DOCUMENTATION IS
 NOT PROVIDED THE SUBSTRATE SHALL BE CONSIDERED MASONRY
 AND THE O/C SPACING SHALL BE ADJUSTED ACCORDINGLY.
  
 7)PER 713.13(2) F.S. IF THE IMPROVEMENT DESCRIBED IN
 THE NOC HAS NOT COMMENCED WITHIN 90 DAYS OF RECORDING,
 THE NOTICE IS VOID, PLEASE HAVE RERECORDED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date   Cont ID  
Sent By   Date 2008-03-19 Time   Rev Time 0.00
Received By   Date 2008-03-19 Time   Sent To  
Notes
2008-03-18 18:58:44 
  
  
 1)SIMONTON WINDOW PRODUCT APPROVAL DOES NOT COVER
 DH36 SIZE (53 1/8" X 74 1/4")
  
 2)SIMONTON SGD PRODUCT APPROVAL ONLY COVERS 3 LITE
 UNIT IN 107" X 80" SIZE THE UNIT BEING REPLACE IS
 12'-0"WIDE (144") BY 8'-0" TALL (96")
  
 3)PRODUCT APPROVALS AREA COMBINATION OF THE FLORIDA
 STATEWIDE PRODUCT APPROVAL AND MIAMI-DADE NOA'S AND
 NEITHER ONE MEETS THE SIZE REQUIREMENTS.
  
 4)PROVIDE ONLY THE APPROVALS THAT WILL MEET YOUR
 REQUIREMENTS FROM ONE ENTITY, THE CITY OF WEST PALM
 REQUIRES THE STATEWIDE APPROVALS WHEN AVAILABLE IF NOT
 MIAMI-DADE NOA'S WILL BE GIVEN LOCAL PRODUCT APPROVAL.
  
 5)IN EXISTING BUILDINGS WHERE MORE THAN 25% OF THE
 AGGREGATE AREA OF GLAZED OPENINGS ARE BEING REPLACED IN
 ANY 12 MONTH PERIOD IMPACT PROTECTION IS REQUIRED PER
 507.3 FBC EXISTING.
  
 6)SHUTTERAPPLICATIONS REQUIRE A KEY PLAN (WITH
 EGRESS SHOWN), SHUTTER SCHEDULE AND THE PRODUCT
 APPROVALS. APPROVAL DRAWINGS CAN BE MARKED FOR MOUNTING
 METHOD AND CONNECTION TYPE AND THE SCHEDULE FILLED OUT
 WITH ALL PERTINENT INFORMATION SPECIFIC TO THE SITE
 (TYPE OF CONSTRUCTION, MOUNTING CONNECTION METHOD,
 ANCHOR TYPE, SHUTTER SPAN (VERTICAL OR HORIZONTAL),
 ETC.) PLEASE SEE THE ATTACHED MEMO AND SCHEDULE.
  
 *******NOTE********
 SHUTTER INSTALLATION: FASTENERS FOR FILLED CELL
 BLOCK-WORK-CONTRACTOR CANNOT ASSUME THAT THERE IS A
 CONCRETE SUBSTRATE WHEN SELECTING FASTENERS (AND
 SPACING) UNLESS THEY CAN PROVIDE DOCUMENTATION TO
 VERIFY COMPRESSIVE STRENGTH OF 3,000 PSI, OR 3,500 PSI,
 ETC, AND THE REQUIRED FASTENER EMBEDMENT DEPTH,AS
 REQUIRED ON THE PRODUCT APPROVAL. IF DOCUMENTATION IS
 NOT PROVIDED THE SUBSTRATE SHALL BE CONSIDERED MASONRY
 AND THE O/C SPACING SHALL BE ADJUSTED ACCORDINGLY.
  
 7)PER 713.13(2) F.S. IF THE IMPROVEMENT DESCRIBED IN
 THE NOC HAS NOT COMMENCED WITHIN 90 DAYS OF RECORDING,
 THE NOTICE IS VOID, PLEASE HAVE RERECORDED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-11-29 Cont ID  
Sent By amorse Date 2007-11-29 Time 18:00 Rev Time 0.00
Received By amorse Date 2007-11-29 Time 18:00 Sent To PC
Notes
2007-11-29 18:04:22 
  
 PASSED
  
 1)ADDITIONAL PERMIT FEES ARE REQUIRED IN THE AMOUNT
 OF $571.31 DUE TO INCREASED VALUE BASED ON MARSHALL &
 SWIFT GUIDE FOR INTERIOR RESIDENTIAL RENOVATIONS. THIS
 FEE WILL BE REQUIRED BEFORE A PERMIT CAN BE ISSUED.
  
 2)AS WITH ELECTRICAL AND PLUMBING REVIEWERS COMMENTS
 THE 2ND SET OF DRAWINGS IS REQUIRED TO BE SIGNED AND
 SEALED BY RESPONSIBLE ENGINEER AND COMMENTS ADDRESSED
 BEFORE FINAL PERMIT STAMPS CAN BE ADDED AND PERMIT
 PRINTED
 BLDG PLAN REVIEW
  
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-22 Cont ID  
Sent By amorse Date 2007-09-22 Time 15:11 Rev Time 0.00
Received By amorse Date 2007-09-22 Time 15:11 Sent To PC
Notes
2007-09-22 15:53:42 
  
 DENIED
  
 1)PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL
 COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006
 AMENDMENTS PER 106.1.1 FBC*
  
 2)IN AN EXISTING BUILDING WHERE ALTERATIONS ARE BEING
 MADE A DESIGN PROFESSIONAL MUST ELECT THE LEVEL OF
 ALTERATION PER 301.5 OF EXISTING BUILDING CODE AND
 STATE ALONG WITH THE TYPE OF CONSTRUCTION ON THE
 DRAWINGS
  
 3)CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE, AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE PER 106.1.1
 FBC*. NO EXISTING LAYOUT IS SHOWN, IS SHOWER DOOR #6
 FROM EXISTING 2'-6" X 4'-2"SHOWER ? AND ARE NEW
 SHOWER WALLS GLAZED ?
  
 4)PROVIDE COMPLETE SCOPE OF WORK- DEMOLITION,
 CONSTRUCTION, NEW FIXTURES, NEW KITCHEN, NEW FLOORING.
 THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS LOW.
 FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST EXCLUDING
 LAND VALUE. OUR VALUATION REFERENCE IS ICC (BVD),
 MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES PER
 108.3 FBC*.
  
 5)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2008-06-04 Cont ID  
Sent By btrobaug Date 2008-06-04 Time 16:15 Rev Time 0.00
Received By btrobaug Date 2008-06-04 Time 14:58 Sent To B
Notes
2008-06-04 16:16:01 
  
 REVISION AND FILE COPY TO ADRIAN'S DESK./WRT.
2008-06-04 16:15:08 

Review Stop E ELECTRICAL
Rev No 5 Status N Date 2008-05-19 Cont ID  
Sent By btrobaug Date 2008-05-19 Time 09:57 Rev Time 0.00
Received By btrobaug Date 2008-05-19 Time 09:57 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-04-08 Cont ID  
Sent By btrobaug Date 2008-04-08 Time 07:47 Rev Time 0.00
Received By btrobaug Date 2008-04-08 Time 07:27 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-03-20 Cont ID  
Sent By btrobaug Date 2008-03-12 Time 15:57 Rev Time 0.00
Received By btrobaug Date 2008-03-12 Time 15:26 Sent To P
Notes
2008-03-12 15:55:53 
  
  
  
 PROVISO
  
 THESE ISSUES MUST BE CORRECTED AND PLANS RESUBMITTED
 FOR REVIEW PRIOR TO CALLING A ROUGH ELECTRICAL
 INSPECTION.
  
 1} BATH CIRCUITS ARE REQUIRED TO HAVE A 20 AMP
 RECEPTACLE PER 210.11(C) (3), LOCATED PER 210.52(D),
 AND BE GFI PROTECTED PER 210.8(A) (1). CIRCUIT #17 IN
 THE MASTER BATH IS NOT RATED ON THE PANEL SCHEDULE,
 THEY COULD BE ON 23 AS THAT CIRCUIT MEETS THE INTENT OF
 THE EXCEPTION 210.11(C) (3).
  
 2} THE "EXISTING BATH", SAME COMMENT AS ABOVE WITH
 CIRCUITS19 AND 25.
  
 3} PER 210.52(B) (1) & (2), THE CIRCUITS IN THE DINING
 ROOM (# 27)MUST BE 20 AMP AS IT IS, BUT MUST BE
 LABLED "DINING ROOM", NOT "GENERAL LIGHTING. ALSO
 "SHALL HAVE NO OTHER OUTLETS" MEANS THE LIVING ROOM IS
 IN VIOLATION BEING ON THE SAME CIRCUIT.
  
 4}THE LIGHTING IN THE KITCHEN SHALL NOT BE ON A SMALL
 APPLIANCE CIRCUIT, 210.52(B) (2).
  
 5} CIRCUIT #6 IS LABLED "COOK TOP" ON THE SCHEDULE AND
 "DOUBLE OVEN" ON THE PLAN, CORRELATE SAME.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-11-21 Cont ID  
Sent By btrobaug Date 2007-11-21 Time 08:33 Rev Time 0.00
Received By btrobaug Date 2007-11-21 Time 07:41 Sent To P
Notes
2007-11-21 08:07:26 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 THIS COMMENT IS FROM THE 9/5/07 REVIEW;
  
 2} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI
 PROTECTED PER 210.8(A) (1). THAT CIRCUIT(S) IS NOT
 SHOWN ON THE IN THE PANEL SCHEDULE. * THE CIRCUIUT IS
 NOW SHOWN---AT 15 AMPS. PLEASE READ THE COMMENT THEN
 REVIEW THE ARTICLE FOR CLARIFICATION.
  
 THESE ARE COMMENTS GENERATED FROM THE PLANS SUBMITTED
 11/15/07.
  
 1} THE NOTE ON SHEET E-1 AT THE LOAD CALCULATIONS
 INDICATES THE SERVICE IS 200 AMPS, THE FEEDERS ARE
 INDICATED AS 1/0 WHICH PER 310.15(B)(6) IS RATED FOR
 175 AMPS. PLEASE FIELD VERIFY ACTUAL CONDITIONS AND
 CORRECT THE PLAN.
  
 2} THE ENGINEER OF RECORD MUST SEAL THE DOCUMENTS WITH
 A SEAL ACCEPTABLE TO THE BOARD PER 61G15-23.001. ONLY
 ONE SET OF PLANS ARE SEALED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-09-05 Cont ID  
Sent By btrobaug Date 2007-09-05 Time 09:05 Rev Time 0.00
Received By btrobaug Date 2007-09-05 Time 08:49 Sent To M
Notes
2007-09-05 09:05:50 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. WHEN
 INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE PROVIDED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE ALARMS
 SHALL BE INTERCONNECTED AND HARD WIRED. INDICATE
 COMPLIANCE ON THE PLAN.
  
 2} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI
 PROTECTED PER 210.8(A) (1). THAT CIRCUIT(S) IS NOT
 SHOWN ON THE IN THE PANEL SCHEDULE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-05-27 Cont ID  
Sent By adarroug Date 2008-05-27 Time 14:24 Rev Time 0.00
Received By adarroug Date 2008-05-27 Time 14:24 Sent To E
Notes
2008-05-27 14:25:02TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-05-08 Cont ID  
Sent By adarroug Date 2008-05-08 Time 14:52 Rev Time 0.00
Received By adarroug Date 2008-05-08 Time 14:52 Sent To E
Notes
2008-05-08 14:53:58TO "BTROBAUG" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-04-24 Cont ID  
Sent By adarroug Date 2008-04-24 Time 15:48 Rev Time 0.00
Received By adarroug Date 2008-04-24 Time 15:48 Sent To B
Notes
2008-04-24 15:48:49TO "AMORSE" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-04-02 Cont ID  
Sent By adarroug Date 2008-04-02 Time 10:32 Rev Time 0.00
Received By adarroug Date 2008-04-02 Time 10:32 Sent To E
Notes
2008-04-02 10:33:22TO "AMORSE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-03-11 Cont ID  
Sent By adarroug Date 2008-03-11 Time 14:09 Rev Time 0.00
Received By adarroug Date 2008-03-11 Time 14:09 Sent To E
Notes
2008-03-11 14:09:31TO "BTROBAUG" DESK/RESUB--NE SHEETS FOR "BLDG"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-15 Cont ID  
Sent By adarroug Date 2007-11-15 Time 13:30 Rev Time 0.00
Received By adarroug Date 2007-11-15 Time 13:30 Sent To E
Notes
2007-11-15 13:30:58TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-09-22 Time   Rev Time 0.00
Received By adarroug Date 2007-08-28 Time 16:06 Sent To  
Notes
2007-08-28 16:06:17TO "SFR" "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-09-06 Cont ID  
Sent By tgordon Date 2007-09-06 Time 10:37 Rev Time 0.20
Received By tgordon Date 2007-09-06 Time 10:37 Sent To P
Notes
2007-09-06 10:37:47NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-03-13 Cont ID  
Sent By btrobaug Date 2008-03-20 Time 13:25 Rev Time 0.00
Received By mperson Date 2008-03-13 Time 08:19 Sent To B
Notes
2008-03-13 08:33:15****************PROVISO****************
 A} WATER SEAL TRAPS ARE REQUIRED FOR THE NEW LAVS IN
 THE MASTER BATH. PER FBC PLUMBING SECTION 1002.1
 FIXTURE TRAPS.
  
 B} PER FBC PLUMBING SECTION 802.1.6 THE NEW DOMESTIC
 DISHWASHING MACHINE SHALL DISCHARGE INDIRECTLY THROUGH
 AN AIR GAP OR AIR BREAK INTO A STANDPIPE OR WASTE
 RECEPTOR IN ACCORDANCE WITH SECTION 802.2 OR DISCHARGE
 INTO A WYE-BRANCH FITTING ON THE TAILPIECE OF THE
 KITCHEN SINK OR THE DISHWASHER CONNECTION OF A FOOD
 WASTE GRINDER.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-11-29 Cont ID  
Sent By mperson Date 2007-11-29 Time 08:11 Rev Time 0.00
Received By mperson Date 2007-11-29 Time 08:11 Sent To B
Notes
2007-11-29 08:17:43PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 05 & 06 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS
 TO CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED 2ND TIME:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET A-4 PLUMBING RISER DIAGRAM: THE TUB AND
 SHOWER REQUIRE TRAPS. PER *1002.1 FIXTURE TRAPS.
  
 2. THE ENGINEER OF RECORD MUST SEAL THE DOCUMENTS WITH
 A SEAL ACCEPTABLE TO THE BOARD PER F.A.C. 61G15-23.001
 AND F.S. 471.025.
 **NOTE: ONLY ONE SET OF PLANS WERE SEALED.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-09-14 Cont ID  
Sent By mperson Date 2007-09-14 Time 11:40 Rev Time 0.00
Received By mperson Date 2007-09-14 Time 11:40 Sent To B
Notes
2007-09-14 13:33:35DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING WITH 2006 REVISIONS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SHEET A-3 FLOOR PLAN: CLEARLY IDENTIFY ALL PLUMBING
 FIXTURES IN THE MASTER BATH PER FBC-2004 CHAPTER 1,
 SECTION 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS,
 AS DETERMINED BY THE
 BUILDING OFFICIAL.
  
 2. SHEET A-4 PLUMBING RISER DIAGRAM KITCHEN PLEASE
 CORRECT THE FOLLOWING:
  
 A} A SANITARY TEE IS NOT ALLOWED ON THE KITCHEN SINK
 FOR HORIZONTAL TO HORIZONTAL DRAINAGE PER FBC-2004
 PLBG. TABLE 706.3.
  
 B} A DRAIN FOR THE DISHWASHER IS REQUIRED AND NEEDS TO
 BE INDICATED IN THE RESUBMITTED RISER DIAGRAM PER
 FBC-2004 PLBG. SECTION 802.1.6,DOMESTIC DISHWASHING
 MACHINES SHALL DISCHARGE INDIRECTLY THROUGH AN AIR GAP
 OR AIR BREAK INTO A STANDPIPE OR WASTE RECEPTOR IN
 ACCORDANCE WITH SECTION 802.2 OR DISCHARGE INTO A
 WYE-BRANCH FITTING ON THE TAILPIECE OF THE KITCHEN SINK
 OR THE DISHWASHER CONNECTION OF A FOOD WASTE GRINDER.
  
 3. SHEET A-4 PLUMBING RISER DIAGRAM MASTER BATH PLEASE
 CORRECT THE FOLLOWING:
  
 A} A VENT IS REQUIRED FOR BOTH THE TUB AND SHOWER PER
 FBC-2004 PLBG. TABLE 906.1, THE 2 INCH TRAPS CAN NOT BE
 MORE THAN 6 FEET FROM THE VENT. THE TRAPS ARE NOW
 AROUND 8 FEET FROM THE VENT.
  
 B} A SANITARY TEE IS NOT ALLOWED ON THE LAVATORIES FOR
 HORIZONTAL TO HORIZONTAL DRAINAGE PER FBC-2004 PLBG.
 TABLE 706.3.
  
 C} SEND MANUFACTURER SPECIFICATION SHEET OF THE
 CIRCLED FITTING PER FBC-2004 CHAPTER 1, SECTION
 106.1.1, INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS,
 AS DETERMINED BY THE
 BUILDING OFFICIAL.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING IN RED INK
 ON THE INDICATED PLAN SHEETS BY THIS PLANS EXAMINER FOR
 REFERENCE FOR THE RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***