| Plan Review Stops For Permit 07080800 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2007-11-21 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-11-21 |
Time |
17:52 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-11-21 |
Time |
16:28 |
Sent To |
PC |
|
| Notes |
| 2007-11-21 17:52:06 | | | | BUILDING PLAN REVIEW | | | PERMIT: 07080800 | | | ADD: 525 S. FLAGLER DR #2402 | | | CONT: MOTIFF GROUP LLC | | | TEL: (561)202-5104 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: 4TH | | | ACTION: DENIED | | | 11/21/07 | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | **NO RESPONSE NOT ADDRESSED** | | | 2)2004 FBC EXISTING | | | 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE | | | OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO | | | SECTIONS 303, 304 AND 305 OF THIS CODE. | | | **INFORMATION REQUIRED ON DRAWINGS** | | | | | | **NO RESPONSE NOT ADDRESSED** | | | 3)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS | | | LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS | | | AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO | | | INCLUDE STRUCTURAL, PLUMBING, ELECTRIC, MECHANICAL, | | | INTERIOR FINISHES, ARCHITECTURAL AND DESIGN FEES AND | | | OVERHEAD AND PROFIT EXCLUDING LAND VALUE. OUR VALUATION | | | REFERENCE IS ICC (BVD), MARSHALL-SWIFT AND MEANS COST | | | ANALYSIS SERVICES PER 108.3 FBC*. | | | | | | 4)OK | | | 5)OK | | | | | | **NEW** **NO RESPONSE NOT ADDRESSED** | | | A)SUBMIT A FRAMING DETAIL FOR THE NEW CEILING | | | INDICATING ALL MATERIALS. STATE THE TYPE OF MATERIAL TO | | | BE USED AROUND ALL WET AREAS. IN THE AREAS WHERE THE | | | FIRE RATED PARTITION IS DISTURBED, INDICATE ON THE | | | DRAWINGS THE TYPE OF UL ASSEMBLY WHICH WILL MAINTAIN | | | THE WALL RATING. | | | | | | ******************************************************* | | | *********** | | | NOTE: NOW THE PROJECT HAS BEEN ALTERED, SEE COMMENTS | | | BELOW. | | | | | | **NO RESPONSE NOT ADDRESSED** | | | 1)2004 FBC EXISTING | | | 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE | | | OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO | | | SECTIONS 303, 304 AND 305 OF THIS CODE. | | | | | | 2)OK | | | | | | 3)OK | | | | | | **NO RESPONSE NOT ADDRESSED** | | | 4)ALL PLANS SUBMITTED AFTER OCTOBER, 1, 2004 SHALL BE | | | DESIGNED TO THE 2004 FLORIDA BUILDING CODE WITH THE | | | 2007 REVISIONS. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2007-10-31 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-10-31 |
Time |
10:15 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-10-31 |
Time |
06:48 |
Sent To |
|
|
| Notes |
| 2007-10-31 10:15:09 | | | | BUILDING PLAN REVIEW | | | PERMIT: 07080800 | | | ADD: 525 S. FLAGLER DR #2402 | | | CONT: MOTIFF GROUP LLC | | | TEL: (561)202-5104 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: 3RD | | | ACTION: DENIED | | | 10/31/07 | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | 2)2004 FBC EXISTING | | | 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE | | | OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO | | | SECTIONS 303, 304 AND 305 OF THIS CODE. | | | **INFORMATION REQUIRED ON DRAWINGS** | | | | | | **NO RESPONSE NOT ADDRESSED** | | | 3)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS | | | LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS | | | AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO | | | INCLUDE STRUCTURAL, PLUMBING, ELECTRIC, MECHANICAL, | | | INTERIOR FINISHES, ARCHITECTURAL AND DESIGN FEES AND | | | OVERHEAD AND PROFIT EXCLUDING LAND VALUE. OUR VALUATION | | | REFERENCE IS ICC (BVD), MARSHALL-SWIFT AND MEANS COST | | | ANALYSIS SERVICES PER 108.3 FBC*. | | | | | | 4)OK | | | | | | 5)OK | | | | | | **NEW** | | | A)SUBMIT A FRAMING DETAIL FOR THE NEW CEILING | | | INDICATING ALL MATERIALS. STATE THE TYPE OF MATERIAL TO | | | BE USED AROUND ALL WET AREAS. IN THE AREAS WHERE THE | | | FIRE RATED PARTITION IS DISTURBED, INDICATE ON THE | | | DRAWINGS THE TYPE OF UL ASSEMBLY WHICH WILL MAINTAIN | | | THE WALL RATING. | | | | | | ******************************************************* | | | *********** | | | NOTE: NOW THE PROJECT HAS BEEN ALTERED, SEE COMMENTS | | | BELOW. | | | | | | 1)2004 FBC EXISTING | | | 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE | | | OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO | | | SECTIONS 303, 304 AND 305 OF THIS CODE. | | | | | | 2)FBC 106.1.3* THE BUILDING OFFICIAL MAY ESTABLISH | | | THROUGH DEPARTMENTAL POLICY STANDARDS FOR PLANS AND | | | SPECIFICATIONS ?NO WHITE OUT, PENCIL, HAND-WRITING OR | | | INK IS PERMITTED ON THE DRAWINGS? | | | | | | 3)CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT | | | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF | | | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL | | | CONFORM TO THE PROVISIONS OF THIS CODE PER FBC 106.1.1. | | | **SUBMIT TWO NEW SETS OF DRAWINGS AND SHOW THE ENTIRE | | | UNIT, ALL DEMO WORK AND NEW FLOOR PLAN, PLUMBING, | | | ELECTRICAL AND MECHANICAL IF CHANGES ARE MADE, ALSO | | | SHOW THE SMOKE ALARM COMPLIANCE.. SHOW THE EXISTING AND | | | PROPOSED FLOOR PLAN. | | | | | | 4)ALL PLANS SUBMITTED AFTER OCTOBER, 1, 2004 SHALL BE | | | DESIGNED TO THE 2004 FLORIDA BUILDING CODE WITH THE | | | 2007 REVISIONS. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-10-12 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-10-12 |
Time |
17:50 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-10-12 |
Time |
16:17 |
Sent To |
|
|
| Notes |
| 2007-10-12 17:50:50 | | | | BUILDING PLAN REVIEW | | | PERMIT: 07080800 | | | ADD: 525 S. FLAGLER DR | | | CONT: MOTIFF GROUP LLC | | | TEL: (561)202-5104 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: 2ND | | | ACTION: DENIED | | | 10/12/07 | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | 2)OK | | | | | | **NO RESPONSE NOT ADDRESSED** | | | 3)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS | | | LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS | | | AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO | | | INCLUDE STRUCTURAL, PLUMBING, ELECTRIC, MECHANICAL, | | | INTERIOR FINISHES, ARCHITECTURAL AND DESIGN FEES AND | | | OVERHEAD AND PROFIT EXCLUDING LAND VALUE. OUR VALUATION | | | REFERENCE IS ICC (BVD), MARSHALL-SWIFT AND MEANS COST | | | ANALYSIS SERVICES PER 108.3 FBC*. | | | | | | 4)OK | | | | | | 5)OK | | | | | | **NEW** | | | A)SUBMIT A FRAMING DETAIL FOR THE NEW CEILING | | | INDICATING ALL MATERIALS. STATE THE TYPE OF MATERIAL TO | | | BE USED AROUND ALL WET AREAS. IN THE AREAS WHERE THE | | | FIRE RATED PARTITION IS DISTURBED, INDICATE ON THE | | | DRAWINGS THE TYPE OF UL ASSEMBLY WHICH WILL MAINTAIN | | | THE WALL RATING. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-09-13 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-09-13 |
Time |
12:34 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-09-13 |
Time |
06:03 |
Sent To |
|
|
| Notes |
| 2007-09-13 12:34:45 | BUILDING PLAN REVIEW | | | PERMIT: | | | ADD: | | | CONT: | | | TEL: (561)###-#### | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | | ANTICIPATED COOPERATION. | | | | | | 2) 2004 FBC EXISTING | | | 301.5A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE | | | OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO | | | SECTIONS 303, 304 AND 305 OF THIS CODE. | | | | | | 3)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS | | | LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS | | | AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST | | | EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC | | | (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES | | | PER 108.3 FBC*. | | | | | | 4)THE CERTIFICATE OF AUTHORIZATION FOR FDC DESIGN | | | SHALL BE INDICATED ON EACH SHEET FILED FOR PUBLIC | | | RECORD. F.A.C. 61G1-16.004 | | | | | | 5)THE OCCUPANCY GROUP R-3 INDICATED ON THE DRAWINGS | | | IS INCORRECT. SEE 2004 FBC TABLE 503 AND TABLE 601 FOR | | | MORE INFORMATION. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2007-11-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-11-08 |
Time |
08:35 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-11-07 |
Time |
16:48 |
Sent To |
|
|
| Notes |
| 2007-11-08 08:35:11 | ** DENIED 3RD REVIEW ** | | | | | | ** PLEASE SEE THE REVISED PLANS NOW SHOW SOME OF THE | | | SAME ITEMS WHICH WERE NOT CODE COMPLIANT ON THE | | | ORIGINAL REVIEW. THESE HAVE NO BEEN CORRECTED. | | | ** THE ITEMS ON PLANS WHICH EXIST AND ARE NOT A LIFE | | | SAFETY/FIRE HAZARD ARE NOT BEING CONSIDERED IN THIS | | | REVIEW. | | | | | | | | | 1) NOTE: PLEASE SEE SOME CIRCUITING IS STILL MISSING | | | FROM PLANS AND REQUIRED CIRCUITS CAN NOT BE VERIFIED. | | | FOR EXAMPLE: PLEASE SEE SMOKE ALARMS ARE MISSING | | | CIRCUITING AND CIRCUITING MUST HAVE AFCI PROTECTION. | | | 210.12 | | | FOR EXAMPLE; MASTER BATH MISSING SPACING AND INDICATION | | | OF GFI AT LAVATORY AREA. PLEASE KNOW THE GFI IS | | | REQUIRED TO BE WITHIN 3FT IF SINK EDGE HOWEVER IT IS | | | NOT PERMISSIBLE TO CROSS OVER A OPEN SINK TO REACH THE | | | RECEPTACLE LOCATION. PLEASE SEE THAT AN ADDITIONAL GFI | | | WILL BE REQUIRED OR RELOCATE THE ONE SHOWN. | | | | | | 2) NOTE: PLEASE SEE 210.8A6 AS ALL KITCHEN COUNTER | | | SPACE RECEPTACLES ARE REQUIRED TO BE GFI/GFI PROTECTED. | | | THE NOTE ON THE LOWER RIGHT HAND SIDE OF PLANS FOR GFI | | | RECEPTACLES IS NOT ACCURATE AS THERE ARE MANY CHANGES | | | IN THE CODES WHERE THESE NOTES ARE NOT. PLEASE ADJUST | | | NOTE. | | | 210.8 | | | | | | 3) NOTE: PLEASE SEE PANEL AND SERVICE SIZE AS PLANS | | | STILL INDICATE 1/0 CONDUCTORS FOR 200AMP PANEL. PLANS | | | ALSO SHOW 3/0, WHICHSIZE CONDUCTORS ARE INSTALLED. | | | | | | 4) NOTE: PLEASE SEE 424.3B AS MIN OCP FOR AHU 10KW HEAT | | | IS 60AMPS. | | | | | | 5) NOTE: PLEASE SEE ELECTRICAL NOTE WHICH MENTIONS ALL | | | WIRING TO BE #12 BETWEEN FIXTURES AND SWITCHES YET THE | | | PANEL SCHEDULE SHOWS #14 ON MOST OF THESE. | | | | | | 6) NOTE: PLEASE SEE 410.8 AS THE LIGHTING IN CLOSET AS | | | SHOWN IS NOT PERMITTED. THIS IS A FIRE HAZARD/LIFE | | | SAFETY SITUATION. | | | | | | ** PLEASE SEE NEC 2005 AND LS CODE NFPA-101 2003 AS | | | THERE ARE SEVERAL CHANGES WHICH ARE NEEDED. | | | PLEASE REVISE PLANS FOR SCOPE OF WORK AND MINIMUM CODE | | | COMPLIANCE. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | | DELAYS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2007-10-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-10-31 |
Time |
14:36 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-10-31 |
Time |
13:11 |
Sent To |
|
|
| Notes |
| 2007-10-31 14:37:02 | | | | ** DENIED 3RD REVIEW** | | | | | | | | | 1) NOTE: PLEASE SEE THE SCOPE OF WORK IS NOW NOT CLEAR | | | AND PLANS DO NOT INDICATE AN ACCURATE DEPICTION OF THE | | | WORK. | | | PLEASE SEE THAT THE ELECTRICAL SCOPE OF WORK IS STILL | | | REQUIRED FOR REMOVAL OF ELECTRICAL AND HOW ELECTRICAL | | | WILL BE TERMINATED. | | | PLEASE PROVIDE A LAYOUT OF KITCHEN RECEPTACLES NEW OR | | | EXISTING FOR NEW KITCHEN CABINETS MEETING 210.52C1, | | | 210.52B1, 220.53, 210.8A6. | | | | | | ** PLEASE KNOW AS THE SCOPE OF WORK IS NOT CLEAR AT | | | THIS TIME, A COMPLETE REVIEW CAN NOT BE DONE. | | | | | | 2) NOTE: PLEASE DO NOT SUBMIT PLANS WITH HAND-DRAWN | | | CHANGES. FS 481, 471. | | | FBC 106.3.1. | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | | DELAYS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2007-10-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-10-11 |
Time |
15:47 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-10-11 |
Time |
12:48 |
Sent To |
|
|
| Notes |
| 2007-10-11 16:25:04 | ** DENIED 2ND REVIEW** | | | | | | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW STILL | | | NEED TO BE ADDRESSED ALONG WITH NEW NOTE DUE TO | | | ADDITIONAL INFORMATION ONLY NOW SUBMITTED WHICH WAS NOT | | | ON PREVIOUS PLANS. | | | | | | 1) NOTE:SAME NOTE AS PREVIOUS REVIEW: THE ELECTRICAL | | | PLANS STILL DO NOT CONTAIN THE REQUIRED RELEVANT CODES | | | AS PREVIOUSLY GIVEN. | | | **PREVIOUS REVIEW NOTE** | | | PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH ARE | | | SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS | | | UNDER THE NEW CODES ADOPTED BY THE STATE. PLEASE SEE | | | THAT THIS SHALL INCLUDE 2006 REVISIONS TO THE 2004 FBC | | | FOR ALL TRADES AND THE 2005 NFPA-70. PLEASE KNOW THERE | | | ARE CHANGES IN THE FBC WHICH MAY AFFECT DESIGNS FOR ALL | | | TRADES. | | | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS | | | REVIEWER AT A MINIMUM. | | | 2004 FBC W/ 2006 REVISIONS | | | 2005 NFPA-70 | | | 2002 NFPA-72 | | | 2003 NFPA-101 | | | | | | ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED | | | FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS | | | NOT MADE BY OTHER TRADE(S). | | | | | | 2) NOTE: PLEASE SEE SMOKE ALARMS ARE NOW SHOWN AS NOTED | | | ON PREVIOUS REVIEW NOTE #2, HOWEVER PLEASE SEE THE | | | CIRCUITING FOR THESE ARE MISSING. PLEASE SEE PREVIOUS | | | NOTE #7 ALSO AS ALL CIRCUITING WAS NOTED. | | | PLEASE BE SURE TO SEE 210.12 FOR REQUIRED ARC FAULT | | | PROTECTION. | | | FBC 106.1.2 | | | | | | 3) NOTE: PLEASE SEE NEW ELECTRICAL FEEDERS ARE NOTED | | | BOTH AS 1/0 AND 3/0. PLEASE KNOW IF THIS IS AN EXISTING | | | 200AMP MAIN AND PANEL AS NOTED ON PLANS THEN THE 1/0 | | | FEEDER CONDUCTOR SIZE IS NOT SUFFICIENT PER 310.16. | | | PLEASE ADJUST. | | | | | | 4) NOTE:PLEASE SEE NOTE #4 FROM PREVIOUS REVIEW: THIS | | | IS THE SAME COMMENT. | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SEE THE WATER HEATER UNDER THE NEW 2005 NEC IS | | | REQUIRED TO BE SHOWN AT 125% IN LOAD CALCULATIONS. | | | 422.13 | | | | | | 5) NOTE: PLEASE SEE THAT THIS IS THE SAME NOTE FROM | | | PREVIOUS REVIEW NOTE #5. THE PLANS STILL DO NOT | | | INDICATE A RECEPTACLE FOR THE DISPOSAL?? PLEASE SEE | | | NOTE WITH RESPECT TO BREAKERS TO THE SAME YOKE AS | | | MENTIONED. | | | ** PREVIOUS REVIEW NOTE** | | | PLEASE SEE PLANS APPEAR TO BE MISSING THE RECEPTACLE | | | LOCATION FOR THE DISPOSAL. PLEASE ALSO SEE THE 210.4B | | | IF BOTH THE DISH/ DISP ARE BEING FED TO THE SAME YOKE | | | WHICH WILL REQUIRE A 2-POLE BREAKER. | | | | | | 6) NOTE: PLEASE SEE PREVIOUS NOTE #8, AS THERE IS STILL | | | REQUIRED GFI MISSING ALONG KITCHEN COUNTER-SPACE. | | | ** PREVIOUS REVIEW NOTE #8** | | | PLEASE SEE 210.52C1 FOR MISSING KITCHEN COUNTER SPACE | | | GFI RECEPTACLES REQUIRED. | | | | | | 7) NOTE:PLEASE SEE THE PREVIOUS REVIEW NOTE #9, AS | | | THIS REMAINS THE EXACT SAME. THE PLAN NOTES WERE STILL | | | NOT ADJUSTED OR CHANGED. | | | ** PREVIOUS REVIEW NOTE #9** | | | PLEASE SEE 210.8A6 AS ALL RECEPTACLES SERVING KITCHEN | | | COUNTER SPACE IS REQUIRED TO BE GFI OR GFI PROTECTED. | | | THIS WAS CHANGED IN THE 1993 CODE. NOTE ON PLANS ONLY | | | MENTIONS RECEPTACLES WITHIN 6FT OF SINKS. THIS IS FOR | | | ALL OTHER AREAS. | | | | | | 8) NOTE: PREVIOUS NOTE #11 REMAINS AS MENTIONED IN NOTE | | | #2 ABOVE FOR ALL NEW OUTLETS IN BEDROOMS. | | | PLEASE ALSO SEE THIS SECTION STILL APPLIES TO OTHER NEW | | | CIRCUITS FOR BEDROOMS WHICH ARE NOT LISTED ON PANEL | | | SCHEDULE WITH AFCI PROTECTION. | | | ** PREVIOUS REVIEW NOTE #11** | | | PLEASE SEE 210.12 FOR REQUIRED ARC FAULT PROTECTION | | | FOR NEW OUTLETS IN BEDROOMS. | | | | | | 9) NOTE: PLEASE KNOW AS THE PANEL SCHEDULE IS NOW | | | SHOWN, PLEASE VERIFY THE OVER CURRENT PROTECTION NOW | | | SHOWN FOR THE A/C. PLEASE SEE 424.3B AS THE LOAD IS | | | SHOWN AT 10KW AND THE MINIMUM OVER CURRENT PROTECTION | | | PER THIS SECTION REQUIRED 125 %(MIN). | | | PLEASE VERIFY AND ADJUST AS NEEDED. | | | | | | 10) NOTE: PLEASE SEE 680.71 AS NO GFI PROTECTION IS | | | BEING SHOWN FOR THE NEW JACUZZI. PLEASE ALSO SEE THAT | | | NO RECEPTACLE, DISCONNECT (IF NOT CORD AND PLUG) OR | | | ACCESS LOCATION IS SHOWN ON PLANS. | | | | | | 11) NOTE: PLEASE VERIFY NOTE WHICH MENTIONS CONDUCTOR | | | INSULATION TO BE USED IS *TW*!!. PLEASE SEE 310.16 AS | | | TW IS ONLY RATED AT THE 60DEGREE RATING. | | | THIS IS ONLY BEING NOTED AS THE USE OF TW IS NOT A | | | READILY AVAILABLE INSULATION AT THIS DAY AND TIME. | | | | | | 12) NOTE: PLEASE VERIFY THE WATER HEATER LOCATION. THE | | | PANEL SCHEDULE LIST THE WATER HEATER HOWEVER THE PLANS | | | DO NOT SHOW THIS AS NEW OR EXISTING?? | | | FBC 106.1.2 | | | | | | 13) NOTE: PLEASE SEE A NOTICE TO FS 553.80(2)(B) IS | | | BEING GIVEN WITH RESPECT TO REPEAT COMMENTS. THIS IS | | | ONLY A NOTICE GIVEN AT THIS TIME. | | | | | | AS STATED ON PREVIOUS REVIEW IF THERE ARE ANY QUESTIONS | | | OR COMMENTS TO PLEASE CALL TO GO OVER. | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | | DELAYS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-09-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-09-08 |
Time |
17:20 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-09-08 |
Time |
16:58 |
Sent To |
|
|
| Notes |
| 2007-09-08 17:22:08 | 2007-09-08 17:22:08 | | | | | | ** DENIED ** | | | | | | | | | | | | 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS | | | WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES | | | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. | | | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO | | | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. | | | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY | | | AFFECT DESIGNS FOR ALL TRADES. | | | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS | | | REVIEWER AT A MINIMUM. | | | 2004 FBC W/ 2006 REVISIONS | | | 2005 NFPA-70 | | | 2002 NFPA-72 | | | 2003 NFPA-101 | | | | | | ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED | | | FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS | | | NOT MADE BY OTHER TRADE(S). | | | | | | 2) NOTE: NOTE: PLEASE SEE PLANS AND PANEL SCHEDULE | | | INDICATE SMOKE DEVICES AS *SD* AND SYMBOL LEGEND HAS | | | THESE AS SMOKE DETECTORS. | | | BY THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE | | | DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL | | | NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY | | | HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF | | | SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS | | | SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS | | | SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS | | | FOR OTHER NEW HOMES. | | | ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC | | | RESIDENTIAL CODE/ FBC AND IN NFPA-72. | | | IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE*. | | | PLEASE SEE NFPA-72 11.5.1.1, 11.8.3 | | | | | | 3) NOTE: PLEASE COMPLETE PANEL SCHEDULE WITH THE | | | CONDUCTOR SIZES PER 240.4, 310.16, AND 408.4. | | | | | | 4) NOTE: PLEASE SEE THE WATER HEATER UNDER THE NEW 2005 | | | NEC IS REQUIRED TO BE SHOWN AT 125% IN LOAD | | | CALCULATIONS. | | | 422.13 | | | | | | 5) NOTE: PLEASE SEE PLANS APPEAR TO BE MISSING THE | | | RECEPTACLE LOCATION FOR THE DISPOSAL. PLEASE ALSO SEE | | | THE 210.4B IF BOTH THE DISH/ DISP ARE BEING FED TO THE | | | SAME YOKE WHICH WILL REQUIRE A 2-POLE BREAKER. | | | | | | 6) NOTE: PLEASE BE SURE TO STATE THE TYPE OF RECESSED | | | LIGHTING FIXTURE TO BE USED FBC 13-606.1.ABC.1.2.4. | | | THIS IS TO ALLEVIATE THE AIR MOVEMENT FROM CONDITIONED | | | SPACE ETC. | | | | | | 7) NOTE: PLEASE INDICATE ALL CIRCUITING ON PLANS FOR | | | NEW ELECTRICAL AS SHOWN. | | | PLEASE BE SURE TO CORRELATE THIS WITH A PANEL SCHEDULE | | | TO BE SUBMITTED SHOWING NEW AND EXISTING CIRCUITS. | | | PLEASE KNOW AT THIS TIME THE MINIMUM REQUIRED CIRCUITS | | | UNDER THE NEC ARE NOT SHOWN.PLEASE KNOW THAT THE PLANS | | | NEED TO LABEL AND PROVIDE ROOM AND AREA DESIGNATIONS ON | | | PLANS AND CORRELATE WITH THE PANEL SCHEDULES SHOWING | | | ALL ROOMS AND AREAS IN WHICH CIRCUITS FEED WILL BE | | | REQUIRED FOR EACH PANEL. PLEASE SEE TEXT WHICH IS TAKEN | | | FROM COMMENTARY IN THE CODE WHICH STATES THE USE OF | | | *GEN LT* ETC IS NOT ACCEPTABLE. | | | | | | *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE | | | THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A | | | PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE | | | THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. | | | CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED | | | AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE | | | BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, | | | DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE | | | CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT | | | ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS | | | ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR | | | RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT | | | OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE | | | ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT | | | PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS | | | SECTION.* | | | 408.4, 310.16, 240.4 ETC | | | FBC 106.3.5.4 | | | | | | 8) NOTE: PLEASE SEE 210.52C1 FOR MISSING KITCHEN | | | COUNTER SPACE GFI RECEPTACLES REQUIRED. | | | | | | 9) NOTE: PLEASE SEE 210.8A6 AS ALL RECEPTACLES SERVING | | | KITCHEN COUNTER SPACE IS REQUIRED TO BE GFI OR GFI | | | PROTECTED. THIS WAS CHANGED IN THE 1993 CODE. NOTE ON | | | PLANS ONLY MENTIONS RECEPTACLES WITHIN 6FT OF SINKS. | | | THIS IS FOR ALL OTHER AREAS. | | | | | | 10) NOTE: PLEASE SEE SEVERAL SECTIONS OF THE NEC FOR | | | MINIMUM LOADS AND CIRCUITS FOR SMALL APPLIANCE, | | | DINING/BREAKFAST AREAS, DISHWASHER, DISPOSAL, ETC ETC. | | | PLEASE INCLUDE ALL OF THESE MINIMUM CIRCUITS AND LOADS | | | ON THE PANEL SCHEDULE AS NOTED ABOVE WITH CONDUCTOR | | | SIZES. | | | PLEASE SUBMIT LOAD CALCULATIONS WITH NEW AND EXISTING | | | LOADS. | | | PLEASE SEE NEC 220.53, 210.52B1, 210.11C1, 210.11C2, | | | ETC. | | | | | | 11) NOTE: PLEASE SEE 210.12 FOR REQUIRED ARC FAULT | | | PROTECTION FOR NEW OUTLETS IN BEDROOMS. | | | | | | 12) NOTE: PLEASE SEE 210.11C3,FOR MINIMUM 20AMP AND | | | #12 FOR BATH(S) CIRCUIT(S). | | | | | | 13) NOTE: PLEASE SEE MISSING LICENSE NUMBER INFORMATION | | | FOR ARCHITECTURAL AND DESIGN FIRM AS LISTED ON TITLE | | | BLOCKS PER FLORIDA ADMINISTRATIVE CODE 61G1-16.004, | | | FLORIDA STATUTES 481.023. | | | | | | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
F |
Date |
2007-11-20 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-11-20 |
Time |
14:15 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-11-20 |
Time |
13:41 |
Sent To |
|
|
| Notes |
| 2007-11-20 13:46:34 | *****DENIED***** | | | | | | THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN | | | REVIEWS STILL NEED TO BE ADDRESSED.SHEET A-1 WAS NOT | | | SUBMITTED FOR THE 3RD REVIEW. | | | | | | 1.ON SHEET A-1 UNDER CODE SUMMARY,INDICATE 2003 | | | EDITION OF NFPA 101. YOU LISTED 241 INSTEAD OF 101 | | | | | | 2.CONSTRUCTION, ALTERATION, OR DEMOLITION OPERATIONS | | | SHALL COMPLY WITH NFPA 241.THE 2000 EDITION SHALL BE | | | REFERENCED | | | | | | | | | PLEASE BE ADVISED THAT NFPA 101 IS A LIFE SAFETY CODE; | | | NFPA 241 IS THE STANDARD FOR SAFEGUARDING CONSTRUCTION, | | | ALTERATION AND DEMOLITION OPERATIONS, | | | | | | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A REPONSE | | | LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2007-11-03 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-11-03 |
Time |
17:31 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-11-03 |
Time |
17:24 |
Sent To |
|
|
| Notes |
| 2007-11-03 17:31:21 | *****DENIED***** | | | | | | THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN | | | REVIEWS STILL NEED TO BE ADDRESSED: | | | | | | 1.ON SHEET A-1 UNDER CODE SUMMARY,INDICATE 2003 | | | EDITION OF NFPA 101. YOU LISTED 241 INSTEAD OF 101 | | | | | | 2.CONSTRUCTION, ALTERATION, OR DEMOLITION OPERATIONS | | | SHALL COMPLY WITH NFPA 241.THE 2000 EDITION SHALL BE | | | REFERENCED | | | | | | | | | PLEASE BE ADVISED THAT NFPA 101 IS A LIFE SAFETY CODE; | | | NFPA 241 IS THE STANDARD FOR SAFEGUARDING CONSTRUCTION, | | | ALTERATION AND DEMOLITION OPERATIONS, | | | | | | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A REPONSE | | | LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2007-10-15 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-10-15 |
Time |
11:48 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-10-15 |
Time |
11:31 |
Sent To |
|
|
| Notes |
| 2007-10-15 11:48:45 | *****DENIED***** | | | | | | THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN | | | REVIEW STILL NEED TO BE ADDRESSED: | | | | | | 1.ON SHEET A-1 UNDER CODE SUMMARY,INDICATE 2003 | | | EDITION OF NFPA 101. YOU LISTED 241 INSTEAD OF 101 | | | | | | 2.CONSTRUCTION, ALTERATION, OR DEMOLITION OPERATIONS | | | SHALL COMPLY WITH NFPA 241.THE 2000 EDITION SHALL BE | | | REFERENCED | | | | | | | | | PLEASE BE ADVISED THAT NFPA 101 IS A LIFE SAFETY CODE; | | | NFPA 241 IS THE STANDARD FOR SAFEGUARDING CONSTRUCTION, | | | ALTERATION AND DEMOLITION OPERATIONS, | | | | | | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A REPONSE | | | LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2007-09-20 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-09-20 |
Time |
13:49 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-09-20 |
Time |
12:21 |
Sent To |
|
|
| Notes |
| 2007-09-20 12:47:13 | *****DENIED***** | | | | | | | | | 1.ON SHEET A-1 UNDER CODE SUMMARY,INDICATE 2003 | | | EDITION OF NFPA 101. | | | | | | 2.CONSTRUCTION, ALTERATION, OR DEMOLITION OPERATIONS | | | SHALL COMPLY WITH NFPA 241. | | | | | | 3.THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF | | | NEW BUILDING MATERIALS & SUPPLIES SHALL NOT INTERFERE | | | OR HINDER ACCESS TO OR EGRESS FROM THE FLOOR OR THE | | | BUILDING. | | | | | | 4.SPECIFY THE NEW INTERIOR WALL AND CEILING FINISH | | | MATERIALS IN TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | | | 5.IT IS SHOWN ON SHEET E-1 OF SMOKE DETECTORS (SD) IN | | | THE DWELLING UNIT.AMEND TO SHOW THESE DEVICES AS | | | SMOKE ALARMS (SA).PLEASE BE ADVISED THAT SMOKE | | | DETECTORS ARE TIED INTO THE BUILDING'S FIRE ALARM | | | SYSTEM, WHEREAS SMOKE ALARMS WHEN ACTIVATED ALERT THE | | | THE OCCUPANTS OF THE INDIVIDUAL DWELLING UNIT. | | | | | | 6.THE CORRECT DWELLING UNIT NUMBER SHALL BE IN THE | | | TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.PLEASE SEE | | | THAT OUR COMPUTER SYSTEM (AS WELL AS YOUR APPLICATION) | | | HAS THIS SPACE AS 2402 BUT IS SHOWN AS 24B ON THE | | | SUBMITTED PLANS. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A REPONSE | | | LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2007-11-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-11-06 |
Time |
16:22 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-11-06 |
Time |
16:22 |
Sent To |
|
|
| Notes |
| 2007-11-07 11:07:41 | TO "BOB"#17 | | 2007-11-06 16:23:06 | WAITING FOR "BOB" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-10-26 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-10-26 |
Time |
15:26 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-10-26 |
Time |
15:26 |
Sent To |
|
|
| Notes |
| 2007-10-30 15:00:42 | TO "BOB"#16 | | 2007-10-26 15:26:37 | WAITING FOR "BOB" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-10-05 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-10-05 |
Time |
11:09 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-10-05 |
Time |
11:09 |
Sent To |
|
|
| Notes |
| 2007-10-10 12:02:15 | TO "BOB"#13 | | 2007-10-05 11:10:22 | WAITING FOR "BOB" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-09-20 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-09-20 |
Time |
12:21 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-08-28 |
Time |
16:00 |
Sent To |
|
|
| Notes |
| 2007-09-08 16:58:41 | TO BOB BOARD SPACE #15 | | 2007-08-28 16:00:47 | WAITING FOR "BOB" |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
N |
Date |
2007-10-17 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-10-17 |
Time |
11:07 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2007-10-17 |
Time |
11:07 |
Sent To |
|
|
| Notes |
| 2007-10-17 11:07:40 | NO MECHANICAL PLANS SUBMITTED, AND NO | | | MECHANICAL PERMIT NUMBER APPLIED FOR AT | | | THIS TIME. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2007-09-11 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-09-11 |
Time |
09:12 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2007-09-11 |
Time |
09:12 |
Sent To |
|
|
| Notes |
| 2007-09-11 09:22:31 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | | PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA | | | ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS). | | | | | | *** DENIED *** | | | 1) NO MECHANICAL (A/C) PLANS WERE SUBMITTED FOR REVIEW, | | | PLEASE SUBMIT MECHANICAL PLANS IF ANY MECHANICAL | | | ALTERATIONS ARE TO BE DONE, SEE FBC 106.3.5 AND (WPB) | | | AMEND.106.3.5.4 (10)). | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2007-11-20 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-11-20 |
Time |
13:15 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-11-20 |
Time |
13:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2007-10-24 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-10-24 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-10-24 |
Time |
14:17 |
Sent To |
|
|
| Notes |
| 2007-10-24 14:35:33 | DENIED; | | | 1. THE SANITARY RISER DIAGRAMS ARE STILL NOT CORRECT. | | | A) KITCHEN STACK( OK) | | | B) NEW LAVATORY STACK IN MASTER BATH; W/M | | | DOES NOT DISCHARGE INTO THIS STACK (NOT ON SAME WALL, | | | AND NOT FOR W/M'S. | | | C) REMOVE AND CAP BAR SINK RISER; IS THE W/M | | | STACK. | | | D) ADD MASTER BATHROOM STACK FOR TOILET. THIS | | | STACK WOULD BE THE STACK THAT THE DELETED LAVS WERE | | | TIED INTO. | | | E) BATHROOM STACK (OK) | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-09-15 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-09-15 |
Time |
08:15 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-09-15 |
Time |
08:04 |
Sent To |
|
|
| Notes |
| 2007-09-15 08:37:20 | DENIED; | | | THE SANITARY RISER DIAGRAM ON PAGE A-6 IS NOT CORRECT. | | | THERE SHOULD BE A SEPORATE STACK EXISTING FOR THE | | | AUTOMATIC CLOTHES WASHER AND ONE FOR THE KITCHEN. ( | | | KITCHEN WASTE ARE ONLY PERMITED A MAX. OF 8' OF 2" WITH | | | 1 1/2" TRAPS OR MUST BE REVENTED). THE PROPER RISER | | | CONFIGERATION OF THE MASTER BATHROOM IS VERY IMPORTANT. | | | BY MOVING THE LAVATORYS THE TOILET MAY NOT BE VENTED. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2007-09-13 |
|
|
Cont ID |
|
| Sent By |
mflis |
Date |
2007-09-13 |
Time |
16:24 |
Rev Time |
0.00 |
| Received By |
mflis |
Date |
2007-09-13 |
Time |
16:24 |
Sent To |
|
|
| Notes |
| 2007-09-13 16:24:34 | ZONING REVIEW: NOT REQUIRED | | | | | | * INTERIOR RENOVATIONS ONLY | | | | | | MATT FLIS - 822-1445 |
|
|