Plan Review Details - Permit 07080800
Plan Review Stops For Permit 07080800
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-11-21 Cont ID  
Sent By mjacobs Date 2007-11-21 Time 17:52 Rev Time 0.00
Received By mjacobs Date 2007-11-21 Time 16:28 Sent To PC
Notes
2007-11-21 17:52:06 
 BUILDING PLAN REVIEW
 PERMIT: 07080800
 ADD: 525 S. FLAGLER DR #2402
 CONT: MOTIFF GROUP LLC
 TEL: (561)202-5104
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 4TH
 ACTION: DENIED
 11/21/07
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
 **NO RESPONSE NOT ADDRESSED**
 2)2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 **INFORMATION REQUIRED ON DRAWINGS**
  
 **NO RESPONSE NOT ADDRESSED**
 3)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO
 INCLUDE STRUCTURAL, PLUMBING, ELECTRIC, MECHANICAL,
 INTERIOR FINISHES, ARCHITECTURAL AND DESIGN FEES AND
 OVERHEAD AND PROFIT EXCLUDING LAND VALUE. OUR VALUATION
 REFERENCE IS ICC (BVD), MARSHALL-SWIFT AND MEANS COST
 ANALYSIS SERVICES PER 108.3 FBC*.
  
 4)OK
 5)OK
  
 **NEW** **NO RESPONSE NOT ADDRESSED**
 A)SUBMIT A FRAMING DETAIL FOR THE NEW CEILING
 INDICATING ALL MATERIALS. STATE THE TYPE OF MATERIAL TO
 BE USED AROUND ALL WET AREAS. IN THE AREAS WHERE THE
 FIRE RATED PARTITION IS DISTURBED, INDICATE ON THE
 DRAWINGS THE TYPE OF UL ASSEMBLY WHICH WILL MAINTAIN
 THE WALL RATING.
  
 *******************************************************
 ***********
 NOTE: NOW THE PROJECT HAS BEEN ALTERED, SEE COMMENTS
 BELOW.
  
 **NO RESPONSE NOT ADDRESSED**
 1)2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 2)OK
  
 3)OK
  
 **NO RESPONSE NOT ADDRESSED**
 4)ALL PLANS SUBMITTED AFTER OCTOBER, 1, 2004 SHALL BE
 DESIGNED TO THE 2004 FLORIDA BUILDING CODE WITH THE
 2007 REVISIONS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-10-31 Cont ID  
Sent By mjacobs Date 2007-10-31 Time 10:15 Rev Time 0.00
Received By mjacobs Date 2007-10-31 Time 06:48 Sent To  
Notes
2007-10-31 10:15:09 
 BUILDING PLAN REVIEW
 PERMIT: 07080800
 ADD: 525 S. FLAGLER DR #2402
 CONT: MOTIFF GROUP LLC
 TEL: (561)202-5104
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 3RD
 ACTION: DENIED
 10/31/07
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 **INFORMATION REQUIRED ON DRAWINGS**
  
 **NO RESPONSE NOT ADDRESSED**
 3)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO
 INCLUDE STRUCTURAL, PLUMBING, ELECTRIC, MECHANICAL,
 INTERIOR FINISHES, ARCHITECTURAL AND DESIGN FEES AND
 OVERHEAD AND PROFIT EXCLUDING LAND VALUE. OUR VALUATION
 REFERENCE IS ICC (BVD), MARSHALL-SWIFT AND MEANS COST
 ANALYSIS SERVICES PER 108.3 FBC*.
  
 4)OK
  
 5)OK
  
 **NEW**
 A)SUBMIT A FRAMING DETAIL FOR THE NEW CEILING
 INDICATING ALL MATERIALS. STATE THE TYPE OF MATERIAL TO
 BE USED AROUND ALL WET AREAS. IN THE AREAS WHERE THE
 FIRE RATED PARTITION IS DISTURBED, INDICATE ON THE
 DRAWINGS THE TYPE OF UL ASSEMBLY WHICH WILL MAINTAIN
 THE WALL RATING.
  
 *******************************************************
 ***********
 NOTE: NOW THE PROJECT HAS BEEN ALTERED, SEE COMMENTS
 BELOW.
  
 1)2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 2)FBC 106.1.3* THE BUILDING OFFICIAL MAY ESTABLISH
 THROUGH DEPARTMENTAL POLICY STANDARDS FOR PLANS AND
 SPECIFICATIONS ?NO WHITE OUT, PENCIL, HAND-WRITING OR
 INK IS PERMITTED ON THE DRAWINGS?
  
 3)CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE PER FBC 106.1.1.
 **SUBMIT TWO NEW SETS OF DRAWINGS AND SHOW THE ENTIRE
 UNIT, ALL DEMO WORK AND NEW FLOOR PLAN, PLUMBING,
 ELECTRICAL AND MECHANICAL IF CHANGES ARE MADE, ALSO
 SHOW THE SMOKE ALARM COMPLIANCE.. SHOW THE EXISTING AND
 PROPOSED FLOOR PLAN.
  
 4)ALL PLANS SUBMITTED AFTER OCTOBER, 1, 2004 SHALL BE
 DESIGNED TO THE 2004 FLORIDA BUILDING CODE WITH THE
 2007 REVISIONS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-10-12 Cont ID  
Sent By mjacobs Date 2007-10-12 Time 17:50 Rev Time 0.00
Received By mjacobs Date 2007-10-12 Time 16:17 Sent To  
Notes
2007-10-12 17:50:50 
 BUILDING PLAN REVIEW
 PERMIT: 07080800
 ADD: 525 S. FLAGLER DR
 CONT: MOTIFF GROUP LLC
 TEL: (561)202-5104
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 2ND
 ACTION: DENIED
 10/12/07
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)OK
  
 **NO RESPONSE NOT ADDRESSED**
 3)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO
 INCLUDE STRUCTURAL, PLUMBING, ELECTRIC, MECHANICAL,
 INTERIOR FINISHES, ARCHITECTURAL AND DESIGN FEES AND
 OVERHEAD AND PROFIT EXCLUDING LAND VALUE. OUR VALUATION
 REFERENCE IS ICC (BVD), MARSHALL-SWIFT AND MEANS COST
 ANALYSIS SERVICES PER 108.3 FBC*.
  
 4)OK
  
 5)OK
  
 **NEW**
 A)SUBMIT A FRAMING DETAIL FOR THE NEW CEILING
 INDICATING ALL MATERIALS. STATE THE TYPE OF MATERIAL TO
 BE USED AROUND ALL WET AREAS. IN THE AREAS WHERE THE
 FIRE RATED PARTITION IS DISTURBED, INDICATE ON THE
 DRAWINGS THE TYPE OF UL ASSEMBLY WHICH WILL MAINTAIN
 THE WALL RATING.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-13 Cont ID  
Sent By mjacobs Date 2007-09-13 Time 12:34 Rev Time 0.00
Received By mjacobs Date 2007-09-13 Time 06:03 Sent To  
Notes
2007-09-13 12:34:45BUILDING PLAN REVIEW
 PERMIT:
 ADD:
 CONT:
 TEL: (561)###-####
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 2) 2004 FBC EXISTING
 301.5A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 3)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*.
  
 4)THE CERTIFICATE OF AUTHORIZATION FOR FDC DESIGN
 SHALL BE INDICATED ON EACH SHEET FILED FOR PUBLIC
 RECORD. F.A.C. 61G1-16.004
  
 5)THE OCCUPANCY GROUP R-3 INDICATED ON THE DRAWINGS
 IS INCORRECT. SEE 2004 FBC TABLE 503 AND TABLE 601 FOR
 MORE INFORMATION.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-11-08 Cont ID  
Sent By dpalmer Date 2007-11-08 Time 08:35 Rev Time 0.00
Received By dpalmer Date 2007-11-07 Time 16:48 Sent To  
Notes
2007-11-08 08:35:11** DENIED 3RD REVIEW **
  
 ** PLEASE SEE THE REVISED PLANS NOW SHOW SOME OF THE
 SAME ITEMS WHICH WERE NOT CODE COMPLIANT ON THE
 ORIGINAL REVIEW. THESE HAVE NO BEEN CORRECTED.
 ** THE ITEMS ON PLANS WHICH EXIST AND ARE NOT A LIFE
 SAFETY/FIRE HAZARD ARE NOT BEING CONSIDERED IN THIS
 REVIEW.
  
  
 1) NOTE: PLEASE SEE SOME CIRCUITING IS STILL MISSING
 FROM PLANS AND REQUIRED CIRCUITS CAN NOT BE VERIFIED.
 FOR EXAMPLE: PLEASE SEE SMOKE ALARMS ARE MISSING
 CIRCUITING AND CIRCUITING MUST HAVE AFCI PROTECTION.
 210.12
 FOR EXAMPLE; MASTER BATH MISSING SPACING AND INDICATION
 OF GFI AT LAVATORY AREA. PLEASE KNOW THE GFI IS
 REQUIRED TO BE WITHIN 3FT IF SINK EDGE HOWEVER IT IS
 NOT PERMISSIBLE TO CROSS OVER A OPEN SINK TO REACH THE
 RECEPTACLE LOCATION. PLEASE SEE THAT AN ADDITIONAL GFI
 WILL BE REQUIRED OR RELOCATE THE ONE SHOWN.
  
 2) NOTE: PLEASE SEE 210.8A6 AS ALL KITCHEN COUNTER
 SPACE RECEPTACLES ARE REQUIRED TO BE GFI/GFI PROTECTED.
 THE NOTE ON THE LOWER RIGHT HAND SIDE OF PLANS FOR GFI
 RECEPTACLES IS NOT ACCURATE AS THERE ARE MANY CHANGES
 IN THE CODES WHERE THESE NOTES ARE NOT. PLEASE ADJUST
 NOTE.
 210.8
  
 3) NOTE: PLEASE SEE PANEL AND SERVICE SIZE AS PLANS
 STILL INDICATE 1/0 CONDUCTORS FOR 200AMP PANEL. PLANS
 ALSO SHOW 3/0, WHICHSIZE CONDUCTORS ARE INSTALLED.
  
 4) NOTE: PLEASE SEE 424.3B AS MIN OCP FOR AHU 10KW HEAT
 IS 60AMPS.
  
 5) NOTE: PLEASE SEE ELECTRICAL NOTE WHICH MENTIONS ALL
 WIRING TO BE #12 BETWEEN FIXTURES AND SWITCHES YET THE
 PANEL SCHEDULE SHOWS #14 ON MOST OF THESE.
  
 6) NOTE: PLEASE SEE 410.8 AS THE LIGHTING IN CLOSET AS
 SHOWN IS NOT PERMITTED. THIS IS A FIRE HAZARD/LIFE
 SAFETY SITUATION.
  
 ** PLEASE SEE NEC 2005 AND LS CODE NFPA-101 2003 AS
 THERE ARE SEVERAL CHANGES WHICH ARE NEEDED.
 PLEASE REVISE PLANS FOR SCOPE OF WORK AND MINIMUM CODE
 COMPLIANCE.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-10-31 Cont ID  
Sent By dpalmer Date 2007-10-31 Time 14:36 Rev Time 0.00
Received By dpalmer Date 2007-10-31 Time 13:11 Sent To  
Notes
2007-10-31 14:37:02 
 ** DENIED 3RD REVIEW**
  
  
 1) NOTE: PLEASE SEE THE SCOPE OF WORK IS NOW NOT CLEAR
 AND PLANS DO NOT INDICATE AN ACCURATE DEPICTION OF THE
 WORK.
 PLEASE SEE THAT THE ELECTRICAL SCOPE OF WORK IS STILL
 REQUIRED FOR REMOVAL OF ELECTRICAL AND HOW ELECTRICAL
 WILL BE TERMINATED.
 PLEASE PROVIDE A LAYOUT OF KITCHEN RECEPTACLES NEW OR
 EXISTING FOR NEW KITCHEN CABINETS MEETING 210.52C1,
 210.52B1, 220.53, 210.8A6.
  
 ** PLEASE KNOW AS THE SCOPE OF WORK IS NOT CLEAR AT
 THIS TIME, A COMPLETE REVIEW CAN NOT BE DONE.
  
 2) NOTE: PLEASE DO NOT SUBMIT PLANS WITH HAND-DRAWN
 CHANGES. FS 481, 471.
 FBC 106.3.1.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-10-11 Cont ID  
Sent By dpalmer Date 2007-10-11 Time 15:47 Rev Time 0.00
Received By dpalmer Date 2007-10-11 Time 12:48 Sent To  
Notes
2007-10-11 16:25:04** DENIED 2ND REVIEW**
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW STILL
 NEED TO BE ADDRESSED ALONG WITH NEW NOTE DUE TO
 ADDITIONAL INFORMATION ONLY NOW SUBMITTED WHICH WAS NOT
 ON PREVIOUS PLANS.
  
 1) NOTE:SAME NOTE AS PREVIOUS REVIEW: THE ELECTRICAL
 PLANS STILL DO NOT CONTAIN THE REQUIRED RELEVANT CODES
 AS PREVIOUSLY GIVEN.
 **PREVIOUS REVIEW NOTE**
 PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH ARE
 SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE. PLEASE SEE
 THAT THIS SHALL INCLUDE 2006 REVISIONS TO THE 2004 FBC
 FOR ALL TRADES AND THE 2005 NFPA-70. PLEASE KNOW THERE
 ARE CHANGES IN THE FBC WHICH MAY AFFECT DESIGNS FOR ALL
 TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED
 FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS
 NOT MADE BY OTHER TRADE(S).
  
 2) NOTE: PLEASE SEE SMOKE ALARMS ARE NOW SHOWN AS NOTED
 ON PREVIOUS REVIEW NOTE #2, HOWEVER PLEASE SEE THE
 CIRCUITING FOR THESE ARE MISSING. PLEASE SEE PREVIOUS
 NOTE #7 ALSO AS ALL CIRCUITING WAS NOTED.
 PLEASE BE SURE TO SEE 210.12 FOR REQUIRED ARC FAULT
 PROTECTION.
 FBC 106.1.2
  
 3) NOTE: PLEASE SEE NEW ELECTRICAL FEEDERS ARE NOTED
 BOTH AS 1/0 AND 3/0. PLEASE KNOW IF THIS IS AN EXISTING
 200AMP MAIN AND PANEL AS NOTED ON PLANS THEN THE 1/0
 FEEDER CONDUCTOR SIZE IS NOT SUFFICIENT PER 310.16.
 PLEASE ADJUST.
  
 4) NOTE:PLEASE SEE NOTE #4 FROM PREVIOUS REVIEW: THIS
 IS THE SAME COMMENT.
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THE WATER HEATER UNDER THE NEW 2005 NEC IS
 REQUIRED TO BE SHOWN AT 125% IN LOAD CALCULATIONS.
 422.13
  
 5) NOTE: PLEASE SEE THAT THIS IS THE SAME NOTE FROM
 PREVIOUS REVIEW NOTE #5. THE PLANS STILL DO NOT
 INDICATE A RECEPTACLE FOR THE DISPOSAL?? PLEASE SEE
 NOTE WITH RESPECT TO BREAKERS TO THE SAME YOKE AS
 MENTIONED.
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE PLANS APPEAR TO BE MISSING THE RECEPTACLE
 LOCATION FOR THE DISPOSAL. PLEASE ALSO SEE THE 210.4B
 IF BOTH THE DISH/ DISP ARE BEING FED TO THE SAME YOKE
 WHICH WILL REQUIRE A 2-POLE BREAKER.
  
 6) NOTE: PLEASE SEE PREVIOUS NOTE #8, AS THERE IS STILL
 REQUIRED GFI MISSING ALONG KITCHEN COUNTER-SPACE.
 ** PREVIOUS REVIEW NOTE #8**
 PLEASE SEE 210.52C1 FOR MISSING KITCHEN COUNTER SPACE
 GFI RECEPTACLES REQUIRED.
  
 7) NOTE:PLEASE SEE THE PREVIOUS REVIEW NOTE #9, AS
 THIS REMAINS THE EXACT SAME. THE PLAN NOTES WERE STILL
 NOT ADJUSTED OR CHANGED.
 ** PREVIOUS REVIEW NOTE #9**
 PLEASE SEE 210.8A6 AS ALL RECEPTACLES SERVING KITCHEN
 COUNTER SPACE IS REQUIRED TO BE GFI OR GFI PROTECTED.
 THIS WAS CHANGED IN THE 1993 CODE. NOTE ON PLANS ONLY
 MENTIONS RECEPTACLES WITHIN 6FT OF SINKS. THIS IS FOR
 ALL OTHER AREAS.
  
 8) NOTE: PREVIOUS NOTE #11 REMAINS AS MENTIONED IN NOTE
 #2 ABOVE FOR ALL NEW OUTLETS IN BEDROOMS.
 PLEASE ALSO SEE THIS SECTION STILL APPLIES TO OTHER NEW
 CIRCUITS FOR BEDROOMS WHICH ARE NOT LISTED ON PANEL
 SCHEDULE WITH AFCI PROTECTION.
 ** PREVIOUS REVIEW NOTE #11**
 PLEASE SEE 210.12 FOR REQUIRED ARC FAULT PROTECTION
 FOR NEW OUTLETS IN BEDROOMS.
  
 9) NOTE: PLEASE KNOW AS THE PANEL SCHEDULE IS NOW
 SHOWN, PLEASE VERIFY THE OVER CURRENT PROTECTION NOW
 SHOWN FOR THE A/C. PLEASE SEE 424.3B AS THE LOAD IS
 SHOWN AT 10KW AND THE MINIMUM OVER CURRENT PROTECTION
 PER THIS SECTION REQUIRED 125 %(MIN).
 PLEASE VERIFY AND ADJUST AS NEEDED.
  
 10) NOTE: PLEASE SEE 680.71 AS NO GFI PROTECTION IS
 BEING SHOWN FOR THE NEW JACUZZI. PLEASE ALSO SEE THAT
 NO RECEPTACLE, DISCONNECT (IF NOT CORD AND PLUG) OR
 ACCESS LOCATION IS SHOWN ON PLANS.
  
 11) NOTE: PLEASE VERIFY NOTE WHICH MENTIONS CONDUCTOR
 INSULATION TO BE USED IS *TW*!!. PLEASE SEE 310.16 AS
 TW IS ONLY RATED AT THE 60DEGREE RATING.
 THIS IS ONLY BEING NOTED AS THE USE OF TW IS NOT A
 READILY AVAILABLE INSULATION AT THIS DAY AND TIME.
  
 12) NOTE: PLEASE VERIFY THE WATER HEATER LOCATION. THE
 PANEL SCHEDULE LIST THE WATER HEATER HOWEVER THE PLANS
 DO NOT SHOW THIS AS NEW OR EXISTING??
 FBC 106.1.2
  
 13) NOTE: PLEASE SEE A NOTICE TO FS 553.80(2)(B) IS
 BEING GIVEN WITH RESPECT TO REPEAT COMMENTS. THIS IS
 ONLY A NOTICE GIVEN AT THIS TIME.
  
 AS STATED ON PREVIOUS REVIEW IF THERE ARE ANY QUESTIONS
 OR COMMENTS TO PLEASE CALL TO GO OVER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-09-08 Cont ID  
Sent By dpalmer Date 2007-09-08 Time 17:20 Rev Time 0.00
Received By dpalmer Date 2007-09-08 Time 16:58 Sent To  
Notes
2007-09-08 17:22:082007-09-08 17:22:08
  
 ** DENIED **
  
  
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED
 FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS
 NOT MADE BY OTHER TRADE(S).
  
 2) NOTE: NOTE: PLEASE SEE PLANS AND PANEL SCHEDULE
 INDICATE SMOKE DEVICES AS *SD* AND SYMBOL LEGEND HAS
 THESE AS SMOKE DETECTORS.
 BY THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE
 DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL
 NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY
 HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF
 SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS
 SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS
 SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS
 FOR OTHER NEW HOMES.
 ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC
 RESIDENTIAL CODE/ FBC AND IN NFPA-72.
 IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE*.
 PLEASE SEE NFPA-72 11.5.1.1, 11.8.3
  
 3) NOTE: PLEASE COMPLETE PANEL SCHEDULE WITH THE
 CONDUCTOR SIZES PER 240.4, 310.16, AND 408.4.
  
 4) NOTE: PLEASE SEE THE WATER HEATER UNDER THE NEW 2005
 NEC IS REQUIRED TO BE SHOWN AT 125% IN LOAD
 CALCULATIONS.
 422.13
  
 5) NOTE: PLEASE SEE PLANS APPEAR TO BE MISSING THE
 RECEPTACLE LOCATION FOR THE DISPOSAL. PLEASE ALSO SEE
 THE 210.4B IF BOTH THE DISH/ DISP ARE BEING FED TO THE
 SAME YOKE WHICH WILL REQUIRE A 2-POLE BREAKER.
  
 6) NOTE: PLEASE BE SURE TO STATE THE TYPE OF RECESSED
 LIGHTING FIXTURE TO BE USED FBC 13-606.1.ABC.1.2.4.
 THIS IS TO ALLEVIATE THE AIR MOVEMENT FROM CONDITIONED
 SPACE ETC.
  
 7) NOTE: PLEASE INDICATE ALL CIRCUITING ON PLANS FOR
 NEW ELECTRICAL AS SHOWN.
 PLEASE BE SURE TO CORRELATE THIS WITH A PANEL SCHEDULE
 TO BE SUBMITTED SHOWING NEW AND EXISTING CIRCUITS.
 PLEASE KNOW AT THIS TIME THE MINIMUM REQUIRED CIRCUITS
 UNDER THE NEC ARE NOT SHOWN.PLEASE KNOW THAT THE PLANS
 NEED TO LABEL AND PROVIDE ROOM AND AREA DESIGNATIONS ON
 PLANS AND CORRELATE WITH THE PANEL SCHEDULES SHOWING
 ALL ROOMS AND AREAS IN WHICH CIRCUITS FEED WILL BE
 REQUIRED FOR EACH PANEL. PLEASE SEE TEXT WHICH IS TAKEN
 FROM COMMENTARY IN THE CODE WHICH STATES THE USE OF
 *GEN LT* ETC IS NOT ACCEPTABLE.
  
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 8) NOTE: PLEASE SEE 210.52C1 FOR MISSING KITCHEN
 COUNTER SPACE GFI RECEPTACLES REQUIRED.
  
 9) NOTE: PLEASE SEE 210.8A6 AS ALL RECEPTACLES SERVING
 KITCHEN COUNTER SPACE IS REQUIRED TO BE GFI OR GFI
 PROTECTED. THIS WAS CHANGED IN THE 1993 CODE. NOTE ON
 PLANS ONLY MENTIONS RECEPTACLES WITHIN 6FT OF SINKS.
 THIS IS FOR ALL OTHER AREAS.
  
 10) NOTE: PLEASE SEE SEVERAL SECTIONS OF THE NEC FOR
 MINIMUM LOADS AND CIRCUITS FOR SMALL APPLIANCE,
 DINING/BREAKFAST AREAS, DISHWASHER, DISPOSAL, ETC ETC.
 PLEASE INCLUDE ALL OF THESE MINIMUM CIRCUITS AND LOADS
 ON THE PANEL SCHEDULE AS NOTED ABOVE WITH CONDUCTOR
 SIZES.
 PLEASE SUBMIT LOAD CALCULATIONS WITH NEW AND EXISTING
 LOADS.
 PLEASE SEE NEC 220.53, 210.52B1, 210.11C1, 210.11C2,
 ETC.
  
 11) NOTE: PLEASE SEE 210.12 FOR REQUIRED ARC FAULT
 PROTECTION FOR NEW OUTLETS IN BEDROOMS.
  
 12) NOTE: PLEASE SEE 210.11C3,FOR MINIMUM 20AMP AND
 #12 FOR BATH(S) CIRCUIT(S).
  
 13) NOTE: PLEASE SEE MISSING LICENSE NUMBER INFORMATION
 FOR ARCHITECTURAL AND DESIGN FIRM AS LISTED ON TITLE
 BLOCKS PER FLORIDA ADMINISTRATIVE CODE 61G1-16.004,
 FLORIDA STATUTES 481.023.
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2007-11-20 Cont ID  
Sent By mawillia Date 2007-11-20 Time 14:15 Rev Time 0.00
Received By mawillia Date 2007-11-20 Time 13:41 Sent To  
Notes
2007-11-20 13:46:34*****DENIED*****
  
 THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN
 REVIEWS STILL NEED TO BE ADDRESSED.SHEET A-1 WAS NOT
 SUBMITTED FOR THE 3RD REVIEW.
  
 1.ON SHEET A-1 UNDER CODE SUMMARY,INDICATE 2003
 EDITION OF NFPA 101. YOU LISTED 241 INSTEAD OF 101
  
 2.CONSTRUCTION, ALTERATION, OR DEMOLITION OPERATIONS
 SHALL COMPLY WITH NFPA 241.THE 2000 EDITION SHALL BE
 REFERENCED
  
  
 PLEASE BE ADVISED THAT NFPA 101 IS A LIFE SAFETY CODE;
 NFPA 241 IS THE STANDARD FOR SAFEGUARDING CONSTRUCTION,
 ALTERATION AND DEMOLITION OPERATIONS,
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A REPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2007-11-03 Cont ID  
Sent By mawillia Date 2007-11-03 Time 17:31 Rev Time 0.00
Received By mawillia Date 2007-11-03 Time 17:24 Sent To  
Notes
2007-11-03 17:31:21*****DENIED*****
  
 THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN
 REVIEWS STILL NEED TO BE ADDRESSED:
  
 1.ON SHEET A-1 UNDER CODE SUMMARY,INDICATE 2003
 EDITION OF NFPA 101. YOU LISTED 241 INSTEAD OF 101
  
 2.CONSTRUCTION, ALTERATION, OR DEMOLITION OPERATIONS
 SHALL COMPLY WITH NFPA 241.THE 2000 EDITION SHALL BE
 REFERENCED
  
  
 PLEASE BE ADVISED THAT NFPA 101 IS A LIFE SAFETY CODE;
 NFPA 241 IS THE STANDARD FOR SAFEGUARDING CONSTRUCTION,
 ALTERATION AND DEMOLITION OPERATIONS,
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A REPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-10-15 Cont ID  
Sent By mawillia Date 2007-10-15 Time 11:48 Rev Time 0.00
Received By mawillia Date 2007-10-15 Time 11:31 Sent To  
Notes
2007-10-15 11:48:45*****DENIED*****
  
 THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN
 REVIEW STILL NEED TO BE ADDRESSED:
  
 1.ON SHEET A-1 UNDER CODE SUMMARY,INDICATE 2003
 EDITION OF NFPA 101. YOU LISTED 241 INSTEAD OF 101
  
 2.CONSTRUCTION, ALTERATION, OR DEMOLITION OPERATIONS
 SHALL COMPLY WITH NFPA 241.THE 2000 EDITION SHALL BE
 REFERENCED
  
  
 PLEASE BE ADVISED THAT NFPA 101 IS A LIFE SAFETY CODE;
 NFPA 241 IS THE STANDARD FOR SAFEGUARDING CONSTRUCTION,
 ALTERATION AND DEMOLITION OPERATIONS,
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A REPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-09-20 Cont ID  
Sent By mawillia Date 2007-09-20 Time 13:49 Rev Time 0.00
Received By mawillia Date 2007-09-20 Time 12:21 Sent To  
Notes
2007-09-20 12:47:13*****DENIED*****
  
  
 1.ON SHEET A-1 UNDER CODE SUMMARY,INDICATE 2003
 EDITION OF NFPA 101.
  
 2.CONSTRUCTION, ALTERATION, OR DEMOLITION OPERATIONS
 SHALL COMPLY WITH NFPA 241.
  
 3.THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF
 NEW BUILDING MATERIALS & SUPPLIES SHALL NOT INTERFERE
 OR HINDER ACCESS TO OR EGRESS FROM THE FLOOR OR THE
 BUILDING.
  
 4.SPECIFY THE NEW INTERIOR WALL AND CEILING FINISH
 MATERIALS IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 5.IT IS SHOWN ON SHEET E-1 OF SMOKE DETECTORS (SD) IN
 THE DWELLING UNIT.AMEND TO SHOW THESE DEVICES AS
 SMOKE ALARMS (SA).PLEASE BE ADVISED THAT SMOKE
 DETECTORS ARE TIED INTO THE BUILDING'S FIRE ALARM
 SYSTEM, WHEREAS SMOKE ALARMS WHEN ACTIVATED ALERT THE
 THE OCCUPANTS OF THE INDIVIDUAL DWELLING UNIT.
  
 6.THE CORRECT DWELLING UNIT NUMBER SHALL BE IN THE
 TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.PLEASE SEE
 THAT OUR COMPUTER SYSTEM (AS WELL AS YOUR APPLICATION)
 HAS THIS SPACE AS 2402 BUT IS SHOWN AS 24B ON THE
 SUBMITTED PLANS.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A REPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-11-06 Cont ID  
Sent By adarroug Date 2007-11-06 Time 16:22 Rev Time 0.00
Received By adarroug Date 2007-11-06 Time 16:22 Sent To  
Notes
2007-11-07 11:07:41TO "BOB"#17
2007-11-06 16:23:06WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-10-26 Cont ID  
Sent By adarroug Date 2007-10-26 Time 15:26 Rev Time 0.00
Received By adarroug Date 2007-10-26 Time 15:26 Sent To  
Notes
2007-10-30 15:00:42TO "BOB"#16
2007-10-26 15:26:37WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-05 Cont ID  
Sent By adarroug Date 2007-10-05 Time 11:09 Rev Time 0.00
Received By adarroug Date 2007-10-05 Time 11:09 Sent To  
Notes
2007-10-10 12:02:15TO "BOB"#13
2007-10-05 11:10:22WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-09-20 Cont ID  
Sent By mawillia Date 2007-09-20 Time 12:21 Rev Time 0.00
Received By mawillia Date 2007-08-28 Time 16:00 Sent To  
Notes
2007-09-08 16:58:41TO BOB BOARD SPACE #15
2007-08-28 16:00:47WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2007-10-17 Cont ID  
Sent By tgordon Date 2007-10-17 Time 11:07 Rev Time 0.20
Received By tgordon Date 2007-10-17 Time 11:07 Sent To  
Notes
2007-10-17 11:07:40NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-09-11 Cont ID  
Sent By tgordon Date 2007-09-11 Time 09:12 Rev Time 0.20
Received By tgordon Date 2007-09-11 Time 09:12 Sent To  
Notes
2007-09-11 09:22:31PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA
 ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS).
  
 *** DENIED ***
 1) NO MECHANICAL (A/C) PLANS WERE SUBMITTED FOR REVIEW,
 PLEASE SUBMIT MECHANICAL PLANS IF ANY MECHANICAL
 ALTERATIONS ARE TO BE DONE, SEE FBC 106.3.5 AND (WPB)
 AMEND.106.3.5.4 (10)).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-11-20 Cont ID  
Sent By jleech Date 2007-11-20 Time 13:15 Rev Time 0.00
Received By jleech Date 2007-11-20 Time 13:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-10-24 Cont ID  
Sent By jleech Date 2007-10-24 Time 14:17 Rev Time 0.00
Received By jleech Date 2007-10-24 Time 14:17 Sent To  
Notes
2007-10-24 14:35:33DENIED;
 1. THE SANITARY RISER DIAGRAMS ARE STILL NOT CORRECT.
 A) KITCHEN STACK( OK)
 B) NEW LAVATORY STACK IN MASTER BATH; W/M
 DOES NOT DISCHARGE INTO THIS STACK (NOT ON SAME WALL,
 AND NOT FOR W/M'S.
 C) REMOVE AND CAP BAR SINK RISER; IS THE W/M
 STACK.
 D) ADD MASTER BATHROOM STACK FOR TOILET. THIS
 STACK WOULD BE THE STACK THAT THE DELETED LAVS WERE
 TIED INTO.
 E) BATHROOM STACK (OK)
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-09-15 Cont ID  
Sent By jleech Date 2007-09-15 Time 08:15 Rev Time 0.00
Received By jleech Date 2007-09-15 Time 08:04 Sent To  
Notes
2007-09-15 08:37:20DENIED;
 THE SANITARY RISER DIAGRAM ON PAGE A-6 IS NOT CORRECT.
 THERE SHOULD BE A SEPORATE STACK EXISTING FOR THE
 AUTOMATIC CLOTHES WASHER AND ONE FOR THE KITCHEN. (
 KITCHEN WASTE ARE ONLY PERMITED A MAX. OF 8' OF 2" WITH
 1 1/2" TRAPS OR MUST BE REVENTED). THE PROPER RISER
 CONFIGERATION OF THE MASTER BATHROOM IS VERY IMPORTANT.
 BY MOVING THE LAVATORYS THE TOILET MAY NOT BE VENTED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status N Date 2007-09-13 Cont ID  
Sent By mflis Date 2007-09-13 Time 16:24 Rev Time 0.00
Received By mflis Date 2007-09-13 Time 16:24 Sent To  
Notes
2007-09-13 16:24:34ZONING REVIEW: NOT REQUIRED
  