Plan Review Details - Permit 07080729
Plan Review Stops For Permit 07080729
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-07-25 Cont ID  
Sent By mjacobs Date 2008-07-25 Time 08:10 Rev Time 0.00
Received By mjacobs Date 2008-07-25 Time 07:34 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-07-25 Cont ID  
Sent By mjacobs Date 2008-05-09 Time 14:34 Rev Time 0.00
Received By mjacobs Date 2008-05-09 Time 10:22 Sent To  
Notes
2008-05-09 14:48:56ONE SET OF PLANS NEEDS THE SEAL OF THE ENGINEER. THE
 SET WILL BE STAMPED WHEN SEAL BY THE ENGINEER. MJ

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-01-10 Cont ID  
Sent By mjacobs Date 2008-01-10 Time 06:58 Rev Time 0.00
Received By mjacobs Date 2008-01-09 Time 11:28 Sent To  
Notes
2008-01-10 06:49:25BUILDING PLAN REVIEW
 PERMIT: 07080729
 ADD: 5407 N HAVERHILL RD. #341
 CONT: CARL LIPUMA INC.
 TEL: (954)753-9189
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 2ND
 ACTION: DENIED
 1-9-08
  
 1)OK
 2)OK
 3)OK
 4)OK
 5)OK
 6)OK
 7)OK
 8)OK
 9)OK
  
 **NEW** THE CLAIMED VALUATION ON THE PERMIT APPLICATION
 IS LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL COST EXCLUDING LAND
 VALUE. OUR VALUATION REFERENCE IS ICC (BVD),
 MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES PER
 108.3 FBC*
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-07 Cont ID  
Sent By mjacobs Date 2007-09-07 Time 14:57 Rev Time 0.00
Received By mjacobs Date 2007-09-07 Time 07:07 Sent To  
Notes
2007-09-07 14:57:29 
 BUILDING PLAN REVIEW
 PERMIT:
 ADD:
 CONT:
 TEL: (561)###-####
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 2)2004 FBC EXISTING
 301.5A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 3) 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PROJECT IS DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT
 . -------------------------------------
 ) NUMBER OF UNITS
 ) NUMBER OF FLOORS
 ) NUMBER OF ROOMS
 ) SQ. FT. FOOTPRINT
  
 4)ADDITIONAL INFORMATION REQUIRED, 106.1.2*. PLANS
 INDICATE THERE IS A MEZZANINE LEVEL, PROVIDE WHAT WALLS
 ARE FOR THE FIRST FLOOR AND MEZZANINE LEVEL.
  
 5) FBC 505.4. A MEZZANINE SHALL BE OPEN AND
 UNOBSTRUCTED TO THE ROOM IN WHICH SUCH MEZZANINE IS
 LOCATED EXCEPT FOR WALL NOT MORE THAN 42 INCHES HIGH,
 COLUMNS AND POSTS.
  
 6)SUBMIT ELEVATION DRAWINGS SHOWING THE CLEAR HEIGHT
 ABOVE AND BELOW THE MEZZANINE FLOOR WHICH SHALL NOT BE
 LESS THAN 7 FEET. THE AREA OF A MEZZANINE SHALL NOT
 EXCEED ONE-THIRD OF THE AREA OF THAT ROOM OR SPACE IN
 WHICH IT IS LOCATED. FBC.505.1 AND 505.2
  
 7)TABLE 803.3 MINIMUM INTERIOR FINISH CLASSIFICATION;
 PROVIDE INFORMATION
 BASE ON INTERIOR FINISH REQUIREMENTS BASED ON
 OCCUPANCY
  
 8)PROVIDE A LIFE SAFETY PLAN SHOWING THE EXIT ACCESS
 TRAVEL DISTANCE. FBC 1013 ? 1016.
  
 9)A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS
 A RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-07-10 Cont ID  
Sent By btrobaug Date 2008-07-10 Time 09:59 Rev Time 0.00
Received By btrobaug Date 2008-07-10 Time 09:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-05-01 Cont ID  
Sent By btrobaug Date 2008-05-01 Time 13:59 Rev Time 0.00
Received By btrobaug Date 2008-05-01 Time 06:52 Sent To  
Notes
2008-05-01 12:25:59 
  
  
  
 **DENIED 3RD REVIEW**
  
 THE FOLLOWING ARE COMMENTS FROM PREVIOUS REVIEWS THAT
 HAVE NOT BEEN CORRECTED FOR CODE COMPLIANCE.
  
 2}THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS
 AMENDED.
  
 A PERMIT SHALL NOT BE ISSUED UNTIL FEES AUTHORIZED
 UNDER SECTION 553.80, FLORIDA STATUTES, HAVE BEEN PAID.
 108.1 FBC.
  
 ADJUST THE VALUE AT THE PERMIT CLERK?S DESK, AND PAY
 THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING.*THE VALUE
 WAS ADJUSTED ON THE APPLICATION BUT NOT AT PERMIT
 SPECIALISTS DESK, AND THE DIFFERENCE HAS NOT BEEN PAID.
 SEE ATTACHED STATEMENT.
  
 6} 13-415.1.ABC1.1 WAS NOT COMPLIED WITH. SEE
 13-415.1.ABC.1.1 AUTOMATIC LIGHTING SHUTOFF.
  
 7} ENERGY CALCULATIONS WERE NOT SUBMITTED PER 13-101
 FBCTHE LIGHTING PERFORMANCE CALCULATIONS PER
 13-415.2B THAT ARE ON SHEET ELEC ARE COMPLIANT FOR
 METHOD C.
  
 9} THE LIGHTING LEVELS INDICATED FOR THE STAIRS IS NOT
 IN COMPLIANCE WITH 7.8.1.3 (1).NFPA 101 IS
 10FT-CANDLE.
  
 NEW COMMENTS GENERATED FROM THE REVISED PANEL
 SCHEDULE:
  
 1} THE CIRCUIT NUMBERS 2,4 AND 6,8 FOR THE DISCONNECTS
 DO NOT CORRELATE WITH THE PANEL SCHEDULE.IF THE
 DISCONNECTS ARE FOR THE CONDENSING UNITS, THE THIRD ONE
 IS NOT LOCATED ON THE PLAN. SHOW THE LOCATION OF THE
 A/C EQUIPMENT ON THE PLAN. ALSO SHOW COMPLIANCE WITH
 THE REQUIRED DISCONNECT PER 440.14,RECEPTACLE PER
 210.63.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-01-04 Cont ID  
Sent By dpalmer Date 2008-01-04 Time 09:46 Rev Time 0.00
Received By dpalmer Date 2008-01-04 Time 09:46 Sent To  
Notes
2008-01-04 09:46:49** DENIED 2ND REVIEW **
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING.
  
 ** COMMENTS BELOW ARE FROM PREVIOUS REVIEW WITH A NOTE
 IN FRONT OF NOTE WHETHER OR NOT IT WAS ADDRESSED.
  
 1) NOTE:NO, PLEASE SEE NO SPECIFIC CODES AS REQUIRED
 WERE STATED OR SHOWN ON PLANS.
  
 *** PREVIOUS REVIEW NOTE ***
 PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH ARE
 SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE. PLEASE SEE
 THAT THIS SHALL INCLUDE 2006 REVISIONS TO THE 2004 FBC
 FOR ALL TRADES AND THE 2005 NFPA-70. PLEASE KNOW THERE
 ARE CHANGES IN THE FBC WHICH MAY AFFECT DESIGNS FOR ALL
 TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72(IF AN FA SYSTEM IS IN BUILDING)
 2003 NFPA-101
  
 2) NOTE: NO, VALUE FOR SCOPE OF WORK ON PLANS DID NOT
 CHANGE. VALUE STILL SHOWN AS $2500 AND A VALUE MAY BE
 ASSESSED USING THE ADOPTED GUIDES INTO THE FBC IF AN
 APPROPRIATE VALUE IS NOT ADJUSTED.
  
 **PREVIOUS REVIEW NOTE ***
 PLEASE SEE THE VALUE AS SUBMITTED ON PERMIT
 APPLICATION BASED ON THE SCOPE OF WORK ON PLANS AND
 WHICH WILL BE REQUIRED IS EXTREMELY LOW.
 PLEASE SEE FBC 108.3 AS THE VALUE SHALL INCLUDE ALL
 LABOR, MATERIALS, COST OF
 DESIGN/ARCHITECTURAL/ENGINEERING SERVICES AND COST.
 THIS DOES NOT MATTER IF ANY OF THESE ITEMS ARE OWNER
 SUPPLIED.
 PLEASE KNOW THE VALUE WILL BE REQUIRED TO BE ADJUSTED
 OR A VALUE MAY BE APPLIED BY THIS OFFICE USING THE
 MINIMUM STANDARDS ADOPTED INTO AND BY THE FLORIDA
 BUILDING CODE AND ADOPTED STANDARDS.
 ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 ANY OTHER TRADE(S).
  
 3) NOTE: OK.
  
 4) NOTE: OK.
  
 5) NOTE: OK.
  
 6) NOTE: NO, PLEASE SEE NO DEVICES ARE SHOWN FOR NEW TO
 BE INSTALLED FOR COMPLIANCE WITH FBC AND CHAPTER 13.
  
 ** PREVIOUS REVIEW NOTE ***
 PLEASE SUBMIT PLANS WITH COMPLIANCE FOR FBC CHAPTER 13
 FOR LIGHTING CONTROLS. PLEASE SEE 13-415.1.ABC.1.1,
 .1.2.
 PLEASE INDICATE THE TYPE OF DEVICES OR SYSTEM WHICH
 WILL BE PROPOSED.
 PLEASE INCLUDE MAXIMUM TIMES ON ANY OVER RIDE DEVICES
 OR OCCUPANCY SENSOR DEVICES ETC.
 AS NO INFORMATION OR ITEMS WERE SUBMITTED FOR REVIEW, A
 FULL REVIEW FOR CODE COMPLIANCE COULD NOT BE DONE AT
 THIS TIME.
  
 7) NOTE:NO, PLEASE SEE NO LIGHTING PERFORMANCE
 CALCULATIONS FOR NEW AREAS WERE SUBMITTED. PLEASE SEE
 13-415.2 OF THE FBC. FIXTURE LEGEND WAS SUBMITTED AS
 REQUESTED FROM PREVIOUS NOTE.
  
 *** PREVIOUS REVIEW NOTE ***
 PLEASE SUBMIT AND COMPLETE A FIXTURE LEGEND. PLEASE
 INCLUDE THE LIGHTING PERFORMANCE CALCULATIONS PER
 13-415.2.
 PLEASE KNOW IF SPACE IS NOW BEING AIR CONDITIONED,
 PLEASE SUBMIT ENERGY CALCULATIONS.
 13-101, 13-103.1.1.1, 13-415.1.B, 13-415.1.C, 13-415.2
 AS NO INFORMATION WAS SUBMITTED FOR MINIMUM CODE
 COMPLIANCE A REVIEW OF THESE ITEMS COULD NOT BE DONE.
  
 8) NOTE: OK.
  
 9) NOTE:NO, PLEASE SEE PLANS INDICATE THE UPPER
 MEZZANINE HOWEVER NO LEVELS FOR EGRESS LIGHTING WAS
 INDICATED FOR STAIRS, CORRIDOR.
 PLEASE SEE NFPA-101 7.8.1.3, 7.9.2.2 , 7.8, 7.9. FAC
 61G15-33.004.
  
 ** PREVIOUS REVIEW NOTE **
 PLANS DO NOT INDICATE THE UPPER MEZZANINE LEVEL AS
 NOTED.
 PLANS DO NOT INDICATE ANY EMERGENCY LIGHTING FIXTURES
 NEEDED FOR MINIMUM EGRESS.
 PLEASE SEE THE STAIRS ALONE NEEDS LIGHTING LEVELS UNDER
 NORMAL AND EMERGENCY TO MEET THE LEVELS AS STATED IN
 THE LIFE SAFETY CODE 101, 7.8.1.3, AND 7.9.2.2. PLEASE
 SUBMIT THE PHOTO-METRIC LEVELS FOR STAIRS. PLEASE
 INDICATE THE EMERGENCY LIGHTING FIXTURES AT OTHER
 LOCATIONS TO MEET 1FT CANDLE MINIMUM.
 ** PLEASE BE SURE TO SEE NEC 700.12F FOR CIRCUITING OF
 THESE FIXTURES.
  
 10) NOTE: NO, LOADSARE SHOWN ON PANEL SCHEDULE
 HOWEVER PLEASE INDICATE WHERE THE CONTINUOUS LOADS AT
 125% ARE SHOWN??
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT THE LOAD CALCULATIONS WHICH INDICATE ALL
 CONTINUOUS LOADS AT 125%.
 215.3, 230.42 ETC.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-09-08 Cont ID  
Sent By dpalmer Date 2007-09-08 Time 20:11 Rev Time 0.00
Received By dpalmer Date 2007-09-08 Time 19:37 Sent To  
Notes
2007-09-08 20:12:012007-09-08 20:12:01
  
 ** DENIED **
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72(IF AN FA SYSTEM IS IN BUILDING)
 2003 NFPA-101
  
 2) NOTE: PLEASE SEE THE VALUE AS SUBMITTED ON PERMIT
 APPLICATION BASED ON THE SCOPE OF WORK ON PLANS AND
 WHICH WILL BE REQUIRED IS EXTREMELY LOW.
 PLEASE SEE FBC 108.3 AS THE VALUE SHALL INCLUDE ALL
 LABOR, MATERIALS, COST OF
 DESIGN/ARCHITECTURAL/ENGINEERING SERVICES AND COST.
 THIS DOES NOT MATTER IF ANY OF THESE ITEMS ARE OWNER
 SUPPLIED.
 PLEASE KNOW THE VALUE WILL BE REQUIRED TO BE ADJUSTED
 OR A VALUE MAY BE APPLIED BY THIS OFFICE USING THE
 MINIMUM STANDARDS ADOPTED INTO AND BY THE FLORIDA
 BUILDING CODE AND ADOPTED STANDARDS.
 ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 ANY OTHER TRADE(S).
  
 3) NOTE: PLEASE SEE THE PERMIT APPLICATIONS AS
 SUBMITTED. THE CGC APPLICATION STATES WORK AT 5407 AND
 THE ELECTRICAL CONTRACTOR HAS 5701 ON APPLICATION.
 PLEASE BE SURE TO COORDINATE.
  
 4) NOTE: PLEASE SEE THE SUITE/UNIT NUMBER IS TO BE
 INCLUDED ON PLANS IN THE TITLE BLOCKS.
 FAC 61G15-23.002, 61G1-16.004, FBC 106.1.2, 106.1,
 110.1.2.
  
 5) NOTE: PLEASE SEE THE PLANS AS SUBMITTED DO NOT
 CONTAIN ANY DESIGN PROFESSIONAL PRINTED, SIGNED, DATED
 OR SEALED ON PLANS.
 PLEASE SEE THAT PLANS ARE REQUIRED TO BE DONE BY A
 DESIGN PROFESSIONAL UNDER FS 471,481,489 (WHERE
 PERMITTED).
  
 6) NOTE: PLEASE SUBMIT PLANS WITH COMPLIANCE FOR FBC
 CHAPTER 13 FOR LIGHTING CONTROLS. PLEASE SEE
 13-415.1.ABC.1.1, .1.2.
 PLEASE INDICATE THE TYPE OF DEVICES OR SYSTEM WHICH
 WILL BE PROPOSED.
 PLEASE INCLUDE MAXIMUM TIMES ON ANY OVER RIDE DEVICES
 OR OCCUPANCY SENSOR DEVICES ETC.
 AS NOT INFORMATION OR ITEMS WERE SUBMITTED FOR REVIEW,
 A FULL REVIEW FOR CODE COMPLIANCE COULD NOT BE DONE AT
 THIS TIME.
  
 7) NOTE: PLEASE SUBMIT AND COMPLETE A FIXTURE LEGEND.
 PLEASE INCLUDE THE LIGHTING PERFORMANCE CALCULATIONS
 PER 13-415.2.
 PLEASE KNOW IF SPACE IS NOW BEING AIR CONDITIONED,
 PLEASE SUBMIT ENERGY CALCULATIONS.
 13-101, 13-103.1.1.1, 13-415.1.B, 13-415.1.C, 13-415.2
 AS NO INFORMATION WAS SUBMITTED FOR MINIMUM CODE
 COMPLIANCE A REVIEW OF THESE ITEMS COULD NOT BE DONE.
  
 8) NOTE: PLEASE SEE THE SPACE DOES NOT STATE USE AND
 WHAT ITEMS WILL BE STORED AND/OR WHAT WAREHOUSE WILL BE
 USED FOR.
 PLEASE STATE USE AND OCCUPANCY.
 PLEASE BE AWARE OF ANY LOCATIONS WHICH MAY INVOKE
 SECTIONS OF THE LIFE SAFETY CODE, BUILDING CODE,
 ELECTRICAL CODE AND OTHER POSSIBLE CODES FOR WIRING,
 CONSTRUCTION OF WALLS ETC.
 FBC 106.1.2
  
 9) NOTE: PLANS DO NOT INDICATE THE UPPER MEZZANINE
 LEVEL AS NOTED.
 PLANS DO NOT INDICATE ANY EMERGENCY LIGHTING FIXTURES
 NEEDED FOR MINIMUM EGRESS.
 PLEASE SEE THE STAIRS ALONE NEEDS LIGHTING LEVELS UNDER
 NORMAL AND EMERGENCY TO MEET THE LEVELS AS STATED IN
 THE LIFE SAFETY CODE 101, 7.8.1.3, AND 7.9.2.2. PLEASE
 SUBMIT THE PHOTO-METRIC LEVELS FOR STAIRS. PLEASE
 INDICATE THE EMERGENCY LIGHTING FIXTURES AT OTHER
 LOCATIONS TO MEET 1FT CANDLE MINIMUM.
 ** PLEASE BE SURE TO SEE NEC 700.12F FOR CIRCUITING OF
 THESE FIXTURES.
  
 10) NOTE: PLEASE SUBMIT THE LOAD CALCULATIONS WHICH
 INDICATE ALL CONTINUOUS LOADS AT 125%.
 215.3, 230.42 ETC.
  
 ** PLEASE KNOW ONE SET OF PLANS MAY BE RETAINED BY THIS
 OFFICE.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-07-22 Cont ID  
Sent By mwennerg Date 2008-07-22 Time 10:26 Rev Time 0.00
Received By mwennerg Date 2008-07-22 Time 10:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2008-05-12 Cont ID  
Sent By mawillia Date 2008-05-12 Time 14:06 Rev Time 0.00
Received By mawillia Date 2008-05-12 Time 13:17 Sent To  
Notes
2008-05-12 13:55:00*****PROVISO*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED;PLAN SHEETS 1, 2, AND 5 WERE STAMPED,
 INITIALED AND DATED.HOWEVER:
  
 1.PLAN SHEET 6 TO BE FIRE-STAMPED WHEN THE ELECTRICAL
 REVIEW COMMENT(S) HAVE BEEN SATISFIED.
  
 2.THE ENGINEERED SEAL FOR SHEET 1, 2, 3, AND 5 IN ONE
 OF THE PLAN SETS IS MISSING.
  
 PLEASE ADDRESS THE ABOVE COMMENTS IN ORDER FOR PLAN
 REVIEW STATUS TO BE APPROVED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-01-10 Cont ID  
Sent By mawillia Date 2008-01-10 Time 15:22 Rev Time 0.00
Received By mawillia Date 2008-01-10 Time 14:47 Sent To  
Notes
2008-01-10 15:22:16*****DENIED*****
  
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE ADDRESSED:
  
 1.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 4.SPECIFY THE NEW WALL AND CEILING INTERIOR FINISH
 MATERIALS IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 6.PROVIDE/SHOW LAYOUT OF THE FIRE ALARM SYSTEM.IF
 THE FIRE ALARM SYSTEM IS REMODELED DUE TO THE SCOPE OF
 WORK, SEPARATE PLANS AND PERMIT WILL BE REQUIRED.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE IN THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-09-17 Cont ID  
Sent By mawillia Date 2007-09-17 Time 23:00 Rev Time 0.00
Received By mawillia Date 2007-09-17 Time 21:19 Sent To  
Notes
2007-09-17 23:42:12*****DENIED*****
  
  
 1.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.THE SUITE NUMBER SHALL BE INCLUDED WITH THE ADDRESS
 IN THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 4.SPECIFY THE NEW WALL AND CEILING INTERIOR FINISH
 MATERIALS IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 5. PROVIDE/SHOW A LAYOUT OF THE FIRE SPRINKLER HEADS IN
 THE TENANT SPACE.IF THE SPRINKLER SYSTEM IS REMODELED
 DUE TO THE SCOPE OF WORK, SEPARATE PLANS AND PERMIT
 WILL BE REQUIRED.
  
 6.PROVIDE/SHOW LAYOUT OF THE FIRE ALARM SYSTEM.IF
 THE FIRE ALARM SYSTEM IS REMODELED DUE TO THE SCOPE OF
 WORK, SEPARATE PLANS AND PERMIT WILL BE REQUIRED.
  
 7.INDICATE THE LOCATION OF EXIT LIGHTS, EMERGENCY
 LIGHTS, 2A:10BC FIRE EXTINGUISHER(S), AND TRAVEL
 DISTANCES TO EXITS.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE IN THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-07-09 Cont ID  
Sent By adarroug Date 2008-07-09 Time 11:46 Rev Time 0.00
Received By adarroug Date 2008-07-09 Time 11:46 Sent To  
Notes
2008-07-09 11:56:58TO "BOB"#10

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-04-30 Cont ID  
Sent By adarroug Date 2008-04-30 Time 10:41 Rev Time 0.00
Received By adarroug Date 2008-04-30 Time 10:41 Sent To  
Notes
2008-04-30 10:44:37TO "BOB"#3

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-01-04 Cont ID  
Sent By adarroug Date 2008-01-04 Time 08:16 Rev Time 0.00
Received By adarroug Date 2008-01-04 Time 08:16 Sent To  
Notes
2008-01-04 08:18:24TO "BOB"#5

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-09-17 Cont ID  
Sent By mawillia Date 2007-09-17 Time 21:20 Rev Time 0.00
Received By mawillia Date 2007-08-27 Time 13:36 Sent To  
Notes
2007-09-06 11:09:22TO "BOB"#14
2007-08-27 13:37:34WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-09-10 Cont ID  
Sent By tgordon Date 2007-09-10 Time 16:34 Rev Time 0.20
Received By tgordon Date 2007-09-10 Time 16:34 Sent To  
Notes
2007-09-10 16:35:10NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop Z ZONING
Rev No 1 Status N Date 2007-09-06 Cont ID  
Sent By choops Date 2007-09-06 Time 12:20 Rev Time 0.00
Received By choops Date 2007-09-06 Time 12:19 Sent To  
Notes
2007-09-06 12:20:17*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.