Plan Review Details - Permit 07080709
Plan Review Stops For Permit 07080709
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-04-09 Cont ID  
Sent By mjacobs Date 2008-04-09 Time 12:16 Rev Time 0.00
Received By mjacobs Date 2008-04-09 Time 09:39 Sent To PC
Notes
2008-04-09 12:16:09BUILDING PLAN REVIEW
 PERMIT: 07080709
 ADD: 101 EXECUTIVE CENTER DR.
 CONT: KAY RESTORATION CORP.
 TEL: (561)994-9300
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)THE ALTERATION LEVEL 1 STATED ON SHEET 3/3 IS
 INCORRECT. FBC (EXISTING) SEC. 304 ANY RECONFIGURATION
 OF SPACE, THE ADDITION OR ELIMINATION OF ANY DOOR OR
 WINDOW, THE RECONFIGURATION OR EXTENSION OF ANY SYSTEM,
 OR THE INSTALLATION OF ANY ADDITIONAL EQUIPMENT IS A
 LEVEL 2 ALTERATION. THE CHANGES SHOWN ON THE PLANS
 INDICATE THIS PROJECT AS A LEVEL 2 NOT LEVEL 1 AS
 STATED ON THE PLANS.
  
 3)FBC 106.1.1* CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND SHALL BE OF SUFFICIENT CLARITY TO
 INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 FBC 2004 CODE AND RELEVANT LAWS. THERE ARE NO
 DIMENSIONS ON THE DRAWINGS.
  
 4)110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING:
 A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
 ) NUMBER OF UNITS
 ) NUMBER OF FLOORS
 ) NUMBER OF ROOMS
 ) SQ. FT. FOOTPRINT
 THE ENTIRE FLOOR PLAN SHALL BE SUBMITTED ON THE
 DRAWINGS NOT A PARTIAL FLOOR PLAN.
  
 5)FBC 11-4.17.2 WATER CLOSETS IN ACCESSIBLE STALLS
 SHALL COMPLY WITH SECTION 11-4.16.AND FIG 30E. SHOW
 THE CLEAR FLOOR SPACE, OF THE WATER CLOSEST, THE FLUSH
 CONTROLS AND TOILET PAPER DISPENSERS.
  
 6)A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS
 A RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 7)A WALL DETAIL SHALL BE SUBMITTED INDICATING WHAT
 MATERIALS WILL BE USED TO CONSTRUCT THE NEW WALLS.
 SUBMIT A WALL LEGEND SHOW THE DIFFERENT TYPE OF WALL.
  
 8)FBC SEC.803 INDICATE THE TYPE OF FINISH IN
 ACCORDANCE WITH TABLE 803.5
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  
 %%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%
  
 BUILDING PLAN REVIEW #2
 PERMIT: 07080709
 ADD: 101 EXECUTIVE CENTER DR.
 CONT: KAY RESTORATION CORP.
 TEL: (561)994-9300
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 2ND
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)OK
 3)OK
  
 4)110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING:
 A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
 ) NUMBER OF UNITS
 ) NUMBER OF FLOORS
 ) NUMBER OF ROOMS
 ) SQ. FT. FOOTPRINT
 THE ENTIRE FLOOR PLAN SHALL BE SUBMITTED ON THE
 DRAWINGS NOT A PARTIAL FLOOR PLAN.
 IS THIS A STAND ALONE BUILDING, OR IS IT CONNECTED TO
 ANOTHER?
  
 5)FBC 11-4.17.2 WATER CLOSETS IN ACCESSIBLE STALLS
 SHALL COMPLY WITH SECTION 11-4.16.AND FIG 30E. SHOW
 THE CLEAR FLOOR SPACE, OF THE WATER CLOSEST, THE FLUSH
 CONTROLS AND TOILET PAPER DISPENSERS.
  
 6)A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS
 A RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 7)A WALL DETAIL SHALL BE SUBMITTED INDICATING WHAT
 MATERIALS WILL BE USED TO CONSTRUCT THE NEW WALLS.
 SUBMIT A WALL LEGEND SHOW THE DIFFERENT TYPE OF WALL.
  
 8)FBC SEC.803 INDICATE THE TYPE OF FINISH IN
 ACCORDANCE WITH TABLE 803.5
  
 **NEW**
 9)FBC 1210.2 WALLS WITHIN 2 FEET OF URINALS AND WATER
 CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT
 SURFACE, TO A HEIGHT OF 4 FEET ABOVE THE FINISH FLOOR.
 NOTE: PAINT ON DRYWALL IN NOT CONSIDERED A HARD
 SURFACE.SHOW COMPLIANCE.
  
 10)61G15-23.002 A TITLE BLOCK SHALL BE USED ON EACH
 SHEET CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE
 NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND
 LICENSE NUMBER OF THE ENGINEER, AND IF PRACTICING
 THROUGH A DULY AUTHORIZED ENGINEERING BUSINESS, THE
 NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-08 Cont ID  
Sent By mjacobs Date 2007-09-08 Time 10:37 Rev Time 0.00
Received By mjacobs Date 2007-09-08 Time 07:43 Sent To  
Notes
2007-09-08 07:51:00BUILDING PLAN REVIEW
 PERMIT: 07080709
 ADD:101 EXECUTIVE CENTRE DR.
 CONT: KAY RESTORATION CORP.
 TEL: (561)994-9300
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)THE ALTERATION LEVEL 1 STATED ON SHEET 3/3 IS
 INCORRECT. FBC (EXISTING) SEC. 304 ANY RECONFIGURATION
 OF SPACE, THE ADDITION OR ELIMINATION OF ANY DOOR OR
 WINDOW, THE RECONFIGURATION OR EXTENSION OF ANY SYSTEM,
 OR THE INSTALLATION OF ANY ADDITIONAL EQUIPMENT IS A
 LEVEL 2 ALTERATION. THE CHANGES SHOWN ON THE PLANS
 INDICATE THIS PROJECT AS A LEVEL 2 NOT LEVEL 1 AS
 STATED ON THE PLANS.
  
 3)FBC 106.1.1* CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND SHALL BE OF SUFFICIENT CLARITY TO
 INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 FBC 2004 CODE AND RELEVANT LAWS. THERE ARE NO
 DIMENSIONS ON THE DRAWINGS.
  
 4)110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING:
 A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
 ) NUMBER OF UNITS
 ) NUMBER OF FLOORS
 ) NUMBER OF ROOMS
 ) SQ. FT. FOOTPRINT
 THE ENTIRE FLOOR PLAN SHALL BE SUBMITTED ON THE
 DRAWINGS NOT A PARTIAL FLOOR PLAN.
  
 5)FBC 11-4.17.2 WATER CLOSETS IN ACCESSIBLE STALLS
 SHALL COMPLY WITH SECTION 11-4.16.AND FIG 30E. SHOW
 THE CLEAR FLOOR SPACE, OF THE WATER CLOSEST, THE FLUSH
 CONTROLS AND TOILET PAPER DISPENSERS.
  
 6)A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS
 A RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 7)A WALL DETAIL SHALL BE SUBMITTED INDICATING WHAT
 MATERIALS WILL BE USED TO CONSTRUCT THE NEW WALLS.
 SUBMIT A WALL LEGEND SHOW THE DIFFERENT TYPE OF WALL.
  
 8)FBC SEC.803 INDICATE THE TYPE OF FINISH IN
 ACCORDANCE WITH TABLE 803.5
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-04-07 Cont ID  
Sent By dpalmer Date 2008-04-07 Time 15:10 Rev Time 0.00
Received By dpalmer Date 2008-04-07 Time 15:10 Sent To  
Notes
2008-04-07 15:10:54** DENIED 2ND REVIEW **
  
 ** PLEASE SEE NOTES FROM PREVIOUS REVIEW ARE STILL IN
 NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS DUE TO
 CHANGES MADE TO PLANS NOT IN ORIGINAL REVIEW.
  
 1) NOTE: PLEASE SEE THE TITLE BLOCKS HAVE BEEN REVISED
 TO SHOW A NEW DESIGNER OF RECORD.
 PLEASE ALSO SEE THE NEW DESIGN FIRM IS MISSING REQUIRED
 CERTIFICATE OF AUTHORIZATION NUMBER AS REQUIRED PER FS
 471.023 AND FAC 61G15-23.002.
 THIS IS REQUIRED ON ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADES.
  
 2) NOTE: PLEASE SEE MINIMUM LIGHTING CONTROLS FOR NEW
 BATHROOMS ARE NOT BEING SHOWN PER 13-415.1.ABC.1.1,
 .1.2.
  
 3) NOTE: PLEASE SEE NO MAXIMUM LIGHTING LEVELS ARE
 SHOWN PER 13-415.2, 13-415.2.ABC.1.1 ETC.
 PLEASE SUBMIT AND SHOW.
  
 4) NOTE: PLEASE SEE NO CIRCUITING IS SHOWN AND NOT
 CIRCUITING FOR EMERGENCY LIGHTS IS BEING SHOWN. A NOTE
 WAS ADDED TO PLANS HOWEVER NOTES IN LIEU OF MINIMUM
 DETAILS IS NOT PERMITTED.
  
 5) NOTE: PLEASE COMPLETE PLANS WITH MINIMUMS REQUIRED
 PER CODES.
  
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-09-08 Cont ID  
Sent By dpalmer Date 2007-09-08 Time 19:32 Rev Time 0.00
Received By dpalmer Date 2007-09-08 Time 19:16 Sent To  
Notes
2007-09-08 19:33:002007-09-08 19:33:00
  
 ** DENIED **
  
  
  
 1) NOTE:PLEASE SEE SHEET 3, NOTES FOR FIRE ALARM
 WHICH MENTIONS NPPA. THIS SHOULD BE NFPA. PLEASE
 ADJUST.(MISPRINT)
  
 2) NOTE: PLEASE SEE THAT HAND WRITTEN ITEMS ON SIGNED,
 DATED AND SEALED PLANS ARE NOT PERMITTED.
 PLEASE RE-PRINT.
 FS 471.025
  
 3) NOTE: PLEASE SEE NOTES FOR FIRE ALARM MENTIONS
 SECURITY LOCKING SYSTEM HOWEVER PLANS DO NOT SHOW ANY
 OF THESE ITEMS OR FAIL SAFE OPERATION SO THAT EGRESS IN
 NOT IMPEDED UNDER EMERGENCY CONDITIONS.
 PLEASE SEE NFPA-101 CHAPTER 7. 7.2.1.5, 7.2.1.6.2
  
 4) NOTE: PLEASE INDICATE THE CIRCUITING FOR THE
 EMERGENCY BATTERY BACK UP LIGHT FIXTURE PER 700.12F. **
 SHALL BE CIRCUITED TO THE NORMAL BRANCH CIRCUIT WHICH
 FEEDS THE OTHER LIGHTING IN THE AREA BEING SERVED.
  
 5) NOTE: PLEASE SEE A NOTE ON SHEET 3 MENTIONS THIS IS
 A DWELLING??
 PLEASE ADJUST. PLEASE ALSO SEE BUILDING REVIEW COMMENTS
 FOR LEVEL OF ALTERATION.
  
 6) NOTE: PLEASE SEE THE REQUIREMENTS FOR LIGHTING
 CONTROLS FOR NEW DEVICES PER13-415.1.ABC.1.1, .1.2.
 PLEASE SEE THE TYPE OF DEVICE SHALL NOT ONLY BE MOTION
 SENSOR AS THERE ARE STALL WALLS WHICH WOULD AFFECT
 PERFORMANCE OF DEVICE.
 PLEASE SEE 13-415.2 FOR SPECIFIC LIGHTING LEVEL TO BE
 INDICATED. (MAX FOR BATHROOMS).
 13-101.
  
 7) NOTE: PLEASE INDICATE THE MINIMUM LEVELS FOR STROBES
 AND OR HORN DEVICES TO MEET FBCFOR ADA. PLEASE SEE
 11-4.28.1, .2, AND .3(4).
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-04-08 Cont ID  
Sent By mawillia Date 2008-04-08 Time 15:22 Rev Time 0.00
Received By mawillia Date 2008-04-08 Time 15:02 Sent To B1
Notes
2008-04-08 15:14:40***** PROVISO******
  
 THE APPROPIATE PLAN SHEET(S) TO BE FIRE-STAMPED WHEN
 THE OTHER REVIEWERS AS WELL AS THE BELOW COMMENT TAKEN
 FROM THE PREVIOUS FIRE REVIEW HAVE BEEN ADDRESSED:
  
 2.SPECIFY THE WALL AND CEILING INTERIOR FINISH
 MATERIALIN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHEREON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-09-17 Cont ID  
Sent By mawillia Date 2007-09-17 Time 23:03 Rev Time 0.00
Received By mawillia Date 2007-09-17 Time 21:23 Sent To  
Notes
2007-09-17 23:24:23***** DENIED******
  
  
 1.STRUCTURES UNDERGOINGCONSTRUCTION, ALTERATIONS,
 OR DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.SPECIFY THE WALL AND CEILING INTERIOR FINISH
 MATERIALIN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 3.SEPARATE PLANS ANDPERMITREQUIRED FORFIRE
 ALARM REMODEL.
  
 4.NFPA 72- 2002 EDITION, NATIONAL FIRE ALARM CODE,
 SHALL BE REFERENCED.
  
 5.AMEND FIRE ALARM NOTE IN REFERENCE TO HVAC DUCT
 SMOKE DETECTORS TO REFLECT THAT THEY SHALL INITIATE A
 GENERAL FIRE ALARM.
  
 6.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER
 EGRESS FROM OR ACCESS TO OTHER SPACES ON THE FLOOR OR
 THE BUILDING.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHEREON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-04-04 Cont ID  
Sent By adarroug Date 2008-04-04 Time 09:57 Rev Time 0.00
Received By adarroug Date 2008-04-04 Time 09:57 Sent To  
Notes
2008-04-04 10:21:30TO "BOB"#5
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-09-17 Cont ID  
Sent By mawillia Date 2007-09-17 Time 21:23 Rev Time 0.00
Received By mawillia Date 2007-08-27 Time 11:18 Sent To  
Notes
2007-09-04 10:58:31TO "BOB"#11
2007-08-27 11:20:36WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-04-08 Cont ID  
Sent By tgordon Date 2008-04-08 Time 11:58 Rev Time 0.25
Received By tgordon Date 2008-04-08 Time 11:58 Sent To  
Notes
2008-04-08 12:05:03PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) INFORMATION MISSING FROM TITLE BLOCK, THE ENGINEERS
 LICENSE NUMBER AND THE ENGINEERING BUSINESS CERTIFICATE
 OF AUTHORIZATION NUMBER.
 SEE FAC 61G15-23.002 (2)A TITLE BLOCK ON EACH SHEET
 CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE
 NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND
 LICENSE NUMBER OF THE ENGINEER, AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-09-07 Cont ID  
Sent By tgordon Date 2007-09-07 Time 11:17 Rev Time 0.20
Received By tgordon Date 2007-09-07 Time 11:17 Sent To  
Notes
2007-09-07 11:23:27*** PROVISO ***
 1) BATHROOM EXHAUST FAN TO BE A MINIMUM OF 150 CFM'S,
 PER 2004 FBC/M TABLE 403.3.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-04-08 Cont ID  
Sent By jleech Date 2008-04-08 Time 08:10 Rev Time 0.00
Received By jleech Date 2008-04-08 Time 07:59 Sent To  
Notes
2008-04-08 08:44:21DENIED;
 1. CERTIFICATE OF AUTHORIZATION NUMBER IS MISSING FROM
 TITLE BLOCK.
 2. SHEET 2 OF 4, (2.1) ADA BATHROOM REQUIREMENTS,
 PLEASE CORRECT MESSUREMENTS. 34" TO THE RIM OF THE
 LAVATORY, SEE FBC-BUILDING CHAPTER 11, SECTION
 11-4.19.2 AND FROM CENTER OF TOILET TO EDGE OF LAVATORY
 TO BE 42". SEE FIGURE 30E.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-09-13 Cont ID  
Sent By jleech Date 2007-09-13 Time 07:34 Rev Time 0.00
Received By jleech Date 2007-09-13 Time 07:23 Sent To  
Notes
2007-09-13 07:49:24DENIED;
 1.DETAILS WITH ALL MEASUREMENTS REQUIRED FOR HANDICAP
 FIXTURES. HIGHT, WIDTH, ETC. TOILET AND LAVATORYS.
 2.LIST ON PLANS THE OCCUPANCY LOAD.3.
 3. WATER RISER REQUIRED. SEE FBC-2004 WEST PALM BEACH
 ADMINISTRATION AMENDMENTS TO CHAPTER 1, SECTION
 106.3.5.1.3
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status N Date 2007-09-05 Cont ID  
Sent By choops Date 2007-09-05 Time 10:41 Rev Time 0.00
Received By choops Date 2007-09-05 Time 10:41 Sent To  
Notes
2007-09-05 10:41:16*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.