Plan Review Details - Permit 07080697
Plan Review Stops For Permit 07080697
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2007-12-04 Cont ID  
Sent By lursu Date 2007-12-04 Time 10:19 Rev Time 0.00
Received By lursu Date 2007-12-04 Time 10:19 Sent To  
Notes
2007-12-04 10:20:43PERMIT ASSIGNED CORRECTLY TO THE VALID PCN =
 74424322080010020 .
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]
  

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2007-09-12 Cont ID  
Sent By lursu Date 2007-09-12 Time 10:31 Rev Time 0.00
Received By lursu Date 2007-08-23 Time 12:01 Sent To  
Notes
2007-09-12 10:32:02THE UNITY OF TITLE FOR THE TWO PROPERTIES MUST BE
 RECORDED AND THEN A NEW PARCEL CONTROL NUMBER WILL BE
 ISSUED BY THE PROPERTY APPRAISER'S OFFICE .THE NEW PCN
 WILL BE USED WITH THE CURRENT ADDRESS 6901 OKEECHOBEE
 BLVD.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL .
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]
2007-08-23 12:01:17A COPY SENT TO LILLY MMILLER

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-08-25 Cont ID  
Sent By rmcdouga Date 2008-08-25 Time 15:58 Rev Time 0.00
Received By rmcdouga Date 2008-08-25 Time 15:58 Sent To  
Notes
2008-08-25 15:59:26RESTAMP PLANS AND PRINT NEW PERMIT CARD.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-12-04 Cont ID  
Sent By rmcdouga Date 2007-12-04 Time 09:48 Rev Time 0.00
Received By rmcdouga Date 2007-12-04 Time 09:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-10-17 Cont ID  
Sent By rmcdouga Date 2007-10-17 Time 06:56 Rev Time 0.00
Received By rmcdouga Date 2007-10-17 Time 06:56 Sent To  
Notes
2007-10-17 07:23:442004 FBC W/2007 REVISIONS
 INSTALL SIGNS
  
 DENIED BY BUILDING
  
 1) THE TITLE BLOCKS FOR DRAWINGS A2 AND A2.1 CONTAIN
 THE NAME OF AN ARCHITECT AND HIS FIRM. FLORIDA STATUTE
 481 AND F.A.C. 61G1-16.003 REQUIRE THESE DRAWINGS TO BE
 SIGNED, SEALED AND DATED BY THE ARCHITECT OF RECORD.
  
 2) THE TITLE BLOCK FOR DRAWING C-2 CONTAINS THE NAME OF
 AN ENGINEER. FLORIDA STATUTE 471 AND F.A.C.
 61G15-23.022 REQUIRE THIS DRAWING TO BE SIGNED, SEALED
 AND DATED BY THE ENGINEER.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-07 Cont ID  
Sent By rmcdouga Date 2007-09-07 Time 09:37 Rev Time 0.00
Received By rmcdouga Date 2007-09-07 Time 08:13 Sent To  
Notes
2007-09-07 09:07:242004 FBC W/2007 SUPPLEMENT
 INSTALL 3 ILLUMINATED SIGNS
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE VALUE OF THE WORK LISTED ON THE APPLICATION IS
 TOO LOW. THE VALUE OF THE WORK HAS BEEN INCREASED BASED
 ON THE MARSHALL AND SWIFT COST ESTIMATING GUIDE.
 ADDITIONAL PERMIT FEES OF $92.66 ARE DUE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-11-26 Cont ID  
Sent By btrobaug Date 2007-11-26 Time 08:51 Rev Time 0.00
Received By btrobaug Date 2007-11-26 Time 08:41 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-10-12 Cont ID  
Sent By btrobaug Date 2007-10-12 Time 15:12 Rev Time 0.00
Received By btrobaug Date 2007-10-12 Time 15:02 Sent To B
Notes
2007-10-12 15:17:59 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417
 FS, RESPECTIVELY.
 THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL
 IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES,
 IF EXEMPTIONS APPLY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-09-04 Cont ID  
Sent By btrobaug Date 2007-09-04 Time 14:09 Rev Time 0.00
Received By btrobaug Date 2007-09-04 Time 13:21 Sent To B
Notes
2007-09-04 14:09:41 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 THERE IS NO ELECTRICAL INFORMATION TO REVIEW SUBMITTED
 WITH THIS APPLICATION. SUBMIT PLANS INDICATING
 COMPLIANCE WITH ARTICLE 600, 2005 NEC. (600.5 & 600.6)
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-08-20 Cont ID  
Sent By adarroug Date 2008-08-20 Time 15:57 Rev Time 0.00
Received By adarroug Date 2008-08-20 Time 15:57 Sent To B
Notes
2008-08-20 15:58:13TO "RMCDOUGAL" DESK/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-11-16 Cont ID  
Sent By adarroug Date 2007-11-16 Time 16:12 Rev Time 0.00
Received By adarroug Date 2007-11-16 Time 16:12 Sent To Z
Notes
2007-11-16 16:13:10TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-10-10 Cont ID  
Sent By adarroug Date 2007-10-10 Time 15:17 Rev Time 0.00
Received By adarroug Date 2007-10-10 Time 15:17 Sent To Z
Notes
2007-10-10 15:17:52TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-09-04 Cont ID  
Sent By adarroug Date 2007-09-04 Time 11:39 Rev Time 0.00
Received By adarroug Date 2007-09-04 Time 11:39 Sent To E
Notes
2007-09-04 11:50:43TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-09-07 Cont ID  
Sent By rmcdouga Date 2007-09-07 Time 09:37 Rev Time 0.00
Received By rmcdouga Date 2007-08-27 Time 10:42 Sent To  
Notes
2007-08-27 10:42:40TO "Z" BOX

Review Stop Z ZONING
Rev No 3 Status P Date 2007-11-19 Cont ID  
Sent By kdfreema Date 2007-11-19 Time 10:09 Rev Time 0.00
Received By kdfreema Date 2007-11-19 Time 10:09 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2007-10-11 Cont ID  
Sent By kdfreema Date 2007-10-11 Time 16:14 Rev Time 0.00
Received By kdfreema Date 2007-10-11 Time 16:14 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2007-08-31 Cont ID  
Sent By kdfreema Date 2007-08-31 Time 16:48 Rev Time 0.00
Received By kdfreema Date 2007-08-31 Time 16:48 Sent To I
Notes
2007-08-31 16:50:31***FAILED***
  
 PLEASE PROVIDE A UNITY OF TITLE FOR THE PARCELS
 HIGHLIGHTED IN THE ATTACHED SHEET.
  
 PLEASE CALL KELLY FREEMAN, PLANNER, AT 561-822-1435
 WITH QUESTIONS.