 |
Plan Review Details - Permit 07080679
| Plan Review Stops For Permit 07080679 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2008-06-10 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2008-06-06 |
Time |
16:54 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2008-06-06 |
Time |
16:54 |
Sent To |
PC |
|
| Notes |
| 2008-06-06 16:55:05 | BUILDING REVIEWCHECKLIST. | | | 1- ENERGY CALCULATIONS ARE NOT TAKEN THE "DEFAULT" | | | COEFFICIENTFOR GLASS TYPE U-FACTOR AND SHGC (ITEMS | | | 7-AAND 7-B), THEREFORE NEED TO PROVIDE PROOF THAT | | | GLASS IN WINDOWS MEET THE U-FACTOR AND SHGC CALCULATED | | | BY THE ENGINEER.SEE SEC. 13-104.4.5 FBC 2004. | | | 2- PROVIDE DETAIL/SPECS SHOWING HOW PROVIDING R-7.1 ON | | | EXTERIOR CONCRETE WALLS AS SHOWN ON ENERGY CALCULATIONS | | | ITEM #9A. | | | 3- REVISE NAME OF CONTRACTOR ON ENERGY CALCULATIONS. | | | 4- PROVIDE 3 COPIES OF SOIL TEST REPORT. SEC. 1802.1 | | | FBC 2004. | | | 5-A) SHINGLES NOA 03-0306.14 NEED TO BE REVIEWED AND | | | APPROVED BY DESIGNER OF RECORD. SEC. 106.3.3 CITY | | | AMENDMENTS TO FBC 2004. | | | B) ROOF VENTS NOA 01-0614.05 IS EXPIRED. PROVIDE | | | CURRENT NOA AND NEEDS TO BE APPROVED BY THE DESIGNER OF | | | RECORD. | | | C) TWO HOUR FIRE RATED CONCRETE BLOCK LETTER NEEDS | | | TO BE SIGNED BY PERSON RESPONSIBLE FOR LETTER. | | | D) PROVIDE PRODUCT APPROVAL FOR HARDIPANEL SHOWN ON | | | ARCHITECTURAL DRAWINGS.DESIGNER OR RECORD TO APPROVE | | | IT AS REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC | | | 2004. | | | 6- ARCHITECT'S WALL OPENINGS CALCULATIONS NEED TO | | | HAVE ARCHITECT'SORIGINAL SEAL, SIGNATURE AND | | | INFORMATION OF ARCHITECT'S SIGNING IT AS REQUIRED BY | | | 481 FLORIDA STATUTES AND FLORIDA ADMINISTRATIVE CODE | | | SEC. 61G1-16.003. | | | 7- PROVIDE CUT SHEETS FOR 90 MINUTE FIRE RATED ENTRY | | | DOORS AS REQUIRED ON SHEET A408. | | | 8- OWES $15,105.52FOR UPDATED VALUATION AND RADON | | | FEES. | | | 9- NEEDSRECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 | | | FLORIDA STATUTE. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-10-10 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2007-10-10 |
Time |
15:19 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2007-10-10 |
Time |
15:18 |
Sent To |
|
|
| Notes |
| 2007-10-10 15:20:00 | BUILDING REVIEW FIRST CHECKLIST FOR NEW R2 RESIDENTIAL | | | BUILDING. | | | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. | | | | | | 1- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 | | | FLORIDA STATUTE. | | | | | | 2- ENERGY CALCULATIONS: | | | A) NEED TO HAVE ENGINEER'S ORIGINAL SIGNATURE AS | | | REQUIRED BY CHAPTER 471 FLORIDA STATUTE. | | | | | | B) CONTRACTOR'S INFORMATION DOESN'T MATCH | | | CONTRACTOR'S INFORMATION SHOWN ON PERMIT APPLICATION. | | | | | | C) REVISE PERMIT NUMBER. | | | | | | D) REVISE OWNER INFORMATION. | | | | | | 3- PROVIDE THREE COPIES OF SURVEYS. ONLY ONE | | | SUBMITTED. | | | | | | 4-A) SHEET A110. DETAIL #19 CALLS FOR GA SYSTEM -WP | | | 1052, WHILE ON TOP OF DETAIL IT CALLS FOR WP 3240. | | | REVISE AS REQUIRED. | | | ***NOTE: THIS ITEM APPLIES TO THE OTHER BUILDINGS AS | | | WELL.REVISE SHEET IN ALL BUILDINGSAS REQUIRED | | | | | | B) SHEET A111:FIRE ASSEMBLY DETAIL 16 IS FOR UL | | | FIRE ASSEMBLY L523 OR L521.TOP OF DETAIL CALLS FOR | | | L521, WHILE BOTTOM OF DETAIL CALLS FOR L563. REVISE AS | | | REQUIRED TO MATCH. | | | | | | 5- PROVIDE 3 COPIES OF SOIL TEST REPORT. SEC. 1802.1 | | | FBC 2004. | | | | | | 6- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE | | | 9B-72 FOR: | | | A) 700 SERIES LOUVERED ROOF VENTS. NOA01-0614.05 | | | SUBMITTED EXPIRED ON 08/16/2006. NEED CURRENT ONE. | | | ***NOTE:PLEASE MAKE SURE NOAAND FLORIDA PRODUCT | | | APPROVAL COVER PAGE SUBMITTED CORRESPOND TO EACH OTHER. | | | OTHERWISE PROVIDE NOA ONLY TO BE ADDED TO THE CITY | | | PRODUCT APPROVAL REFERENCE LIBRARY. | | | | | | B) BENCHMARK DOOR NOA 02-0215.04 SUBMITTED EXPIRED | | | ON MAY 30, 2007.NEED CURRENT ONE. | | | ***NOTE: CLARIFY WHY SUBMITTING SEPARATE PRODUCT | | | APPROVAL FOR DOOR FRAME IF THIS NOAINCLUDES THE DOOR | | | FRAME?. | | | | | | | | | 7- DESIGNER OF RECORD TO REVIEW AND APPROVE ALL | | | RE-SUBMITTED PRODUCT APPROVALS AS REQUIRED BY SEC. | | | 106.3.3 CITY AMENDMENTS TO FBC 2004. | | | | | | 8- OWES $15,105.52FOR LOW VALUATION AND RADON FEES. | | | SEC. 108.3 CITY AMENDMENTS TO FBC 2004. | | | | | | 9- PROVIDE COMPLETE MANUFACTURER SPECS FOR 2 HOUR FIRE | | | RATED CONCRETE BLOCK. SEC. 106.1.2 CITY AMENDMENTS TO | | | FBC 2004 AND SEC. 703 FBC 2004. | | | | | | 10- REMOVE PRODUCT APPROVALS FROM PROJECT MANUAL. THESE | | | PRODUCT APPROVALS ARE FOR ANOTHER BUILDING. | | | | | | 11- SURVEY AND SITE PLAN ON SHEETSA100 AND A101 DON'T | | | MATCH. BUILDINGS "K" AND "L" ARE REVERSED. REVISE | | | EITHER ONE AS REQUIRED TO MATCH. | | | | | | 12- SHOW ASSUMED PROPERTY LINE BETWEEN THE TWO | | | BUILDINGS TO VERIFY COMPLIANCE WITH TABLE704.8 FBC | | | 2004.CLEARLYSPECIFY DIMENSIONFROM BUILDING TO | | | ASSUMED PROPERTY LINE. | | | | | | 13- REVISE ROOF FRAMING PLANS IN STRUCTURAL DRAWINGS. | | | ARCHITECTURAL PLANS SHOW TENANT SEPARATION WALL GOING | | | ALL THE WAY UP TO BOTTOM OF ROOF SHEATHING.NEED TO | | | REVISE TIE BEAM ELEVATION AND SPECIFY RAKE BEAMS WHERE | | | REQUIRED. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. | | | | | | ***NOTE: THIS ITEM APPLIES TO ALL BUILDINGS. | | | | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2008-05-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-05-13 |
Time |
08:45 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-05-13 |
Time |
08:45 |
Sent To |
|
|
| Notes |
| 2008-05-13 08:45:13 | ** DENIED 2ND REVIEW** | | | | | | ** PLEASE SEE THE COMMENTS BELOW ARE THE SAME COMMENTS | | | FROM THE PREVIOUS REVIEW. | | | | | | 1) NOTE:PLEASE SEE PREVIOUS REVIEW WITH RESPECT TO | | | THE REQUIRED MINIMUM CODES. THE MINIMUM REQUIRED DESIGN | | | FOR PROJECT PERMITTED AFTER DECEMBER 6TH, 2008 IS THE | | | 2005 NEC/ NFPA-70 | | | PLEASE SEE FOR EXAMPLE THE SHEET E202 WHICH STILL | | | REFLECTS DESIGN FROM THE 2002 CODE. | | | PLEASE SEE ITEMS LISTED IN THE FOLLOWING COMMENTS WHICH | | | WERE CHANGED IN THE 2005 NEC. | | | PLANS MUST STATE THE CODES RELEVANT FOR DESIGN. | | | FS 553.73 | | | FBC 106.1.2, 106.5 ADMIN SECTIONS ADOPTED BY THE CITY | | | OF WEST PALM BEACH | | | | | | 2) NOTE: PLEASE SEE THE REQUIRED DISCONNECTING MEANS | | | FOR APPLIANCES ARE STILL NOT SHOWN ON PLANS. | | | FOR EXAMPLE: | | | DISHWASHER, | | | DISPOSAL, | | | HOOD FAN ETC | | | 422.30, 422.31 | | | THESE ARE SOME EXAMPLES ONLY AND ARE NOT AN EXHAUSTED | | | LIST. THESE ARE ONLY GIVEN AS A BENEFIT. | | | | | | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-08-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-08-28 |
Time |
20:09 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-08-28 |
Time |
20:09 |
Sent To |
|
|
| Notes |
| 2007-08-28 20:09:44 | 2007-08-28 20:09:44 | | | | | | ** DENIED ** | | | | | | 1) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED | | | ARE NOT SIGNED, DATED AND SEALED AS REQUIRED PER FS | | | 471.025 AND FAC 61G15-23.002. | | | PLEASE SEE ALLCOPIES SUBMITTED IN FACT CONTAIN A | | | RAISED SEAL OVER *PHOTO-COPIED* SIGNATURES. | | | PLEASE KNOW THAT PLACING A RAISED SEAL OVER THE | | | REQUIRED ORIGINAL SIGNATURE AND DATE DOES NOT MEET THE | | | FLORIDA STATUTES AND THE FLORIDA ADMINISTRATIVE CODE. | | | FBC 103.1.1.1 | | | | | | 2) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS | | | WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES | | | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. | | | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO | | | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. | | | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY | | | AFFECT DESIGNS FOR ALL TRADES. | | | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS | | | REVIEWER AT A MINIMUM. | | | 2004 FBC W/ 2006 REVISIONS(NEW CODE) | | | 2005 NFPA-70 (WRONG CODE LISTED ON PLANS) | | | 2002 NFPA-72 (SHOWN) | | | 2003 NFPA-101( ON A-SHEETS NOT ON E-SHEETS) | | | | | | ** SOME OF THESE ARE LISTED AND SOME NEED TO BE | | | CORRECTED. | | | | | | 3) NOTE: PLEASE SEE THE FAN/HOOD, DISHWASHER AND | | | DISPOSAL ARE ALL BEING SHOWN WITH J-BOX AS THESE ITEMS | | | ARE TO BE HARDWIRED. | | | PLEASE SEE 422.30, 422.31 FOR REQUIRED DISCONNECTING | | | MEANS. | | | ARE THESE NOT CORD AND PLUG TYPE APPLIANCES? | | | | | | | | | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
F |
Date |
2008-05-15 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2008-05-15 |
Time |
09:03 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2008-05-15 |
Time |
09:01 |
Sent To |
|
|
| Notes |
| 2008-05-15 09:03:28 | ***FAILED**** PLEASE PROVIDE THE FOLLOWING: | | | | | | WE HAVE NOT FOUND CIVIL DRAWINGS & ENG REVIEW INFO IN | | | YOUR PACKAGE YOU SUBMITTED FOR THIS PERMIT.JUST TO | | | LET YOU KNOW A HEAD OF TIME THATWE NEED FOR ENG | | | REVIEW,STORM WATER QUALITY CALS, POLLUTION PREVENTION | | | PLANS, CITY STANDARDS SHOWN ON DRAWINGS ETC, ETC. | | | THEREFORE, WE ARE ASKING YOU TO INCLUDE THE FOLLOWING | | | WHEN YOU SUBMIT CIVIL DRAWINGS FOR ENGINEERING REVIEW, | | | SO WE CAN EXPEDITE OUR ENG REVIEW PROCESS. | | | | | | 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI). | | | PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR | | | NOI. | | | YOU CAN GET NOI INFO FROM | | | WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/ | | | NOTICE OF INTENT DEP FORM 62-621.300(4)(B), | | | EFFECTIVE MAY 1, 2003 | | | | | | 2. PLEASE SHOW ON CIVIL DRAWING THE SITE PLAN SHOWING | | | STREETS/ROADS AROUND THE SITE WITH NORTH ARROW. | | | | | | 3.PLEASE SHOW ON DRAWING ALL CITY STANDARDS NOTES FOR | | | SIDEWALK, DRIVEWAY, APPROACH, PARKINGS, HANDICAP | | | PARKINGS, DUMPSTER ENCLOSURE, YOU CAN GET A C D FROM | | | 1000, 45 STREET FOR ALL THESE CITY STANDARDS NOTES. | | | PHONE# 494-1040 | | | | | | 4. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE | | | DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION | | | MUST BE ACCESSIBLE FOR PICKUP TRUCK. | | | | | | 5. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD , | | | SIDEWALK ELEVATION MUST MEET FLOOD ZONE AREA, & 5,10, | | | 25, 100 YEAR FLOOD CRITERIATO DETERMINE THE FIRST | | | FLOOR ELEVATION, PLEASE SHOW IN YOUR STORM WATER CALS | | | THAT HOW DID YOU DETERMINE THE FIRST FLOOR | | | ELEVATION??. | | | | | | 6. PLEASE SHOW ON DRAWINGTHE SITE AREA, YOU ARE | | | DEVELOPING FOR THIS PROJECT . PLEASE ALSO SHOW TOTAL | | | PERVIOUS,& IMPERVIOUS AREA FOR THIS PROJECT, | | | LAKE,SIDEWALK, PARKING,BUILDING AREA ETC. MAKE SURE | | | THESE AREAS SHOWN ON DRAWINGS MUST MATCH WITH AND USED | | | IN STORM WATER QUALITY CALCULATIONS. | | | | | | 7. HOW DO YOU CONNECT TO THE STORM WATER PIPES IN YOUR | | | SITE? ITS DETAILS.PLEASE SHOW ALL STORM WATER PIPES | | | AROUND YOUR SITE SO, WE CANSEE THE LAYOUT OF STORM | | | WATER PIPES FROM ALL OTHER STORM WATER PIPES. PLEASE | | | SHOW DETAIL OF THE CONTROL STRUCTURESWITH | | | ELEVATIONS, NOTCHES, BLEEDING ELEVATION, ETC ON | | | DRAWINGS, CALCULATION FOR EXFILTRATION TRENCHES, PLEASE | | | SHOW DRY DETENTION/WET DETENTION AREAS IN STORM WATER | | | CALS. | | | | | | 8. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND | | | YOUR SITE FOR STORM WATER DRAIN. | | | | | | 9. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, & PLEASE | | | ALSO PROVIDE A COPY OF GEOTECH REPORT & STORM WATER | | | QUALITY CALCULATIONS TO 1000 45TH STREET ENGINEERING | | | SERVICES FOR THEIR APPROVAL BEFORE WE ISSUE A PERMIT, | | | | | | 10. PLEASE SHOW ON DRAWINGS THE POLLUTION PREVENTION | | | DETAILS,CLOTHES USED FOR SILT ETC., PLANS SHOWING SILT | | | FENCE AROUND THE SITE & CATCH BASINS.HEIGHT OF FENCE | | | SHOULD BE HIGH ENOUGH PER FDEP TO STOP DUST & | | | PARTICLES. | | | | | | 11. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH | | | STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED. | | | | | | PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR | | | PERMITTING PROCESS | | | | | | RASIK CHOKSHI805-6723 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2007-09-07 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2007-09-07 |
Time |
13:46 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2007-09-07 |
Time |
13:45 |
Sent To |
|
|
| Notes |
| 2007-09-07 13:46:24 | ***FAILED**** PLEASE PROVIDE THE FOLLOWING: | | | | | | WE HAVE NOT FOUND CIVIL DRAWINGS & ENG REVIEW INFO IN | | | YOUR PACKAGE YOU SUBMITTED FOR THIS PERMIT.JUST TO | | | LET YOU KNOW A HEAD OF TIME THATWE NEED FOR ENG | | | REVIEWSTORM WATER CALS, POLLUTION PREVENTION PLANS, | | | CITY STANDARDS SHOWN ON DRAWINGS ETC, ETC.THEREFORE, | | | WE ARE ASKING YOU TO INCLUDE THE FOLLOWING WHEN YOU | | | SUBMIT CIVIL DRAWINGS FOR ENGINEERING REVIEW, SO WE CAN | | | EXPEDITE OUR ENG REVIEW PROCESS. | | | | | | 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI). | | | PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR | | | NOI. | | | YOU CAN GET NOI INFO FROM | | | WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/ | | | NOTICE OF INTENT DEP FORM 62-621.300(4)(B), | | | EFFECTIVE MAY 1, 2003 | | | 2. PLEASE SHOW ON CIVIL DRAWING THE SITE PLAN SHOWING | | | STREETS/ROADS AROUND THE SITE WITH NORTH ARROW. | | | 3.PLEASE SHOW ON DRAWING ALL CITY STANDARDS NOTES FOR | | | SIDEWALK, DRIVEWAY, APPROACH, PARKINGS, HANDICAP | | | PARKINGS, DUMPSTER ENCLOSURE, YOU CAN GET A C D FROM | | | 1000, 45 STREET FOR ALL THESE CITY STANDARDS NOTES. | | | PHONE# 494-1040 | | | 4. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE | | | DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION | | | MUST BE ACCESSIBLE FOR PICKUP TRUCK. | | | 5. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD , | | | SIDEWALK ELEVATION MUST MEET FLOOD ZONE AREA, & 5,10, | | | 25, 100 YEAR FLOOD CRITERIATO DETERMINE THE FIRST | | | FLOOR ELEVATION, PLEASE SHOW IN YOUR STORM WATER CALS | | | THAT HOW DID YOU DETERMINE THE FIRST FLOOR ELEVATION??. | | | | | | 6. PLEASE SHOW ON DRAWINGTHE SITE AREA, YOU ARE | | | DEVELOPING FOR THIS PROJECT . PLEASE ALSO SHOW TOTAL | | | PERVIOUS,& IMPERVIOUS AREA FOR THIS PROJECT, | | | LAKE,SIDEWALK, PARKING,BUILDING AREA ETC. MAKE SURE | | | THESE AREAS SHOWN ON DRAWINGS MUST MATCH WITH AND USED | | | IN STORM WATER QUALITY CALCULATIONS. | | | 7. HOW DO YOU CONNECT TO THE STORM WATER PIPES IN YOUR | | | SITE? ITS DETAILS.PLEASE SHOW ALL STORM WATER PIPES | | | AROUND YOUR SITE SO, WE CANSEE THE LAYOUT OF STORM | | | WATER PIPES FROM ALL OTHER STORM WATER PIPES. PLEASE | | | SHOW DETAIL OF THE CONTROL STRUCTURESWITH | | | ELEVATIONS, NOTCHES, BLEEDING ELEVATION, ETC ON | | | DRAWINGS, CALCULATION FOR EXFILTRATION TRENCHES, PLEASE | | | SHOW DRY DETENTION/WET DETENTION AREAS IN STORM WATER | | | CALS. | | | 8. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND | | | YOUR SITE FOR STORM WATER DRAIN. | | | 9. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, &STORM | | | WATER QUALITY CALCULATIONS, | | | 10. PLEASE SHOW ON DRAWINGS THE POLLUTION PREVENTION | | | DETAILS,CLOTHES USED FOR SILT ETC., PLANS SHOWING SILT | | | FENCE AROUND THE SITE & CATCH BASINS.HEIGHT OF FENCE | | | SHOULD BE HIGH ENOUGH PER FDEP TO STOP DUST & | | | PARTICLES. | | | 11. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH | | | STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED. | | | | | | PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR | | | PERMITTING PROCESS | | | | | | RASIK CHOKSHI805-6723 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2008-05-27 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-05-27 |
Time |
14:26 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-05-27 |
Time |
13:29 |
Sent To |
|
|
| Notes |
| 2008-05-27 14:26:22 | *****PROVISO***** | | | | | | WITH THE EXCEPTION THE FOLLOWING COMMENT FROM THE | | | PREVIOUS FIRE PLAN REVIEWS, ALL OTHERS HAVE BEEN | | | ADDRESSED: | | | | | | 3. DISPLAY THE ADDRESS NUMBER ON THE APPROPIATE | | | EXTERIOR ELEVATION WHICH FRONTS MERRY PLACE. AS PER | | | WEST PALM BEACH CODE, THOSE NUMBERS SHALL BE NO LESS | | | THAN 6" IN HEIGHT AND NO LESS THAN 1" IN STROKE. IN | | | ADDITION, DISPLAY THE INDIVIDUAL DWELLING UNIT NUMBER | | | FOR THIS PROJECT SITE. AS PER WEST PALM BEACH CODE, | | | UNIT NUMBERS SHALL BE NO LESS THAN 3" IN HEIGHT AND NO | | | LESS THAN 1" IN STROKE. BASED UPON FIELD INSPECTIONS | | | CONDUCTED AT THE MERRY PLACE PROJECT BY THIS WRITER: | | | | | | A) A SINGLE ADDRESS NUMBER BE CENTERED ON THE BUILDING, | | | OR HAVE THE ADDRESS AT BOTH ENDS OF THE EXTERIOR | | | ELEVATION WHICH FRONTS MERRY PLACE. | | | B) TENANT UNIT NUMBERS SHALL BE ON THE STRUCTURE OF THE | | | BUILDING, NOT THE DOOR. | | | | | | | | | | | | THE APPROPIATE PLAN SHEETS TO BE FIRE-STAMPED WHEN THE | | | OTHER REVIEWERS COMMENTS AS WELL AS THE ABOVE COMMENT | | | HAVE BEEN SATISFIED. | | | | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2007-11-05 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-11-05 |
Time |
10:46 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-11-05 |
Time |
09:31 |
Sent To |
|
|
| Notes |
| 2007-11-05 10:02:46 | *****DENIED***** | | | | | | 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 2. CONSTRUCTION OPERATIONS SHALL NOT INTERFERE OR | | | HINDER EMERGENCY ACCESS TO THE SAID PROPERTY OR | | | VICINITY THEREOF. | | | | | | 3. DISPLAY THE ADDRESS NUMBER ON THE APPROPIATE | | | EXTERIOR ELEVATION WHICH FRONTS MERRY PLACE. AS PER | | | WEST PALM BEACH CODE, THOSE NUMBERS SHALL BE NO LESS | | | THAN 6" IN HEIGHT AND NO LESS THAN 1" IN STROKE. IN | | | ADDITION, DISPLAY THE INDIVIDUAL DWELLING UNIT NUMBER | | | FOR THIS PROJECT SITE. AS PER WEST PALM BEACH CODE, | | | UNIT NUMBERS SHALL BE NO LESS THAN 3" IN HEIGHT AND NO | | | LESS THAN 1" IN STROKE. | | | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED. | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
N |
Date |
2008-05-15 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-05-09 |
Time |
18:34 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-05-09 |
Time |
18:34 |
Sent To |
|
|
| Notes |
| 2008-05-09 18:36:46 | SEPARATE GAS PERMIT REQUIRED.--PLANS AND OTHER | | | REQUIREMENTS TO BE SUBMITTED AT TIME OF APPLICATION. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2008-05-09 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-09-13 |
Time |
16:26 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-09-13 |
Time |
16:26 |
Sent To |
|
|
| Notes |
| 2008-05-09 16:27:48 | DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | | | | A. THE FOLLOWING REQUIREMENTS FOR THE REQUIRED GAS | | | PERMIT SHALL BE SUBMITTED: | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. | | | | | | 2. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE IF BEING USED. | | | | | | 3. TYPE OF GAS, (LP OR NATURAL). | | | | | | 4. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). | | | | | | 5. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | | | | 6. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | | | | 7. CLEARLY SHOW THE LOCATION AND CAP- | | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | | OR ASME), THE DISTANCE OF THE TANK FROM | | | THE BUILDING AND ADJACENT PROPERTY LINES | | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | | CES OF IGNITION, OTHER CONTAINERS, BUILD | | | INGS, AND THE LOCATION OF ANY BUILDING | | | OPENINGS BELOW THE RELIEF VALVE OF THE | | | TANK PER NFPA 58, TABLE 3-2.2.2. | | | | | | 8. CLEARLY INDICATE ON THE PLAN IF THE | | | LP TANK IS ABOVE OR BELOW GROUND, AND | | | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES | | | PER NFPA 58. IF THE TANK | | | IS BELOW GROUND THE CONTAINER SHALL BE | | | SECURILY ANCHORED PER NFPA 58 SECTION | | | 3-2.2.7(H). | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | | FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-04-30 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-04-30 |
Time |
15:37 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-04-30 |
Time |
15:37 |
Sent To |
|
|
| Notes |
| 2008-04-30 15:37:13 | TO "COMM" BD#44--PLANS ON RACK"LARGE FOLDED | | | PLANS"--EXPEDITED-- |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-11-05 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-11-05 |
Time |
09:31 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-08-24 |
Time |
10:32 |
Sent To |
|
|
| Notes |
| 2007-08-27 13:49:33 | TO "COMM" BD#26/PLANS ON RACK--8 ROLLS AND 4 | | | APPL'S---EXPEDITED PERMIT--- | | 2007-08-24 10:33:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2008-05-05 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-05-05 |
Time |
16:38 |
Rev Time |
1.00 |
| Received By |
tgordon |
Date |
2008-05-05 |
Time |
16:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2007-09-10 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-09-10 |
Time |
14:15 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2007-09-10 |
Time |
14:15 |
Sent To |
|
|
| Notes |
| 2007-09-10 14:17:00 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | | PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA | | | ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS). | | | | | | *** DENIED *** | | | | | | 1) SEE ELECTRICAL REVIEW NOTE #1 REGARDING SIGNATURE ON | | | ENERGY CALCULATIONS, PLEASE CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2008-05-15 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-05-12 |
Time |
14:49 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-05-09 |
Time |
18:34 |
Sent To |
|
|
| Notes |
| 2008-05-12 14:59:28 | PASSED PROVISO--RISER 4S REQUIRES A 3" STACK PER | | | SECTION 406.3. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-09-13 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-09-13 |
Time |
18:23 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-09-13 |
Time |
18:23 |
Sent To |
|
|
| Notes |
| 2007-09-13 18:25:47 | DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | | | | A. THE FOLLOWING REQUIREMENTS FOR THE REQUIRED GAS | | | PERMIT SHALL BE SUBMITTED: | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. | | | | | | 2. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE IF BEING USED. | | | | | | 3. TYPE OF GAS, (LP OR NATURAL). | | | | | | 4. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). | | | | | | 5. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | | | | 6. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | | | | 7. CLEARLY SHOW THE LOCATION AND CAP- | | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | | OR ASME), THE DISTANCE OF THE TANK FROM | | | THE BUILDING AND ADJACENT PROPERTY LINES | | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | | CES OF IGNITION, OTHER CONTAINERS, BUILD | | | INGS, AND THE LOCATION OF ANY BUILDING | | | OPENINGS BELOW THE RELIEF VALVE OF THE | | | TANK PER NFPA 58, TABLE 3-2.2.2. | | | | | | 8. CLEARLY INDICATE ON THE PLAN IF THE | | | LP TANK IS ABOVE OR BELOW GROUND, AND | | | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES | | | PER NFPA 58. IF THE TANK | | | IS BELOW GROUND THE CONTAINER SHALL BE | | | SECURILY ANCHORED PER NFPA 58 SECTION | | | 3-2.2.7(H). | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | | FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2008-05-07 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2008-05-07 |
Time |
11:38 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2008-05-07 |
Time |
11:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2007-09-04 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2007-09-04 |
Time |
18:02 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2007-09-04 |
Time |
18:02 |
Sent To |
|
|
| Notes |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |