Plan Review Details - Permit 07080679
Plan Review Stops For Permit 07080679
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-06-10 Cont ID  
Sent By jgomez Date 2008-06-06 Time 16:54 Rev Time 0.00
Received By jgomez Date 2008-06-06 Time 16:54 Sent To PC
Notes
2008-06-06 16:55:05BUILDING REVIEWCHECKLIST.
 1- ENERGY CALCULATIONS ARE NOT TAKEN THE "DEFAULT"
 COEFFICIENTFOR GLASS TYPE U-FACTOR AND SHGC (ITEMS
 7-AAND 7-B), THEREFORE NEED TO PROVIDE PROOF THAT
 GLASS IN WINDOWS MEET THE U-FACTOR AND SHGC CALCULATED
 BY THE ENGINEER.SEE SEC. 13-104.4.5 FBC 2004.
 2- PROVIDE DETAIL/SPECS SHOWING HOW PROVIDING R-7.1 ON
 EXTERIOR CONCRETE WALLS AS SHOWN ON ENERGY CALCULATIONS
 ITEM #9A.
 3- REVISE NAME OF CONTRACTOR ON ENERGY CALCULATIONS.
 4- PROVIDE 3 COPIES OF SOIL TEST REPORT. SEC. 1802.1
 FBC 2004.
 5-A) SHINGLES NOA 03-0306.14 NEED TO BE REVIEWED AND
 APPROVED BY DESIGNER OF RECORD. SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004.
 B) ROOF VENTS NOA 01-0614.05 IS EXPIRED. PROVIDE
 CURRENT NOA AND NEEDS TO BE APPROVED BY THE DESIGNER OF
 RECORD.
 C) TWO HOUR FIRE RATED CONCRETE BLOCK LETTER NEEDS
 TO BE SIGNED BY PERSON RESPONSIBLE FOR LETTER.
 D) PROVIDE PRODUCT APPROVAL FOR HARDIPANEL SHOWN ON
 ARCHITECTURAL DRAWINGS.DESIGNER OR RECORD TO APPROVE
 IT AS REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC
 2004.
 6- ARCHITECT'S WALL OPENINGS CALCULATIONS NEED TO
 HAVE ARCHITECT'SORIGINAL SEAL, SIGNATURE AND
 INFORMATION OF ARCHITECT'S SIGNING IT AS REQUIRED BY
 481 FLORIDA STATUTES AND FLORIDA ADMINISTRATIVE CODE
 SEC. 61G1-16.003.
 7- PROVIDE CUT SHEETS FOR 90 MINUTE FIRE RATED ENTRY
 DOORS AS REQUIRED ON SHEET A408.
 8- OWES $15,105.52FOR UPDATED VALUATION AND RADON
 FEES.
 9- NEEDSRECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-10 Cont ID  
Sent By jgomez Date 2007-10-10 Time 15:19 Rev Time 0.00
Received By jgomez Date 2007-10-10 Time 15:18 Sent To  
Notes
2007-10-10 15:20:00BUILDING REVIEW FIRST CHECKLIST FOR NEW R2 RESIDENTIAL
 BUILDING.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
  
 2- ENERGY CALCULATIONS:
 A) NEED TO HAVE ENGINEER'S ORIGINAL SIGNATURE AS
 REQUIRED BY CHAPTER 471 FLORIDA STATUTE.
  
 B) CONTRACTOR'S INFORMATION DOESN'T MATCH
 CONTRACTOR'S INFORMATION SHOWN ON PERMIT APPLICATION.
  
 C) REVISE PERMIT NUMBER.
  
 D) REVISE OWNER INFORMATION.
  
 3- PROVIDE THREE COPIES OF SURVEYS. ONLY ONE
 SUBMITTED.
  
 4-A) SHEET A110. DETAIL #19 CALLS FOR GA SYSTEM -WP
 1052, WHILE ON TOP OF DETAIL IT CALLS FOR WP 3240.
 REVISE AS REQUIRED.
 ***NOTE: THIS ITEM APPLIES TO THE OTHER BUILDINGS AS
 WELL.REVISE SHEET IN ALL BUILDINGSAS REQUIRED
  
 B) SHEET A111:FIRE ASSEMBLY DETAIL 16 IS FOR UL
 FIRE ASSEMBLY L523 OR L521.TOP OF DETAIL CALLS FOR
 L521, WHILE BOTTOM OF DETAIL CALLS FOR L563. REVISE AS
 REQUIRED TO MATCH.
  
 5- PROVIDE 3 COPIES OF SOIL TEST REPORT. SEC. 1802.1
 FBC 2004.
  
 6- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) 700 SERIES LOUVERED ROOF VENTS. NOA01-0614.05
 SUBMITTED EXPIRED ON 08/16/2006. NEED CURRENT ONE.
 ***NOTE:PLEASE MAKE SURE NOAAND FLORIDA PRODUCT
 APPROVAL COVER PAGE SUBMITTED CORRESPOND TO EACH OTHER.
 OTHERWISE PROVIDE NOA ONLY TO BE ADDED TO THE CITY
 PRODUCT APPROVAL REFERENCE LIBRARY.
  
 B) BENCHMARK DOOR NOA 02-0215.04 SUBMITTED EXPIRED
 ON MAY 30, 2007.NEED CURRENT ONE.
 ***NOTE: CLARIFY WHY SUBMITTING SEPARATE PRODUCT
 APPROVAL FOR DOOR FRAME IF THIS NOAINCLUDES THE DOOR
 FRAME?.
  
  
 7- DESIGNER OF RECORD TO REVIEW AND APPROVE ALL
 RE-SUBMITTED PRODUCT APPROVALS AS REQUIRED BY SEC.
 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 8- OWES $15,105.52FOR LOW VALUATION AND RADON FEES.
 SEC. 108.3 CITY AMENDMENTS TO FBC 2004.
  
 9- PROVIDE COMPLETE MANUFACTURER SPECS FOR 2 HOUR FIRE
 RATED CONCRETE BLOCK. SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004 AND SEC. 703 FBC 2004.
  
 10- REMOVE PRODUCT APPROVALS FROM PROJECT MANUAL. THESE
 PRODUCT APPROVALS ARE FOR ANOTHER BUILDING.
  
 11- SURVEY AND SITE PLAN ON SHEETSA100 AND A101 DON'T
 MATCH. BUILDINGS "K" AND "L" ARE REVERSED. REVISE
 EITHER ONE AS REQUIRED TO MATCH.
  
 12- SHOW ASSUMED PROPERTY LINE BETWEEN THE TWO
 BUILDINGS TO VERIFY COMPLIANCE WITH TABLE704.8 FBC
 2004.CLEARLYSPECIFY DIMENSIONFROM BUILDING TO
 ASSUMED PROPERTY LINE.
  
 13- REVISE ROOF FRAMING PLANS IN STRUCTURAL DRAWINGS.
 ARCHITECTURAL PLANS SHOW TENANT SEPARATION WALL GOING
 ALL THE WAY UP TO BOTTOM OF ROOF SHEATHING.NEED TO
 REVISE TIE BEAM ELEVATION AND SPECIFY RAKE BEAMS WHERE
 REQUIRED. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 ***NOTE: THIS ITEM APPLIES TO ALL BUILDINGS.
  
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-05-13 Cont ID  
Sent By dpalmer Date 2008-05-13 Time 08:45 Rev Time 0.00
Received By dpalmer Date 2008-05-13 Time 08:45 Sent To  
Notes
2008-05-13 08:45:13** DENIED 2ND REVIEW**
  
 ** PLEASE SEE THE COMMENTS BELOW ARE THE SAME COMMENTS
 FROM THE PREVIOUS REVIEW.
  
 1) NOTE:PLEASE SEE PREVIOUS REVIEW WITH RESPECT TO
 THE REQUIRED MINIMUM CODES. THE MINIMUM REQUIRED DESIGN
 FOR PROJECT PERMITTED AFTER DECEMBER 6TH, 2008 IS THE
 2005 NEC/ NFPA-70
 PLEASE SEE FOR EXAMPLE THE SHEET E202 WHICH STILL
 REFLECTS DESIGN FROM THE 2002 CODE.
 PLEASE SEE ITEMS LISTED IN THE FOLLOWING COMMENTS WHICH
 WERE CHANGED IN THE 2005 NEC.
 PLANS MUST STATE THE CODES RELEVANT FOR DESIGN.
 FS 553.73
 FBC 106.1.2, 106.5 ADMIN SECTIONS ADOPTED BY THE CITY
 OF WEST PALM BEACH
  
 2) NOTE: PLEASE SEE THE REQUIRED DISCONNECTING MEANS
 FOR APPLIANCES ARE STILL NOT SHOWN ON PLANS.
 FOR EXAMPLE:
 DISHWASHER,
 DISPOSAL,
 HOOD FAN ETC
 422.30, 422.31
 THESE ARE SOME EXAMPLES ONLY AND ARE NOT AN EXHAUSTED
 LIST. THESE ARE ONLY GIVEN AS A BENEFIT.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-08-28 Cont ID  
Sent By dpalmer Date 2007-08-28 Time 20:09 Rev Time 0.00
Received By dpalmer Date 2007-08-28 Time 20:09 Sent To  
Notes
2007-08-28 20:09:442007-08-28 20:09:44
  
 ** DENIED **
  
 1) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED
 ARE NOT SIGNED, DATED AND SEALED AS REQUIRED PER FS
 471.025 AND FAC 61G15-23.002.
 PLEASE SEE ALLCOPIES SUBMITTED IN FACT CONTAIN A
 RAISED SEAL OVER *PHOTO-COPIED* SIGNATURES.
 PLEASE KNOW THAT PLACING A RAISED SEAL OVER THE
 REQUIRED ORIGINAL SIGNATURE AND DATE DOES NOT MEET THE
 FLORIDA STATUTES AND THE FLORIDA ADMINISTRATIVE CODE.
 FBC 103.1.1.1
  
 2) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS(NEW CODE)
 2005 NFPA-70 (WRONG CODE LISTED ON PLANS)
 2002 NFPA-72 (SHOWN)
 2003 NFPA-101( ON A-SHEETS NOT ON E-SHEETS)
  
 ** SOME OF THESE ARE LISTED AND SOME NEED TO BE
 CORRECTED.
  
 3) NOTE: PLEASE SEE THE FAN/HOOD, DISHWASHER AND
 DISPOSAL ARE ALL BEING SHOWN WITH J-BOX AS THESE ITEMS
 ARE TO BE HARDWIRED.
 PLEASE SEE 422.30, 422.31 FOR REQUIRED DISCONNECTING
 MEANS.
 ARE THESE NOT CORD AND PLUG TYPE APPLIANCES?
  
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2008-05-15 Cont ID  
Sent By rchokshi Date 2008-05-15 Time 09:03 Rev Time 0.00
Received By rchokshi Date 2008-05-15 Time 09:01 Sent To  
Notes
2008-05-15 09:03:28***FAILED**** PLEASE PROVIDE THE FOLLOWING:
  
 WE HAVE NOT FOUND CIVIL DRAWINGS & ENG REVIEW INFO IN
 YOUR PACKAGE YOU SUBMITTED FOR THIS PERMIT.JUST TO
 LET YOU KNOW A HEAD OF TIME THATWE NEED FOR ENG
 REVIEW,STORM WATER QUALITY CALS, POLLUTION PREVENTION
 PLANS, CITY STANDARDS SHOWN ON DRAWINGS ETC, ETC.
 THEREFORE, WE ARE ASKING YOU TO INCLUDE THE FOLLOWING
 WHEN YOU SUBMIT CIVIL DRAWINGS FOR ENGINEERING REVIEW,
 SO WE CAN EXPEDITE OUR ENG REVIEW PROCESS.
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
  
 2. PLEASE SHOW ON CIVIL DRAWING THE SITE PLAN SHOWING
 STREETS/ROADS AROUND THE SITE WITH NORTH ARROW.
  
 3.PLEASE SHOW ON DRAWING ALL CITY STANDARDS NOTES FOR
 SIDEWALK, DRIVEWAY, APPROACH, PARKINGS, HANDICAP
 PARKINGS, DUMPSTER ENCLOSURE, YOU CAN GET A C D FROM
 1000, 45 STREET FOR ALL THESE CITY STANDARDS NOTES.
 PHONE# 494-1040
  
 4. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
  
 5. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD ,
 SIDEWALK ELEVATION MUST MEET FLOOD ZONE AREA, & 5,10,
 25, 100 YEAR FLOOD CRITERIATO DETERMINE THE FIRST
 FLOOR ELEVATION, PLEASE SHOW IN YOUR STORM WATER CALS
 THAT HOW DID YOU DETERMINE THE FIRST FLOOR
 ELEVATION??.
  
 6. PLEASE SHOW ON DRAWINGTHE SITE AREA, YOU ARE
 DEVELOPING FOR THIS PROJECT . PLEASE ALSO SHOW TOTAL
 PERVIOUS,& IMPERVIOUS AREA FOR THIS PROJECT,
 LAKE,SIDEWALK, PARKING,BUILDING AREA ETC. MAKE SURE
 THESE AREAS SHOWN ON DRAWINGS MUST MATCH WITH AND USED
 IN STORM WATER QUALITY CALCULATIONS.
  
 7. HOW DO YOU CONNECT TO THE STORM WATER PIPES IN YOUR
 SITE? ITS DETAILS.PLEASE SHOW ALL STORM WATER PIPES
 AROUND YOUR SITE SO, WE CANSEE THE LAYOUT OF STORM
 WATER PIPES FROM ALL OTHER STORM WATER PIPES. PLEASE
 SHOW DETAIL OF THE CONTROL STRUCTURESWITH
 ELEVATIONS, NOTCHES, BLEEDING ELEVATION, ETC ON
 DRAWINGS, CALCULATION FOR EXFILTRATION TRENCHES, PLEASE
 SHOW DRY DETENTION/WET DETENTION AREAS IN STORM WATER
 CALS.
  
 8. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN.
  
 9. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, & PLEASE
 ALSO PROVIDE A COPY OF GEOTECH REPORT & STORM WATER
 QUALITY CALCULATIONS TO 1000 45TH STREET ENGINEERING
 SERVICES FOR THEIR APPROVAL BEFORE WE ISSUE A PERMIT,
  
 10. PLEASE SHOW ON DRAWINGS THE POLLUTION PREVENTION
 DETAILS,CLOTHES USED FOR SILT ETC., PLANS SHOWING SILT
 FENCE AROUND THE SITE & CATCH BASINS.HEIGHT OF FENCE
 SHOULD BE HIGH ENOUGH PER FDEP TO STOP DUST &
 PARTICLES.
  
 11. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2007-09-07 Cont ID  
Sent By rchokshi Date 2007-09-07 Time 13:46 Rev Time 0.00
Received By rchokshi Date 2007-09-07 Time 13:45 Sent To  
Notes
2007-09-07 13:46:24***FAILED**** PLEASE PROVIDE THE FOLLOWING:
  
 WE HAVE NOT FOUND CIVIL DRAWINGS & ENG REVIEW INFO IN
 YOUR PACKAGE YOU SUBMITTED FOR THIS PERMIT.JUST TO
 LET YOU KNOW A HEAD OF TIME THATWE NEED FOR ENG
 REVIEWSTORM WATER CALS, POLLUTION PREVENTION PLANS,
 CITY STANDARDS SHOWN ON DRAWINGS ETC, ETC.THEREFORE,
 WE ARE ASKING YOU TO INCLUDE THE FOLLOWING WHEN YOU
 SUBMIT CIVIL DRAWINGS FOR ENGINEERING REVIEW, SO WE CAN
 EXPEDITE OUR ENG REVIEW PROCESS.
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
 2. PLEASE SHOW ON CIVIL DRAWING THE SITE PLAN SHOWING
 STREETS/ROADS AROUND THE SITE WITH NORTH ARROW.
 3.PLEASE SHOW ON DRAWING ALL CITY STANDARDS NOTES FOR
 SIDEWALK, DRIVEWAY, APPROACH, PARKINGS, HANDICAP
 PARKINGS, DUMPSTER ENCLOSURE, YOU CAN GET A C D FROM
 1000, 45 STREET FOR ALL THESE CITY STANDARDS NOTES.
 PHONE# 494-1040
 4. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
 5. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD ,
 SIDEWALK ELEVATION MUST MEET FLOOD ZONE AREA, & 5,10,
 25, 100 YEAR FLOOD CRITERIATO DETERMINE THE FIRST
 FLOOR ELEVATION, PLEASE SHOW IN YOUR STORM WATER CALS
 THAT HOW DID YOU DETERMINE THE FIRST FLOOR ELEVATION??.
  
 6. PLEASE SHOW ON DRAWINGTHE SITE AREA, YOU ARE
 DEVELOPING FOR THIS PROJECT . PLEASE ALSO SHOW TOTAL
 PERVIOUS,& IMPERVIOUS AREA FOR THIS PROJECT,
 LAKE,SIDEWALK, PARKING,BUILDING AREA ETC. MAKE SURE
 THESE AREAS SHOWN ON DRAWINGS MUST MATCH WITH AND USED
 IN STORM WATER QUALITY CALCULATIONS.
 7. HOW DO YOU CONNECT TO THE STORM WATER PIPES IN YOUR
 SITE? ITS DETAILS.PLEASE SHOW ALL STORM WATER PIPES
 AROUND YOUR SITE SO, WE CANSEE THE LAYOUT OF STORM
 WATER PIPES FROM ALL OTHER STORM WATER PIPES. PLEASE
 SHOW DETAIL OF THE CONTROL STRUCTURESWITH
 ELEVATIONS, NOTCHES, BLEEDING ELEVATION, ETC ON
 DRAWINGS, CALCULATION FOR EXFILTRATION TRENCHES, PLEASE
 SHOW DRY DETENTION/WET DETENTION AREAS IN STORM WATER
 CALS.
 8. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN.
 9. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, &STORM
 WATER QUALITY CALCULATIONS,
 10. PLEASE SHOW ON DRAWINGS THE POLLUTION PREVENTION
 DETAILS,CLOTHES USED FOR SILT ETC., PLANS SHOWING SILT
 FENCE AROUND THE SITE & CATCH BASINS.HEIGHT OF FENCE
 SHOULD BE HIGH ENOUGH PER FDEP TO STOP DUST &
 PARTICLES.
 11. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-05-27 Cont ID  
Sent By mawillia Date 2008-05-27 Time 14:26 Rev Time 0.00
Received By mawillia Date 2008-05-27 Time 13:29 Sent To  
Notes
2008-05-27 14:26:22*****PROVISO*****
  
 WITH THE EXCEPTION THE FOLLOWING COMMENT FROM THE
 PREVIOUS FIRE PLAN REVIEWS, ALL OTHERS HAVE BEEN
 ADDRESSED:
  
 3. DISPLAY THE ADDRESS NUMBER ON THE APPROPIATE
 EXTERIOR ELEVATION WHICH FRONTS MERRY PLACE. AS PER
 WEST PALM BEACH CODE, THOSE NUMBERS SHALL BE NO LESS
 THAN 6" IN HEIGHT AND NO LESS THAN 1" IN STROKE. IN
 ADDITION, DISPLAY THE INDIVIDUAL DWELLING UNIT NUMBER
 FOR THIS PROJECT SITE. AS PER WEST PALM BEACH CODE,
 UNIT NUMBERS SHALL BE NO LESS THAN 3" IN HEIGHT AND NO
 LESS THAN 1" IN STROKE. BASED UPON FIELD INSPECTIONS
 CONDUCTED AT THE MERRY PLACE PROJECT BY THIS WRITER:
  
 A) A SINGLE ADDRESS NUMBER BE CENTERED ON THE BUILDING,
 OR HAVE THE ADDRESS AT BOTH ENDS OF THE EXTERIOR
 ELEVATION WHICH FRONTS MERRY PLACE.
 B) TENANT UNIT NUMBERS SHALL BE ON THE STRUCTURE OF THE
 BUILDING, NOT THE DOOR.
  
  
  
 THE APPROPIATE PLAN SHEETS TO BE FIRE-STAMPED WHEN THE
 OTHER REVIEWERS COMMENTS AS WELL AS THE ABOVE COMMENT
 HAVE BEEN SATISFIED.
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-11-05 Cont ID  
Sent By mawillia Date 2007-11-05 Time 10:46 Rev Time 0.00
Received By mawillia Date 2007-11-05 Time 09:31 Sent To  
Notes
2007-11-05 10:02:46*****DENIED*****
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2. CONSTRUCTION OPERATIONS SHALL NOT INTERFERE OR
 HINDER EMERGENCY ACCESS TO THE SAID PROPERTY OR
 VICINITY THEREOF.
  
 3. DISPLAY THE ADDRESS NUMBER ON THE APPROPIATE
 EXTERIOR ELEVATION WHICH FRONTS MERRY PLACE. AS PER
 WEST PALM BEACH CODE, THOSE NUMBERS SHALL BE NO LESS
 THAN 6" IN HEIGHT AND NO LESS THAN 1" IN STROKE. IN
 ADDITION, DISPLAY THE INDIVIDUAL DWELLING UNIT NUMBER
 FOR THIS PROJECT SITE. AS PER WEST PALM BEACH CODE,
 UNIT NUMBERS SHALL BE NO LESS THAN 3" IN HEIGHT AND NO
 LESS THAN 1" IN STROKE.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2008-05-15 Cont ID  
Sent By kstevens Date 2008-05-09 Time 18:34 Rev Time 0.00
Received By kstevens Date 2008-05-09 Time 18:34 Sent To  
Notes
2008-05-09 18:36:46SEPARATE GAS PERMIT REQUIRED.--PLANS AND OTHER
 REQUIREMENTS TO BE SUBMITTED AT TIME OF APPLICATION.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-05-09 Cont ID  
Sent By kstevens Date 2007-09-13 Time 16:26 Rev Time 0.00
Received By kstevens Date 2007-09-13 Time 16:26 Sent To  
Notes
2008-05-09 16:27:48DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 A. THE FOLLOWING REQUIREMENTS FOR THE REQUIRED GAS
 PERMIT SHALL BE SUBMITTED:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 5. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 6. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 7. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 8. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-04-30 Cont ID  
Sent By adarroug Date 2008-04-30 Time 15:37 Rev Time 0.00
Received By adarroug Date 2008-04-30 Time 15:37 Sent To  
Notes
2008-04-30 15:37:13TO "COMM" BD#44--PLANS ON RACK"LARGE FOLDED
 PLANS"--EXPEDITED--

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-11-05 Cont ID  
Sent By mawillia Date 2007-11-05 Time 09:31 Rev Time 0.00
Received By mawillia Date 2007-08-24 Time 10:32 Sent To  
Notes
2007-08-27 13:49:33TO "COMM" BD#26/PLANS ON RACK--8 ROLLS AND 4
 APPL'S---EXPEDITED PERMIT---
2007-08-24 10:33:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-05-05 Cont ID  
Sent By tgordon Date 2008-05-05 Time 16:38 Rev Time 1.00
Received By tgordon Date 2008-05-05 Time 16:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-09-10 Cont ID  
Sent By tgordon Date 2007-09-10 Time 14:15 Rev Time 0.30
Received By tgordon Date 2007-09-10 Time 14:15 Sent To  
Notes
2007-09-10 14:17:00PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA
 ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS).
  
 *** DENIED ***
  
 1) SEE ELECTRICAL REVIEW NOTE #1 REGARDING SIGNATURE ON
 ENERGY CALCULATIONS, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-05-15 Cont ID  
Sent By kstevens Date 2008-05-12 Time 14:49 Rev Time 0.00
Received By kstevens Date 2008-05-09 Time 18:34 Sent To  
Notes
2008-05-12 14:59:28PASSED PROVISO--RISER 4S REQUIRES A 3" STACK PER
 SECTION 406.3.

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-09-13 Cont ID  
Sent By kstevens Date 2007-09-13 Time 18:23 Rev Time 0.00
Received By kstevens Date 2007-09-13 Time 18:23 Sent To  
Notes
2007-09-13 18:25:47DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 A. THE FOLLOWING REQUIREMENTS FOR THE REQUIRED GAS
 PERMIT SHALL BE SUBMITTED:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 5. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 6. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 7. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 8. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2008-05-07 Cont ID  
Sent By ajones Date 2008-05-07 Time 11:38 Rev Time 0.00
Received By ajones Date 2008-05-07 Time 11:38 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2007-09-04 Cont ID  
Sent By ajones Date 2007-09-04 Time 18:02 Rev Time 0.00
Received By ajones Date 2007-09-04 Time 18:02 Sent To  
Notes
***NONE***