Plan Review Details - Permit 07080669
Plan Review Stops For Permit 07080669
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2008-07-02 Cont ID  
Sent By jwitmer Date 2008-07-02 Time 11:42 Rev Time 0.77
Received By jwitmer Date 2008-07-02 Time 11:42 Sent To  
Notes
2008-07-02 11:43:19BUILDING PLAN REVIEW
 PERMIT: 07080669
 ADD: 6215 S DIXIE HWY
 CONT: MONARCH
 TEL: (561)767-7176
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISIONREVIEW
 ACTION: DENIED
  
 1) WORKING OUT OF THE SCOPE OF LICENSURE. FLORIDA STATE
 STATUTE 489.113(2)(G) NO GENERAL, BUILDINGOR
 RESIDENTIAL CONTRACTOR CERTIFIFIED AFTER 12-31-1973
 SHALL ACT AS,HOLD HIMSELF OUT TO BE, OR ADVERTISE
 HIMSELF TO BE A ROOFING CONTRACTOR UNLESHE IS CERTIFIED
 OR REGISTERED AS A ROOFING CONTRACTOR. PLEASE SEE THE
 COPY OF YOUR PERMIT APPLICATION, NO ROOFING CONTRACTOR
 WAS REGISTEERED WITH THE CITY AT TIME OF PERMIT
 APPLICATION DATE. THE ROOFING SUBPERMIT WAS STRUCK
 REQUIURING A SEPERATE PERMIT, FEES & REVIEW.
  
 NOTE THE ASPHALT SHINGLE REPORT SUBMITTED UNDER THE
 ORIGINAL PERMIT WAS A APPROVAL UNDER THEFLORIDA
 SYSTEM FL 5444-R0TRINITY/ ERD REPORT. IF NEW REPORTS
 ARE GOING TO BE SUBMITTED UNDER THE SEPERATE ROOFING
 PERMIT THEY MUST BE REVIEWED BY THE DESIGNER OF
 RECORD.
  
  
 WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-06-03 Cont ID  
Sent By jwitmer Date 2008-06-03 Time 15:36 Rev Time 2.77
Received By jwitmer Date 2008-06-03 Time 15:36 Sent To PC
Notes
2008-06-03 15:39:17SEE SHEET 7:
 BUILDING PROVISO 1203.2 ATTIC SPACES THE NET FREE
 VENTILATING AREA SHALL NOT BE LESS THAN 1 / 150 OF THE
 AREA OF THE SPACE VENTILATED, WITH 50 PERCENT OF THE
 REQUIRED VENTILATING AREA PROVIDED BY VENTILATORS
 LOCATED IN THE UPPER PORTION OF THE SPACE TO BE
 VENTILATED AT LEAST 3 FEET (914 MM) ABOVE EAVE OR
 CORNICE VENTS WITH THE BALANCE OF THE REQUIRED
 VENTILATION PROVIDED BY EAVE OR CORNICE VENTS.
  
 BUILDING PROVISO 1209.2 AN OPENING NOT LESS THAN 20
 INCHES BY 30 INCHES (559 MM BY 762 MM) SHALL BE
 PROVIDED TO ANY ATTIC AREA HAVING A CLEAR HEIGHT OF
 OVER 30 INCHES (762 MM). A 30-INCH (762 MM) MINIMUM
 CLEAR HEADROOM IN THE ATTIC SPACE SHALL BE PROVIDED AT
 OR ABOVE THE ACCESS OPENING.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-03-21 Cont ID  
Sent By lmartine Date 2008-03-21 Time 14:24 Rev Time 0.00
Received By lmartine Date 2008-03-21 Time 14:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-02-06 Cont ID  
Sent By jwitmer Date 2008-02-06 Time 12:02 Rev Time 2.22
Received By jwitmer Date 2008-02-06 Time 12:02 Sent To PC
Notes
2008-02-06 12:29:48BUILDING PLAN REVIEW
 PERMIT: 07080669
 ADD: 6215 S DIXIE HWY
 CONT: MONARCH
 TEL: (561)767-7176
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2007 SUPPLEMENTS.
  
 2) THE PLANS, SHEET # 7 THE FOLLOWING INFORMATION IS
 MISSING OR INCORRECT:
  
 A) THE ROOF SHEATHING BEING NAILED DOWN WITH 8D X 1
 1/2" RING SHANK NAILS, THE LENGTH OF THE 8D IS 2 1/2"
 NOTA 1 1/2". PLEASE SEE FASTENER PENETRATION TABLES
 FROM USP OR SIMPSON FOR
 FULL SHEAR LOAD VALUES.
  
 B)PLANS DO NOT INDICATE THE ATTIC VENTING REQUIRED
 ABOVE THE EAVE HEIGHT. THE NET FREE VENTILATING AREA
 SHALL NOT BE LESS THAN 1 / 150 OF THE AREA OF THE SPACE
 VENTILATED, WITH 50
 PERCENT OF THE REQUIRED VENTILATING AREA
 PROVIDED BY VENTILATORS LOCATED IN THE UPPER PORTION OF
 THE SPACE TO BE VENTILATED AT LEAST 3 FEET (914 MM)
 ABOVE EAVE OR CORNICE VENTS WITH
 THE BALANCE OF THE REQUIRED VENTILATION
 PROVIDED BY EAVE OR CORNICE VENTS.
  
 C) PRODUCT APPROVALS: MISSING REPORTS ARE ON THE
 TRUSS ANCHOR AND OR TRUSS STRAPS, RULE 9B-72(31)(G)
 TRUSS ANCHORS.WILL ALSO REQUIRE FLORIDA COVER SHEET AND
 THE DESIGN PROFESSIONALS
 REVIEW AND APPROVAL.
  
 D) PLANS DO NOT PROVIDE WHAT THE HEADROOM WWITHIN THE
 NEW ATTIC SPACE WILL BE WITHIN THE TRUSSED IN AREA,
 PLEASE DEMONSTRATE COMPLIANCE WITH 1209.2 ATTIC
 SPACES.
  
 3) TRUSS DRAWINGS PLEASE REVIEW FAC 61G15-23.002 AND
 61G15-31.003 SIGNING AND SEALING REQUIRED FOR TRUSS
 DRAWINGS.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-24 Cont ID  
Sent By jjohnsto Date 2007-09-24 Time 14:20 Rev Time 6.20
Received By jjohnsto Date 2007-09-24 Time 08:00 Sent To  
Notes
2007-09-24 14:19:39CONSTRUCTION SERVICES DEPARTMENT
 200 SECOND STREET, 3RD FLOOR, WEST PALM BEACH,
 FLORIDA33401
 TEL:561-805-6713FAX:
 561-805-6731
  
  
 JAMES JOHNSTON, PERMIT NO 07080669 BUILDING
 PLAN EXAMINERII
 PROJECT MEDICAL BUILDING
 E-MAIL:JJOHNSTON @WPB.ORG ADDRESS 6215 S. DIXIE
 HIGHWAY
  CONTRACTOR MONARCH CONSTRUCTION OF S. F.
  DATE SEPTEMBER 21, 2007
  
 STRUCTURALPLANREVIEW
 CORRECTION SUBMITTAL
 WHEN RE-SUBMITTINGCORRECTED PLANS FOR PERMITTING,
 PLEASEREMOVE AND REPLACE ANY SHEETS AS NECESSARY.
 INCLUDE A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER WITH A DESCRIPTION OF THE
 REVISION MADE. IDENTIFY THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND AND INCLUDE THE OLD
 SHEETS IN THE RE-SUBMITTAL PACKAGE FOR THE PLAN
 REVIEWER?S REFERENCE.
 THIS SHALL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
 COMMENT-FOR YOUR INFORMATION
  
 RETAIN ORIGINAL PLANS
 ONE SET OF ORIGINAL PLANS AND ONE SET OF REVISIONS WILL
 BE RETAINED FOR THE POSSIBILITY OF FORWARDING TO THE
 STATE BOARD OF ENGINEERS. REMOVE ALL OLD (VOID) SHEETS
 AND RETAIN ONE SET.
 COMMENT-FOR YOUR INFORMATION
  
  
 F.S.713.13NOTICE OF COMMENCEMENT
 FILE NOTICE WITH THE CLERK OF COURT RECORDING DIVISION.
 IF THE WORK DESCRIBED IN THE NOTICE IS NOT COMMENCED
 WITHIN 90 DAYS OF FILING THE NOTICE WILL BECOME NULL
 AND VOID. SUBMIT THE NOTICE AT THE TIME OF PERMIT
 ISSUANCE AND POST A COPY AT THE JOB SITE BEFORE THE
 FIRST INSPECTION.
 COMMENT-FOR YOUR INFORMATION
  
  
 IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT MAY BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY.
 THE PERMITTED SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 PALM BEACH COUNTY ASSESSMENT
 PALM BEACH COUNTY IMPACT FEE ASSESSMENT HAS MOVED TO:
 2300 N JOG ROAD, SUITE 2 WPB 33411
 COMMENT-FOR YOUR INFORMATION
  
 WINDOWS / DOORS PRODUCT APPROVALS
 WPB ADMINISTRATIVE CODE 106.3 REGULATED BY DCA RULE
 9B-72FLORIDA PRODUCT APPROVAL
 SUBMIT TWO COPIES OF EACH APPROVAL WITH FLORIDA PRODUCT
 APPROVAL COVER SHEET THE ARCHITECT?S / ENGINEER?S
 SIGNATURE AS APPLICABLE, STATING ?TO THE BEST OF THEIR
 KNOWLEDGE THE PRODUCT APPROVAL COMPLIES WITH THE PLANS
 AND SPECIFICATIONS.SEE:WEB SITE
 WWW.FLORIDABUILDING.COM
 NOTE: SEE DIVISION FACTOR TO BE USED IN DESIGN PRESSURE
 BY LEGACYFPA
 COMMENT-SUBMIT TWO COPIES OF EACH PRODUCT APPROVAL
 MIAMI-DADE AND FLORIDA PRODUCT APPROVAL
  
  
 1. PRODUCT APPROVAL
 LAWSON INDUSTRIES PRODUCT APPROVALNOA 06-0117.02
 COMMENT-EXPIRED AUGUST 22,2007
  
 2. PRODUCT APPROVALS
 COMMENT-MIAMI DADE PRODUCT APPROVALS MISSING FLORIDA
 PRODUCT APPROVAL SHEET
  
 3. NORDIC FLAT ROOF TILE
 COMMENT-IDENTIFY WHICH SYSTEM AND FASTENERS YOU ARE
 USING FROM TABLES PROVIDED IN THE PRODUCT APPROVAL
  
 4. POLYPROAH160
 COMMENT-IDENTIFY WHICH SYSTEM AND FASTENERS YOU ARE
 USING FROM TABLES PROVIDED IN THE PRODUCT APPROVAL
  
 5. PRODUCT APPROVAL
 LAWSON INDUSTRIES LA PORTE OUT SWING FRENCH DOOR
 COMMENT-IDENTIFY UNIT AND COMPONENTS TO BE USED
  
 6. PRODUCT APPROVAL
 LAWSON INDUSTRIES FIXED WINDOW
 COMMENT-IDENTIFY UNIT AND COMPONENTS TO BE USED
  
 7. PRODUCT APPROVAL
 LAWSON INDUSTRIES SINGLE HUNG WINDOW
 COMMENT-IDENTIFY UNIT AND COMPONENTS TO BE USED
  
 8. SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE
 FOLLOWING
 FIXED GLASS
 WINDOWS
 MULLION TUBES
 EXTERIORHOLLOW METAL DOORS
 EXTERIOR DOORS-OTHER
 ROOF COVERING SYSTEMS
  
 9. PLEASE PROVIDE ALL NOTES ON COVER SHEET 1
 FBC2004 BUILDING W/ 2005 AND 6 REVISIONS
 FBC2004 EXISTING BUILDING
 LEVEL OF ALTERATION
 TYPE OF CONSTRUCTION / SPRINKLED / UN-SPRINKLED WIND
 SPEED AND EXPOSURE
 WIND IMPORTANCE FACTOR
 TYPE OF OCCUPANCY
 OCCUPANT LOAD
 GROSS LOAD
 NET LOAD
  
 10. DOOR NO. 8 NOT NOTED ON DEMOLITION PLAN COMMENT-
 IDENTIFY POURED CELLS FOR THIS DOOR
  
 11. 704.5 FIRE-RESISTANCE RATINGS.
 EXTERIOR WALLS SHALL BE FIRE-RESISTANCE RATED IN
 ACCORDANCE WITH TABLES 601 AND 602 . THE
 FIRE-RESISTANCE RATING OF EXTERIOR WALLS WITH A FIRE
 SEPARATION DISTANCE OF GREATER THAN 5 FEET (1524 MM)
 SHALL BE RATED FOR EXPOSURE TO FIRE FROM THE INSIDE.
 THE FIRE-RESISTANCE RATING OF EXTERIOR WALLS WITH A
 FIRE SEPARATION DISTANCE OF 5 FEET (1524 MM) OR LESS
 SHALL BE RATED FOR EXPOSURE TO FIRE FROM BOTH SIDES.
 COMMENT-ON SHEET 1 SHOW ADJACENT BUILDINGS AND PUBLIC
 ROADS TO DETERMINE FIRE RESISTANCE RATINGS OF OPENINGS
 IN THE EXTERIOR TWO HOUR WALL.SEE TABLE704.8TO
 DETERMINE PROTECTION OF OPENINGS
  
  
  
 12. PROVIDE TRUSS FRAMING PLAN WITH SHEATHING AND
 ANCHORAGE. INFORMATION PROVIDED HEREIN
 FBC2304.9.1 FASTENER REQUIREMENTS.
 CONNECTIONS FOR WOOD MEMBERS SHALL BE DESIGNED IN
 ACCORDANCE WITH THE APPROPRIATE METHODOLOGY IN SECTION
 2301.2 . THE NUMBER AND SIZE OF NAILS CONNECTING WOOD
 MEMBERS SHALL NOT BE LESS THAN THAT SET FORTH IN TABLE
 2304.9.1 .
 FBC2304.7 FLOOR AND ROOF SHEATHING
 FBC2304.7.2 STRUCTURAL ROOF SHEATHING.
 COMMENT-STRUCTURAL ROOF SHEATHING SHALL BE DESIGNED
 IN ACCORDANCE WITH THE GENERAL PROVISIONS OF THIS CODE
 AND THE SPECIAL PROVISIONS IN THIS SECTION. USE RATING
 INDICATED IN TABLE.EX.5/8 PANELS EQUAL 19/32
 RATING SEE TABLES IN THIS SECTION.
  
 13. FBC EXISTING 601.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE .
  (A)13-400.0 GENERAL.
 THE PROVISIONS OF THIS CHAPTER APPLY TO ALL NEW
 COMMERCIAL OCCUPANCY BUILDINGS, ADDITIONS TO EXISTING
 COMMERCIAL OCCUPANCY BUILDINGS, AND MULTIPLE-FAMILY
 RESIDENTIAL BUILDINGS OVER THREE STORIES IN HEIGHT.
 BUILDING TYPE CLASSIFICATIONS SHALL BE THOSE DEFINED IN
 SUBCHAPTER 13-2 OF THIS CODE UNDER ?OCCUPANCY
 CLASSIFICATION.? THIS SUBCHAPTER PROVIDES THREE METHODS
 BY WHICH COMMERCIAL BUILDINGS MAY BE BROUGHT INTO
 COMPLIANCE WITH THIS CODE.
 COMMENT-NEW CONSTRUCTION FOR WALLS, ROOF, INTERIOR
 MUST COMPLY WITH FBC BUILDING CHAPTER 13-400.0
  
 14. SHEET 7SECTION 2-7
 COMMENT-IDENTIFY NELSON STUD EMBEDMENT INTO BEAM
  
 15. SHEET7SECTION 1-7
 COMMENT - DEFINE R VALUE FOR EXTERIOR WALL AND ATTIC
 INSULATION
  
 16. SHEET 7 CONCRETE TO BE USED FOR THIS PROJECT
 COMMENTS - IDENTIFY STRENGTH OF CONCRETE FOR FOOTINGS,
 BEAMS, COLUMNS, FILLED CELLS, MASONRY UNITS
  
 FBC11-4FLORIDA ACCESSIBILITY CODE
  
 1A. FBC 11-4.8 RAMPS
 COMMENT-RAMP DESIGN REQUIRED WITH ALL ELEMENTS PER
 THIS CHAPTER
 SEE FIGURE 17 EXAMPLES OF EDGE PROTECTION AND HANDRAIL
 EXTENSIONS
  
 2A. FBC 11-4.9.4STAIRS
 COMMENT-DEFINE HANDRAIL AND LOCATION ON SHEET 6.
 IDENTIFY 36? FROM TREAD TO RAILING FOR FIELD USE SEE
 FIGURE 19 STAIR HANDRAILS
  
 3A. FBC 11-4.13.4 DOUBLE-LEAF DOORWAYS.( DOOR NO.1
 &2ON PLAN )
 COMMENT-IF DOORWAYS HAVE TWO INDEPENDENTLY OPERATED
 DOOR LEAVES, THEN AT LEAST ONE LEAF SHALL MEET THE
 SPECIFICATIONS IN SECTION 11-4.13.5 AND SECTION
 11-4.13.6 . THAT LEAF SHALL BE AN ACTIVE LEAF.
  
 (1) 11-4.13.5 CLEAR WIDTH.
 DOORWAYS SHALL HAVE A MINIMUM CLEAR OPENING OF 32
 INCHES (813 MM) WITH THE DOOR OPEN 90 DEGREES, MEASURED
 BETWEEN THE FACE OF THE DOOR AND THE OPPOSITE STOP SEE
 FIGURE 24 (A), FIGURE 24 (B), FIGURE
  
 5A. TOILET ROOM NO. 1
 COMMENT-IDENTIFY PASS THRU WINDOW HEIGHT ABOVE
 FINISHED FLOOR

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-03-27 Cont ID  
Sent By dpalmer Date 2008-03-27 Time 13:03 Rev Time 0.00
Received By dpalmer Date 2008-03-27 Time 13:03 Sent To PC
Notes
2008-03-27 13:03:50INSERTED NEW SHEETS INTO SETS.
 NEW PLUMBING SHEETS STAMPED.
 VOIDED OLD SHEETS.
 ELEC SHEETS ORIGINALLY STAMPED AND DATED REVIEWED
 1/17/08 ARE VOID AND NOT VALID.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-03-05 Cont ID  
Sent By dpalmer Date 2008-03-05 Time 20:08 Rev Time 0.00
Received By dpalmer Date 2008-03-05 Time 20:07 Sent To  
Notes
2008-03-05 20:14:25** DENIEDREVIEW **
  
 ** PLEASE SEE SOME ITEMS WHICH WERE OK ON PREVIOUS
 REVIEW HAVE NOW BEEN CHANGED AND DID NOT COORDINATE AND
 REVISE OTHER SHEETS. PLEASE SEE THE FOLLOWING COMMENTS
  
 1) NOTE:PLEASE SEE THE SCOPE OF WORK HAS CHANGED AND
 LIGHTING FIXTURE TYPES AND COUNTS HAVE CHANGED YET THE
 LIGHTING PERFORMANCE CALCULATIONS WERE NOT REVISED.
 PLEASE SEE FOR EXAMPLE ONLY 3-TYPE A FIXTURES SHOWN IN
 LP CALCULATIONS.
 PLEASE SEE THE A FIXTURES ARE NOW 3-32 W ?
 PLEASE SEE 13-415.2, 13-415.2.ABC.1.1, .1.2 AND .1.3.
  
 2) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH GAVE PROVISO
 FOR SOME ROOMS WHICH DO REQUIRED AUTOMATED LIGHTING
 CONTROLS PER 13-415.1.ABC.1.2 EVEN IF THE BUILDING IS
 UNDER 5K SQFT. PLEASE SEE ROOMS IN SECTION GIVEN WILL
 REQUIRE OCCUPANCY SENSORS.
 ** THIS WAS CONFIRMED WITH THE FLORIDA BUILDING
 COMMISSION/ DEPARTMENT OF COMMUNITY AFFAIRS.
  
 3) NOTE: ** PLEASE KNOW ANY AREAS IN WHICH EXISTING
 WIRING IS EXPOSED, DOES NOT MEET CODE, UNSAFE, WATER
 DAMAGED ETC WILL REQUIRE RE-WIRE UP TO CURRENT CODE.
 PLEASE SEE MOST OF THE AREAS ARE SHOWN AS NEW TO MEET
 CURRENT CODES, HOWEVER MANY ARE SHOWN AS EXISTING.
 AREAS WHICH ARE NOT SAFE ETC WILL BE REQUIRED TO BE
 BROUGHT UP TO CODE.
 ** THIS IS GIVEN FOR INFORMATIONAL PURPOSE.
 BASED ON THE PICTURES AND CONDITIONS AT SITE
 REVIEWER/OFFICE IS GIVING NOTICE FOR AREAS OF CONCERN
 WHICH ARE NOT MENTIONED ON PLANS.
 ANY ITEMS WHICH MAY BE IN QUESTION FOR LIFE SAFETY/
 PROPERTY HAZARD WHICH ARE KNOWN TO CONTRACTOR OR DESIGN
 PROFESSIONALS NEEDS TO BE ADDRESSED ON PLANS AND IS THE
 RESPONSIBILITY OF SUCH INDIVIDUALS.
 FS 481, 471, 489
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-01-17 Cont ID  
Sent By dpalmer Date 2008-01-17 Time 17:11 Rev Time 0.00
Received By dpalmer Date 2008-01-17 Time 17:11 Sent To  
Notes
2008-01-17 17:12:00** PROVISO **
  
 1) NOTE: PLEASE SEE THE LOUNGE AND TRAINING ROOMS WILL
 REQUIRE LIGHTING CONTROLS WHICH WILL AUTOMATICALLY TURN
 OFF LIGHTING WITHIN 30MINS OF THE OCCUPANT LEAVING THE
 SPACE.
 PLEASE SEE 13-415.1.ABC.1.2
 THIS WAS CONFIRMED WITH THE FLORIDA BUILDING COMMISSION
 SINCE THE LAST REVIEW. THESE AUTOMATED LIGHTING
 CONTROLS ARE REQUIRED EVEN IN BUILDINGS LESS THAN 5K SQ
 FT FOR THESE ROOMS AS MENTIONED ABOVE.
  
 ** ELECTRICAL PLANS ARE STAMPED AND DO NOT NEED TO BE
 REVISED UNTIL BEFORE ROUGH ELECTRICAL INSPECTION.
 REVISED PLANS ARE TO BE ON-SITE FOR ELECTRICAL
 INSPECTOR.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PAM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-09-16 Cont ID  
Sent By dpalmer Date 2007-09-16 Time 12:15 Rev Time 0.00
Received By dpalmer Date 2007-09-16 Time 11:26 Sent To  
Notes
2007-09-16 12:16:062007-09-16 12:16:06
  
 ** DENIED **
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE SEE ANY CODES RELEVANT FROM OTHER TRADES
 WHICH MAY BE REQUESTED.
  
 2) NOTE: PLEASE SEE MECHANICAL/BUILDING REVIEW COMMENTS
 FOR VALUE OF PROJECT AND SCOPE OF WORK WHICH MAY
 REQUIRE SOME ITEMS TO MEET CHAPTER 13 FOR OTHER THAN
 ELECTRICAL.
 THE VALUE EXCEEDS THE 30% AS STATED FOR RENOVATIONS.
 THIS IS FOR INFORMATION ONLY, PLEASE SEE NEXT COMMENT
 FOR ELECTRICAL.
  
 3) NOTE: PLEASE COMPLETE THE FIXTURE LEGEND AS
 SUBMITTED INCLUDING FIXTURES TO BE OWNER SELECTED. THE
 ONLY ACCURATE WAY TO FIGURE THE CALCULATIONS FOR
 LIGHTING PERFORMANCE IS TO PROVIDE ALL INFORMATION.
 (THIS CAN ALWAYS BE REVISED IF AN OWNER WOULD LIKE TO
 CHANGE A FIXTURE TYPE AT A LATER DATE).
 PLEASE BE SURE TO PLACE ALL FIXTURE DESIGNATIONS ON
 PLANS AND CORRELATE WITH THE LEGEND.
 PLEASE SEE FOR EXAMPLE THERE IS A FIXTURE
 (HAND-WRITTEN) ON PLANS WHICH CALL FOR A 40W
 FLUORESCENT HOWEVER THIS IS NOT ON THE LEGEND? PLEASE
 SEE 13-415.2, 13-415.1.B, 13-415.1.C. PLEASE COMPLETE.
  
 4) NOTE: PLEASE LABEL ALL ROOM AND AREA DESIGNATIONS ON
 PLANS. THERE ARE SOME ITEMS WHICH NEED TO DETERMINED
 CODE COMPLIANCE FOR EXAMPLE AS X-RAY ROOMS,
 EXAM/PATIENT CARE ROOMS WHICH CAN NOT BE DETERMINED AT
 THIS TIME.
 FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION.
  
 5) NOTE: PLEASE BE SURE THE PANEL SCHEDULE AND
 CIRCUITING CORRELATE WITH ALL ROOMS AND AREAS IN WHICH
 THEY FEED. PLEASE SEE NEC 408.4 WHICH REQUIRES ALL
 CIRCUITING TO BE SPECIFIC TO ROOMS AND AREAS IN WHICH
 THEY FEED. EXAMPLE: EXAM RM #3 RECEPTS,LIGHTING RM
 102, 105 ETC.
 PLEASE SEE THE FOLLOWING TEXT IS TAKEN FROM THE NEC
 COMMENTARY.
  
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 6) NOTE: PLEASE INCLUDE NOTES FOR REDUNDANT GROUNDING
 AS REQUIRED FOR ALL PATIENT CARE AREAS AS DEFINED UNDER
 NEC 517 AND 517.13 AND 517.17.
 PLEASE ADJUST PLANS.
  
 7) NOTE: PLEASE VERIFY AND INDICATE NEW OR EXISTING
 DISCONNECTS FOR A/C EQUIPMENT PER 440.11
 PLEASE VERIFY NEW OR EXISTING GFI RECEPTACLE(S) FOR A/C
 EQUIPMENT. 210.63,210.8B
 ** IT IS KNOWN THAT PLANS CALL FOR A/C WORK TO BE DONE
 BY OTHERS HOWEVER DUE TO THE EXTEND OF THE SCOPE OF
 WORK AND LEVEL OF ALTERATION FOR THE FBC EXISTING
 BUILDING CODE, THESE SHOULD BE VERIFIED AND INDICATED
 AS THE EXISTING MAY NOT MEET CODE OR BE SAFE. PLEASE
 KNOW THIS CAN BE GONE OVER ON PHONE IF NEEDED FOR BEST
 POSSIBLE WAY TO INDICATE.
  
 8) NOTE: PLEASE VERIFY NEW OR EXISTING REQUIRED SIGN
 CIRCUIT PER 600.5.
 PLEASE ADJUST LOAD CALCULATIONS.
  
 9) NOTE: PLEASE SEE THE LOAD CALCULATIONS AS SUBMITTED
 ARE NOT COMPLETE AT THIS TIME.
 PLEASE SEE 220.12,220.14,220.42,220.44 ETC
 PLEASE SEE THAT ANY CONTINUOUS LOADS ARE TO BE SHOWN AT
 125%.
 215.3, 230.42.
 PLEASE SEE 422.13 OF THE 2005 NEC AS THE LOAD FOR WATER
 HEATERS ARE NOW CONSIDERED CONTINUOUS LOADS AND NEED TO
 BE SHOWN AT 125%.
 PLEASE ADJUST.
  
 10) NOTE: PLEASE CLARIFY NOTE #1 ON ELECTRICAL LIGHTING
 PLANS WHICH STATES LIGHTING DEVICES FOR SENSOR TYPE,
 BUT THE NOTE COULD NOT BE LOCATED ON PLANS AND FOR THE
 INTENT OF DESIGN WHICH IS BEING PROPOSED.
  
 11) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS.
 PLEASE SEE FOR EXAMPLE THERE ARE SEVERAL EMERGENCY AND
 EXIT LIGHTS WHICH ARE SHOWN WITH OUT CIRCUITING. PLEASE
 SEE 700.12F AS THE FIXTURES ARE REQUIRED TO BE
 CIRCUITED TO THE OTHER BRANCH CIRCUITS FOR NORMAL
 LIGHTING IN ANY ONE AREA.
  
 12) NOTE: PLEASE SEE NFPA-101 2003 7.8 AND 7.9 AS
 BATTERY BACK FIXTURE OF SOME TYPE FOR STAIR AREA
 LEADING TO THE PUBLIC RIGHT OF WAY IS REQUIRED. PLEASE
 KNOW THE LEVEL UNDER NORMAL IS 10FT CANDLES AND 1FT
 CANDLE UNDER EMERGENCY. 7.8.1.3, 7.9.2.2 PLEASE SEE FAC
 61G15-33.004
  
 13) NOTE: PLEASE KNOW THAT NO HAND-DRAWN CHANGES ARE
 PERMITTED TO PLANS BY PEN OR PENCIL.
 PLEASE BE SURE ANY CHANGES ARE DONE BY THE DESIGNER OF
 RECORD.
 FS 471.025, 481.221
  
 14) NOTE: PLEASE SHOW LOCATION OF THE SERVICE AS THIS
 IS NOT BEING SHOWN ON BUILDING ??
 IS THE SERVICE LOCATED ON BUILDING?
 NEED TO VERIFY 230.70,230.71,230.72,230.76,230.79,
 225.31-225.39
 FBC 106.3.5.1.2
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
  
 *** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS
 OR COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE.
 IF THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY
 WAY, NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR,
 PLEASE DO NOT HESITATE IN CONTACTING THIS OFFICE AND
 THIS REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-03-14 Cont ID  
Sent By mwennerg Date 2008-03-14 Time 14:48 Rev Time 0.00
Received By mwennerg Date 2008-03-14 Time 14:48 Sent To  
Notes
2008-03-14 14:49:20PLANS APPROVED BY B/C CARSILLO ON 10/23/07 AND STAMPED
 ON THIS DATE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2007-10-23 Cont ID  
Sent By mcarsill Date 2007-10-23 Time 10:09 Rev Time 0.00
Received By mcarsill Date 2007-10-23 Time 09:54 Sent To  
Notes
2007-10-23 10:09:111. DEMOLITION, RENOVATION, AND CONSTRUCTION TO COMPLY
 WITH NFPA 241.
  
 2. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY.
  
 3. HANDRAIL (S) SHALL MEET THE PRESCRIPTIVE STRENGTH
 REQUIREMENTS UNDER THE NECESSARY CODES.
  
 4. BUILDING ADDRESS DISPLAYED ON PAGE 4 SHALL BE AT
 LEAST 1" WIDE.
  
 5. FIRE EXTINGUISHERS DISPLAYED ON PLANS SHALL BE
 CURRENTLY SERVICE TAGGED.
  
 6. INTERIOR FINISH CLASSIFICATIONS FOR WALLS AND
 CEILINGS SHALL MEET MINIMUM CODE REQUIREMENTS.
  
 APPROVED PROVISO
  
  
 MIKE CARSILLO, BATTALION CHIEF
 804-4709 PHONE
 804-4774 FAX

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-08-06 Cont ID  
Sent By adarroug Date 2008-08-06 Time 09:54 Rev Time 0.00
Received By adarroug Date 2008-08-06 Time 09:54 Sent To M
Notes
2008-08-06 09:55:07TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-07-02 Cont ID  
Sent By adarroug Date 2008-07-02 Time 16:57 Rev Time 0.00
Received By adarroug Date 2008-07-02 Time 16:57 Sent To P
Notes
2008-07-02 16:57:48TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-05-27 Cont ID  
Sent By adarroug Date 2008-05-27 Time 14:44 Rev Time 0.00
Received By adarroug Date 2008-05-27 Time 14:44 Sent To  
Notes
2008-05-29 11:57:57TO "COMM" BD#22
2008-05-27 14:44:46WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-03-24 Cont ID  
Sent By adarroug Date 2008-03-24 Time 10:03 Rev Time 0.00
Received By adarroug Date 2008-03-24 Time 10:03 Sent To E
Notes
2008-03-24 10:03:46TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-02-22 Cont ID  
Sent By adarroug Date 2008-02-22 Time 11:49 Rev Time 0.00
Received By adarroug Date 2008-02-22 Time 11:49 Sent To  
Notes
2008-02-22 11:55:06TO "COMM" BD#35

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-01-10 Cont ID  
Sent By mmiller Date 2008-01-10 Time 15:25 Rev Time 0.00
Received By mmiller Date 2008-01-10 Time 15:25 Sent To  
Notes
2008-01-10 15:25:51SENT TO COMM BOARD # 28

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-08-24 Time   Rev Time 0.00
Received By adarroug Date 2007-08-24 Time 11:36 Sent To  
Notes
2007-09-16 11:26:27TO COMMBOARD SPACE #52, DVP
2007-08-24 11:38:55WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-08-06 Cont ID  
Sent By tgordon Date 2008-08-06 Time 16:05 Rev Time 0.30
Received By tgordon Date 2008-08-06 Time 16:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-07-31 Cont ID  
Sent By tgordon Date 2008-07-31 Time 08:51 Rev Time 1.30
Received By tgordon Date 2008-07-31 Time 08:51 Sent To  
Notes
2008-07-31 09:43:40PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 ** RE-STAMP DENIED **
  
 1) WHEN MASTER PERMIT #07080669 WAS APPLIED FOR THEIR
 WAS NO MECHANICAL WORK TO BE DONE. A MECHANICAL
 SUB-PERMIT WAS OBTAINED A YEAR LATTER #08070445 AND DID
 NOT PAY THE CORRECTFEES, PLEASE CHECK ALL MECHANICAL
 WORK BEING DONE AND ADJUST THE VALUE TO MECHANICAL
 PERMIT #08070445, THE VALUE ON THE PERMIT MUST BE
 ADJUSTED TO THE FAIR MARKET VALUE (REPLACEMENT VALUE)
 FOR THE A/C WORK, WITH ALL MATERIALS AND LABOR. IF THE
 VALUE IS NOT ADJUSTED THEN THE CITY WILL NEED TO ADJUST
 IT USING THE MARSHALL & SWIFT NATIONAL VALUATION
 SERVICE, PER 2004 WPB AMEND. 108.3.
  
 2) THE MECHANICAL INFORMATION ON THE REVISED PLAN IS
 UPSIDE-DOWN FROM THE FLOOR PLAN, PLEASE CORRECT.
  
 3) PLEASE SHOW THE CFM'S AT ALL SUPPLY AIR GRILLS NEW
 AND REPLACE EXISTING FLEX AND GRILL, PER 2004 FBC
 106.3.5.
  
 4) THE MECHANICAL INFORMATION ON THE PLAN IS DIFFICULT
 TO DETERMINE FROM THE FLOOR PLAN INFORMATION ON THE
 PLAN. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, SEE F.B.C. 106.1.1. PLEASE CORRECT.
  
 5) THIS RE-STAMP IS ACTUALLY A REVISION, THE FEE FOR
 THE REVISION HAS BEEN ADJUSTED, PLEASE PAY.
  
 6) THE REVISED PLAN NEEDS TO BE SIGNED AND SEALED BY
 THE ARCHITECT (ROBERT L. BELL), PER FAC 61G1-16.003.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-10-03 Cont ID  
Sent By hmoser Date 2007-10-03 Time 17:04 Rev Time 0.00
Received By hmoser Date 2007-10-03 Time 17:04 Sent To  
Notes
2007-10-03 17:01:5210/3/07
 PLEASE HAVE MECHANICAL CONTRACTOR SUBMIT PLANS AND
 ENERGY CALCULATIONS AT TIME OF PERMIT APPLICATION .
 INSPECTION BY HAROLD MOSER561-805-6732

Review Stop P PLUMBING
Rev No 5 Status P Date 2008-07-23 Cont ID  
Sent By kstevens Date 2008-07-23 Time 14:03 Rev Time 0.00
Received By kstevens Date 2008-07-23 Time 14:03 Sent To  
Notes
2008-07-23 14:08:47REVISION OK--SHT 10

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-03-27 Cont ID  
Sent By mperson Date 2008-03-27 Time 11:43 Rev Time 0.00
Received By mperson Date 2008-03-27 Time 11:43 Sent To E
Notes
2008-03-27 11:45:59NOTE: NEW SHEET 10 W/ELECTRICAL REVISIONS, HOWEVER NO
 PLBG CHANGES TO RISER DIAGRAMS.

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-03-18 Cont ID  
Sent By kstevens Date 2008-03-18 Time 10:40 Rev Time 0.00
Received By kstevens Date 2008-03-18 Time 10:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-02-05 Cont ID  
Sent By kstevens Date 2008-02-05 Time 10:02 Rev Time 0.00
Received By kstevens Date 2008-02-05 Time 10:02 Sent To  
Notes
2008-02-05 10:06:25DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 ****FROM PREVIOUS REVIEW:
  
  
 1. SHT 3 THE LOUNGE SINK SHALL BE ACCESSIBLE. PLEASE
 PROVIDE A DETAIL WITH ELEVATION SHOWING COMPLIANCE WITH
 THE FOLLOWING:
 A. OK
 B. OK
 C. 11-4.24.5 CLEAR FLOOR SPACE. FORWARD APPROACH
 REQUIRED. CABINET DOORS NOT APPROVED.
 ****NO RESPONSE FOR THE CLEAR FLOOR SPACE. NOT
 ADDRESSED.
 D. OK
 E. OK
  
 2. SUBMIT A DETAIL WITH ELEVATION FOR THE DRINKING
 FOUNTAIN SHOWING COMPLIANCE WITH SECTION 11-4.15 WITH
 ALL SUBSECTIONS.
 ****NO RESPONSE, NOT ADDRESSED.
  
 3. OK
  
 4. SHTS 9 & 10 ONLY THE FIXTURES WITHIN THE BATHROOM
 GROUPS SHALL CONNECT TO THE WET-VENTED HORIZONTAL
 BRANCH DRAIN. ANY ADDITIONAL FIXTURES SHALL DESCHARGE
 DOWNSTREAM OF THE WET VENT. (SEE THE LAB SINK SANT.
 RISER 3, AS WELL AS THE XRAY & DARKROOM SINK SANT.
 RISER 4. SECTION 909.1.
 ****RESPONSE NOTED, BUT THE LAB SINK IS STILL
 DISCHARGING INTO THE WET VENT SYSTEM FOR THE TOILET
 ROOM. THIS IS SHOWN ON THE SANT. RISER DIAGRAM RISER 3
 AS WELL.
  
 5. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-10-29 Cont ID  
Sent By kstevens Date 2007-10-29 Time 07:46 Rev Time 0.00
Received By kstevens Date 2007-10-27 Time 17:52 Sent To  
Notes
2007-10-29 08:11:38DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SHT 3 THE LOUNGE SINK SHALL BE ACCESSIBLE. PLEASE
 PROVIDE A DETAIL WITH ELEVATION SHOWING COMPLIANCE WITH
 THE FOLLOWING:
 A. 11-4.24.2 HEIGHT
 B. 11-4.24.3 KNEE CLEARANCE
 C. 11-4.24.5 CLEAR FLOOR SPACE. FORWARD APPROACH
 REQUIRED. CABINET DOORS NOT APPROVED.
 D. 11-4.24.6 EXPOSED PIPES & SURFACES
 E. 11-4.24.7 FAUCETS
  
 2. SUBMIT A DETAIL WITH ELEVATION FOR THE DRINKING
 FOUNTAIN SHOWING COMPLIANCE WITH SECTION 11-4.15 WITH
 ALL SUBSECTIONS.
  
 3. SHT 9 IN THE INSTALLATION OR REMOVAL OF ANY PART OF
 A DRAINAGE SYSTEM, DEAD ENDS SHALL BE PROHIBITED. SEE
 THE END OF THE RUN UPSTREAM OF SANITARY RISER 4.
  
 4. SHTS 9 & 10 ONLY THE FIXTURES WITHIN THE BATHROOM
 GROUPS SHALL CONNECT TO THE WET-VENTED HORIZONTAL
 BRANCH DRAIN. ANY ADDITIONAL FIXTURES SHALL DESCHARGE
 DOWNSTREAM OF THE WET VENT. (SEE THE LAB SINK SANT.
 RISER 3, AS WELL AS THE XRAY & DARKROOM SINK SANT.
 RISER 4. SECTION 909.1.
  
 5. SUBMIT A WATER RISER DIAGRAM SHOWING ALL PIPE SIZES,
 INCLUDING THE WATER MAINS THAT NEW FIXTURES CONNECT TO,
 VALVES ETC. SECTION 106.3.5.1.3(3)(10)(13).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date 2008-06-02 Cont ID  
Sent By choops Date 2008-06-02 Time 10:36 Rev Time 0.00
Received By choops Date 2008-06-02 Time 10:36 Sent To  
Notes
2008-06-02 10:38:12***APPROVED - REVISION - STRUCTURAL CHANGES TO
 ACCOMODATE USING EXISTING STRUCTURAL ELEMENTS***
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2008-02-26 Cont ID  
Sent By choops Date 2008-02-26 Time 10:32 Rev Time 0.00
Received By choops Date 2008-02-26 Time 10:32 Sent To  
Notes
2008-02-26 10:34:33***APPROVED - RESUB #2 - REVISED SCOPE OF WORK UNDER
 THIS SUBMITTAL***
  
 PROVISO:AS THE VALUE OF THE PROPOSED WORK STILL
 EXCEEDS 50% OF THE IMPROVEMENT VALUE AS LISTED WITH THE
 PALM BEACH COUNTY PROPERTY APPRAISER, A COPY OF THE
 PRIVATE APPRAISAL SHALL BE SUBMITTED AND SHALL BE
 INCLUDED WITH THE PERMIT PACKET.

Review Stop Z ZONING
Rev No 2 Status F Date 2008-01-15 Cont ID  
Sent By choops Date 2008-01-15 Time 09:03 Rev Time 0.00
Received By choops Date 2008-01-15 Time 09:03 Sent To  
Notes
2008-01-15 09:03:59***FAILED - RESUB #1***
  
  
 REPEAT COMMENTS:
  
 1)AS THE VALUE OF THE PROPOSED WORK EXCEEDS 50% OF
 THE STRUCTURE'S VALUE, LANDSCAPING SHALL BE BROUGHT TO
 COMPLIANCE WITH ARTICLE XIV OF THE CITY OF WEST PALM
 BEACH ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDRS).
  
 THE VALUATION IS BASED UPON THE EXISTING STRUCTURE (THE
 DEPRECIATION MUST BE SUBTRACTED), NOT INCLUDING THE
 LAND VALUE.THE PROVIDED APPRAISAL CLEARLY SHOWS THAT
 UNDER EITHER OF THE THREE (3) METHODS OF CALCULATION,
 THE VALUE OF THE PROPOSED WORK STILL EXCEEDS 50% OF THE
 STRUCTURE'S VALUE:
  
 COST APPROACH: $475,000 - $276,000 (LAND VALUE) =
 $199,000 WHICH THE VALUE OF THE PROPOSED WORK
 ($190,000) EXCEEDS 50% OF.
 SALES COMPARISON APPROACH: $480,000 - $276,000 (LAND
 VALUE) = $204,000 WHICH THE VALUE OF THE PROPOSED WORK
 ($190,000) EXCEEDS 50% OF.
 INCOME APPROACH: $473,000 - $276,000 (LAND VALUE) =
 $197,000 WHICH THE VALUE OF THE PROPOSED WORK
 ($190,000) EXCEEDS 50% OF.
  
 2)TANDEM PARKING SPACES SHALL BE REMOVED FROM PLANS.
 REMOVAL OF THESE SPACES LEAVES THE SITE ONE (1) PARKING
 SPACE SHORT OF ITS REQUIRED NUMBER OF 14.PLEASE SHOW
 COMPLIANCE WITH REQUIRED PARKING.
  
 NEW COMMENT:
  
 1)IF PARKING IS TO BE RESTRIPED, A STRIPING DETAIL
 SHALL BE PROVIDED SHOWING COMPLIANCE WITH THE CITY'S
 TYPICAL STRIPING DETAIL (SEE PROVIDED DETAIL).
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2007-10-03 Cont ID  
Sent By choops Date 2007-10-02 Time 14:52 Rev Time 0.00
Received By choops Date 2007-10-02 Time 14:52 Sent To  
Notes
2007-10-02 14:58:53***FAILED***
  
  
 1)PLEASE PROVIDE TWO (2) COPIES OF A CURRENT SURVEY
 SHOWING THE SETBACK DIMENSION TO THE PROPERTY LINES
 FROM THE PROPOSED WORK.
  
 2)AS THE VALUE OF THE PROPOSED WORK EXCEEDS 50% OF
 THE STRUCTURE'S VALUE, LANDSCAPING SHALL BE BROUGHT TO
 COMPLIANCE WITH ARTICLE XIV OF THE CITY OF WEST PALM
 BEACH ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDRS)
  
 3)INDICATE HEIGHT OF THE PROPOSED FROM GRADE TO THE
 MIDPOINT OF THE ROOF'S PITCH.
  
 4)AS YOU ARE PROPOSING TO DEMOLISH EXISTING AND
 REBUILD, ALL NEW CONSTRUCTION SHALL CONFORM WITH
 CURRENT REGULATIONS.A MINIMUM FRONT SETBACK OF 5'
 SHALL BE OBSERVED.PER SECTION 94-305(E) OF THE ZLDRS:
 NO OBJECT BETWEEN 18" AND 8' SHALL BE BUILT WITHIN THE
 VISIBILITY TRIANGLE (20' BACK FROM CORNER OF PROPERTY)
  
 5)TANDEM PARKING NOT PERMITTED.
  
 NOTE:THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved