| Plan Review Stops For Permit 07080669 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2008-07-02 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-07-02 |
Time |
11:42 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2008-07-02 |
Time |
11:42 |
Sent To |
|
|
| Notes |
| 2008-07-02 11:43:19 | BUILDING PLAN REVIEW | | | PERMIT: 07080669 | | | ADD: 6215 S DIXIE HWY | | | CONT: MONARCH | | | TEL: (561)767-7176 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVISIONREVIEW | | | ACTION: DENIED | | | | | | 1) WORKING OUT OF THE SCOPE OF LICENSURE. FLORIDA STATE | | | STATUTE 489.113(2)(G) NO GENERAL, BUILDINGOR | | | RESIDENTIAL CONTRACTOR CERTIFIFIED AFTER 12-31-1973 | | | SHALL ACT AS,HOLD HIMSELF OUT TO BE, OR ADVERTISE | | | HIMSELF TO BE A ROOFING CONTRACTOR UNLESHE IS CERTIFIED | | | OR REGISTERED AS A ROOFING CONTRACTOR. PLEASE SEE THE | | | COPY OF YOUR PERMIT APPLICATION, NO ROOFING CONTRACTOR | | | WAS REGISTEERED WITH THE CITY AT TIME OF PERMIT | | | APPLICATION DATE. THE ROOFING SUBPERMIT WAS STRUCK | | | REQUIURING A SEPERATE PERMIT, FEES & REVIEW. | | | | | | NOTE THE ASPHALT SHINGLE REPORT SUBMITTED UNDER THE | | | ORIGINAL PERMIT WAS A APPROVAL UNDER THEFLORIDA | | | SYSTEM FL 5444-R0TRINITY/ ERD REPORT. IF NEW REPORTS | | | ARE GOING TO BE SUBMITTED UNDER THE SEPERATE ROOFING | | | PERMIT THEY MUST BE REVIEWED BY THE DESIGNER OF | | | RECORD. | | | | | | | | | WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE | | | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | | | | PRODUCT APPROVALS SUBMITTED WITH PERMIT | | | APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO | | | COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR | | | INFORMATION PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE | | | APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER | | | SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, | | | SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR | | | SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT. | | | WWW.FLORIDABUILDING.ORG | | | | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2008-06-03 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-06-03 |
Time |
15:36 |
Rev Time |
2.77 |
| Received By |
jwitmer |
Date |
2008-06-03 |
Time |
15:36 |
Sent To |
PC |
|
| Notes |
| 2008-06-03 15:39:17 | SEE SHEET 7: | | | BUILDING PROVISO 1203.2 ATTIC SPACES THE NET FREE | | | VENTILATING AREA SHALL NOT BE LESS THAN 1 / 150 OF THE | | | AREA OF THE SPACE VENTILATED, WITH 50 PERCENT OF THE | | | REQUIRED VENTILATING AREA PROVIDED BY VENTILATORS | | | LOCATED IN THE UPPER PORTION OF THE SPACE TO BE | | | VENTILATED AT LEAST 3 FEET (914 MM) ABOVE EAVE OR | | | CORNICE VENTS WITH THE BALANCE OF THE REQUIRED | | | VENTILATION PROVIDED BY EAVE OR CORNICE VENTS. | | | | | | BUILDING PROVISO 1209.2 AN OPENING NOT LESS THAN 20 | | | INCHES BY 30 INCHES (559 MM BY 762 MM) SHALL BE | | | PROVIDED TO ANY ATTIC AREA HAVING A CLEAR HEIGHT OF | | | OVER 30 INCHES (762 MM). A 30-INCH (762 MM) MINIMUM | | | CLEAR HEADROOM IN THE ATTIC SPACE SHALL BE PROVIDED AT | | | OR ABOVE THE ACCESS OPENING. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2008-03-21 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2008-03-21 |
Time |
14:24 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2008-03-21 |
Time |
14:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2008-02-06 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-02-06 |
Time |
12:02 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2008-02-06 |
Time |
12:02 |
Sent To |
PC |
|
| Notes |
| 2008-02-06 12:29:48 | BUILDING PLAN REVIEW | | | PERMIT: 07080669 | | | ADD: 6215 S DIXIE HWY | | | CONT: MONARCH | | | TEL: (561)767-7176 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW | | | ACTION: DENIED | | | | | | 1A)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | | ANTICIPATED COOPERATION. | | | | | | 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS, | | | REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR | | | REVIEW FOR PERMIT. | | | IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF | | | YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A | | | THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID | | | DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1* | | | /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH | | | ADMINISTRATIVE CODE. | | | | | | 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 | | | DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN | | | THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF | | | MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY | | | WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE | | | SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS | | | A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS | | | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC | | | INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE | | | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND | | | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT | | | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS | | | DETERMINED BY THE BUILDING OFFICIAL. | | | | | | 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE | | | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT | | | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) | | | AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC | | | BUILDING WITH THE2007 SUPPLEMENTS. | | | | | | 2) THE PLANS, SHEET # 7 THE FOLLOWING INFORMATION IS | | | MISSING OR INCORRECT: | | | | | | A) THE ROOF SHEATHING BEING NAILED DOWN WITH 8D X 1 | | | 1/2" RING SHANK NAILS, THE LENGTH OF THE 8D IS 2 1/2" | | | NOTA 1 1/2". PLEASE SEE FASTENER PENETRATION TABLES | | | FROM USP OR SIMPSON FOR | | | FULL SHEAR LOAD VALUES. | | | | | | B)PLANS DO NOT INDICATE THE ATTIC VENTING REQUIRED | | | ABOVE THE EAVE HEIGHT. THE NET FREE VENTILATING AREA | | | SHALL NOT BE LESS THAN 1 / 150 OF THE AREA OF THE SPACE | | | VENTILATED, WITH 50 | | | PERCENT OF THE REQUIRED VENTILATING AREA | | | PROVIDED BY VENTILATORS LOCATED IN THE UPPER PORTION OF | | | THE SPACE TO BE VENTILATED AT LEAST 3 FEET (914 MM) | | | ABOVE EAVE OR CORNICE VENTS WITH | | | THE BALANCE OF THE REQUIRED VENTILATION | | | PROVIDED BY EAVE OR CORNICE VENTS. | | | | | | C) PRODUCT APPROVALS: MISSING REPORTS ARE ON THE | | | TRUSS ANCHOR AND OR TRUSS STRAPS, RULE 9B-72(31)(G) | | | TRUSS ANCHORS.WILL ALSO REQUIRE FLORIDA COVER SHEET AND | | | THE DESIGN PROFESSIONALS | | | REVIEW AND APPROVAL. | | | | | | D) PLANS DO NOT PROVIDE WHAT THE HEADROOM WWITHIN THE | | | NEW ATTIC SPACE WILL BE WITHIN THE TRUSSED IN AREA, | | | PLEASE DEMONSTRATE COMPLIANCE WITH 1209.2 ATTIC | | | SPACES. | | | | | | 3) TRUSS DRAWINGS PLEASE REVIEW FAC 61G15-23.002 AND | | | 61G15-31.003 SIGNING AND SEALING REQUIRED FOR TRUSS | | | DRAWINGS. | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-09-24 |
|
|
Cont ID |
|
| Sent By |
jjohnsto |
Date |
2007-09-24 |
Time |
14:20 |
Rev Time |
6.20 |
| Received By |
jjohnsto |
Date |
2007-09-24 |
Time |
08:00 |
Sent To |
|
|
| Notes |
| 2007-09-24 14:19:39 | CONSTRUCTION SERVICES DEPARTMENT | | | 200 SECOND STREET, 3RD FLOOR, WEST PALM BEACH, | | | FLORIDA33401 | | | TEL:561-805-6713FAX: | | | 561-805-6731 | | | | | | | | | JAMES JOHNSTON, PERMIT NO 07080669 BUILDING | | | PLAN EXAMINERII | | | PROJECT MEDICAL BUILDING | | | E-MAIL:JJOHNSTON @WPB.ORG ADDRESS 6215 S. DIXIE | | | HIGHWAY | | | CONTRACTOR MONARCH CONSTRUCTION OF S. F. | | | DATE SEPTEMBER 21, 2007 | | | | | | STRUCTURALPLANREVIEW | | | CORRECTION SUBMITTAL | | | WHEN RE-SUBMITTINGCORRECTED PLANS FOR PERMITTING, | | | PLEASEREMOVE AND REPLACE ANY SHEETS AS NECESSARY. | | | INCLUDE A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER WITH A DESCRIPTION OF THE | | | REVISION MADE. IDENTIFY THE SHEET OR SPECIFICATION PAGE | | | WHERE THE CHANGES CAN BE FOUND AND INCLUDE THE OLD | | | SHEETS IN THE RE-SUBMITTAL PACKAGE FOR THE PLAN | | | REVIEWER?S REFERENCE. | | | THIS SHALL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | COMMENT-FOR YOUR INFORMATION | | | | | | RETAIN ORIGINAL PLANS | | | ONE SET OF ORIGINAL PLANS AND ONE SET OF REVISIONS WILL | | | BE RETAINED FOR THE POSSIBILITY OF FORWARDING TO THE | | | STATE BOARD OF ENGINEERS. REMOVE ALL OLD (VOID) SHEETS | | | AND RETAIN ONE SET. | | | COMMENT-FOR YOUR INFORMATION | | | | | | | | | F.S.713.13NOTICE OF COMMENCEMENT | | | FILE NOTICE WITH THE CLERK OF COURT RECORDING DIVISION. | | | IF THE WORK DESCRIBED IN THE NOTICE IS NOT COMMENCED | | | WITHIN 90 DAYS OF FILING THE NOTICE WILL BECOME NULL | | | AND VOID. SUBMIT THE NOTICE AT THE TIME OF PERMIT | | | ISSUANCE AND POST A COPY AT THE JOB SITE BEFORE THE | | | FIRST INSPECTION. | | | COMMENT-FOR YOUR INFORMATION | | | | | | | | | IMPACT FEES | | | BEFORE A PERMIT TO CONSTRUCT MAY BE ISSUED, IMPACT FEES | | | MUST BE PAID TO PALM BEACH COUNTY. | | | THE PERMITTED SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE | | | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | PALM BEACH COUNTY ASSESSMENT | | | PALM BEACH COUNTY IMPACT FEE ASSESSMENT HAS MOVED TO: | | | 2300 N JOG ROAD, SUITE 2 WPB 33411 | | | COMMENT-FOR YOUR INFORMATION | | | | | | WINDOWS / DOORS PRODUCT APPROVALS | | | WPB ADMINISTRATIVE CODE 106.3 REGULATED BY DCA RULE | | | 9B-72FLORIDA PRODUCT APPROVAL | | | SUBMIT TWO COPIES OF EACH APPROVAL WITH FLORIDA PRODUCT | | | APPROVAL COVER SHEET THE ARCHITECT?S / ENGINEER?S | | | SIGNATURE AS APPLICABLE, STATING ?TO THE BEST OF THEIR | | | KNOWLEDGE THE PRODUCT APPROVAL COMPLIES WITH THE PLANS | | | AND SPECIFICATIONS.SEE:WEB SITE | | | WWW.FLORIDABUILDING.COM | | | NOTE: SEE DIVISION FACTOR TO BE USED IN DESIGN PRESSURE | | | BY LEGACYFPA | | | COMMENT-SUBMIT TWO COPIES OF EACH PRODUCT APPROVAL | | | MIAMI-DADE AND FLORIDA PRODUCT APPROVAL | | | | | | | | | 1. PRODUCT APPROVAL | | | LAWSON INDUSTRIES PRODUCT APPROVALNOA 06-0117.02 | | | COMMENT-EXPIRED AUGUST 22,2007 | | | | | | 2. PRODUCT APPROVALS | | | COMMENT-MIAMI DADE PRODUCT APPROVALS MISSING FLORIDA | | | PRODUCT APPROVAL SHEET | | | | | | 3. NORDIC FLAT ROOF TILE | | | COMMENT-IDENTIFY WHICH SYSTEM AND FASTENERS YOU ARE | | | USING FROM TABLES PROVIDED IN THE PRODUCT APPROVAL | | | | | | 4. POLYPROAH160 | | | COMMENT-IDENTIFY WHICH SYSTEM AND FASTENERS YOU ARE | | | USING FROM TABLES PROVIDED IN THE PRODUCT APPROVAL | | | | | | 5. PRODUCT APPROVAL | | | LAWSON INDUSTRIES LA PORTE OUT SWING FRENCH DOOR | | | COMMENT-IDENTIFY UNIT AND COMPONENTS TO BE USED | | | | | | 6. PRODUCT APPROVAL | | | LAWSON INDUSTRIES FIXED WINDOW | | | COMMENT-IDENTIFY UNIT AND COMPONENTS TO BE USED | | | | | | 7. PRODUCT APPROVAL | | | LAWSON INDUSTRIES SINGLE HUNG WINDOW | | | COMMENT-IDENTIFY UNIT AND COMPONENTS TO BE USED | | | | | | 8. SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE | | | FOLLOWING | | | FIXED GLASS | | | WINDOWS | | | MULLION TUBES | | | EXTERIORHOLLOW METAL DOORS | | | EXTERIOR DOORS-OTHER | | | ROOF COVERING SYSTEMS | | | | | | 9. PLEASE PROVIDE ALL NOTES ON COVER SHEET 1 | | | FBC2004 BUILDING W/ 2005 AND 6 REVISIONS | | | FBC2004 EXISTING BUILDING | | | LEVEL OF ALTERATION | | | TYPE OF CONSTRUCTION / SPRINKLED / UN-SPRINKLED WIND | | | SPEED AND EXPOSURE | | | WIND IMPORTANCE FACTOR | | | TYPE OF OCCUPANCY | | | OCCUPANT LOAD | | | GROSS LOAD | | | NET LOAD | | | | | | 10. DOOR NO. 8 NOT NOTED ON DEMOLITION PLAN COMMENT- | | | IDENTIFY POURED CELLS FOR THIS DOOR | | | | | | 11. 704.5 FIRE-RESISTANCE RATINGS. | | | EXTERIOR WALLS SHALL BE FIRE-RESISTANCE RATED IN | | | ACCORDANCE WITH TABLES 601 AND 602 . THE | | | FIRE-RESISTANCE RATING OF EXTERIOR WALLS WITH A FIRE | | | SEPARATION DISTANCE OF GREATER THAN 5 FEET (1524 MM) | | | SHALL BE RATED FOR EXPOSURE TO FIRE FROM THE INSIDE. | | | THE FIRE-RESISTANCE RATING OF EXTERIOR WALLS WITH A | | | FIRE SEPARATION DISTANCE OF 5 FEET (1524 MM) OR LESS | | | SHALL BE RATED FOR EXPOSURE TO FIRE FROM BOTH SIDES. | | | COMMENT-ON SHEET 1 SHOW ADJACENT BUILDINGS AND PUBLIC | | | ROADS TO DETERMINE FIRE RESISTANCE RATINGS OF OPENINGS | | | IN THE EXTERIOR TWO HOUR WALL.SEE TABLE704.8TO | | | DETERMINE PROTECTION OF OPENINGS | | | | | | | | | | | | 12. PROVIDE TRUSS FRAMING PLAN WITH SHEATHING AND | | | ANCHORAGE. INFORMATION PROVIDED HEREIN | | | FBC2304.9.1 FASTENER REQUIREMENTS. | | | CONNECTIONS FOR WOOD MEMBERS SHALL BE DESIGNED IN | | | ACCORDANCE WITH THE APPROPRIATE METHODOLOGY IN SECTION | | | 2301.2 . THE NUMBER AND SIZE OF NAILS CONNECTING WOOD | | | MEMBERS SHALL NOT BE LESS THAN THAT SET FORTH IN TABLE | | | 2304.9.1 . | | | FBC2304.7 FLOOR AND ROOF SHEATHING | | | FBC2304.7.2 STRUCTURAL ROOF SHEATHING. | | | COMMENT-STRUCTURAL ROOF SHEATHING SHALL BE DESIGNED | | | IN ACCORDANCE WITH THE GENERAL PROVISIONS OF THIS CODE | | | AND THE SPECIAL PROVISIONS IN THIS SECTION. USE RATING | | | INDICATED IN TABLE.EX.5/8 PANELS EQUAL 19/32 | | | RATING SEE TABLES IN THIS SECTION. | | | | | | 13. FBC EXISTING 601.3 COMPLIANCE. | | | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND | | | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE | | | FLORIDA BUILDING CODE . | | | (A)13-400.0 GENERAL. | | | THE PROVISIONS OF THIS CHAPTER APPLY TO ALL NEW | | | COMMERCIAL OCCUPANCY BUILDINGS, ADDITIONS TO EXISTING | | | COMMERCIAL OCCUPANCY BUILDINGS, AND MULTIPLE-FAMILY | | | RESIDENTIAL BUILDINGS OVER THREE STORIES IN HEIGHT. | | | BUILDING TYPE CLASSIFICATIONS SHALL BE THOSE DEFINED IN | | | SUBCHAPTER 13-2 OF THIS CODE UNDER ?OCCUPANCY | | | CLASSIFICATION.? THIS SUBCHAPTER PROVIDES THREE METHODS | | | BY WHICH COMMERCIAL BUILDINGS MAY BE BROUGHT INTO | | | COMPLIANCE WITH THIS CODE. | | | COMMENT-NEW CONSTRUCTION FOR WALLS, ROOF, INTERIOR | | | MUST COMPLY WITH FBC BUILDING CHAPTER 13-400.0 | | | | | | 14. SHEET 7SECTION 2-7 | | | COMMENT-IDENTIFY NELSON STUD EMBEDMENT INTO BEAM | | | | | | 15. SHEET7SECTION 1-7 | | | COMMENT - DEFINE R VALUE FOR EXTERIOR WALL AND ATTIC | | | INSULATION | | | | | | 16. SHEET 7 CONCRETE TO BE USED FOR THIS PROJECT | | | COMMENTS - IDENTIFY STRENGTH OF CONCRETE FOR FOOTINGS, | | | BEAMS, COLUMNS, FILLED CELLS, MASONRY UNITS | | | | | | FBC11-4FLORIDA ACCESSIBILITY CODE | | | | | | 1A. FBC 11-4.8 RAMPS | | | COMMENT-RAMP DESIGN REQUIRED WITH ALL ELEMENTS PER | | | THIS CHAPTER | | | SEE FIGURE 17 EXAMPLES OF EDGE PROTECTION AND HANDRAIL | | | EXTENSIONS | | | | | | 2A. FBC 11-4.9.4STAIRS | | | COMMENT-DEFINE HANDRAIL AND LOCATION ON SHEET 6. | | | IDENTIFY 36? FROM TREAD TO RAILING FOR FIELD USE SEE | | | FIGURE 19 STAIR HANDRAILS | | | | | | 3A. FBC 11-4.13.4 DOUBLE-LEAF DOORWAYS.( DOOR NO.1 | | | &2ON PLAN ) | | | COMMENT-IF DOORWAYS HAVE TWO INDEPENDENTLY OPERATED | | | DOOR LEAVES, THEN AT LEAST ONE LEAF SHALL MEET THE | | | SPECIFICATIONS IN SECTION 11-4.13.5 AND SECTION | | | 11-4.13.6 . THAT LEAF SHALL BE AN ACTIVE LEAF. | | | | | | (1) 11-4.13.5 CLEAR WIDTH. | | | DOORWAYS SHALL HAVE A MINIMUM CLEAR OPENING OF 32 | | | INCHES (813 MM) WITH THE DOOR OPEN 90 DEGREES, MEASURED | | | BETWEEN THE FACE OF THE DOOR AND THE OPPOSITE STOP SEE | | | FIGURE 24 (A), FIGURE 24 (B), FIGURE | | | | | | 5A. TOILET ROOM NO. 1 | | | COMMENT-IDENTIFY PASS THRU WINDOW HEIGHT ABOVE | | | FINISHED FLOOR |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2008-03-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-03-27 |
Time |
13:03 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-03-27 |
Time |
13:03 |
Sent To |
PC |
|
| Notes |
| 2008-03-27 13:03:50 | INSERTED NEW SHEETS INTO SETS. | | | NEW PLUMBING SHEETS STAMPED. | | | VOIDED OLD SHEETS. | | | ELEC SHEETS ORIGINALLY STAMPED AND DATED REVIEWED | | | 1/17/08 ARE VOID AND NOT VALID. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2008-03-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-03-05 |
Time |
20:08 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-03-05 |
Time |
20:07 |
Sent To |
|
|
| Notes |
| 2008-03-05 20:14:25 | ** DENIEDREVIEW ** | | | | | | ** PLEASE SEE SOME ITEMS WHICH WERE OK ON PREVIOUS | | | REVIEW HAVE NOW BEEN CHANGED AND DID NOT COORDINATE AND | | | REVISE OTHER SHEETS. PLEASE SEE THE FOLLOWING COMMENTS | | | | | | 1) NOTE:PLEASE SEE THE SCOPE OF WORK HAS CHANGED AND | | | LIGHTING FIXTURE TYPES AND COUNTS HAVE CHANGED YET THE | | | LIGHTING PERFORMANCE CALCULATIONS WERE NOT REVISED. | | | PLEASE SEE FOR EXAMPLE ONLY 3-TYPE A FIXTURES SHOWN IN | | | LP CALCULATIONS. | | | PLEASE SEE THE A FIXTURES ARE NOW 3-32 W ? | | | PLEASE SEE 13-415.2, 13-415.2.ABC.1.1, .1.2 AND .1.3. | | | | | | 2) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH GAVE PROVISO | | | FOR SOME ROOMS WHICH DO REQUIRED AUTOMATED LIGHTING | | | CONTROLS PER 13-415.1.ABC.1.2 EVEN IF THE BUILDING IS | | | UNDER 5K SQFT. PLEASE SEE ROOMS IN SECTION GIVEN WILL | | | REQUIRE OCCUPANCY SENSORS. | | | ** THIS WAS CONFIRMED WITH THE FLORIDA BUILDING | | | COMMISSION/ DEPARTMENT OF COMMUNITY AFFAIRS. | | | | | | 3) NOTE: ** PLEASE KNOW ANY AREAS IN WHICH EXISTING | | | WIRING IS EXPOSED, DOES NOT MEET CODE, UNSAFE, WATER | | | DAMAGED ETC WILL REQUIRE RE-WIRE UP TO CURRENT CODE. | | | PLEASE SEE MOST OF THE AREAS ARE SHOWN AS NEW TO MEET | | | CURRENT CODES, HOWEVER MANY ARE SHOWN AS EXISTING. | | | AREAS WHICH ARE NOT SAFE ETC WILL BE REQUIRED TO BE | | | BROUGHT UP TO CODE. | | | ** THIS IS GIVEN FOR INFORMATIONAL PURPOSE. | | | BASED ON THE PICTURES AND CONDITIONS AT SITE | | | REVIEWER/OFFICE IS GIVING NOTICE FOR AREAS OF CONCERN | | | WHICH ARE NOT MENTIONED ON PLANS. | | | ANY ITEMS WHICH MAY BE IN QUESTION FOR LIFE SAFETY/ | | | PROPERTY HAZARD WHICH ARE KNOWN TO CONTRACTOR OR DESIGN | | | PROFESSIONALS NEEDS TO BE ADDRESSED ON PLANS AND IS THE | | | RESPONSIBILITY OF SUCH INDIVIDUALS. | | | FS 481, 471, 489 | | | | | | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | | DELAYS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2008-01-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-01-17 |
Time |
17:11 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-01-17 |
Time |
17:11 |
Sent To |
|
|
| Notes |
| 2008-01-17 17:12:00 | ** PROVISO ** | | | | | | 1) NOTE: PLEASE SEE THE LOUNGE AND TRAINING ROOMS WILL | | | REQUIRE LIGHTING CONTROLS WHICH WILL AUTOMATICALLY TURN | | | OFF LIGHTING WITHIN 30MINS OF THE OCCUPANT LEAVING THE | | | SPACE. | | | PLEASE SEE 13-415.1.ABC.1.2 | | | THIS WAS CONFIRMED WITH THE FLORIDA BUILDING COMMISSION | | | SINCE THE LAST REVIEW. THESE AUTOMATED LIGHTING | | | CONTROLS ARE REQUIRED EVEN IN BUILDINGS LESS THAN 5K SQ | | | FT FOR THESE ROOMS AS MENTIONED ABOVE. | | | | | | ** ELECTRICAL PLANS ARE STAMPED AND DO NOT NEED TO BE | | | REVISED UNTIL BEFORE ROUGH ELECTRICAL INSPECTION. | | | REVISED PLANS ARE TO BE ON-SITE FOR ELECTRICAL | | | INSPECTOR. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PAM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-09-16 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-09-16 |
Time |
12:15 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-09-16 |
Time |
11:26 |
Sent To |
|
|
| Notes |
| 2007-09-16 12:16:06 | 2007-09-16 12:16:06 | | | | | | ** DENIED ** | | | | | | 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS | | | WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES | | | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. | | | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO | | | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. | | | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY | | | AFFECT DESIGNS FOR ALL TRADES. | | | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS | | | REVIEWER AT A MINIMUM. | | | 2004 FBC W/ 2006 REVISIONS | | | 2005 NFPA-70 | | | 2002 NFPA-72 | | | 2003 NFPA-101 | | | | | | ** PLEASE SEE ANY CODES RELEVANT FROM OTHER TRADES | | | WHICH MAY BE REQUESTED. | | | | | | 2) NOTE: PLEASE SEE MECHANICAL/BUILDING REVIEW COMMENTS | | | FOR VALUE OF PROJECT AND SCOPE OF WORK WHICH MAY | | | REQUIRE SOME ITEMS TO MEET CHAPTER 13 FOR OTHER THAN | | | ELECTRICAL. | | | THE VALUE EXCEEDS THE 30% AS STATED FOR RENOVATIONS. | | | THIS IS FOR INFORMATION ONLY, PLEASE SEE NEXT COMMENT | | | FOR ELECTRICAL. | | | | | | 3) NOTE: PLEASE COMPLETE THE FIXTURE LEGEND AS | | | SUBMITTED INCLUDING FIXTURES TO BE OWNER SELECTED. THE | | | ONLY ACCURATE WAY TO FIGURE THE CALCULATIONS FOR | | | LIGHTING PERFORMANCE IS TO PROVIDE ALL INFORMATION. | | | (THIS CAN ALWAYS BE REVISED IF AN OWNER WOULD LIKE TO | | | CHANGE A FIXTURE TYPE AT A LATER DATE). | | | PLEASE BE SURE TO PLACE ALL FIXTURE DESIGNATIONS ON | | | PLANS AND CORRELATE WITH THE LEGEND. | | | PLEASE SEE FOR EXAMPLE THERE IS A FIXTURE | | | (HAND-WRITTEN) ON PLANS WHICH CALL FOR A 40W | | | FLUORESCENT HOWEVER THIS IS NOT ON THE LEGEND? PLEASE | | | SEE 13-415.2, 13-415.1.B, 13-415.1.C. PLEASE COMPLETE. | | | | | | 4) NOTE: PLEASE LABEL ALL ROOM AND AREA DESIGNATIONS ON | | | PLANS. THERE ARE SOME ITEMS WHICH NEED TO DETERMINED | | | CODE COMPLIANCE FOR EXAMPLE AS X-RAY ROOMS, | | | EXAM/PATIENT CARE ROOMS WHICH CAN NOT BE DETERMINED AT | | | THIS TIME. | | | FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION. | | | | | | 5) NOTE: PLEASE BE SURE THE PANEL SCHEDULE AND | | | CIRCUITING CORRELATE WITH ALL ROOMS AND AREAS IN WHICH | | | THEY FEED. PLEASE SEE NEC 408.4 WHICH REQUIRES ALL | | | CIRCUITING TO BE SPECIFIC TO ROOMS AND AREAS IN WHICH | | | THEY FEED. EXAMPLE: EXAM RM #3 RECEPTS,LIGHTING RM | | | 102, 105 ETC. | | | PLEASE SEE THE FOLLOWING TEXT IS TAKEN FROM THE NEC | | | COMMENTARY. | | | | | | *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE | | | THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A | | | PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE | | | THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. | | | CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED | | | AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE | | | BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, | | | DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE | | | CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT | | | ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS | | | ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR | | | RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT | | | OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE | | | ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT | | | PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS | | | SECTION.* | | | 408.4, 310.16, 240.4 ETC | | | FBC 106.3.5.4 | | | | | | 6) NOTE: PLEASE INCLUDE NOTES FOR REDUNDANT GROUNDING | | | AS REQUIRED FOR ALL PATIENT CARE AREAS AS DEFINED UNDER | | | NEC 517 AND 517.13 AND 517.17. | | | PLEASE ADJUST PLANS. | | | | | | 7) NOTE: PLEASE VERIFY AND INDICATE NEW OR EXISTING | | | DISCONNECTS FOR A/C EQUIPMENT PER 440.11 | | | PLEASE VERIFY NEW OR EXISTING GFI RECEPTACLE(S) FOR A/C | | | EQUIPMENT. 210.63,210.8B | | | ** IT IS KNOWN THAT PLANS CALL FOR A/C WORK TO BE DONE | | | BY OTHERS HOWEVER DUE TO THE EXTEND OF THE SCOPE OF | | | WORK AND LEVEL OF ALTERATION FOR THE FBC EXISTING | | | BUILDING CODE, THESE SHOULD BE VERIFIED AND INDICATED | | | AS THE EXISTING MAY NOT MEET CODE OR BE SAFE. PLEASE | | | KNOW THIS CAN BE GONE OVER ON PHONE IF NEEDED FOR BEST | | | POSSIBLE WAY TO INDICATE. | | | | | | 8) NOTE: PLEASE VERIFY NEW OR EXISTING REQUIRED SIGN | | | CIRCUIT PER 600.5. | | | PLEASE ADJUST LOAD CALCULATIONS. | | | | | | 9) NOTE: PLEASE SEE THE LOAD CALCULATIONS AS SUBMITTED | | | ARE NOT COMPLETE AT THIS TIME. | | | PLEASE SEE 220.12,220.14,220.42,220.44 ETC | | | PLEASE SEE THAT ANY CONTINUOUS LOADS ARE TO BE SHOWN AT | | | 125%. | | | 215.3, 230.42. | | | PLEASE SEE 422.13 OF THE 2005 NEC AS THE LOAD FOR WATER | | | HEATERS ARE NOW CONSIDERED CONTINUOUS LOADS AND NEED TO | | | BE SHOWN AT 125%. | | | PLEASE ADJUST. | | | | | | 10) NOTE: PLEASE CLARIFY NOTE #1 ON ELECTRICAL LIGHTING | | | PLANS WHICH STATES LIGHTING DEVICES FOR SENSOR TYPE, | | | BUT THE NOTE COULD NOT BE LOCATED ON PLANS AND FOR THE | | | INTENT OF DESIGN WHICH IS BEING PROPOSED. | | | | | | 11) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS. | | | PLEASE SEE FOR EXAMPLE THERE ARE SEVERAL EMERGENCY AND | | | EXIT LIGHTS WHICH ARE SHOWN WITH OUT CIRCUITING. PLEASE | | | SEE 700.12F AS THE FIXTURES ARE REQUIRED TO BE | | | CIRCUITED TO THE OTHER BRANCH CIRCUITS FOR NORMAL | | | LIGHTING IN ANY ONE AREA. | | | | | | 12) NOTE: PLEASE SEE NFPA-101 2003 7.8 AND 7.9 AS | | | BATTERY BACK FIXTURE OF SOME TYPE FOR STAIR AREA | | | LEADING TO THE PUBLIC RIGHT OF WAY IS REQUIRED. PLEASE | | | KNOW THE LEVEL UNDER NORMAL IS 10FT CANDLES AND 1FT | | | CANDLE UNDER EMERGENCY. 7.8.1.3, 7.9.2.2 PLEASE SEE FAC | | | 61G15-33.004 | | | | | | 13) NOTE: PLEASE KNOW THAT NO HAND-DRAWN CHANGES ARE | | | PERMITTED TO PLANS BY PEN OR PENCIL. | | | PLEASE BE SURE ANY CHANGES ARE DONE BY THE DESIGNER OF | | | RECORD. | | | FS 471.025, 481.221 | | | | | | 14) NOTE: PLEASE SHOW LOCATION OF THE SERVICE AS THIS | | | IS NOT BEING SHOWN ON BUILDING ?? | | | IS THE SERVICE LOCATED ON BUILDING? | | | NEED TO VERIFY 230.70,230.71,230.72,230.76,230.79, | | | 225.31-225.39 | | | FBC 106.3.5.1.2 | | | | | | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES | | | WHICH MAY AFFECT ELECTRICAL PLANS. | | | | | | ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. | | | | | | *** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS | | | OR COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. | | | IF THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY | | | WAY, NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, | | | PLEASE DO NOT HESITATE IN CONTACTING THIS OFFICE AND | | | THIS REVIEWER. | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2008-03-14 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-03-14 |
Time |
14:48 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-03-14 |
Time |
14:48 |
Sent To |
|
|
| Notes |
| 2008-03-14 14:49:20 | PLANS APPROVED BY B/C CARSILLO ON 10/23/07 AND STAMPED | | | ON THIS DATE. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2007-10-23 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2007-10-23 |
Time |
10:09 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2007-10-23 |
Time |
09:54 |
Sent To |
|
|
| Notes |
| 2007-10-23 10:09:11 | 1. DEMOLITION, RENOVATION, AND CONSTRUCTION TO COMPLY | | | WITH NFPA 241. | | | | | | 2. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. | | | | | | 3. HANDRAIL (S) SHALL MEET THE PRESCRIPTIVE STRENGTH | | | REQUIREMENTS UNDER THE NECESSARY CODES. | | | | | | 4. BUILDING ADDRESS DISPLAYED ON PAGE 4 SHALL BE AT | | | LEAST 1" WIDE. | | | | | | 5. FIRE EXTINGUISHERS DISPLAYED ON PLANS SHALL BE | | | CURRENTLY SERVICE TAGGED. | | | | | | 6. INTERIOR FINISH CLASSIFICATIONS FOR WALLS AND | | | CEILINGS SHALL MEET MINIMUM CODE REQUIREMENTS. | | | | | | APPROVED PROVISO | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | 804-4709 PHONE | | | 804-4774 FAX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2008-08-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-08-06 |
Time |
09:54 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-08-06 |
Time |
09:54 |
Sent To |
M |
|
| Notes |
| 2008-08-06 09:55:07 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2008-07-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-07-02 |
Time |
16:57 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-07-02 |
Time |
16:57 |
Sent To |
P |
|
| Notes |
| 2008-07-02 16:57:48 | TO "P" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2008-05-27 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-05-27 |
Time |
14:44 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-05-27 |
Time |
14:44 |
Sent To |
|
|
| Notes |
| 2008-05-29 11:57:57 | TO "COMM" BD#22 | | 2008-05-27 14:44:46 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2008-03-24 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-03-24 |
Time |
10:03 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-03-24 |
Time |
10:03 |
Sent To |
E |
|
| Notes |
| 2008-03-24 10:03:46 | TO "DPALMER" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2008-02-22 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-02-22 |
Time |
11:49 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-02-22 |
Time |
11:49 |
Sent To |
|
|
| Notes |
| 2008-02-22 11:55:06 | TO "COMM" BD#35 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-01-10 |
|
|
Cont ID |
|
| Sent By |
mmiller |
Date |
2008-01-10 |
Time |
15:25 |
Rev Time |
0.00 |
| Received By |
mmiller |
Date |
2008-01-10 |
Time |
15:25 |
Sent To |
|
|
| Notes |
| 2008-01-10 15:25:51 | SENT TO COMM BOARD # 28 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2007-08-24 |
Time |
|
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-08-24 |
Time |
11:36 |
Sent To |
|
|
| Notes |
| 2007-09-16 11:26:27 | TO COMMBOARD SPACE #52, DVP | | 2007-08-24 11:38:55 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2008-08-06 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-08-06 |
Time |
16:05 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2008-08-06 |
Time |
16:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2008-07-31 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-07-31 |
Time |
08:51 |
Rev Time |
1.30 |
| Received By |
tgordon |
Date |
2008-07-31 |
Time |
08:51 |
Sent To |
|
|
| Notes |
| 2008-07-31 09:43:40 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | ** RE-STAMP DENIED ** | | | | | | 1) WHEN MASTER PERMIT #07080669 WAS APPLIED FOR THEIR | | | WAS NO MECHANICAL WORK TO BE DONE. A MECHANICAL | | | SUB-PERMIT WAS OBTAINED A YEAR LATTER #08070445 AND DID | | | NOT PAY THE CORRECTFEES, PLEASE CHECK ALL MECHANICAL | | | WORK BEING DONE AND ADJUST THE VALUE TO MECHANICAL | | | PERMIT #08070445, THE VALUE ON THE PERMIT MUST BE | | | ADJUSTED TO THE FAIR MARKET VALUE (REPLACEMENT VALUE) | | | FOR THE A/C WORK, WITH ALL MATERIALS AND LABOR. IF THE | | | VALUE IS NOT ADJUSTED THEN THE CITY WILL NEED TO ADJUST | | | IT USING THE MARSHALL & SWIFT NATIONAL VALUATION | | | SERVICE, PER 2004 WPB AMEND. 108.3. | | | | | | 2) THE MECHANICAL INFORMATION ON THE REVISED PLAN IS | | | UPSIDE-DOWN FROM THE FLOOR PLAN, PLEASE CORRECT. | | | | | | 3) PLEASE SHOW THE CFM'S AT ALL SUPPLY AIR GRILLS NEW | | | AND REPLACE EXISTING FLEX AND GRILL, PER 2004 FBC | | | 106.3.5. | | | | | | 4) THE MECHANICAL INFORMATION ON THE PLAN IS DIFFICULT | | | TO DETERMINE FROM THE FLOOR PLAN INFORMATION ON THE | | | PLAN. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT | | | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF | | | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL | | | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT | | | LAWS, SEE F.B.C. 106.1.1. PLEASE CORRECT. | | | | | | 5) THIS RE-STAMP IS ACTUALLY A REVISION, THE FEE FOR | | | THE REVISION HAS BEEN ADJUSTED, PLEASE PAY. | | | | | | 6) THE REVISED PLAN NEEDS TO BE SIGNED AND SEALED BY | | | THE ARCHITECT (ROBERT L. BELL), PER FAC 61G1-16.003. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2007-10-03 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2007-10-03 |
Time |
17:04 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2007-10-03 |
Time |
17:04 |
Sent To |
|
|
| Notes |
| 2007-10-03 17:01:52 | 10/3/07 | | | PLEASE HAVE MECHANICAL CONTRACTOR SUBMIT PLANS AND | | | ENERGY CALCULATIONS AT TIME OF PERMIT APPLICATION . | | | INSPECTION BY HAROLD MOSER561-805-6732 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2008-07-23 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-07-23 |
Time |
14:03 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-07-23 |
Time |
14:03 |
Sent To |
|
|
| Notes |
| 2008-07-23 14:08:47 | REVISION OK--SHT 10 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2008-03-27 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-03-27 |
Time |
11:43 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-03-27 |
Time |
11:43 |
Sent To |
E |
|
| Notes |
| 2008-03-27 11:45:59 | NOTE: NEW SHEET 10 W/ELECTRICAL REVISIONS, HOWEVER NO | | | PLBG CHANGES TO RISER DIAGRAMS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2008-03-18 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-03-18 |
Time |
10:40 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-03-18 |
Time |
10:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2008-02-05 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-02-05 |
Time |
10:02 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-02-05 |
Time |
10:02 |
Sent To |
|
|
| Notes |
| 2008-02-05 10:06:25 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | | | | ****FROM PREVIOUS REVIEW: | | | | | | | | | 1. SHT 3 THE LOUNGE SINK SHALL BE ACCESSIBLE. PLEASE | | | PROVIDE A DETAIL WITH ELEVATION SHOWING COMPLIANCE WITH | | | THE FOLLOWING: | | | A. OK | | | B. OK | | | C. 11-4.24.5 CLEAR FLOOR SPACE. FORWARD APPROACH | | | REQUIRED. CABINET DOORS NOT APPROVED. | | | ****NO RESPONSE FOR THE CLEAR FLOOR SPACE. NOT | | | ADDRESSED. | | | D. OK | | | E. OK | | | | | | 2. SUBMIT A DETAIL WITH ELEVATION FOR THE DRINKING | | | FOUNTAIN SHOWING COMPLIANCE WITH SECTION 11-4.15 WITH | | | ALL SUBSECTIONS. | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | 3. OK | | | | | | 4. SHTS 9 & 10 ONLY THE FIXTURES WITHIN THE BATHROOM | | | GROUPS SHALL CONNECT TO THE WET-VENTED HORIZONTAL | | | BRANCH DRAIN. ANY ADDITIONAL FIXTURES SHALL DESCHARGE | | | DOWNSTREAM OF THE WET VENT. (SEE THE LAB SINK SANT. | | | RISER 3, AS WELL AS THE XRAY & DARKROOM SINK SANT. | | | RISER 4. SECTION 909.1. | | | ****RESPONSE NOTED, BUT THE LAB SINK IS STILL | | | DISCHARGING INTO THE WET VENT SYSTEM FOR THE TOILET | | | ROOM. THIS IS SHOWN ON THE SANT. RISER DIAGRAM RISER 3 | | | AS WELL. | | | | | | 5. OK | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | | FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-10-29 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-10-29 |
Time |
07:46 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-10-27 |
Time |
17:52 |
Sent To |
|
|
| Notes |
| 2007-10-29 08:11:38 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | | | | 1. SHT 3 THE LOUNGE SINK SHALL BE ACCESSIBLE. PLEASE | | | PROVIDE A DETAIL WITH ELEVATION SHOWING COMPLIANCE WITH | | | THE FOLLOWING: | | | A. 11-4.24.2 HEIGHT | | | B. 11-4.24.3 KNEE CLEARANCE | | | C. 11-4.24.5 CLEAR FLOOR SPACE. FORWARD APPROACH | | | REQUIRED. CABINET DOORS NOT APPROVED. | | | D. 11-4.24.6 EXPOSED PIPES & SURFACES | | | E. 11-4.24.7 FAUCETS | | | | | | 2. SUBMIT A DETAIL WITH ELEVATION FOR THE DRINKING | | | FOUNTAIN SHOWING COMPLIANCE WITH SECTION 11-4.15 WITH | | | ALL SUBSECTIONS. | | | | | | 3. SHT 9 IN THE INSTALLATION OR REMOVAL OF ANY PART OF | | | A DRAINAGE SYSTEM, DEAD ENDS SHALL BE PROHIBITED. SEE | | | THE END OF THE RUN UPSTREAM OF SANITARY RISER 4. | | | | | | 4. SHTS 9 & 10 ONLY THE FIXTURES WITHIN THE BATHROOM | | | GROUPS SHALL CONNECT TO THE WET-VENTED HORIZONTAL | | | BRANCH DRAIN. ANY ADDITIONAL FIXTURES SHALL DESCHARGE | | | DOWNSTREAM OF THE WET VENT. (SEE THE LAB SINK SANT. | | | RISER 3, AS WELL AS THE XRAY & DARKROOM SINK SANT. | | | RISER 4. SECTION 909.1. | | | | | | 5. SUBMIT A WATER RISER DIAGRAM SHOWING ALL PIPE SIZES, | | | INCLUDING THE WATER MAINS THAT NEW FIXTURES CONNECT TO, | | | VALVES ETC. SECTION 106.3.5.1.3(3)(10)(13). | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | | FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2008-06-02 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2008-06-02 |
Time |
10:36 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2008-06-02 |
Time |
10:36 |
Sent To |
|
|
| Notes |
| 2008-06-02 10:38:12 | ***APPROVED - REVISION - STRUCTURAL CHANGES TO | | | ACCOMODATE USING EXISTING STRUCTURAL ELEMENTS*** | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2008-02-26 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2008-02-26 |
Time |
10:32 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2008-02-26 |
Time |
10:32 |
Sent To |
|
|
| Notes |
| 2008-02-26 10:34:33 | ***APPROVED - RESUB #2 - REVISED SCOPE OF WORK UNDER | | | THIS SUBMITTAL*** | | | | | | PROVISO:AS THE VALUE OF THE PROPOSED WORK STILL | | | EXCEEDS 50% OF THE IMPROVEMENT VALUE AS LISTED WITH THE | | | PALM BEACH COUNTY PROPERTY APPRAISER, A COPY OF THE | | | PRIVATE APPRAISAL SHALL BE SUBMITTED AND SHALL BE | | | INCLUDED WITH THE PERMIT PACKET. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2008-01-15 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2008-01-15 |
Time |
09:03 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2008-01-15 |
Time |
09:03 |
Sent To |
|
|
| Notes |
| 2008-01-15 09:03:59 | ***FAILED - RESUB #1*** | | | | | | | | | REPEAT COMMENTS: | | | | | | 1)AS THE VALUE OF THE PROPOSED WORK EXCEEDS 50% OF | | | THE STRUCTURE'S VALUE, LANDSCAPING SHALL BE BROUGHT TO | | | COMPLIANCE WITH ARTICLE XIV OF THE CITY OF WEST PALM | | | BEACH ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDRS). | | | | | | THE VALUATION IS BASED UPON THE EXISTING STRUCTURE (THE | | | DEPRECIATION MUST BE SUBTRACTED), NOT INCLUDING THE | | | LAND VALUE.THE PROVIDED APPRAISAL CLEARLY SHOWS THAT | | | UNDER EITHER OF THE THREE (3) METHODS OF CALCULATION, | | | THE VALUE OF THE PROPOSED WORK STILL EXCEEDS 50% OF THE | | | STRUCTURE'S VALUE: | | | | | | COST APPROACH: $475,000 - $276,000 (LAND VALUE) = | | | $199,000 WHICH THE VALUE OF THE PROPOSED WORK | | | ($190,000) EXCEEDS 50% OF. | | | SALES COMPARISON APPROACH: $480,000 - $276,000 (LAND | | | VALUE) = $204,000 WHICH THE VALUE OF THE PROPOSED WORK | | | ($190,000) EXCEEDS 50% OF. | | | INCOME APPROACH: $473,000 - $276,000 (LAND VALUE) = | | | $197,000 WHICH THE VALUE OF THE PROPOSED WORK | | | ($190,000) EXCEEDS 50% OF. | | | | | | 2)TANDEM PARKING SPACES SHALL BE REMOVED FROM PLANS. | | | REMOVAL OF THESE SPACES LEAVES THE SITE ONE (1) PARKING | | | SPACE SHORT OF ITS REQUIRED NUMBER OF 14.PLEASE SHOW | | | COMPLIANCE WITH REQUIRED PARKING. | | | | | | NEW COMMENT: | | | | | | 1)IF PARKING IS TO BE RESTRIPED, A STRIPING DETAIL | | | SHALL BE PROVIDED SHOWING COMPLIANCE WITH THE CITY'S | | | TYPICAL STRIPING DETAIL (SEE PROVIDED DETAIL). | | | | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, | | | ZONING TECHNICIAN (561)805-6720 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2007-10-03 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-10-02 |
Time |
14:52 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-10-02 |
Time |
14:52 |
Sent To |
|
|
| Notes |
| 2007-10-02 14:58:53 | ***FAILED*** | | | | | | | | | 1)PLEASE PROVIDE TWO (2) COPIES OF A CURRENT SURVEY | | | SHOWING THE SETBACK DIMENSION TO THE PROPERTY LINES | | | FROM THE PROPOSED WORK. | | | | | | 2)AS THE VALUE OF THE PROPOSED WORK EXCEEDS 50% OF | | | THE STRUCTURE'S VALUE, LANDSCAPING SHALL BE BROUGHT TO | | | COMPLIANCE WITH ARTICLE XIV OF THE CITY OF WEST PALM | | | BEACH ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDRS) | | | | | | 3)INDICATE HEIGHT OF THE PROPOSED FROM GRADE TO THE | | | MIDPOINT OF THE ROOF'S PITCH. | | | | | | 4)AS YOU ARE PROPOSING TO DEMOLISH EXISTING AND | | | REBUILD, ALL NEW CONSTRUCTION SHALL CONFORM WITH | | | CURRENT REGULATIONS.A MINIMUM FRONT SETBACK OF 5' | | | SHALL BE OBSERVED.PER SECTION 94-305(E) OF THE ZLDRS: | | | NO OBJECT BETWEEN 18" AND 8' SHALL BE BUILT WITHIN THE | | | VISIBILITY TRIANGLE (20' BACK FROM CORNER OF PROPERTY) | | | | | | 5)TANDEM PARKING NOT PERMITTED. | | | | | | NOTE:THE SUBMITTAL OF THE REQUESTED INFORMATION MAY | | | GENERATE ADDITIONAL COMMENTS. | | | | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING | | | TECHNICIAN | | | (561)805-6720 |
|
|