Plan Review Details - Permit 07080649
Plan Review Stops For Permit 07080649
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-11-13 Cont ID  
Sent By shill Date 2007-11-13 Time 17:04 Rev Time 0.00
Received By shill Date 2007-11-13 Time 17:03 Sent To  
Notes
2007-11-13 17:06:38****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FACFLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 _XX_4.IMPACT PROTECTION REQUIRED,FBC1609.1.4.
  
 THE LETTER PREPARED BY CONTRACTOR WAS REVIEWED BY
 ASSISTANT BUILDING OFFICIAL, SEE ATTACHED AND REVIEW
 #2.
  
 _XX_6.PROVIDE A FLOOR PLAN SHOWING: WINDOW
 LOCATIONS, SIZES, WINDOW TYPE.
  
 THIS WAS ADDRESSED, BUT DOCUMENTS PREPARED BY AN
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-11-12 Cont ID  
Sent By rbrown Date 2007-11-12 Time 15:51 Rev Time 0.00
Received By rbrown Date 2007-11-12 Time 15:51 Sent To  
Notes
2007-11-12 16:34:03BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 LETTER DATED 10/8/07 FROM GLASS QUEST, INC. ONLY.
 REMAINDER OF REVIEW WILL BE PERFORMED BY SAMANTHA HILL.
  
  
 FBC = FLORIDA BUILDING CODE 2004
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 FEBC = FLORIDA EXISTING BUILDING CODE 2004
 F.S.= FLORIDA (STATE) STATUTE
  
 1) FBC* 102.1SPECIFIC REQUIREMENTS.IN READING THE
 FOLLOWING COMMENTS PLEASE NOTE THAT EVEN IF THERE WAS A
 CONFLICT BETWEEN A GENERAL REQUIREMENT FOR WINDOW
 REPLACEMENT AND A SPECIFIC REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 2) FEBC 303.1 CLASSIFICATION OF WORK, ALTERATION LEVEL
 1.THE REMOVAL AND REPLACEMENT OF EXISTING MATERIALS
 OR ELEMENTS USING NEW MATERIALS OR ELEMENTS IS
 CLASSIFIED AS A LEVEL 1 ALTERATION, AND SHALL COMPLY
 WITH THE PROVISIONS OF CHAPTER 5.THE DEFINITION OF
 'REPAIR' CITED IN THE LETTER IS NOT APPLICABLE BECAUSE
 WINDOW REPLACEMENT CANNOT BE CONSIDERED "MINOR
 REPLACEMENT OF MATERIALS OR ELEMENTS".SEE COMMENT (3)
 BELOW.
  
 3) FEBC 507.3REPLACEMENT OF WINDOWS.THIS SECTION IS
 SPECIFIC TO REPLACEMENT OF WINDOWS (SEE COMMENT (1)
 ABOVE).ALSO, IT IS INCLUDED IN CHAPTER 5 (LEVEL 1
 ALTERRATION), AND NOT CHAPTER 4 (REPAIR), BECAUSE
 WINDOW REPLACEMENT IS A LEVEL 1 ALTERATION NOT A
 "REPAIR".AS STATED WINDOWS THAT ARE REPLACED MUST
 COMPLY WITH CHAPTER 16 OF FLORIDA BUILDING CODE,
 INCLUDING THE REQUIREMENT FOR IMPACT PROTECTION.THE
 25% AREA EXEMPTION IS FOR ONE AND TWO FAMILY DWELLINGS,
 SO IT IS NOT APPLICABLE TO THIS PROJECT.IMPACT
 PROTECTION MUST BE PROVIDED BY THOSE WINDOWS THAT ARE
 REPLACED.THE INTENT OF THE CODE IS THAT BY PROVIDING
 IMPACT PROTECTION WITH THOSE WINDOWS THAT ARE REPLACED
 EVENTUALLY, IF ALL WINDOWS GET REPLACED AT DIFFERENT
 TIMES, ALL OF THE WINDOWS WILL OFFER IMPACT PROTECTION.
 THE CODE INTENT STANDS EVEN IF ALL OF THE WINDOWS ARE
 NOT EVENTUALLY REPLACED, BECAUSE PROVIDING IMPACT
 PROTECTION WITH THOSE WINDOWS THAT ARE REPLACED REDUCES
 THE ODDS OF WIND BORNE MISSILES IMPACTING A WINDOW THAT
 DOES NOT OFFER IMPACT PROTECTION.
  
 4) PLEASE ADDRESS ALL COMMENTS FROM SAMANTHA HILL'S
 REVIEW.
  
 ROBERT BROWN
 LICENSE AND PERMIT SERVICES MANAGER / ASSISTANT
 BUILDING OFFICIAL
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE:
 (561) 805 6652ROBERT BROWN
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-02 Cont ID  
Sent By shill Date 2007-09-02 Time 16:39 Rev Time 0.00
Received By shill Date 2007-09-02 Time 16:39 Sent To  
Notes
2007-09-02 16:41:23****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
 FACFLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 ***WINDOW OR DOOR PERMIT APPLICATION, ONLY CHECKED
 ITEMS APPLY***
  
 ____1.A NOTICE OF COMMENCEMENT MUST BE FILED WITH
 THE CLERK OF COURTS PRIOR TO PERMIT PICKUP, FS713.13.
  
 _XX_2.PROVIDE BUILDING HEIGHT.DESIGN PRESSURES
 FOR BUILDINGS OVER 60FEET ARE REQUIRED TO BE DESIGNED
 USING ASCE7, FBC1609.1.1. DOCUMENTS PREPARED BY AN
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED SEALED ORIGINALS FAC61G15-23.002.
  
 ____3.PROVIDE A COPY OF THE CONDO ASSOCIATION
 APPROVAL.
  
 _XX_4.IMPACT PROTECTION REQUIRED,FBC1609.1.4.
  
 ____5.FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED, FAC9B72, WWW.FLORIDABUILDING.ORG.
  
 _XX_6.PROVIDE A FLOOR PLAN SHOWING: WINDOW
 LOCATIONS, SIZES, WINDOW TYPE.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-10-10 Cont ID  
Sent By adarroug Date 2007-10-10 Time 16:16 Rev Time 0.00
Received By adarroug Date 2007-10-10 Time 16:16 Sent To B
Notes
2007-10-10 16:17:02TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-04 Cont ID  
Sent By adarroug Date 2007-10-04 Time 09:32 Rev Time 0.00
Received By adarroug Date 2007-10-04 Time 09:32 Sent To B
Notes
2007-10-04 09:32:22TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-09-02 Cont ID  
Sent By shill Date 2007-09-02 Time 16:41 Rev Time 0.00
Received By shill Date 2007-08-24 Time 13:39 Sent To  
Notes
2007-08-24 13:39:15TO "MISC" BOX#1

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***