Plan Review Details - Permit 07080639
Plan Review Stops For Permit 07080639
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-25 Cont ID  
Sent By mjacobs Date 2007-09-25 Time 11:05 Rev Time 0.00
Received By mjacobs Date 2007-09-21 Time 11:08 Sent To  
Notes
2007-09-21 15:34:29BUILDING PLAN REVIEW
 PERMIT: 07080639
 ADD: 605-609 PBL BLVD.
 CONT:
 TEL: (561)310-1739
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 / 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 NOTE: DUE TO THE FACT THAT A TRUE PROPERTY LINE IS NOT
 SHOWN ON THE DRAWINGS FOR EACH UNIT, AND THE TYPE AND
 OCCUPANCY OF THE BUILDINGS ARE NOT INDICATED ON THE
 DRAWINGS, THE REVIEW WILL BE IN ACCORDANCE WITH THE FBC
 2004 AND THE 2006/2007 FBC REVISIONS. THE TWO BUILDINGS
 DOES NOT MEET THE DEFINITION OF ?TOWNHOUSE? THEREFORE,
 THE WORD SHALL BE REMOVED FROM THE DRAWINGS.
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)FBC 106 ALL PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS PREPARED BY A DESIGN PROFESSIONAL AND BEING
 FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE,
 PRINTED NAME, SEAL, ADDRESS AND LICENSE NUMBER OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENTS, IN
 ACCORDANCE WITH FLORIDA STATUTES 481 AND 471.
  
 3)2004 FL. BLD CODE 1603.1.4 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE SHOWN ON THE
 CONSTRUCTION DRAWINGS,
 1) - BASIC WIND SPEED, MPH
 2) - WIND IMPORTANCE FACTOR, & BUILDING CATEGORY
 3) - WIND EXPOSURE
 4) - INTERNAL PRESSURE COEFFICIENT,
 5) - COMPONENTS & CLADDING, THE DESIGN WIND PRESSURES
 IN TERMS OF PSF.
  
 4)110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
 A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
 . -------------------------------------
 ) NUMBER OF UNITS
 ) NUMBER OF FLOORS
 ) NUMBER OF BEDROOMS
 ) NUMBER OF ROOMS
 ) NUMBER OF BEDROOMS
 ) SQ. FT. LIV SPACE/ FL
 ) SQ. FT. FOOTPRINT
  
 5)109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A
 MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF
 ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO
 AFFECT SAID PROPERTY PURSUANT TO CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS
 INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST,
 NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS
 OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS,
 DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 6)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 7)FBC 1802.2.1 QUESTIONABLE SOIL. WHERE THE BEARING
 CAPACITY OF THE SOIL IS NOT DEFINITELY KNOWN OR IS IN
 QUESTION, THE BUILDING OFFICIAL SHALL REQUIRE THAT THE
 NECESSARY INVESTIGATION BE MADE. THE INVESTIGATION
 SHALL COMPLY WITH THE PROVISIONS OF SECTIONS 1802.4
 THROUGH 1802.6 OF THE FBC. THE INVESTIGATION SHALL BE
 CERTIFIED BY A GEOTECHNICAL REPORT FROM A DESIGN
 PROFESSIONAL PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 8)FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2). IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6).
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 9)FBC 1609.6.2.2 COMPONENTS & CLADDING.PROVIDE 2
 COPIES OF PRODUCT TESTING REPORTS FOR THE FOLLOWING A)
 WINDOWS B) SWINGING DOORS C) MULLIONS D) ROOFING
 MATERIALS. SEE POLICY IN PACKAGE, E) F) STRUCTURAL
 COMPONENTS ? WOOD CONNECTORS, ANCHORS SEE RULE 9B-72.
  
 10)106.3.3* PRODUCT APPROVALS- 2004 THOSE PRODUCTS
 THAT ARE REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. SUBMIT THE
 PRODUCT APPROVALS FOR WINDOWS, DOORS, ROOFING
 MATERIALS, AND STRUCTURAL COMPONENTS ETC.
  
 11)FBC 1209.2 ATTIC SPACES.
 AN OPENING NOT LESS THAN 20 INCHES BY 30 INCHES (559 MM
 BY 762 MM) SHALL BE PROVIDED TO ANY ATTIC AREA HAVING A
 CLEAR HEIGHT OF OVER 30 INCHES (762 MM). A 30-INCH (762
 MM) MINIMUM CLEAR HEADROOM IN THE ATTIC SPACE SHALL BE
 PROVIDED AT OR ABOVE THE ACCESS OPENING. INDICATE THE
 SIZE OF THE ATTIC ACCESS ON THE PLANS.
  
 12)FBC 2303.4.1 TRUSS CONSTRUCTION DOCUMENTS SHALL
 CONFORM TO THIS SECTION OF THE FBC AND SHALL BE
 PREPARED BY A REGISTERED DESIGN PROFESSIONAL AND
 SUBMITTED TO THE BUILDING OFFICIAL PRIOR TO
 INSTALLATION.
  
 13)FBC 803.5.INTERIOR WALLS AND CEILING FINISH
 SHALL HAVE A FLAME SPREAD INDEX NOT GREATER THAN THAT
 SPECIFIED IN TABLE 803.5. STATE THE INTERIOR FINISH OF
 THE BUILDINGS.
  
 14)FL ENERGY EFFICIENCY CODE 400.ABCD. THE PERSON
 PREPARING THE COMPLIANCE CALCULATION SHALL CERTIFY THAT
 THE CALCULATION IS TRUE AND ACCURATE & DEMONSTRATES
 THAT THE BUILDING IS IN COMPLIANCE. SEE SUBCHAPTER 13-6
 OF THE FBC.
  
 15)FBC 1203.2 INDICATE ON THE DRAWINGS THE CROSS
 VENTILATION OF THE ATTIC SPACE. THE NET FREE
 VENTILATING AREA SHALL NOT BE LESS THAN 1/150 OF THE
 AREA OF THE SPACE VENTILATED. THE MINIMUM OPENINGS
 SHALL BE 1/8 INCH AND SHALL NOT EXCEED ? INCH.
  
 16)THE ROOF AND FLASHING INFORMATION ON SHEET A-15
 SHALL BE REVIEWED TO CH.15 OF THE 2004 FBC.
  
 17)INDICATE THE FIRE-RESISTANCE RATING (HOURS) FOR
 THE MASONRY DEMISING WALLS IN ACCORDANCE WITH TABLE
 721.2.3(1).
  
 104.2.1 W.P.B. ADMINISTRATIVE CODE.DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC AND
 THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR
 IN PART, NOR THE TERM "LEGAL" OR ITS RQUIVALENT BE
 USED
 AS A SUBSTITUTE FOR SPECIFIC INFORMATION"
  
 NOTE: THE ABBREVIATION LEGEND ON SHEET SP ? 1 IS NOT
 LEGIBLE.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-09-16 Cont ID  
Sent By dpalmer Date 2007-09-16 Time 09:56 Rev Time 0.00
Received By dpalmer Date 2007-09-15 Time 21:39 Sent To  
Notes
2007-09-16 09:56:482007-09-16 09:56:48
  
 ** DENIED **
  
 1) NOTE: *** IMPORTANT***
 AS THERE ARE ITEMS WHICH HAVE NOT YET BEEN SUBMITTED
 FOR PLAN REVIEW OR ON PLANS, SOME ITEMS CAN NOT BE
 REVIEWED AT THIS TIME FOR CODE COMPLIANCE.
 REVIEW CAN ONLY BE PERFORMED ON PLANS AND DOCUMENTS
 SUBMITTED AND THERE MAY VERY WELL BE NEW COMMENTS ON
 THE NEXT REVIEW.
  
 2) NOTE:PLEASE SEE THAT PLANS HAVE ONLY BEEN
 SUBMITTED FOR *PLAN REVIEW* AND HAVE NOT BEEN SUBMITTED
 FOR PERMIT APPLICATION. ONCE PLANS ARE CODE COMPLIANT
 REVIEW STATUS WILL BE STILL SHOWN IN A FAILED STATUS
 UNTIL PERMIT APPLICATION HAS BEEN APPLIED. AT TIME OF
 PERMIT APPLICATION AND BEFORE ISSUANCE OF PERMIT
 LICENSING ETC IS VERIFIED.
 ** PLEASE ALSO SEE COMMENTS FROM BUILDING REVIEWER AS
 EACH OF THESE BUILDINGS WILL MOSTLIKELY BE REQUIRED TO
 BE UNDER SEPARATE PERMITS.
  
 3) NOTE: PLEASE SEE THE SITE LIGHTING PLANS ARE NOT
 COMPLETE AT THIS TIME. PLEASE COMPLETE CIRCUITING AND
 CORRELATE WITH THE PANEL SCHEDULE WHICH IS NOTED AS
 HOUSE PANEL.
 PLEASE SUBMIT THE LIGHT POLE INFORMATION FOR
 BUILDING/STRUCTURAL REVIEW. PLEASE SEE THAT THE
 LIGHTING WATTAGES ARE REQUIRED TO BE COMPLETED AT THIS
 TIME AS THIS INFORMATION WILL BE NEEDED IN THE ENERGY
 CALCULATIONS WHICH ARE TO BE SUBMITTED.
 LIGHTING LEGEND INDICATES 60WATT FIXTURES FOR THE
 SYMBOL WHICH IS SHOWN ON PLANS FOR POLE LIGHTS, HOW
 DOES THIS PROVIDE THE PHOTO-METRIC LEVELS AS SHOWN?
 PLEASE CLARIFY THE HOUSE PANEL WHICH INDICATES BUILDING
 LIGHTING YET THE ONLY LIGHTING WHICH COULD BE LOCATED
 ON PLANS FOR BUILDING IS THIS LIGHTING FROM EACH UNIT
 AT THE ENTRANCES/EXITS.
 ** PLEASE COORDINATE ALL SITE LIGHTING AND BUILDING
 LIGHTING INFORMATION WITH PANEL, CIRCUITING, TYPES ETC.
 CAN NOT COMPLETE REVIEW ON THESE ITEMS AT THIS TIME.
  
 4) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS AND
 CORRELATE WITH A PANEL SCHEDULE TO BE SUBMITTED. NO
 PANEL SCHEDULE WAS SUBMITTED INDICATING THE MINIMUM
 REQUIRED CIRCUITS AND COORDINATION WITH PLANS CAN NOT
 BE DONE AT THIS TIME.
 PLEASE SEE THE CONDUCTOR SIZES AND OVER CURRENT/BREAKER
 SIZES FOR ALL CAN NOT BE VERIFIED.
 THERE IS A *PROVIDE PER UNIT* CIRCUIT NOTE LOCATED
 ABOVE UNITS ON BUILDING A. THIS IS NOT NEEDED, BUT MAY
 BE LOCATED ON PLANS. IF THIS IS GOING TO REMAIN PLEASE
 SEE THERE ARE SOME ITEMS WHICH DO NOT CORRELATE WITH
 OTHER INFORMATION ON PLANS.
 EXAMPLES:
 A) PLEASE SEE THE DRYER WHICH IS SHOWN AT 5KW,
 INDICATES THE CIRCUIT TO BE 20AMP.
 B) PLEASE SEE THERE IS A NOTE TO PROVIDE CIRCUIT FOR
 DISHWASHER YET NO DW IS SHOWN ON PLANS?
 C) PLEASE SEE MISSING REQUIRED DEDICATED CIRCUIT(S) FOR
 BATHROOMS PER 210.52D, 210.11C3.
 D) PLEASE SEE MISSING DINING ROOM DESIGNATION/CIRCUIT
 PER 210.52B1, 210.11C1, 220.53. AS THE CIRCUITING IS
 NOT SHOWN THIS CAN NOT BE VERIFIED AT THIS TIME FOR
 DINING.
 PLEASE COMPLETE AND SEE SOME NOTES BELOW FOR ITEMS
 WHICH WILL BE NEEDED ON PANEL SCHEDULE.
 408.4, 310.16, 240.4 ETC.
 FBC 106.3.5.4
 PLEASE SEE THE FOLLOWING TEXT WHICH IS TAKEN DIRECTLY
 FROM THE NEC CODE COMMENTARY.
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.1.2, 106.3.5.4.
 BOTH BUILDINGS. (THIS CAN BE A TYPICAL PANEL SCHEDULE
 FOR EACH OF THE UNITS WHICH ARE THE SAME).
  
 5) NOTE: PLEASE CLARIFY THE SYMBOL BEING USED FOR THE
 SMOKE ALARMS. THIS SD IS A TYPICAL UNIVERSAL SYMBOL FOR
 SMOKE DETECTOR WHICH BY DEFINITION IN NFPA-72 IS A
 DEVICE WHICH ONLY DETECTS AND DOES NOT SOUND AN ALARM.
 PLEASE VERIFY.
 BOTH BUILDINGS.
  
 6) NOTE: PLEASE CLARIFY THE LOCATION OF THE DISHWASHER
 AS NOTED ABOVE IN NOTE #4. PLEASE KNOW IF THIS FROM THE
 SAME DEVICE/YOKE AS THE DISPOSAL (DEPENDING ON
 LOCATION) THEN THE BREAKER/OVER CURRENT PROTECTION IN
 THE PANEL SCHEDULE TO BE SUBMITTED WOULD BE REQUIRED TO
 BE 2-POLE.
 210.4B
 BOTH BUILDINGS.
  
 7) NOTE: PLEASE SEE SOME CONDENSING UNITS ARE SHOWN
 WITH THE A/C DISCONNECTS BEHIND THE UNIT. PLEASE SEE
 110.26. THIS IS ONLY ON SOME OF THE UNIT. PLEASE SEE
 UNIT B AND C FOR EXAMPLE.
 BOTH BUILDINGS.
  
 8) NOTE: PLEASE CLARIFY THE SYMBOL BEING USED FOR WATER
 HEATER CONNECTION. THIS IS THE SAME SYMBOL WHICH IS
 USED FOR THE DRYER. THE DRYER IS PERMITTED TO BE CORD
 AND PLUG CONNECTED HOWEVER THE WATER HEATER IS REQUIRED
 TO BE HARDWIRED PER 422.30, 422.31. (DISCONNECT ONLY
 REQUIRED IF NOT WITHIN SITE).
 BOTH BUILDINGS.
  
 9) NOTE: PLEASE SEE THERE ARE SOME RECEPTACLES MISSING
 PER 210.52 FOR WALL SPACES.
 PLEASE SEE WALL SPACE ALONG THE STAIR SIDE OF UNITS IN
 LIVING/DINING ROOMS.
 PLEASE ALSO SEE SOME UNITS IN KITCHENS WHERE THERE IS
 2FT OR MORE OF WALL SPACE. (UNITS B AND C) PLEASE
 VERIFY AND ADJUST IN BOTH BUILDINGS.
  
 10) NOTE: PLEASE SEE THE LOAD FOR THE WATER HEATER IS
 REQUIRED TO BE FIGURED AT 1255 FOR CONTINUOUS LOAD.
 PLEASE SEE 4220.13 AS THIS WAS A CHANGE IN THE 2005
 NEC. PLEASE ADJUST CALCULATIONS.
  
 11) NOTE: PLEASE SEE MISSING ARC FAULT PROTECTION WHICH
 IS REQUIRED FOR ALL OUTLETS IN SLEEPING ROOMS. PLEASE
 SEE 210.12 OF THE 2005 NEC.
 PLANS ONLY INDICATE AFCI PROTECTION ON THE RECEPTACLES
 HOWEVER THE 2002 AND 2005 CODE EXTENDED THIS PROTECTION
 TO SMOKE ALARMS, LIGHTING, FANS ETC.
 PLEASE BE SURE TO LIST EACH ON PANEL SCHEDULE.
  
 12) NOTE: PLEASE SEE MISSING RECEPTACLE FOR 2FT OR MORE
 OF WALL IN BEDROOM #1 ON SECOND FLOOR OF UNITS *C*.
 210.52
 BOTH BUILDINGS.
  
 13) NOTE: PLEASE SUBMIT AIC RATINGS FOR ALL SERVICE
 EQUIPMENT. MAINS, BREAKERS, PANELS ETC ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 NEC 110.9.
 FBC 106.1.2, 106. 3.5.1.2 ETC
  
 14) NOTE: PLEASE SEE THE CONDUIT SIZE OF ONE AND ONE
 QUARTER INCH IS NOT LARGE ENOUGH BASED ON THE
 CONDUCTORS AND CONDUIT TYPE PER TABLES IN CHAPTER 9. AT
 POINT WHERE SCHEDULE 80 PVC MAY BE USED THIS EXCEEDS
 FILL.
 PLEASE ADJUST CONDUIT FOR FEEDERS TO UNITS IN BOTH
 BUILDINGS.
  
 15) NOTE: PLEASE SEE RISER FOR BUILDING A WHICH
 INDICATES 125AMP BREAKERS TYPICAL OF 6, YET THE HOUSE
 PANEL IS ONE OF THESE PANELS WHICH IS BEING FED AND THE
 PANEL IS ONLY RATED FOR 100AMPS WITH FEEDERS ONLY RATED
 FOR 100AMPS.
 PLEASE COORDINATE BY DECREASING OVER CURRENT PROTECTION
 TO HOUSE PANEL OR INCREASE HOUSE PANEL TO 125AMPS ALONG
 WITH FEEDERS.
 PLEASE CORRELATE. 240.4, 310.16, 408, 110.14, 110.3
 ETC
  
 16) NOTE: PLEASE SEE THE CODE SECTION WHICH IS LISTED
 ON LOAD CALCULATIONS ON SHEET E-5 IS NOT FROM THE
 CURRENT CODE. PLEASE SEE 220.32 IS LISTED.
 PLEASE SEE 2005 NEC, (220.84)
  
 17) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS. PLEASE
 SUBMIT DETAILS FOR HOW SITE LIGHTING IS BEING
 CONTROLLED.
 PLEASE SEE 13-415.1.ABC.1.4, 13-415.1.ABC.2,
 13-415.2.ABC.1.3.
 PLEASE ALSO SEE NOTES FROM OTHER TRADES (MECHANICAL AND
 BUILDING) WHICH MAY MAKE COMMENTS ALSO.
 AS THESE ARE NOT SUBMITTED AT THIS TIME, NO REVIEW CAN
 BE DONE.
  
 18) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
  
 *** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS
 OR COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE.
 IF THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY
 WAY, NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR,
 PLEASE DO NOT HESITATE IN CONTACTING THIS OFFICE AND
 THIS REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-09-16 08:27:512007-09-16 08:27:51
  
 IN PROGRESS
2007-09-15 21:39:422007-09-15 21:39:42
  
 IN ELEC FOR REVIEW.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2007-10-02 Cont ID  
Sent By rchokshi Date 2007-10-02 Time 14:07 Rev Time 0.00
Received By rchokshi Date 2007-10-02 Time 13:54 Sent To  
Notes
2007-10-02 14:07:40***FAILED**** PLEASE PROVIDE THE FOLLOWING:
  
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
 2. PLEASE SHOW ON DRAWING ALL CITY STANDARDS NOTES FOR
 SIDEWALK, DRIVEWAY, APPROACH, PARKINGS, HANDICAP
 PARKINGS, DUMPSTER ENCLOSURE, YOU CAN GET A C D FROM
 1000, 45 STREET FOR ALL THESE CITY STANDARDS NOTES.
 PHONE# 494-1040
 3. PLEASE MAKE SUR THE DUMPSTER LOCATION MUST BE
 ACCESSIBLE FOR PICKUP TRUCK.
 4. PLEASE SHOW ON CALCULATTION THAT YOU HAVE CONSIDERED
 FLOOD ZONE AREA, & 5,10, 25, 100 YEAR FLOOD CRITERIA TO
 DETERMINE THE FIRST FLOOR ELEVATION, PARING LOT
 ELEVATION, CROWN OF THE ROAD ELEVATION, SIDEWALK ETC.
 5. PLEASE SHOW ON DRAINAGE DRAWINGTHE SITE AREA,
 GREEN, LAKE,PARKING AREA, IMPERVIOUS,PERVIOUS AREAYOU
 ARE DEVELOPING FOR THIS PROJECT . PLEASEMAKE SURE
 THESE AREAS SHOWN ON DRAINAGE DRAWINGS MUST MATCH WITH
 AND USED IN STORM WATER QUALITY CALCULATIONS.
 6. PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE
 SO, WE CANSEE THE LAYOUT OF STORM WATER PIPES FROM
 ALL OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF THE
 CONTROL STRUCTURESWITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC ON DRAWINGS, CALCULATION FOR
 EXFILTRATION TRENCHES, PLEASE SHOW DRY DETENTION/WET
 DETENTION AREAS IN STORM WATER CALS.
 7. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN.
 8. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, &STORM
 WATER QUALITY CALCULATIONS. STORM WATER CALS MUST BE
 APPROVED FROM 100045TH STREET ENGINEERING SERVICES.
 9. POLLUTION PREVENTION: MAKE SURE THE HEIGHT OF SILT
 FENCE SHOULD BE HIGH ENOUGH PER FDEP TO STOP DUST &
 PARTICLES.
 10. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-10-23 Cont ID  
Sent By mcarsill Date 2007-10-23 Time 09:35 Rev Time 0.00
Received By mcarsill Date 2007-10-23 Time 09:30 Sent To  
Notes
2007-10-23 09:34:541. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 2. DEBRIS FROM THE SITE SHALL BE REMOVED DAILY.
  
 3. BUILDING ADDRESSES ARE REQUIRED. THE ADDRESSES SHALL
 BE AT LEAST 6" HIGH AND AT LEAST 1" WIDE ON A
 CONTRASTING BACKGROUND.
  
 4. SITE PLAN DOES NOT DISPLAY ANY EXISTING OR NEW FIRE
 HYDRANTS.
  
 5. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS
 FOR ALL HANDRAILS AND GUARDRAILS.
  
 6. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR
 WALLS AND CEILINGS.
  
 7. PLEASE INDICATE THE LOCATIONS OF PORTABLE FIRE
 EXTINGUISHERS.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 804-4709 PHONE
 804-4774 FAX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By adarroug Date 2007-08-23 Time 13:58 Sent To  
Notes
2007-09-11 08:59:32TO "COMM" BD#35
2007-08-23 13:58:33WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-10-31 Cont ID  
Sent By rregueir Date 2007-10-31 Time 14:15 Rev Time 0.00
Received By rregueir Date 2007-10-30 Time 15:34 Sent To PC
Notes
2007-10-31 14:15:04REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PG A-1 WHICH SHOWS PROPERTY LINES INDICATES THAT
 THESE DWELLING UNITS ARE NOT SEPARATED BY PROPERTY
 LINES AND THEREFORE DO NOT MEET THE DEFINITION OF
 TOWNHOUSES AS DEFINED IN FRC SEC.R202. THESE UNITS WILL
 BE REVIEWED AS R-2 MULTI-FAMILY RESIDENTIAL UNITS IN
 ACCORDANCE WITH FBC 310.1.
  
 2. PROVIDE AN ENERGY CODE COMPLIANCE FORM/ CALCULATIONS
 FOR EACH BUILDING TO SHOW COMPLIANCE WITH THE FLORIDA
 ENERGY EFFICIENCY CODE IN ACCORDANCE WITH FBC
 106.3.5.1.4, FBC 13-101.2.1 AND FBC 13-103.2.
  
 3. PG A-12 DOOR SCHEDULE, NOTE #4 CALLS FOR ALL
 INTERIOR DOORS TO BE MADE OF WOOD. IF MECHANICAL
 CLOSETS ARE TO BE USED AS PLENUMS, DOORS SHALL BE OF
 NON COMBUSTIBLE MATERIAL OR MEET THE 25/50 FLAME
 SPREAD/ SMOKE DEVELOPMENT RATING WHEN TESTED IN
 ACCORDANCE WITH AASTM E-84. SEE FBC,M 602.2.1. NOTE:
 WILL A 24X24 GRILL, AS CALLED FOR ON MECHANICAL FLOOR
 PLANS, FIT IN A 2FT-2IN DOOR?
  
 4. PG M-2 AND M-4: RETURN AIR TRANSFERS IN MASTER
 BEDROOMS ARE NOT DESIGNED TO MEET THE BALANCED RETURN
 EXCEPTIONS UNDER FBC,M 601.4. UNDER EXCEPTION #3, ALL
 DROPS INTO THE MASTER SUITE SHALL BE INCLUDED TO
 CALCULATE BALANCED RETURN. UNDER EXCEPTION #2, THE
 TRANSFER GRILL IS REQUIRED TO BE MIN. 50 SQ IN PER 100
 CFM. THIS MEANS A TRANSFER GRILL OF 115 SQ IN WOULD BE
 REQUIRED TO MEET THIS EXCEPTION. IF THE RETURNS ARE NOT
 DESIGNED TO MEET THESE EXCEPTIONS A FIELD TEST WILL BE
 REQUIRED AT FINAL INSPECTION TO VERIFY THAT PRESSURE
 DIFFERENTIALS TO BE 0.01IN W.C. OR LESS ACROSS CLOSED
 BEDROOM DOORS.
  
 5. PG M-1 THROUGH M-4: MECHANICAL FLOOR PLANS DO NOT
 SHOW ANY MECHANICAL VENTILATION BEING PROVIDED. SHOW
 HOW VENTILATION IS TO BE PROVIDED, ALONG WITH
 SUPPORTING CALCULATIONS, UNDER FBC,M SEC. 402 FOR
 NATURAL VENTILATION OR SEC. 403 FOR MECHANICAL. FBC
 106.1.2.
  
 6.PG M-5: CONDENSING UNIT TIE-DOWN DETAIL, PLEASE
 SHOW WHAT TYPE OF ?HURRICANE STRAP? IS TO BE USED.
 INCLUDE TYPE OF METAL, WIDTH AND THICKNESS. PROVIDE
 WIND LOAD CALCULATIONS SHOWING ATTACHMENT DESIGNED TO
 MEET MIN. 140 MPH WIND LOADS FOR STRUCTURAL REVIEW IN
 ACCORDANCE WITH FBC,M 301.13 AND FBC SEC.1609. FBC
 106.1.2.
  
 7. PG M-6: CONDENSATE TRAP DETAIL CALLS FOR CPVC OR
 COPPER DRAIN LINES IN A/C CLOSET. THESE CLOSETS ARE
 BEINGS USED AS PLENUMS AND AS SUCH, ALL MATERIALS SHALL
 BE OF NON COMBUSTIBLE MATERIAL OR MEET THE 25/50 FLAME
 SPREAD/ SMOKE DEVELOPMENT RATING WHEN TESTED IN
 ACCORDANCE WITH AASTM E-84. SEE FBC,M 602.2.1. IF CPVC
 IS TO BE USED, INDICATE THE SIZE AND PROVIDE
 MANUFACTURER?S SUBMITTAL DATA SHOWING THE FLAME SPREAD/
 SMOKE DEVELOPMENT RATING OF THAT SIZE PIPE. NOT ALL
 SIZES OF CPVC MEET THIS REQUIREMENT. NOTE: 3/4IN. CPVC
 DOES MEET THIS REQUIREMENT. HOWEVER, IT DOES NOT HAVE A
 MIN. 3/4IN. INTERNAL DIAMETER AS IS REQUIRED BY FBC,M
 307.2.2.
  
 8. PG M-6: SOFFIT DUCT HANGING DETAIL INDICATES FLEX
 DUCTS ARE TO BE HUNG WITH 1 3/8IN. WIDE HANGER STRAPS.
 IN NO CASE SHALL THE MATERIAL SUPPORTING FLEXIBLE DUCT
 THAT IS IN DIRECT CONTACT WITH IT BE LESS THAN 1?
 INCHES WIDE IN ACCORDANCE WITH FBC,M 603.5.6.6(6).
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-10-29 Cont ID  
Sent By kstevens Date 2007-10-29 Time 10:54 Rev Time 0.00
Received By kstevens Date 2007-10-29 Time 10:54 Sent To  
Notes
2007-10-29 14:05:59DENIED
 REFERENCE: FBC-2004 PLUMBING WITH 2005 & 2006
 REVISIONS
 FBC-2004 CHAPTER 1
  
 1. SHT P-1 UNITS A & B. ONLY THE FIXTURES WITHIN THE
 BATHROOM GROUP SHALL CONNECT TO THE WET-VENTED
 HORIZONTAL BRANCH DRAIN. SECTION 909.1. ADDITIONAL
 FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE WET VENT.
 (WASH MACHINE SHALL CONNECT DOWNSTREAM OF THE BATHROOM
 FIXTURES).
  
 2. SHT P-1 FIRST B UNIT ON THE LEFT SHOWS A BRANCH LINE
 FROM THE BUILDING DRAIN AT THE PORCH. PLEASE CLARIFY.
 SECTION 106.1.1.
  
 3. SHT P-2 UNITS A & B. EVERY DRY VENT CONNECTING TO A
 HORIZONTAL DRAIN SHALL CONNECT ABOVE THE CENTERLINE OF
 THE HORIZONTAL DRAIN PIPE. SECTION 905.3.(SEE VENT
 UPSTREAM OF THE SHOWER IN THE MASTER BATH). PLEASE
 DELETE DRY HORIZONTAL VENT OR SHOW COMPLIANCE.
  
 4. SHT P-3 UNITS A & B. ONLY THE FIXTURES WITHIN THE
 BATHROOM GROUP SHALL CONNECT TO THE WET-VENTED
 HORIZONTAL BRANCH DRAIN. SECTION 909.1. ADDITIONAL
 FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE WET VENT.
 (WASH MACHINE SHALL CONNECT DOWNSTREAM OF THE BATHROOM
 FIXTURES).
  
 5. SHT P-4 UNITS A & B. EVERY DRY VENT CONNECTING TO A
 HORIZONTAL DRAIN SHALL CONNECT ABOVE THE CENTERLINE OF
 THE HORIZONTAL DRAIN PIPE. SECTION 905.3.(SEE VENT
 UPSTREAM OF THE SHOWER IN THE MASTER BATH). PLEASE
 DELETE DRY HORIZONTAL VENT OR SHOW COMPLIANCE.
  
 6. SHT P-5 SANITARY RISER DIAGRAM UNIT A. THE SHOWER
 NOR THE LAV ARE VENTED IN THE FIRST FLOOR SHOWER BATH.
 SECTION 901.2.1.--SHOW ALL PIPE SIZES. MINIMUM 3"
 IS REQUIRED TO THE WASH MACHINE PER 406.3, AND NO SIZE
 TO LAV IN FIRST FLOOR SHOWER BATH IS SHOWN. TABLE
 709.1.--A STANDPIPE IS REQUIRED FOR THE TRAP TO THE
 WASH MACHINE AS WELL AS A CLEANOUT LOCATED A MINIMUM 4'
 ABOVE THE FLOOR. SECTIONS 1002.1 & 708.9.--EVERY
 DRY VENT CONNECTING TO A HORIZONTAL DRAIN SHALL CONNECT
 ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN PIPE.
 SECTION 905.3.(SEE VENT UPSTREAM OF THE SHOWER IN THE
 MASTER BATH).--THE LAV IN THE MASTER BATH IS NOT
 VENTED. SECTION 901.2.1. PLEASE CORRECT ALL CODE
 REQUIREMENTS ON THE RISER DIAGRAM.
  
 7. SHT P-5 SANITARY RISER DIAGRAM UNIT B. THE LAV IS
 NOT VENTED IN THE FIRST FLOOR POWDER ROOM. SECTION
 901.2.1.--SHOW ALL PIPE SIZES. MINIMUM 3" IS
 REQUIRED TO THE WASH MACHINE PER 406.3.--A
 STANDPIPE IS REQUIRED FOR THE TRAP TO THE WASH MACHINE
 AS WELL AS A CLEANOUT LOCATED A MINIMUM 4' ABOVE THE
 FLOOR. SECTIONS 1002.1 & 708.9.--EVERY DRY VENT
 CONNECTING TO A HORIZONTAL DRAIN SHALL CONNECT ABOVE
 THE CENTERLINE OF THE HORIZONTAL DRAIN PIPE. SECTION
 905.3.(SEE VENT UPSTREAM OF THE SHOWER IN THE MASTER
 BATH).--THE LAV IN THE MASTER BATH IS NOT VENTED.
 SECTION 901.2.1. PLEASE CORRECT ALL CODE REQUIREMENTS
 ON THE RISER DIAGRAM.
  
 8. SHT P-5 SANITARY RISER DIAGRAM UNIT C. THE LAV IS
 NOT VENTED IN THE FIRST FLOOR POWDER ROOM. SECTION
 901.2.1.--SHOW ALL PIPE SIZES. MINIMUM 3" IS
 REQUIRED TO THE WASH MACHINE PER 406.3.--A
 STANDPIPE IS REQUIRED FOR THE TRAP TO THE WASH MACHINE
 AS WELL AS A CLEANOUT LOCATED A MINIMUM 4' ABOVE THE
 FLOOR. SECTIONS 1002.1 & 708.9. PLEASE CORRECT ALL CODE
 REQUIREMENTS ON THE RISER DIAGRAM.
  
 9. SHT P-6 POTABLE RISER DIAGRAM UNIT A. WATER HAMMER
 ARRESTORS ARE REQUIRED ON THE WASH MACHINE HOT & COLD
 WATER SUPPLIES, THE HOT SUPPLY TO THE DISH WASHER AND
 TO THE COLD WATER SUPPLY TO THE ICE MAKER. SECTION
 604.9. PLEASE SHOW THE WATER HAMMER ARRESTORS LOCATED
 NEAR THE FIXTURES, NOT IN THE CEILING PER PDI-WH 201
 AND MANUF. INSTALLATION INSTRUCTIONS.--A FULL OPEN
 VALVE IS REQUIRED ON THE WATER SUPPLY LINE TO THE WATER
 HEATER PER SECTION 606.1(7). PLEASE SHOW VALVE ON RISER
 DIAGRAM.
  
 10. SHT P-6 POTABLE RISER DIAGRAM UNIT B. WATER HAMMER
 ARRESTORS ARE REQUIRED ON THE WASH MACHINE HOT & COLD
 WATER SUPPLIES, THE HOT SUPPLY TO THE DISH WASHER AND
 TO THE COLD WATER SUPPLY TO THE ICE MAKER. SECTION
 604.9. PLEASE SHOW THE WATER HAMMER ARRESTORS LOCATED
 NEAR THE FIXTURES, NOT IN THE CEILING PER PDI-WH 201
 AND MANUF. INSTALLATION INSTRUCTIONS.--A FULL OPEN
 VALVE IS REQUIRED ON THE WATER SUPPLY LINE TO THE WATER
 HEATER PER SECTION 606.1(7). PLEASE SHOW VALVE ON RISER
 DIAGRAM.--THE WATER RISER DIAGRAM DOES NOT REFLECT
 THE FLOOR PLAN AT THE WATER CLOSET. SECTION 106.1.1.
 PLEASE MAKE SURE THE RISER DIAGRAM RELECTS THE FLOOR
 PLAN.
  
 11. SHT P-6 POTABLE RISER DIAGRAM UNIT C. WATER HAMMER
 ARRESTORS ARE REQUIRED ON THE WASH MACHINE HOT & COLD
 WATER SUPPLIES, THE HOT SUPPLY TO THE DISH WASHER AND
 TO THE COLD WATER SUPPLY TO THE ICE MAKER. SECTION
 604.9. PLEASE SHOW THE WATER HAMMER ARRESTORS LOCATED
 NEAR THE FIXTURES, NOT IN THE CEILING PER PDI-WH 201
 AND MANUF. INSTALLATION INSTRUCTIONS.--A FULL OPEN
 VALVE IS REQUIRED ON THE WATER SUPPLY LINE TO THE WATER
 HEATER PER SECTION 606.1(7). PLEASE SHOW VALVE ON RISER
 DIAGRAM.--THE WATER RISER DIAGRAM DOES NOT REFLECT
 THE FLOOR PLAN AT THE WATER HEATER. SECTION 106.1.1.
 PLEASE MAKE SURE THE RISER DIAGRAM RELECTS THE FLOOR
 PLAN.
  
 12. SHT P-7 WATER HEATER DETAIL INDICATES RUN P/T AND
 PAN DRAIN TO MOP SINK. THERE IS NO MOP SINK ON THE
 PLANS. (PAN NOT REQUIRED ON THE FIRST FLOOR UNLESS ON A
 SHELF). PLEASE CLARIFY. SECTION 106.1.1.--VACUUM
 RELIEF VALVE IS REQUIRED ON ALL BOTTOM FED WATER
 HEATERS. SECTION 504.2. PLEASE INDICATE ON DETAIL IF
 BOTTOM FED AS SHOWN.
  
 13. ENERGY CALCULATIONS ARE REQUIRED FOR THE WATER
 HEATERS EACH UNIT. SECTION 13-103. PLEASE SUBMIT ENERGY
 CALCULATIONS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2007-08-28 Cont ID  
Sent By kdfreema Date 2007-08-28 Time 08:41 Rev Time 0.00
Received By kdfreema Date 2007-08-28 Time 08:41 Sent To  
Notes
2007-08-28 08:52:02***FAILED***
  
 PLEASE INCLUDE THE STAMPED DRAWINGS IN YOUR ROLLED
 SETS. SWAP OUT SHEETS ACCORDINGLY.
  
 PLEASE ENSURE CONSISTENCY BETWEEN THE PARKING DETAILS
 INCLUDED ON THE CIVIL PLANS WITH THOSE DONE BY THE
 ARCHITECT. THE ARCHITECT'S DRAWINGS ARE CORRECT AND THE
 CIVIL DRAWINGS ARE INCORRECT.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 561-822-1435
 OR [email protected] WITH QUESTIONS.