Plan Review Details - Permit 07080598
Plan Review Stops For Permit 07080598
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-12-17 Cont ID  
Sent By jwitmer Date 2007-12-17 Time 10:24 Rev Time 1.22
Received By jwitmer Date 2007-12-17 Time 10:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-17 Cont ID  
Sent By jwitmer Date 2007-09-17 Time 21:13 Rev Time 0.77
Received By jwitmer Date 2007-09-17 Time 21:13 Sent To  
Notes
2007-09-17 21:37:47 
 AN CADILLAC OF WPB LLC
 2101 45TH ST
 SEPT 17,2007
  
 BUILDING PLAN REVIEW
 PERMIT: 07080598
 ADD: 2101 45TH ST
 CONT: FILTERWORKS USA
 TEL: (954)422-8900
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) NOTICE OF COMMENCEMENT HAS EXPIRED.FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.NOTE: 713.13(2) IF THE WORK DESCRIBED IN
 THE NOTICE OFCOMMENCEMENT IS NOT ACTUALLYCOMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING THEREOF, SUCH NOTICE
 IS NULL & VOID. NOTE: 713.13(6) THE POSTING OF THE
 NOTICE OF COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE
 THE FIRST INSPECTION.
  
 3) JOHN BROWN PE, INC. PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE DESIGN
 PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
  
 4) 416.2 SPRAY ROOMS.
 SPRAY ROOMS SHALL BE ENCLOSED WITH FIRE BARRIER WALLS
 AND HORIZONTAL ASSEMBLIES OR BOTH WITH NOT LESS THAN A
 1-HOUR FIRE-RESISTANCE RATING. FLOORS SHALL BE
 WATERPROOFED AND DRAINED IN AN APPROVED MANNER. 416.2.1
 SURFACES.
 THE INTERIOR SURFACES OF SPRAY ROOMS SHALL BE SMOOTH
 AND SHALL BE SO CONSTRUCTED TO PERMIT THE FREE PASSAGE
 OF EXHAUST AIR FROM ALL PARTS OF THE INTERIOR AND TO
 FACILITATE WASHING AND CLEANING, AND SHALL BE SO
 DESIGNED TO CONFINE RESIDUES WITHIN THE ROOM. ALUMINUM
 SHALL NOT BE USED.
  
 5)110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM ISPROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
 H) SQ. FT. FOOTPRINT (BUILDING)
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE
 APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-12-03 Cont ID  
Sent By dpalmer Date 2007-12-03 Time 15:40 Rev Time 0.00
Received By dpalmer Date 2007-12-03 Time 15:40 Sent To  
Notes
2007-12-03 15:47:16ELECTRICAL RISER HAS BEEN COMPLETELY REVISED TO
 INDICATE SCOPE OF WORK WHICH IS PERMITTED TO BE DONE BY
 AN ELECTRICAL CONTRACTOR.
 STAMPED ELECTRICAL SHEETS
  
  
 ** NO COMMENTS FROM PREVIOUS ELECTRICAL REVIEW
 REQUESTED ANY ITEMS FROM MR. JOHN BROWN. THE PREVIOUS
 COMMENTS DID NOT REQUIRE ANY RESPONSE FROM THE ENGINEER
 OF STRUCTURAL ON ELECTRICAL PLANS. AS A LETTER FROM
 DESIGNER WAS ATTACHED TO ELECTRICAL PLANS WITH RESPECT
 TO COMMENTS FOR FLORIDA STATUTES. THIS OFFICE IS AWARE
 OF SCOPE OF WORK BY DESIGNERS AND WHOM CAN PERFORM OR
 SIGN AND SEAL PLANS. THIS LETTER WAS REMOVED FROM
 ELECTRICAL PLANS AS IT DID NOT APPLY TO CURRENT PLANS
 OR PREIVOUS PLANS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-09-11 Cont ID  
Sent By dpalmer Date 2007-09-11 Time 16:54 Rev Time 0.00
Received By dpalmer Date 2007-09-11 Time 16:54 Sent To  
Notes
2007-09-11 16:54:31*** DENIED ***
  
 1) NOTE: PLEASE SEE THE LATEST ADOPTED CODES RELEVANT
 TO THE MINIMUM DESIGN STANDARDS ARE TO BE STATED ON
 PLANS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
 2004 FBC W/2006 REVISIONS.
 FBC ADMIN SECTION 106.1.2, 106.1, 110.1.2
  
 2) NOTE: PLEASE SEE FS 471.003(2)H2A AS PLANS ARE
 REQUIRED TO BE DONE BY A PE LICENSED IN THE STATE OF
 FLORIDA.
 FBC 105.3.1.2
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-12-24 Cont ID  
Sent By mawillia Date 2007-12-24 Time 13:36 Rev Time 0.00
Received By mawillia Date 2007-12-24 Time 13:09 Sent To  
Notes
2007-12-24 13:31:47******APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS PLAN REVIEW HAVE BEEN
 ADDRESSED;PLAN SHEETS FP 1 AND SHEET A WERE STAMPED,
 INITIALED, AND DATED.
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-10-17 Cont ID  
Sent By mawillia Date 2007-10-17 Time 16:12 Rev Time 0.00
Received By mawillia Date 2007-10-17 Time 15:12 Sent To  
Notes
2007-10-17 16:11:42******DENIED*****
  
  
 1.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.SEVERAL SUB-PERMITS WERE SUBMITTED;PLEASE BE
 ADVISED THAT SUB-PERMITS SHALL NOT BE APPROVED/ATTAINED
 UNTIL SUCH TIME THAT THE MASTER PERMIT HAS BEEN
 ISSUED.
  
 4.THE ADDRESS OF THE PROJECT SITE SHALL BE IN THE
 TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.SHEETS A
 AND B (NO ADDRESS),SHEETS M-1, M-2, AND M-3
 (INCORRECT ADDRESS).
  
 5.PLEASE SEE & ADDRESS BUIDLING PLAN REVIEWER'S
 COMMENTS FOR FUTHERANCE OF THE FIRE PLAN REVIEW.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2007-12-20 Cont ID  
Sent By kstevens Date 2007-12-20 Time 07:28 Rev Time 0.00
Received By kstevens Date 2007-12-20 Time 07:28 Sent To  
Notes
2007-12-20 08:25:30DENIED
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 ****FROM PREVIOUS REVIEW:
  
 A. THE FOLLOWING INFORMATION IS REQUIRED FOR THE GAS
 PERMIT:
  
 1. OK
 2. OK
 3. OK
  
 4. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.--IF MECHANICAL COMBUSTION AIR
 SUPPLY SHOW COMPLIANCE WITH SECTION 304.9 AND ALL
 SUBSECTIONS.
 ****NO RESPONSE, NOT ADDRESSED.
  
 5. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
 ****NO RESPONSE, NOT ADDRESSED.
  
 6. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.--ETL TESTING
 REPORS STATES, "THE PRODUCT COVERED BY THIS REPORT IS A
 PAINT SPRAY BOOTH THAT IS INTENDED TO BE USED WITH A
 LISTED NATURAL GAS HEATING/AIR HANDLING UNIT. PLEASE
 PROVIDE THE MANUF. SPECIFICATIONS SHOWING LISTING AND
 INSTALLATION INSTRUCTIONS FOR THE HEATING/AIR HANDLING
 UNIT.
 ****NO RESPONSE, NOTE ADDRESSED.
  
 7. OK
 8. OK
 9. OK
  
 10. SUBMIT MANUF. MSDS SHEETS FOR ALL MATERIALS
 ASSOCIATED WITH THE PAINT BOOTH AND RELATED CLEANUP. AN
 EYE WASH AND/OR EMERGENCY SHOWER MAY BE REQUIRED.
 SECTION 106.1.2.
 ****NO RESPONSE, NOT ADDRESSED
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-10-12 Cont ID  
Sent By kstevens Date 2007-10-12 Time 16:39 Rev Time 0.00
Received By kstevens Date 2007-10-12 Time 16:39 Sent To  
Notes
2007-10-12 16:56:51DENIED
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 A. THE FOLLOWING INFORMATION IS REQUIRED FOR THE GAS
 PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. - SHOW LENGTH FROM METER TO FIRST TEE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). - 150 FT SHOWN, BUT IT
 ADDS UP TO 155 FT NOT COUNTING THE LENGTH FROM THE
 METER TO THE FIRST TEE.--ALSO INDICATE THE LENGTH
 FROM THE METER TO THE MOST REMOTE OUTLET ON THE
 EXISTING LINE AS ALL GAS PIPING SHALL BE SIZED FROM THE
 LONGEST LENGTH.
  
 4. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.--IF MECHANICAL COMBUSTION AIR
 SUPPLY SHOW COMPLIANCE WITH SECTION 304.9 AND ALL
 SUBSECTIONS.
  
 5. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 6. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.--ETL TESTING
 REPORS STATES, "THE PRODUCT COVERED BY THIS REPORT IS A
 PAINT SPRAY BOOTH THAT IS INTENDED TO BE USED WITH A
 LISTED NATURAL GAS HEATING/AIR HANDLING UNIT. PLEASE
 PROVIDE THE MANUF. SPECIFICATIONS SHOWING LISTING AND
 INSTALLATION INSTRUCTIONS FOR THE HEATING/AIR HANDLING
 UNIT.
  
 7. A SHUT OFF VALVE IS REQUIRED UPSTREAM OF THE
 REGULATOR. SECTION 409.4. PLEASE SHOW ON RISER
 DIAGRAM.
  
 8. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE
 REGULATOR AND INDICATE/HIGHLIGHT THE MODEL NUMBER BEING
 USED. SECTION 106.2.1. MORE INFORMATION REQUIRED.
  
 9. THE PERSON DRAWING THE GAS RISER DIAGRAM SHALL PRINT
 THEIR NAME AND SIGN THE RISER DIAGRAM. SECTION
 106.3.4.3.
  
 10 SUBMIT MANUF. MSDS SHEETS FOR ALL MATERIALS
 ASSOCIATED WITH THE PAINT BOOTH AND RELATED CLEANUP. AN
 EYE WASH AND/OR EMERGENCY SHOWER MAY BE REQUIRED.
 SECTION 106.1.2.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-15 Cont ID  
Sent By adarroug Date 2007-11-15 Time 09:30 Rev Time 0.00
Received By adarroug Date 2007-11-15 Time 09:30 Sent To  
Notes
2007-11-27 14:38:25TO "COMM" BD#57
2007-11-15 09:31:31WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-17 Cont ID  
Sent By mawillia Date 2007-10-17 Time 15:12 Rev Time 0.00
Received By mawillia Date 2007-08-22 Time 16:40 Sent To  
Notes
2007-09-11 09:09:57TO "COMM" BD#50
2007-08-22 16:42:56WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-12-11 Cont ID  
Sent By tgordon Date 2007-12-11 Time 15:41 Rev Time 0.30
Received By tgordon Date 2007-12-11 Time 15:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-09-26 Cont ID  
Sent By hmoser Date 2007-09-26 Time 17:05 Rev Time 0.00
Received By hmoser Date 2007-09-26 Time 16:23 Sent To  
Notes
2007-09-26 17:30:181- PLEASE PROVIDE EXHAUST AND INTAKE DUCT SIZE ON THE
 MECHANICALPLANS .
 2- PLEASE PROVIDE A FAN SCHEDULE FOR EXHAUST AND SUPPLY
 FANS ON MECHANICAL PLANS .
 3- PLEASE PROVIDE A DETAIL FORCURB TIE DOWN TO ROOF
 ON MECHANICAL PLANS .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop Z ZONING
Rev No 1 Status N Date 2007-09-14 Cont ID  
Sent By kdfreema Date 2007-09-14 Time 13:23 Rev Time 0.00
Received By kdfreema Date 2007-09-14 Time 13:23 Sent To  
Notes
***NONE***