| Plan Review Stops For Permit 07080598 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2007-12-17 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-12-17 |
Time |
10:24 |
Rev Time |
1.22 |
| Received By |
jwitmer |
Date |
2007-12-17 |
Time |
10:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-09-17 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-09-17 |
Time |
21:13 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2007-09-17 |
Time |
21:13 |
Sent To |
|
|
| Notes |
| 2007-09-17 21:37:47 | | | | AN CADILLAC OF WPB LLC | | | 2101 45TH ST | | | SEPT 17,2007 | | | | | | BUILDING PLAN REVIEW | | | PERMIT: 07080598 | | | ADD: 2101 45TH ST | | | CONT: FILTERWORKS USA | | | TEL: (954)422-8900 | | | | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | 2) NOTICE OF COMMENCEMENT HAS EXPIRED.FL S S 713.13 | | | NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF | | | THE COURT.NOTE: 713.13(2) IF THE WORK DESCRIBED IN | | | THE NOTICE OFCOMMENCEMENT IS NOT ACTUALLYCOMMENCED | | | WITHIN 90 DAYS AFTER THE RECORDING THEREOF, SUCH NOTICE | | | IS NULL & VOID. NOTE: 713.13(6) THE POSTING OF THE | | | NOTICE OF COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE | | | THE FIRST INSPECTION. | | | | | | 3) JOHN BROWN PE, INC. PLANS, SPECIFICATIONS, | | | REPORTS OR OTHER DOCUMENTS PREPARED BY THE DESIGN | | | PROFESSIONAL AND BEING FILED FOR PUBLIC | | | RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE DESIGN | | | PROFESSIONAL AFFIXED TO THE DOCUMENT. | | | FL STATE STAT: 61G15-23.002 ENGINEERS | | | | | | 4) 416.2 SPRAY ROOMS. | | | SPRAY ROOMS SHALL BE ENCLOSED WITH FIRE BARRIER WALLS | | | AND HORIZONTAL ASSEMBLIES OR BOTH WITH NOT LESS THAN A | | | 1-HOUR FIRE-RESISTANCE RATING. FLOORS SHALL BE | | | WATERPROOFED AND DRAINED IN AN APPROVED MANNER. 416.2.1 | | | SURFACES. | | | THE INTERIOR SURFACES OF SPRAY ROOMS SHALL BE SMOOTH | | | AND SHALL BE SO CONSTRUCTED TO PERMIT THE FREE PASSAGE | | | OF EXHAUST AIR FROM ALL PARTS OF THE INTERIOR AND TO | | | FACILITATE WASHING AND CLEANING, AND SHALL BE SO | | | DESIGNED TO CONFINE RESIDUES WITHIN THE ROOM. ALUMINUM | | | SHALL NOT BE USED. | | | | | | 5)110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION | | | THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE | | | OF OCCUPANCY: | | | A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS | | | DESIGNED. | | | B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE | | | PROVISIONS OF CHAPTER 3. | | | C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6, | | | TABLE 601. | | | D) THE OCCUPANT LOAD, SEE 1004. | | | E) IF AN AUTOMATIC SPRINKLER SYSTEM ISPROVIDED | | | F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED. | | | G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE | | | BUILDING PERMIT | | | H) SQ. FT. FOOTPRINT (BUILDING) | | | | | | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS | | | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF | | | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST | | | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT | | | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC | | | REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE | | | APPLICABLE. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | | | | | | | | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2007-12-03 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-12-03 |
Time |
15:40 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-12-03 |
Time |
15:40 |
Sent To |
|
|
| Notes |
| 2007-12-03 15:47:16 | ELECTRICAL RISER HAS BEEN COMPLETELY REVISED TO | | | INDICATE SCOPE OF WORK WHICH IS PERMITTED TO BE DONE BY | | | AN ELECTRICAL CONTRACTOR. | | | STAMPED ELECTRICAL SHEETS | | | | | | | | | ** NO COMMENTS FROM PREVIOUS ELECTRICAL REVIEW | | | REQUESTED ANY ITEMS FROM MR. JOHN BROWN. THE PREVIOUS | | | COMMENTS DID NOT REQUIRE ANY RESPONSE FROM THE ENGINEER | | | OF STRUCTURAL ON ELECTRICAL PLANS. AS A LETTER FROM | | | DESIGNER WAS ATTACHED TO ELECTRICAL PLANS WITH RESPECT | | | TO COMMENTS FOR FLORIDA STATUTES. THIS OFFICE IS AWARE | | | OF SCOPE OF WORK BY DESIGNERS AND WHOM CAN PERFORM OR | | | SIGN AND SEAL PLANS. THIS LETTER WAS REMOVED FROM | | | ELECTRICAL PLANS AS IT DID NOT APPLY TO CURRENT PLANS | | | OR PREIVOUS PLANS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-09-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-09-11 |
Time |
16:54 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-09-11 |
Time |
16:54 |
Sent To |
|
|
| Notes |
| 2007-09-11 16:54:31 | *** DENIED *** | | | | | | 1) NOTE: PLEASE SEE THE LATEST ADOPTED CODES RELEVANT | | | TO THE MINIMUM DESIGN STANDARDS ARE TO BE STATED ON | | | PLANS. | | | 2005 NFPA-70 | | | 2003 NFPA-101 | | | 2002 NFPA-72 | | | 2004 FBC W/2006 REVISIONS. | | | FBC ADMIN SECTION 106.1.2, 106.1, 110.1.2 | | | | | | 2) NOTE: PLEASE SEE FS 471.003(2)H2A AS PLANS ARE | | | REQUIRED TO BE DONE BY A PE LICENSED IN THE STATE OF | | | FLORIDA. | | | FBC 105.3.1.2 | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2007-12-24 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-12-24 |
Time |
13:36 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-12-24 |
Time |
13:09 |
Sent To |
|
|
| Notes |
| 2007-12-24 13:31:47 | ******APPROVED***** | | | | | | THE COMMENTS FROM THE PREVIOUS PLAN REVIEW HAVE BEEN | | | ADDRESSED;PLAN SHEETS FP 1 AND SHEET A WERE STAMPED, | | | INITIALED, AND DATED. | | | | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2007-10-17 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-10-17 |
Time |
16:12 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-10-17 |
Time |
15:12 |
Sent To |
|
|
| Notes |
| 2007-10-17 16:11:42 | ******DENIED***** | | | | | | | | | 1.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED. | | | | | | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 3.SEVERAL SUB-PERMITS WERE SUBMITTED;PLEASE BE | | | ADVISED THAT SUB-PERMITS SHALL NOT BE APPROVED/ATTAINED | | | UNTIL SUCH TIME THAT THE MASTER PERMIT HAS BEEN | | | ISSUED. | | | | | | 4.THE ADDRESS OF THE PROJECT SITE SHALL BE IN THE | | | TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.SHEETS A | | | AND B (NO ADDRESS),SHEETS M-1, M-2, AND M-3 | | | (INCORRECT ADDRESS). | | | | | | 5.PLEASE SEE & ADDRESS BUIDLING PLAN REVIEWER'S | | | COMMENTS FOR FUTHERANCE OF THE FIRE PLAN REVIEW. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2007-12-20 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-12-20 |
Time |
07:28 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-12-20 |
Time |
07:28 |
Sent To |
|
|
| Notes |
| 2007-12-20 08:25:30 | DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | FBC-2004 CHAPTER 1 | | | | | | ****FROM PREVIOUS REVIEW: | | | | | | A. THE FOLLOWING INFORMATION IS REQUIRED FOR THE GAS | | | PERMIT: | | | | | | 1. OK | | | 2. OK | | | 3. OK | | | | | | 4. SUBMIT CALCULATIONS FOR COMBUSTION | | | AIR (IF APPLICABLE) PER FBC-2004 FUEL | | | GAS CODE SECTION 304.--IF MECHANICAL COMBUSTION AIR | | | SUPPLY SHOW COMPLIANCE WITH SECTION 304.9 AND ALL | | | SUBSECTIONS. | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | 5. SUBMIT A DETAIL SHOWING THE TYPE, | | | LOCATION, SIZE AND TERMINATION OF THE | | | GAS VENTS PER FBC-2004 FUEL GAS CODE | | | SECS. 502 THRU 505. | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | 6. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2.--ETL TESTING | | | REPORS STATES, "THE PRODUCT COVERED BY THIS REPORT IS A | | | PAINT SPRAY BOOTH THAT IS INTENDED TO BE USED WITH A | | | LISTED NATURAL GAS HEATING/AIR HANDLING UNIT. PLEASE | | | PROVIDE THE MANUF. SPECIFICATIONS SHOWING LISTING AND | | | INSTALLATION INSTRUCTIONS FOR THE HEATING/AIR HANDLING | | | UNIT. | | | ****NO RESPONSE, NOTE ADDRESSED. | | | | | | 7. OK | | | 8. OK | | | 9. OK | | | | | | 10. SUBMIT MANUF. MSDS SHEETS FOR ALL MATERIALS | | | ASSOCIATED WITH THE PAINT BOOTH AND RELATED CLEANUP. AN | | | EYE WASH AND/OR EMERGENCY SHOWER MAY BE REQUIRED. | | | SECTION 106.1.2. | | | ****NO RESPONSE, NOT ADDRESSED | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2007-10-12 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-10-12 |
Time |
16:39 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-10-12 |
Time |
16:39 |
Sent To |
|
|
| Notes |
| 2007-10-12 16:56:51 | DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | FBC-2004 CHAPTER 1 | | | | | | A. THE FOLLOWING INFORMATION IS REQUIRED FOR THE GAS | | | PERMIT: | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. - SHOW LENGTH FROM METER TO FIRST TEE. | | | | | | 2. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE IF BEING USED. | | | | | | 3. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). - 150 FT SHOWN, BUT IT | | | ADDS UP TO 155 FT NOT COUNTING THE LENGTH FROM THE | | | METER TO THE FIRST TEE.--ALSO INDICATE THE LENGTH | | | FROM THE METER TO THE MOST REMOTE OUTLET ON THE | | | EXISTING LINE AS ALL GAS PIPING SHALL BE SIZED FROM THE | | | LONGEST LENGTH. | | | | | | 4. SUBMIT CALCULATIONS FOR COMBUSTION | | | AIR (IF APPLICABLE) PER FBC-2004 FUEL | | | GAS CODE SECTION 304.--IF MECHANICAL COMBUSTION AIR | | | SUPPLY SHOW COMPLIANCE WITH SECTION 304.9 AND ALL | | | SUBSECTIONS. | | | | | | 5. SUBMIT A DETAIL SHOWING THE TYPE, | | | LOCATION, SIZE AND TERMINATION OF THE | | | GAS VENTS PER FBC-2004 FUEL GAS CODE | | | SECS. 502 THRU 505. | | | | | | 6. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2.--ETL TESTING | | | REPORS STATES, "THE PRODUCT COVERED BY THIS REPORT IS A | | | PAINT SPRAY BOOTH THAT IS INTENDED TO BE USED WITH A | | | LISTED NATURAL GAS HEATING/AIR HANDLING UNIT. PLEASE | | | PROVIDE THE MANUF. SPECIFICATIONS SHOWING LISTING AND | | | INSTALLATION INSTRUCTIONS FOR THE HEATING/AIR HANDLING | | | UNIT. | | | | | | 7. A SHUT OFF VALVE IS REQUIRED UPSTREAM OF THE | | | REGULATOR. SECTION 409.4. PLEASE SHOW ON RISER | | | DIAGRAM. | | | | | | 8. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE | | | REGULATOR AND INDICATE/HIGHLIGHT THE MODEL NUMBER BEING | | | USED. SECTION 106.2.1. MORE INFORMATION REQUIRED. | | | | | | 9. THE PERSON DRAWING THE GAS RISER DIAGRAM SHALL PRINT | | | THEIR NAME AND SIGN THE RISER DIAGRAM. SECTION | | | 106.3.4.3. | | | | | | 10 SUBMIT MANUF. MSDS SHEETS FOR ALL MATERIALS | | | ASSOCIATED WITH THE PAINT BOOTH AND RELATED CLEANUP. AN | | | EYE WASH AND/OR EMERGENCY SHOWER MAY BE REQUIRED. | | | SECTION 106.1.2. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-11-15 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-11-15 |
Time |
09:30 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-11-15 |
Time |
09:30 |
Sent To |
|
|
| Notes |
| 2007-11-27 14:38:25 | TO "COMM" BD#57 | | 2007-11-15 09:31:31 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-10-17 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-10-17 |
Time |
15:12 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-08-22 |
Time |
16:40 |
Sent To |
|
|
| Notes |
| 2007-09-11 09:09:57 | TO "COMM" BD#50 | | 2007-08-22 16:42:56 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2007-12-11 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-12-11 |
Time |
15:41 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2007-12-11 |
Time |
15:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2007-09-26 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2007-09-26 |
Time |
17:05 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2007-09-26 |
Time |
16:23 |
Sent To |
|
|
| Notes |
| 2007-09-26 17:30:18 | 1- PLEASE PROVIDE EXHAUST AND INTAKE DUCT SIZE ON THE | | | MECHANICALPLANS . | | | 2- PLEASE PROVIDE A FAN SCHEDULE FOR EXHAUST AND SUPPLY | | | FANS ON MECHANICAL PLANS . | | | 3- PLEASE PROVIDE A DETAIL FORCURB TIE DOWN TO ROOF | | | ON MECHANICAL PLANS . | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2007-09-14 |
|
|
Cont ID |
|
| Sent By |
kdfreema |
Date |
2007-09-14 |
Time |
13:23 |
Rev Time |
0.00 |
| Received By |
kdfreema |
Date |
2007-09-14 |
Time |
13:23 |
Sent To |
|
|
| Notes |
|
|