| 2007-09-08 21:11:35 | 2007-09-08 21:11:35 |
| | |
| | ** DENIED ** |
| | |
| | |
| | |
| | 1) NOTE:PLEASE KNOW THAT THE CHANGE IN OCCUPANCY |
| | BASED ON PLANS SUBMITTED AND WORK FROM A BUSINESS TO |
| | EDUCATION WILL REQUIRE WORK WHICH IS REQUIRED TO BE |
| | DONE BY CONTRACTORS LICENSED UNDER FLORIDA STATUTES |
| | 489. |
| | |
| | 2) NOTE: PLEASE KNOW ONCE THE VALUE FOR THE COMPLETE |
| | SCOPE OF CONSTRUCTION, DESIGN, MATERIALS AND EQUIPMENT |
| | HAS BEEN DETERMINED, THE APPLIED VALUE IS REQUIRED TO |
| | MEET FBC 108.3. |
| | |
| | 3) NOTE: PLEASE SEE FBC 2004 W/2006 REVISIONS |
| | SPECIFICALLY THE EXISTING BUILDING CODE CHAPTER 8 FOR |
| | CHANGES IN OCCUPANCY. THE OCCUPANCY CLASSIFICATION OR |
| | GROUP IN CHANGING TO A HIGHER HAZARD AND WILL REQUIRE |
| | SOME SYSTEMS TO BE BROUGHT UP TO CODE IF THEY DO NOT |
| | MEET THE MINIMUM CODES AT THIS TIME. |
| | PLEASE SEE SECTION 808.2, 808.3, 808.4 AND 812, |
| | 812.4.1. AS ELECTRICAL OUTLETS WHICH INCLUDE, LIGHTING |
| | FIXTURES, RECEPTACLES, ELECTRICAL PANELS ETC WHICH DO |
| | NOT MEET THE CURRENT NATIONAL ELECTRICAL CODE AND FCB |
| | CHAPTER 27 WILL BE REQUIRED TO BE BROUGHT UP TO CODE OR |
| | SHOWN AS EXISTING WHICH MEETS THE CURRENT MINIMUM |
| | CODES. |
| | |
| | ** PLEASE SEE NOTES FROM FIRE MARSHAL AND BUILDING |
| | REVIEWER WHICH WILL REQUIRE SOME OTHER SYSTEMS TO MEET |
| | THE CURRENT CODES FOR LIFE SAFETY ETC. |
| | |
| | 4) NOTE: PLEASE SEE NFPA-101 CHAPTER 14 FOR NEW |
| | EDUCATION OCCUPANCIES. |
| | PLEASE SEE CHAPTER 7 FOR MINIMUM LIGHTING FOR EGRESS TO |
| | MEET CURRENT CODES. |
| | THE AMOUNT OF EMERGENCY LIGHTING FIXTURES SHOWN IN |
| | STAIR AREA ON THE NORTH SIDE OF SPACE DOES NOT MEET THE |
| | MINIMUM LEVELS. |
| | PLEASE SUBMIT PHOTO-METRICS FOR NORMAL AND EMERGENCY |
| | LEVELS INCLUDING STAIRS UNDER BOTH CONDITIONS. PLEASE |
| | SEE 7.8.1.3 AND 7.9.2.2. |
| | FAC 61G15-33.004 |
| | ** PLEASE SEE 700.12F FOR CIRCUITING OF THESE |
| | FIXTURES. |
| | |
| | 5) NOTE: PLEASE SEE SECTION 812 AS NOTED ABOVE IN NOTE |
| | #3 FOR THE FIRE ALARM SYSTEM/DEVICES WHICH IS REQUIRED |
| | TO MEET CURRENT CODES IF NOT ALREADY MEETING |
| | NFPA-72/NFPA-70 AND FBC CHAPTER 11. |
| | PLEASE INDICATE THE MINIMUM LEVELS FOR ALL ADA DEVICES |
| | PER FBC 11-4.28.1, .2 AND .3(4). |
| | |
| | 6) NOTE: PLEASE COMPLETE PLANS INDICATING ALL LIGHTING. |
| | PLEASE SEE FBC CHAPTER 13, 13-415.1.ABC.1.1, AND .1.3. |
| | PLEASE SEE 13-415.2 FOR LIGHTING PERFORMANCE DENSITIES |
| | REQUIRED. |
| | FBC, EBC, SECTION 811. |
| | |
| | 7) NOTE: PLEASE SUBMIT INFORMATION ON THE EXISTING |
| | ELECTRICAL SERVICE, PANELS AND EQUIPMENT FOR THE |
| | ELECTRICAL LOADS PROPOSED. EVEN AS LOADS MAY NOT BE |
| | INCREASING THE VERIFICATION OF THE EXISTING SERVICE |
| | EQUIPMENT NEEDS TO BE VERIFIED. |
| | FBC EBC, 808.3 AND FBC CHAPTER 27. |
| | |
| | 8) NOTE: PLEASE SEE THE SITE PLAN ON THE SHEET AND AREA |
| | AS SPECIFIED INVOKES PLACES OF ASSEMBLY PER NEC 518.1. |
| | |
| | PLEASE SEE LS 101 |
| | |
| | 9) NOTE: PLEASE SEE NOTES FROM BUILDING AND FIRE |
| | MARSHAL WITH RESPECT TO THE STORAGE ADJACENT TO THIS |
| | OCCUPANCY. WHAT IS STORED IN THIS ROOM? |
| | |
| | 10) NOTE: PLEASE KNOW THE APPLICATION IS ALSO BEING |
| | ROUTED TO OUR ADDRESSING REVIEWER SO THAT A CORRECT |
| | SUITE/UNIT NUMBER MAY BE AASIGNED. |
| | PLEASE BE SURE TO INCLUDE THIS ON THE APPLICATION AND |
| | TITLE BLOCKS ON PLANS ONCE THIS HAS BEEN DETERMINED. |
| | FBC 106.1.2, 106.1, 110.1.2 ETC |
| | FAC 61G1-16.004, |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |