Plan Review Details - Permit 07080575
Plan Review Stops For Permit 07080575
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-09-13 Cont ID  
Sent By shill Date 2007-09-13 Time 07:54 Rev Time 0.00
Received By shill Date 2007-09-13 Time 07:54 Sent To  
Notes
2007-09-13 07:54:55****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
  
 1.)SIDELITES WERE NOT INCLUDED IN THE CALCULATIONS.
 WHEN THE TWO SIDELITES (1X6.66 X 2) ARE ADDED, THIS IS
 OVER 29% REPLACEMENT.ALSO, NO INFORMATION WAS
 PROVIDED IN REGARDS TO THE EXISTING DOORS AS
 REQUESTED.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-02 Cont ID  
Sent By shill Date 2007-09-02 Time 16:26 Rev Time 0.00
Received By shill Date 2007-09-02 Time 16:26 Sent To  
Notes
2007-09-02 16:27:01****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
 FACFLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 ***WINDOW OR DOOR PERMIT APPLICATION, ONLY CHECKED
 ITEMS APPLY***
  
 ____1.A NOTICE OF COMMENCEMENT MUST BE FILED WITH
 THE CLERK OF COURTS PRIOR TO PERMIT PICKUP, FS713.13.
  
 ____2.PROVIDE BUILDING HEIGHT.DESIGN PRESSURES
 FOR BUILDINGS OVER 60FEET ARE REQUIRED TO BE DESIGNED
 USING ASCE7, FBC1609.1.1. DOCUMENTS PREPARED BY AN
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED SEALED ORIGINALS FAC61G15-23.002.
  
 ____3.PROVIDE A COPY OF THE CONDO ASSOCIATION
 APPROVAL.
  
 _XX_4.IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R
 301.2.1.2.PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS
 ARE USED, COMPLETE THE ATTACHED INSTALLATION SCHEDULE.
 IF YOU ARE USING THE 25% EXEMPTION, PROVIDE
 CALCULATIONS AND PROVIDE INFORMATION IN REGARDS TO THE
 EXISTING DOORS (AMOUNT OF GLAZING).
  
 ____5.FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED, FAC9B72, WWW.FLORIDABUILDING.ORG.
  
 ____6.PROVIDE A FLOOR PLAN SHOWING: WINDOW
 LOCATIONS, SIZES, WINDOW TYPE, ROOM DESIGNATIONS.NOTE
 EXISTING CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE
 FOR BEDROOMS, FBC R310, FBC EB 505.1.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-09-11 Cont ID  
Sent By adarroug Date 2007-09-11 Time 14:23 Rev Time 0.00
Received By adarroug Date 2007-09-11 Time 14:23 Sent To B
Notes
2007-09-11 14:23:24TO "SHILL'D ESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-09-02 Cont ID  
Sent By shill Date 2007-09-02 Time 16:27 Rev Time 0.00
Received By shill Date 2007-08-22 Time 13:45 Sent To  
Notes
2007-08-22 13:45:46TO "MISC" BOX#1

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***