| Plan Review Stops For Permit 07080572 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
P |
Date |
2007-10-16 |
|
|
Cont ID |
|
| Sent By |
lursu |
Date |
2007-10-16 |
Time |
14:47 |
Rev Time |
0.00 |
| Received By |
lursu |
Date |
2007-10-16 |
Time |
14:47 |
Sent To |
|
|
| Notes |
| 2007-10-16 14:50:44 | THE RECORDED UNITY OF TITLE FOR THESE TWO PARCELS WAS | | | RECEIVED AND A NEW SITE ADDRESS : 2671 DAKOTA CIR ,WEST | | | PALM BEACH, FL 33409 IS ASSIGNED TO THE NEW SINGLE | | | HOUSE.BASED ON THE UOT A NEW PARCEL CONTROL NUMBER WILL | | | BE ISSUED BY THE PROPERTY APPRAISER'S OFFICE . | | | | | | LACRAMIOARA URSU | | | MIS - GIS SUPPORT SPECIALIST | | | CITY OF WEST PALM BEACH | | | OFFICE:822-1239 | | | FAX: 822-1249 | | | E-MAIL:[email protected] |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
F |
Date |
2007-08-31 |
|
|
Cont ID |
|
| Sent By |
lursu |
Date |
2007-08-31 |
Time |
11:27 |
Rev Time |
0.00 |
| Received By |
lursu |
Date |
2007-08-31 |
Time |
11:27 |
Sent To |
|
|
| Notes |
| 2007-08-31 11:36:08 | PRIOR OF ISSUING THE NEW SITE ADDRESS FOR THE NEW HOUSE | | | , THE UNITY OF TITLE FOR THE TWO PARCELS MUST BE | | | RECORDED .THE PROPERTY APPRAISER'S OFFICE WILL ISSUE A | | | NEW PARCEL CONTROL NUMBER FOR THE UNIFIED PROPERTIES | | | AND BASED ON THE NEW PCN, THE CITY WILL ISSUE THE NEW | | | SITE ADDRESS. | | | | | | LACRAMIOARA URSU | | | MIS - GIS SUPPORT SPECIALIST | | | CITY OF WEST PALM BEACH | | | OFFICE:822-1239 | | | FAX: 822-1249 | | | E-MAIL:[email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
8 |
Status |
P |
Date |
2009-04-30 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2009-04-30 |
Time |
08:37 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2009-04-30 |
Time |
08:37 |
Sent To |
|
|
| Notes |
| 2009-04-30 09:32:26 | REVISION TO REPLACE GARAGE SIDE DOOR WITH ONE OF A KIND | | | SITE SPECIFIC DOOR IS OK. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
F |
Date |
2009-04-15 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2009-04-15 |
Time |
10:04 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2009-04-15 |
Time |
10:04 |
Sent To |
|
|
| Notes |
| 2009-04-15 10:41:03 | REVISION DENIED BY BUILDING | | | | | | | | | 1) THE REVISION TO CHANGE FRONT DOOR IS OK. FL. PRODUCT | | | APPROVALS WERE SUBMITTED. PLACE COPY OF STAMPED PRODUCT | | | APPROVAL WITH THE PLANS. | | | | | | 2) THE REVISION TO CHANGE SIDE DOOR IS DENIED. THIS | | | DOOR DOES NOT HAVE STATE PRODUCT APPROVAL. LOCAL/SITE | | | SPECIFIC ENGINEERING IS REQUIRED IN ACCORDANCE WITH DCA | | | RULE 9B-72. ORIGINAL SIGNED AND SEALED DOCUMENTS FROM | | | THE ENGINEER ARE REQUIRED. NOTE: THE DESIGN PRESSURES | | | IN THE SUBMITTAL OF +36.0 PSF, -39.3 PSF ARE TOO LOW. | | | THE STRUCTURE IS LOCATED IN EXPOSURE CATEGORY C THE | | | OPENING PRESSURE OF +47.5 PSF, -51.8 PSF ARE SPECIFIED | | | ON SHEET S3.02 OF THE PLANS FOR A 20 SQFT OPENING. THE | | | STREET NAME ON THE LETTER IS INCORRECT, IT IS DAKOTA | | | CIRCLE. PLEASE CORRECT. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2008-02-11 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2008-02-11 |
Time |
11:05 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2008-02-11 |
Time |
11:05 |
Sent To |
|
|
| Notes |
| 2008-02-11 11:07:15 | CONTRACTOR SUBMITTED PRODUCT APPROVAL FOR GARAGE DOORS | | | WITH ADEQUATE DESIGN PRESSURES AS REQUESTED IN THE | | | BUILDING PROVISO. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2008-01-31 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2008-01-31 |
Time |
15:38 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2008-01-31 |
Time |
07:01 |
Sent To |
|
|
| Notes |
| 2008-01-31 15:38:42 | | | | BUILDING PROVISO | | | | | | SUBMIT PRODUCT APPROVALS FOR THE 9' X 8' OVERHEAD | | | GARAGE DOORS WITH DESIGN PRESSURES GREATER THAN + 43.7 | | | / -49.5 PSF. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2008-01-17 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2008-01-17 |
Time |
11:29 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2008-01-16 |
Time |
11:27 |
Sent To |
|
|
| Notes |
| 2008-01-17 11:41:10 | 2004 FBC W/2007 SUPPLEMENTS | | | NSFR | | | | | | DENIED BY BUILDING | | | | | | 1) COMPLIED | | | | | | 2) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT | | | MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. WORK MUST COMMENCE WITHIN 90 DAYS | | | OF THE DATE THE NOC IS RECORDED. FS 713.13. THE ONE | | | THAT WAS SUBMITTED IS EXPIRED. | | | | | | 3) IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY, PLANS STAMPED BY THEM AND | | | COPY OF RECEIPT SUBMITTED TO CITY OF | | | WEST PALM BEACH BUILDING DEPARTMENT, | | | BEFORE A BUILDING PERMIT CAN BE ISSUED. SUBMIT COPY OF | | | THE PAID RECEIPT FOR THE IMPACT FEES. | | | | | | 4) COMPLIED | | | | | | 5)COMPLIED | | | | | | 6) COMPLIED | | | | | | 7) COMPLIED | | | | | | 8) COMPLIED | | | | | | 9)NOTE THAT THE DEFINITION FOR EXPOSURE C HAS CHANGED | | | EFFECTIVE DECEMBER 8, 2006 (2006 AMENDMENTS TO THE | | | FBC), FBC1609.4, FBC R301.2.1.4. | | | EXPOSURE C. OPEN TERRAIN WITH SCATTERED | | | OBSTRUCTIONS, INCLUDING SURFACE UNDULATIONS OR OTHER | | | IRREGULARITIES, HAVING HEIGHTS GENERALLY LESS THAN 30 | | | FEET (9144 MM) EXTENDING MORE THAN 1,500 FEET (457.2 M) | | | FROM THE BUILDING SITE IN ANY QUADRANT. THIS EXPOSURE | | | SHALL ALSO APPLY TO ANY BUILDING LOCATED WITHIN | | | EXPOSURE B-TYPE TERRAIN WHERE THE BUILDING IS DIRECTLY | | | ADJACENT TO OPEN AREAS OF EXPOSURE C-TYPE TERRAIN IN | | | ANY QUADRANT FOR A DISTANCE OF MORE THAN 600 FEET | | | (182.9 M). THE STRUCTURE IS LOCATED ADJACENT TO A GOLF | | | COURSE WHICH MAY REQUIRE IT TO BE DESIGNED AS EXPOSURE | | | C. PLEASE REVISE PLANS OR INDICATE WHY THE EXPOSURE | | | CATEGORY SHOULD NOT BE CHANGED. ADDITIONAL COMMENTS: | | | THE INFORMATION THAT WAS SUBMITTED DOES NOT CONSIDER | | | THE TERRAIN IN THE ENTIRE REAR QUADRANT, WHICH INCLUDES | | | THE TERRAIN FOR 45 DEGREES EITHER SIDE OF THE WIND | | | DIRECTION BEING CONSIDERED. SEE ASCE 7-02 SECTION | | | 6.5.6.1. ALSO SEE ATTACHED COPIES OF THE 2004 FBC | | | RESIDENTIAL CODE COMMENTARY AND ASCE 7-02. | | | | | | 10) COMPLIED | | | | | | 11) COMPLIED | | | | | | 12) COMPLIED | | | | | | 13) COMPLIED | | | | | | 14) COMPLIED | | | | | | 15) COMPLIED | | | | | | 16) COMPLIED | | | | | | 17)COMPLIED | | | | | | 18) COMPLIED | | | | | | 19) COMPLIED | | | | | | 20) COMPLIED | | | | | | 21) COMPLIED | | | | | | 22)COMPLIED | | | | | | 23) COMPLIED | | | | | | 24) COMPLIED | | | | | | 25) REVISE COMPONENT AND CLADDING PRESSURES TO EXPOSURE | | | CATEGORY 'C'. SEE ITEM #9. | | | | | | 26) COMPLIED | | | | | | 27) COMPLIED | | | | | | 28) COMPLIED | | | | | | 29) COMPLIED | | | | | | 30) N/A | | | | | | 31) COMPLIED | | | | | | 32) COMPLIED | | | | | | 33) COMPLIED | | | | | | 34) CORRECTED | | | | | | 35) COMPLIED | | | | | | 36) COMPLIED | | | | | | 37) COMPLIED | | | | | | 38) COMPLIED | | | | | | 39) CORRECTED | | | | | | 40) COMPLIED | | | | | | 41) COMPLIED | | | | | | 42)COMPLIED | | | | | | 43)COMPLIED | | | | | | 44) COMPLIED | | | | | | 45) CORRECTED | | | | | | 46) COMPLIED | | | | | | 47)COMPLIED | | | | | | 48) COMPLIED | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2007-12-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2007-12-20 |
Time |
13:10 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2007-12-19 |
Time |
07:22 |
Sent To |
|
|
| Notes |
| 2007-12-20 13:10:30 | 2004 FBC W/2007 SUPPLEMENTS | | | NSFR | | | | | | DENIED BY BUILDING | | | | | | 1) COMPLIED | | | | | | 2) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT | | | MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. WORK MUST COMMENCE WITHIN 90 DAYS | | | OF THE DATE THE NOC IS RECORDED. FS 713.13. | | | | | | 3) IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY, PLANS STAMPED BY THEM AND | | | COPY OF RECEIPT SUBMITTED TO CITY OF | | | WEST PALM BEACH BUILDING DEPARTMENT, | | | BEFORE A BUILDING PERMIT CAN BE ISSUED. | | | | | | 4) COMPLIED | | | | | | 5)FBC R401.4AREA OF QUESTIONABLE | | | SOIL.SUBMIT A GEOTECHNICAL REPORT | | | TO VERIFY THE SAFE BEARING CAPACITY OF | | | THE SOIL. SUBMIT 2 SIGNED AND SEALED COPIES. | | | | | | 6) COMPLIED | | | | | | 7) THE FLOOD ZONE DESIGNATION ON THE SURVEY IS | | | SPECIFIED AS A8, WHICH IS INCORRECT. THIS AREA IS | | | INCLUDED IN THE LETTER OF MAP REVISION (LOMR) FOR THE | | | VILLAGES OF PALM BEACH LAKES AND SPENCER LAKES PLATS | | | 1,2 AND 3 DATED DECEMBER 3, 1983. PLEASE CORRECT. | | | SUBMIT REVISED SURVEY. | | | | | | 8) THE ENERGY CALCULATIONS LIST THE CONDITIONED FLOOR | | | AREA AS 8000 SQFT AND THE PLANS SPECIFY 8327 SQFT. | | | PLEASE CORRECT. FBC R CHAPTER 11 AND FBC CHAPTER 13. | | | THE NEW FORMS HAVE NOT BEEN SIGNED BY THE OWNER/AGENT | | | AS REQUIRED BY FBC 13-600. | | | | | | 9)NOTE THAT THE DEFINITION FOR EXPOSURE C HAS CHANGED | | | EFFECTIVE DECEMBER 8, 2006 (2006 AMENDMENTS TO THE | | | FBC), FBC1609.4, FBC R301.2.1.4. | | | EXPOSURE C. OPEN TERRAIN WITH SCATTERED | | | OBSTRUCTIONS, INCLUDING SURFACE UNDULATIONS OR OTHER | | | IRREGULARITIES, HAVING HEIGHTS GENERALLY LESS THAN 30 | | | FEET (9144 MM) EXTENDING MORE THAN 1,500 FEET (457.2 M) | | | FROM THE BUILDING SITE IN ANY QUADRANT. THIS EXPOSURE | | | SHALL ALSO APPLY TO ANY BUILDING LOCATED WITHIN | | | EXPOSURE B-TYPE TERRAIN WHERE THE BUILDING IS DIRECTLY | | | ADJACENT TO OPEN AREAS OF EXPOSURE C-TYPE TERRAIN IN | | | ANY QUADRANT FOR A DISTANCE OF MORE THAN 600 FEET | | | (182.9 M). THE STRUCTURE IS LOCATED ADJACENT TO A GOLF | | | COURSE WHICH MAY REQUIRE IT TO BE DESIGNED AS EXPOSURE | | | C. PLEASE REVISE PLANS OR INDICATE WHY THE EXPOSURE | | | CATEGORY SHOULD NOT BE CHANGED. NOTE: ALTHOUGH THE | | | GENERAL NOTES (C) (3) ON A.09 HAVE BEEN REVISED TO | | | EXPOSURE CATEGORY 'C', THE COMPONENT AND CLADDING | | | PRESSURES IN THE TABLE ON S3.02 HAVE NOT BEEN REVISED | | | TO CATEGORY 'C'. PLEASE CORRECT. | | | | | | 10) THE WALLS OF THE WINE ROOM ARE REQUIRED TO BE | | | WATERPROOFED IN ACCORDANCE WITH FBC R406. INDICATE HOW | | | THIS WILL BE ACCOMPLISHED ON THE PLANS. THE SPRAY FOAM | | | INSULATION DOES NOT COMPLY WITH THE REQUIREMENTS OF FBC | | | R406. | | | | | | 11) COMPLIED | | | | | | 12) COMPLIED | | | | | | 13) COMPLIED | | | | | | 14) COMPLIED | | | | | | 15) COMPLIED | | | | | | 16) COMPLIED | | | | | | 17)COMPLIED | | | | | | 18) COMPLIED | | | | | | 19) COMPLIED | | | | | | 20) COMPLIED | | | | | | 21) COMPLIED | | | | | | 22)COMPLIED | | | | | | 23) COMPLIED | | | | | | 24) COMPLIED | | | | | | 25) REVISE COMPONENT AND CLADDING PRESSURES TO EXPOSURE | | | CATEGORY 'C'. SEE ITEM #9. | | | | | | 26) COMPLIED | | | | | | 27) COMPLIED | | | | | | 28) COMPLIED | | | | | | 29) THE SIMPSON H10 OR USP RT16 "R" IN SCHEDULE ON | | | S2.02) WILL NOT WORK FOR ATTACHING THE FLOOR TRUSSES TO | | | THE LEDGERS. THE FLOOR TRUSSES ARE 3-1/2" WIDE AND THE | | | CONNECTORS HAVE A 1-9/16" OPENING FOR THE TRUSS. PLEASE | | | CORRECT. | | | | | | 30) N/A | | | | | | 31) COMPLIED | | | | | | 32) COMPLIED | | | | | | 33) COMPLIED | | | | | | 34) CORRECTED | | | | | | 35) THE TRUSS LAYOUT IS REQUIRED TO BE REVIEWED AND | | | APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR THE | | | STRUCTURE. SEE R802.1.6, FBC106.1.1.2* CITY AMENDMENTS | | | AND FAC 61G15-31.003. | | | | | | 36) THE ROOF TRUSSES ARE REQUIRED TO HAVE A MINIMUM | | | BOTTOM CORD LIVE LOAD OF 10 PSF. SEE TABLE R301.5. | | | PLEASE CORRECT. | | | | | | 37) THE TRUSS DRAWING SUBMITTAL DOES NOT MEET THE | | | REQUIREMENTS OF FAC 61G-15-31.003. PLEASE SEPARATE THE | | | DRAWINGS AND PLACE THEM WITH THE APPROPRIATE COVER | | | SHEETS AND NUMBER THE DRAWINGS TO CORRESPOND TO THE | | | NUMBERING ON THE COVERSHEETS. SEE ATTACHMENT. | | | | | | 38) COMPLIED | | | | | | 39)CORRECTED | | | | | | 40) FBC 106.3* CITY AMENDMENTS PRODUCT | | | APPROVALS. THOSE PRODUCT WHICH ARE | | | REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL | | | FOR JURISDICTIONAL APPROVAL. | | | | | | 41) COMPLIED | | | | | | 42)THE GENERIC PRESSURES IN THE SCHEDULE ON S3.02 MAY | | | BE TOO HIGH FOR THE GARAGE DOORS WHEN THEY ARE | | | INCREASED TO EXPOSURE 'C'. SEE TABLE R301.2(4). PLEASE | | | INDICATE THE REQUIRED OPENING PRESSURES FOR THE GARAGE | | | DOORS ON THE PLANS. | | | | | | 43)COMPLIED | | | | | | 44) COMPLIED. HOWEVER, PLEASE CLARIFY WHICH WINDOWS THE | | | PRODUCT APPROVALS FOR THE WEATHER SHIELD "LEGACY" FIXED | | | CASEMENT WINDOWS ARE FOR. THERE DOES NOT TO BE ANY OF | | | THESE SPECIFIED ON THE PLANS. | | | | | | 45) CORRECTED | | | | | | 46) COMPLIED | | | | | | 47)COMPLIED | | | | | | 48) COMPLIED | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-10-23 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2007-10-23 |
Time |
09:52 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2007-10-23 |
Time |
09:52 |
Sent To |
|
|
| Notes |
| 2007-10-23 09:51:55 | 2004 FBC W/2007 SUPPLEMENTS | | | NSFR | | | | | | DENIED BY BUILDING | | | | | | 1) COMPLIED | | | | | | 2) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT | | | MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. WORK MUST COMMENCE WITHIN 90 DAYS | | | OF THE DATE THE NOC IS RECORDED. FS 713.13. | | | | | | 3) IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY, PLANS STAMPED BY THEM AND | | | COPY OF RECEIPT SUBMITTED TO CITY OF | | | WEST PALM BEACH BUILDING DEPARTMENT, | | | BEFORE A BUILDING PERMIT CAN BE ISSUED. | | | | | | 4)THE PLANS SPECIFY TYPE III UNPROTECTED | | | CONSTRUCTION, WHICH UNDER THE 2004 CODE IS TYPE III-B. | | | PLEASE SPECIFY A OR B ON THE PLANS. SEE FBC CHAPTER 6. | | | NOTE: TYPE III CONSTRUCTION REQUIRES EXTERIOR WALLS TO | | | HAVE A TWO HOUR FIRE RATING IN ADDITION TO OTHER | | | REQUIREMENTS. SEE TABLES 601 AND 602. NOTE: THIS | | | STRUCTURE COULD BE DECLARED TYPE V-B CONSTRUCTIONAND | | | IT WOULD STILL COMPLY WITH THE HEIGHT AND AREA | | | REQUIREMENTS OF TABLE 503. TYPE V-B CONSTRUCTION DOES | | | NOT REQUIRE THE EXTERIOR WALLS TO BE FIRE RATED. IF YOU | | | ARE SPECIFYING TYPE III CONSTRUCTION SUBMIT | | | CALCULATIONS AS TO HOW THE 2 HOUR FIRE RATING WILL BE | | | OBTAINED. SUBMIT A LETTER FROM THE CONCRETE BLOCK | | | SUPPLIER THAT SPECIES THE THICKNESS AND AGGREGATE IN | | | THE BLOCK AND THE FIRE RESISTANCE RATING IN HOURS. | | | | | | 5)FBC R401.4AREA OF QUESTIONABLE | | | SOIL.SUBMIT A GEOTECHNICAL REPORT | | | TO VERIFY THE SAFE BEARING CAPACITY OF | | | THE SOIL. SUBMIT 2 SIGNED AND SEALED COPIES. | | | | | | 6) THE PLANS ARE REQUIRED TO HAVE THE CERTIFICATE OF | | | AUTHORIZATION NUMBERS OF THE ENGINEERING AND | | | ARCHITECTURAL FIRMS. SEE FS 471 AND 481. ALSO SEE THE | | | ELECTRICAL REVIEW COMMENTS. | | | | | | 7) THE FLOOD ZONE DESIGNATION ON THE SURVEY IS | | | SPECIFIED AS A8, WHICH IS INCORRECT. THIS AREA IS | | | INCLUDED IN THE LETTER OF MAP REVISION (LOMR) FOR THE | | | VILLAGES OF PALM BEACH LAKES AND SPENCER LAKES PLATS | | | 1,2 AND 3 DATED DECEMBER 3, 1983. PLEASE CORRECT. | | | | | | 8) THE ENERGY CALCULATIONS LIST THE CONDITIONED FLOOR | | | AREA AS 8000 SQFT AND THE PLANS SPECIFY 8327 SQFT. | | | PLEASE CORRECT. FBC R CHAPTER 11 AND FBC CHAPTER 13 | | | | | | 9)NOTE THAT THE DEFINITION FOR EXPOSURE C HAS CHANGED | | | EFFECTIVE DECEMBER 8, 2006 (2006 AMENDMENTS TO THE | | | FBC), FBC1609.4, FBC R301.2.1.4. | | | EXPOSURE C. OPEN TERRAIN WITH SCATTERED | | | OBSTRUCTIONS, INCLUDING SURFACE UNDULATIONS OR OTHER | | | IRREGULARITIES, HAVING HEIGHTS GENERALLY LESS THAN 30 | | | FEET (9144 MM) EXTENDING MORE THAN 1,500 FEET (457.2 M) | | | FROM THE BUILDING SITE IN ANY QUADRANT. THIS EXPOSURE | | | SHALL ALSO APPLY TO ANY BUILDING LOCATED WITHIN | | | EXPOSURE B-TYPE TERRAIN WHERE THE BUILDING IS DIRECTLY | | | ADJACENT TO OPEN AREAS OF EXPOSURE C-TYPE TERRAIN IN | | | ANY QUADRANT FOR A DISTANCE OF MORE THAN 600 FEET | | | (182.9 M). THE STRUCTURE IS LOCATED ADJACENT TO A GOLF | | | COURSE WHICH MAY REQUIRE IT TO BE DESIGNED AS EXPOSURE | | | C. PLEASE REVISE PLANS OR INDICATE WHY THE EXPOSURE | | | CATEGORY SHOULD NOT BE CHANGED. | | | | | | 10) THE WALLS OF THE WINE ROOM ARE REQUIRED TO BE | | | WATERPROOFED IN ACCORDANCE WITH FBC R406. INDICATE HOW | | | THIS WILL BE ACCOMPLISHED ON THE PLANS. | | | | | | 11) PROVIDE DETAILS OF THE MASONRY FIREPLACES AND | | | CHIMNEYS IN THE LIVING ROOM AND AT THE COVERED PATIO. | | | SEE SECTIONS R1001 AND R1003.SPECIFY REINFORCING, | | | ETC. | | | | | | 12) PROVIDE DETAILS FOR THE PRE-FAB FIREPLACE AND | | | CHIMNEY. SUBMIT THE MANUFACTURER'S SPECIFICATIONS AND | | | LISTING INFORMATION FOR THE FIREPLACE AND CHIMNEY. FBC | | | R1002 AND R1004 | | | | | | 13) PROVIDE DETAILS FOR THE CHIMNEY CAPS. SPECIFY | | | MATERIALS, ATTACHMENTS, FASTENERS, ETC. FBC 106.1.1 | | | CITY AMENDMENTS. | | | | | | 14) PROVIDE STRUCTURAL DETAILS FOR THE WOOD FRAME FALSE | | | CHIMNEY. SPECIFY MATERIALS, CONNECTIONS, ETC. FBC | | | 106.1.1 CITY AMENDMENTS. | | | | | | 15) AT INTERIOR STAIRS AND SECOND FLOOR LANDING SHOW | | | COMPLIANCE WITH R312.2 GUARD OPENING LIMITATIONS. | | | REQUIRED GUARDS ON OPEN SIDES OF STAIRWAYS, RAISED | | | FLOOR AREAS, BALCONIES AND PORCHES SHALL HAVE | | | INTERMEDIATE RAILS OR ORNAMENTAL CLOSURES WHICH DO NOT | | | ALLOW PASSAGE OF A SPHERE 4 INCHES (102MM) OR MORE IN | | | DIAMETER. | | | | | | 16) SHOW COMPLIANCE WITH R807.1 ATTIC ACCESS . | | | IN BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF | | | CONSTRUCTION, AN ATTIC ACCESS OPENING SHALL BE PROVIDED | | | TO ATTIC AREAS THAT EXCEED 30 SQUARE FEET (2.8 M 2 ) | | | AND HAVE A VERTICAL HEIGHT OF 30 INCHES (762 MM) OR | | | GREATER. THE ROUGH-FRAMED OPENING SHALL NOT BE LESS | | | THAN 22 INCHES BY 30 INCHES (559 MM BY 762 MM) AND | | | SHALL BE LOCATED IN A HALLWAY OR OTHER READILY | | | ACCESSIBLE LOCATION. NO ATTIC ACCESS IS SPECIFIED ON | | | THE SECOND FLOOR. | | | | | | 17)COMPLIED | | | | | | 18) SUBMIT THE MANUFACTURER'S SPECIFICATIONS AND | | | LISTING FOR THE OUTDOOR BBQ ON THE COVERED PORCH. | | | INCLUDE SPECS. AND LISTING FOR HOOD IF ONE IS REQUIRED. | | | FBC 106.1.1 CITY AMENDMENTS. | | | | | | 19) SPECIFY THE CEILING FINISHES FOR THE FRONT PORCH, | | | LOGGIA AND COVERED PATIO. FBC 106.1.1 CITY AMENDMENTS. | | | | | | 20) THE ROOF/FLOOR DRAIN AT THE FRONT PORCH IS REQUIRED | | | TO DISCHARGE AT LEAST 1 FOOT AWAY FROM THE STRUCTURE IN | | | ACCORDANCE WITH R320.7. SPECIFY ON THE PLANS. | | | | | | 21) SHOW COMPLIANCE WITH R502.1.2 DRAFTSTOPPING | | | REQUIRED. | | | WHEN THERE IS USABLE SPACE BOTH ABOVE AND BELOW THE | | | CONCEALED SPACE OF A FLOOR/CEILING ASSEMBLY, DRAFTSTOPS | | | SHALL BE INSTALLED SO THAT THE AREA OF THE CONCEALED | | | SPACE DOES NOT EXCEED 1,000 SQUARE FEET (92.9 M 2 ). | | | DRAFTSTOPPING SHALL DIVIDE THE CONCEALED SPACE INTO | | | APPROXIMATELY EQUAL AREAS. WHERE THE ASSEMBLY IS | | | ENCLOSED BY A FLOOR MEMBRANE ABOVE AND A CEILING | | | MEMBRANE BELOW DRAFTSTOPPING SHALL BE PROVIDED IN | | | FLOOR/CEILING ASSEMBLIES UNDER THE FOLLOWING | | | CIRCUMSTANCES: | | | 1.CEILING IS SUSPENDED UNDER THE FLOOR FRAMING. 2. | | | FLOOR FRAMING IS CONSTRUCTED OF TRUSS-TYPE OPEN-WEB OR | | | PERFORATED MEMBERS. | | | R502.1.2.1 MATERIALS. | | | DRAFTSTOPPING MATERIALS SHALL NOT BE LESS THAN 1/2-INCH | | | (12.7 MM) GYPSUM BOARD, 3 / 8 -INCH (9.5 MM) WOOD | | | STRUCTURAL PANELS, 3 / 8 -INCH (9.5 MM) TYPE 2-M-W | | | PARTICLEBOARD OR OTHER APPROVED MATERIALS ADEQUATELY | | | SUPPORTED. DRAFTSTOPPING SHALL BE INSTALLED PARALLEL TO | | | THE FLOOR FRAMING MEMBERS UNLESS OTHERWISE APPROVED BY | | | THE BUILDING OFFICIAL. THE INTEGRITY OF ALL DRAFTSTOPS | | | SHALL BE MAINTAINED. | | | SPECIFY THE MATERIAL THAT WILL BE USED AND LOCATIONS ON | | | THE PLANS. | | | | | | 22)COMPLIED | | | | | | 23) REVISE GENERAL NOTE E(2) ON A9 TO SPECIFY ACI | | | 315-02 AND NOTE F(2) FROM SBC TO FBC. WHICH ARE THE | | | CORRECT REFERENCES PER 2004 FBC RESIDENTIAL CHAPTER | | | 43. | | | | | | 24) ON SHEET S1.01, NOTE 2 INCORRECTLY LISTS S3.01 AS | | | THE SHEET CONTAINING THE WINDOW AND DOOR PRESSURES. THE | | | TABLE IS LOCATED ON S 3.02. | | | | | | 25) PLEASE SPECIFY THE COMPONENT AND CLADDING PRESSURES | | | AT EACH OF THE OPENINGS ON THE PLANS BASED ON THE | | | OPENING SIZES, EXPOSURE CATEGORY AND LOCATIONS. FBC * | | | 106.1.2 | | | | | | 26) COMPLIED | | | | | | 27) ON SHEET A.01 THE STAIR CALCULATIONS ARE INCORRECT. | | | THE SUM OF THE 2 RISERS AND A TREAD IS 23.95" NOT 24" | | | AS SPECIFIED, WHICH IS NOT BETWEEN 24 AND 25 INCHES. | | | SEE FBC R311.5.3.2 PLEASE CORRECT. | | | | | | 28) THE (2)LB-3 BEAMS SPECIFIED AT THE COVERED PORCH | | | ON SHEET S2.01 ARE NOT LISTED IN THE SECOND BEAM | | | SCHEDULE ON SHEET S2.01. PLEASE CORRECT. FBC 106.1.2 | | | CITY AMENDMENTS | | | | | | 29) THE SIMPSON H10 OR USP RT16 "R" IN SCHEDULE ON | | | S2.02) WILL NOT WORK FOR ATTACHING THE FLOOR TRUSSES TO | | | THE LEDGERS. THE FLOOR TRUSSES ARE 3-1/2" WIDE AND THE | | | CONNECTORS HAVE A 1-9/16" OPENING FOR THE TRUSS. PLEASE | | | CORRECT. | | | | | | 30) N/A | | | | | | 31) CONNECTOR "L" IN THE SCHEDULE ON S2.02A SIMPSON | | | MTSM 20,REQUIRES 4 CONCRETE SCREWS TO ACHIEVE THE | | | UPLIFT SPECIFIED. ONLY 3 FASTENERS ARE SPECIFIED IN THE | | | SCHEDULE. PLEASE CORRECT. | | | | | | 32) CONNECTOR "N" ON S2.O2 , THE SIMPSON HTT22 IS | | | INCORRECTLY SPECIFIED WITH 3/4" DIA. ANCHORS AND THE | | | SIMPSON CATALOG SPECS. 5/8" DIA ANCHORS. PLEASE | | | CORRECT. | | | | | | 33) NOTE #4 ON SHEETS S2.01 AND S2.02 STATE SEE PLYWOOD | | | NAILING SCHEDULE ON THIS SHEET AND THE SCHEDULE IS ON | | | SHEET S3.02. PLEASE CORRECT. | | | | | | 34) CORRECTED | | | | | | 35) THE TRUSS LAYOUT IS REQUIRED TO BE REVIEWED AND | | | APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR THE | | | STRUCTURE. R802.1.6 AND FBC106.1.1.2 CITY AMENDMENTS | | | | | | 36) THE ROOF TRUSSES ARE REQUIRED TO HAVE A MINIMUM | | | BOTTOM CORD LIVE LOAD OF 10 PSF. SEE TABLE R301.5. | | | PLEASE CORRECT. | | | | | | 37) THE TRUSS DRAWING SUBMITTAL DOES NOT MEET THE | | | REQUIREMENTS OF FAC 61G-15-31.003. PLEASE SEPARATE THE | | | DRAWINGS AND PLACE THEM WITH THE APPROPRIATE COVER | | | SHEETS AND NUMBER THE DRAWINGS TO CORRESPOND TO THE | | | NUMBERING ON THE COVERSHEETS. | | | | | | 38) THE PLYWOOD SHEATHING FASTENING SCHEDULE FOR WALLS | | | AND ROOFS ON S 3.02 SPECIFIES #8 SCREWS AND THE NOTE | | | CALLS FOR 2-1/2" SELF DRILLING SCREWS FOR ATTACHING TO | | | A METAL DECK.THE SHEATHING AND FRAMING FOR THIS | | | PROJECT IS WOOD. PLEASE CORRECT. FBC R803.2.3.1 | | | REQUIRES 8D RING SHANK NAILS IN ALL ROOF ZONES. PLEASE | | | CORRECT. | | | | | | 39)CORRECTED | | | | | | 40) FBC 106.3* CITY AMENDMENTS PRODUCT | | | APPROVALS. THOSE PRODUCT WHICH ARE | | | REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL | | | FOR JURISDICTIONAL APPROVAL. | | | | | | 41) SPECIFY THE METHOD OF ATTACHMENT THAT WILL BE USED | | | TO INSTALL THE ROOF TILES. PLEASE CIRCLE THE | | | APPROPRIATE METHOD FROM THOSE LISTED IN THE PRODUCT | | | APPROVAL NOA. FBC 106.1.2 CITY AMENDMENTS. | | | | | | 42)THE GENERIC PRESSURES IN THE SCHEDULE ON S3.02 ARE | | | TOO HIGH FOR THE GARAGE DOORS. SEE TABLE R301.2(4). | | | PLEASE INDICATE THE REQUIRED OPENING PRESSURES FOR THE | | | GARAGE DOORS ON THE PLANS. | | | | | | 43)SUBMIT THE PRODUCT EVALUATION REPORT AND | | | INSTALLATION INSTRUCTIONS FOR THE NAN YA PLASTIC CORP. | | | EXTERIOR DOORS IN ACCORDANCE WITH FAC RULE 9B-72. | | | | | | 44) SUBMIT PRODUCT APPROVALS FOR THE FIXED WINDOWS AS | | | REQUIRED BY FAC RULE 9B-72. | | | | | | 45) CORRECTED | | | | | | 46) THE LOCAL PRODUCT APPROVAL APPLICATION FOR THE | | | "SIGNATURE DOOR INC." EXTERIOR DOORS IS INCOMPLETE. | | | SUBMIT THE EVALUATION REPORT, INSTALLATION | | | INSTRUCTIONS, ETC. REQUIRED BY FAC RULE 9B-72. | | | | | | 47)ON THE FIRST FLOOR PLAN SHEET A.01, THERE IS A | | | WALL TYPE 6 SPECIFIED. HOWEVER, THIS WALL TYPE IS NOT | | | LISTED IN THE WALL SCHEDULE. PLEASE CORRECT. FBC | | | 106.1.2 CITY AMENDMENTS. | | | | | | 48) IN ORDER TO EXPEDITE PLAN REVIEW AND HELP AVOID | | | ADDITIONAL PLAN REVIEWS, PLEASE INCLUDE A RESPONSE | | | LETTER SPECIFYING HOW THE COMMENTS HAVE BEEN | | | ADDRESSED. | | | | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-09-18 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2007-09-18 |
Time |
14:45 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2007-09-12 |
Time |
18:04 |
Sent To |
|
|
| Notes |
| 2007-09-17 17:26:36 | 2004 FBC W/2007 SUPPLEMENTS | | | NSFR | | | | | | DENIED BY BUILDING | | | | | | 1) UNITY OF TITLE FOR THE LOTS MUST BE COMPLETED AND | | | ADDRESS ASSIGNED BEFORE PERMIT IS ISSUED. | | | | | | 2) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT | | | MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 3) IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY, PLANS STAMPED BY THEM AND | | | COPY OF RECEIPT SUBMITTED TO CITY OF | | | WEST PALM BEACH BUILDING DEPARTMENT, | | | BEFORE A BUILDING PERMIT CAN BE ISSUED. | | | | | | 4)THE PLANS SPECIFY TYPE III UNPROTECTED | | | CONSTRUCTION, WHICH UNDER THE 2004 CODE IS TYPE III-B. | | | PLEASE SPECIFY A OR BE ON THE PLANS. SEE FBC CHAPTER 6. | | | NOTE: TYPE III CONSTRUCTION REQUIRES EXTERIOR WALLS TO | | | HAVE A TWO HOUR FIRE RATING IN ADDITION TO OTHER | | | REQUIREMENTS. SEE TABLES 601 AND 602. NOTE: THIS | | | STRUCTURE COULD BE DECLARED TYPE V-B CONSTRUCTIONAND | | | IT WOULD STILL COMPLY WITH THE HEIGHT AND AREA | | | REQUIREMENTS OF TABLE 503. TYPE V-B CONSTRUCTION DOES | | | NOT REQUIRE THE EXTERIOR WALLS TO BE FIRE RATED. IF YOU | | | ARE SPECIFYING TYPE III CONSTRUCTION SUBMIT | | | CALCULATIONS AS TO HOW THE 2 HOUR FIRE RATING WILL BE | | | OBTAINED. SUBMIT A LETTER FROM THE CONCRETE BLOCK | | | SUPPLIER THAT SPECIES THE THICKNESS AND AGGREGATE IN | | | THE BLOCK AND THE FIRE RESISTANCE RATING IN HOURS. | | | | | | 5)FBC R401.4AREA OF QUESTIONABLE | | | SOIL.SUBMIT A GEOTECHNICAL REPORT | | | TO VERIFY THE SAFE BEARING CAPACITY OF | | | THE SOIL. SUBMIT 2 SIGNED AND SEALED COPIES. | | | | | | 6) THE PLANS ARE REQUIRED TO HAVE THE ORIGINAL | | | SIGNATURE OF THE ENGINEER AND ARCHITECT IN ADDITION TO | | | THE LICENSE NUMBERS OF THE ENGINEERING AND | | | ARCHITECTURAL FIRMS. SEE FS 471 AND 481. SEE THE | | | ELECTRICAL REVIEW COMMENTS. | | | | | | 7) THE FLOOD ZONE DESIGNATION ON THE SURVEY IS | | | SPECIFIED AS A8, WHICH IS INCORRECT. THIS AREA IS | | | INCLUDED IN THE LETTER OF MAP REVISION (LOMR) FOR THE | | | VILLAGES OF PALM BEACH LAKES AND SPENCER LAKES PLATS | | | 1,2 AND 3 DATED DECEMBER 3, 1983. PLEASE CORRECT. | | | | | | 8) THE ENERGY CALCULATIONS LISTS THE CONDITIONED FLOOR | | | AREA AS 8000 SQFT AND THE PLANS SPECIFY 8327 SQFT. | | | PLEASE CORRECT. | | | | | | 9)NOTE THAT THE DEFINITION FOR EXPOSURE C HAS CHANGED | | | EFFECTIVE DECEMBER 8, 2006 (2006 AMENDMENTS TO THE | | | FBC), FBC1609.4, FBC R301.2.1.4. | | | EXPOSURE C. OPEN TERRAIN WITH SCATTERED | | | OBSTRUCTIONS, INCLUDING SURFACE UNDULATIONS OR OTHER | | | IRREGULARITIES, HAVING HEIGHTS GENERALLY LESS THAN 30 | | | FEET (9144 MM) EXTENDING MORE THAN 1,500 FEET (457.2 M) | | | FROM THE BUILDING SITE IN ANY QUADRANT. THIS EXPOSURE | | | SHALL ALSO APPLY TO ANY BUILDING LOCATED WITHIN | | | EXPOSURE B-TYPE TERRAIN WHERE THE BUILDING IS DIRECTLY | | | ADJACENT TO OPEN AREAS OF EXPOSURE C-TYPE TERRAIN IN | | | ANY QUADRANT FOR A DISTANCE OF MORE THAN 600 FEET | | | (182.9 M). THE STRUCTURE IS LOCATED ADJACENT TO A GOLF | | | COURSE WHICH MAY REQUIRE IT TO BE DESIGNED AS EXPOSURE | | | C. PLEASE REVISE PLANS OR INDICATE WHY THE EXPOSURE | | | CATEGORY SHOULD NOT BE CHANGED. | | | | | | 10) THE WALLS OF THE WINE ROOM ARE REQUIRED TO BE | | | WATERPROOFED IN ACCORDANCE WITH FBC R406. | | | | | | 11) PROVIDE DETAILS OF THE MASONRY FIREPLACES AND | | | CHIMNEYS IN THE LIVING ROOM AND AT THE COVERED PATIO. | | | SEE SECTIONS R1001 AND R1003. COORDINATE WITH THE | | | STRUCTURAL ENGINEER FOR THE FOUNDATION REQUIREMENTS. | | | SPECIFY REINFORCING, ETC. | | | | | | 12) PROVIDE DETAILS FOR THE PRE-FAB FIREPLACE AND | | | CHIMNEY. SUBMIT THE MANUFACTURER'S SPECIFICATIONS AND | | | LISTING INFORMATION FOR THE FIREPLACE AND CHIMNEY. | | | | | | 13) PROVIDE DETAILS FOR THE CHIMNEY CAPS. SPECIFY | | | MATERIALS, ATTACHMENTS, FASTENERS, ETC. | | | | | | 14) PROVIDE STRUCTURAL DETAILS FOR THE WOOD FRAME FAKE | | | CHIMNEY. SPECIFY MATERIALS, CONNECTIONS, ETC. | | | | | | 15) AT INTERIOR STAIRS AND SECOND FLOOR LANDING SHOW | | | COMPLIANCE WITH R312.2 GUARD OPENING LIMITATIONS. | | | REQUIRED GUARDS ON OPEN SIDES OF STAIRWAYS, RAISED | | | FLOOR AREAS, BALCONIES AND PORCHES SHALL HAVE | | | INTERMEDIATE RAILS OR ORNAMENTAL CLOSURES WHICH DO NOT | | | ALLOW PASSAGE OF A SPHERE 4 INCHES (102MM) OR MORE IN | | | DIAMETER. | | | | | | 16) SHOW COMPLIANCE WITH R807.1 ATTIC ACCESS . | | | IN BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF | | | CONSTRUCTION, AN ATTIC ACCESS OPENING SHALL BE PROVIDED | | | TO ATTIC AREAS THAT EXCEED 30 SQUARE FEET (2.8 M 2 ) | | | AND HAVE A VERTICAL HEIGHT OF 30 INCHES (762 MM) OR | | | GREATER. THE ROUGH-FRAMED OPENING SHALL NOT BE LESS | | | THAN 22 INCHES BY 30 INCHES (559 MM BY 762 MM) AND | | | SHALL BE LOCATED IN A HALLWAY OR OTHER READILY | | | ACCESSIBLE LOCATION. | | | | | | 17)SHOW COMPLIANCE WITH R310 FOR EMERGENCY ESCAPE AND | | | RESCUE OPENINGS AT THE SLEEPING ROOMS. SPECIFY THE | | | SECOND FLOOR EGRESS WINDOWS ON THE PLANS. | | | | | | 18) SUBMIT THE MANUFACTURER'S SPECIFICATIONS AND | | | LISTING FOR THE OUTDOOR BBQ ON THE COVERED PORCH. | | | INCLUDE SPECS. AND LISTING FOR HOOD IF ONE IS | | | REQUIRED. | | | | | | 19) SPECIFY THE CEILING FINISHES FOR THE FRONT PORCH, | | | LOGGIA AND COVERED PATIO. | | | | | | 20) THE ROOF/FLOOR DRAIN AT THE FRONT PORCH IS REQUIRED | | | TO DISCHARGE AT LEAST 1 FOOT AWAY FROM THE STRUCTURE IN | | | ACCORDANCE WITH R320.7. | | | | | | 21) SHOW COMPLIANCE WITH R502.1.2 DRAFTSTOPPING | | | REQUIRED. | | | WHEN THERE IS USABLE SPACE BOTH ABOVE AND BELOW THE | | | CONCEALED SPACE OF A FLOOR/CEILING ASSEMBLY, DRAFTSTOPS | | | SHALL BE INSTALLED SO THAT THE AREA OF THE CONCEALED | | | SPACE DOES NOT EXCEED 1,000 SQUARE FEET (92.9 M 2 ). | | | DRAFTSTOPPING SHALL DIVIDE THE CONCEALED SPACE INTO | | | APPROXIMATELY EQUAL AREAS. WHERE THE ASSEMBLY IS | | | ENCLOSED BY A FLOOR MEMBRANE ABOVE AND A CEILING | | | MEMBRANE BELOW DRAFTSTOPPING SHALL BE PROVIDED IN | | | FLOOR/CEILING ASSEMBLIES UNDER THE FOLLOWING | | | CIRCUMSTANCES: | | | 1.CEILING IS SUSPENDED UNDER THE FLOOR FRAMING. 2. | | | FLOOR FRAMING IS CONSTRUCTED OF TRUSS-TYPE OPEN-WEB OR | | | PERFORATED MEMBERS. | | | R502.1.2.1 MATERIALS. | | | DRAFTSTOPPING MATERIALS SHALL NOT BE LESS THAN ?-INCH | | | (12.7 MM) GYPSUM BOARD, 3 / 8 -INCH (9.5 MM) WOOD | | | STRUCTURAL PANELS, 3 / 8 -INCH (9.5 MM) TYPE 2-M-W | | | PARTICLEBOARD OR OTHER APPROVED MATERIALS ADEQUATELY | | | SUPPORTED. DRAFTSTOPPING SHALL BE INSTALLED PARALLEL TO | | | THE FLOOR FRAMING MEMBERS UNLESS OTHERWISE APPROVED BY | | | THE BUILDING OFFICIAL. THE INTEGRITY OF ALL DRAFTSTOPS | | | SHALL BE MAINTAINED. | | | SPECIFY THE MATERIAL AND LOCATIONS ON THE PLAN. | | | | | | 22)REVISE THE TYPICAL DOOR JAMB DETAIL 7 ON A9. THE | | | 2X OR 1X BUCKS ARE REQUIRED TO BE THE FULL WIDTH OF THE | | | JAMB. SEE R613.6.1.1 | | | | | | 23) REVISE GENERAL NOTE E(2) ON A9 TO SPECIFY ACI | | | 315-02 AND NOTE F(2) FROM SBC TO FBC. WHICH ARE THE | | | CORRECT REFERENCES PER 2004 FBC RESIDENTIAL CHAPTER | | | 43. | | | | | | 24) ON SHEET S1.01, NOTE 2 INCORRECTLY LISTS S3.01 AS | | | THE SHEET CONTAINING THE WIDOW AND DOOR PRESSURES. THE | | | TABLE IS LOCATED ON S 3.02. | | | | | | 25) PLEASE SPECIFY THE COMPONENT AND CLADDING PRESSURES | | | AT EACH OF THE OPENINGS ON THE PLANS BASED ON THE | | | OPENING SIZES, EXPOSURE CATEGORY AND LOCATIONS. FBC * | | | 106.1.2 | | | | | | 26) ON SHEET S1.01 THE NOTE FOR CAP PLATE C REFERS TO | | | DETAIL 8 ON S3.01, WHICH IS NOT CORRECT. PLEASE | | | CORRECT. SEE 8 ON S3.02. | | | | | | 27) ON PAGE A1 THE SUM OF 2 RISERS AND A TREAD IS | | | 23.95", WHICH IS NOT BETWEEN 24 AND 25 INCHES. PLEASE | | | CORRECT. | | | | | | 28) THE LB-3 BEAMS ARE NOT LISTED IN THE SECOND BEAM | | | SCHEDULE ON SHEET S2.01. | | | | | | 29) THE SIMPSON H10 OR USP RT16 ("R" IN SCHEDULE ON | | | S2.02) WILL NOT WORK FOR ATTACHING THE FLOOR TRUSSES TO | | | THE LEDGERS. THE FLOOR TRUSSES ARE 3-1/2" WIDE AND THE | | | CONNECTORS HAVE A 1-9/16" OPENING FOR THE TRUSS. | | | | | | 30) THE SCHEDULE SPECIFIES CONNECTOR "W" WHICH IS TWO | | | SIMPSON H10 OR TWO USP RT16 TRUSS ANCHORS. SOME OF THE | | | TRUSSES THAT HAVE THESE CONNECTORS SPECIFIED DO NOT | | | EXTEND PAST THE 2 X 6 WALL SO THEY CAN NOT BE APPLIED | | | TO EACH SIDE OF THE WALL AND THE TRUSS. | | | | | | 31) CONNECTOR "L" IN THE SCHEDULE ON S2.02A SIMPSON | | | MTSM 20,REQUIRES 4 CONCRETE SCREWS TO ACHIEVE THE | | | UPLIFT SPECIFIED. ONLY 3 FASTENERS ARE SPECIFIED IN THE | | | SCHEDULE. PLEASE CORRECT. | | | | | | 32) CONNECTOR "N" ON S2.O2 , THE SIMPSON HTT22 IS | | | INCORRECTLY SPECIFIED WITH 3/4" DIA. ANCHORS AND THE | | | SIMPSON CATALOG SPECS. 5/8" DIA ANCHORS. PLEASE | | | CORRECT. | | | | | | 33) NOTE #4 ON SHEETS S2.01 AND S2.02 STATE SEE PLYWOOD | | | NAILING SCHEDULE ON THIS SHEET AND THE SCHEDULE IS ON | | | SHEET S3.02. PLEASE CORRECT. | | | | | | 34) ALL OF THE DETAILS ON SHEET S3.02 ARE INCORRECTLY | | | LABELED AS BEING ON S3.01. | | | | | | 35) THE TRUSS LAYOUT IS REQUIRED TO BE REVIEWED AND | | | APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR THE | | | STRUCTURE. | | | | | | 36) THE ROOF TRUSSES ARE REQUIRED TO HAVE A MINIMUM | | | BOTTOM CORD LIVE LOAD OF 10 PSF. SEE TABLE R301.5. | | | | | | 37) THE TRUSS DRAWING SUBMITTAL DOES NOT MEET THE | | | REQUIREMENTS OF 61G-15-31.003. PLEASE SEPARATE THE | | | DRAWINGS AND PLACE THEM WITH THE APPROPRIATE COVER | | | SHEETS AND NUMBER THE DRAWINGS TO CORRESPOND TO THE | | | NUMBERING ON THE COVERSHEETS. | | | | | | 38) THE PLYWOOD SHEATHING FASTENING SCHEDULE FOR WALLS | | | AND ROOFS ON S 3.02 SPECIFIES #8 SCREWS AND THE NOTE | | | CALLS FOR 2-1/2" SELF DRILLING SCREWS FOR ATTACHING TO | | | A METAL DECK.THE SHEATHING AND FRAMING FOR THIS | | | PROJECT IS WOOD. PLEASE CORRECT. FBC R803.2.3.1 | | | REQUIRES 8D RING SHANK NAILS IN ALL ROOF ZONES. | | | | | | 39)PRODUCT APPROVALS SUBMITTED WITH PERMIT | | | APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO | | | COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR | | | INFORMATION PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE | | | APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER | | | SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. | | | | | | 40)WPB ADMIN CODE 106.3* PRODUCT | | | APPROVALS. THOSE PRODUCT WHICH ARE | | | REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL | | | FOR JURISDICTIONAL APPROVAL. | | | | | | 41) CIRCLE THE METHOD OF ATTACHMENT THAT WILL BE USED | | | TO INSTALL THE ROOF TILE ON THE NOA. | | | | | | 42)THE GENERIC PRESSURES IN THE SCHEDULE ON S3.02 ARE | | | TOO HIGH FOR THE GARAGE DOORS. SEE TABLE R301.2(4). | | | | | | 43)SUBMIT STATE OR MIAMI-DADE PRODUCT APPROVALS FOR | | | THE NAN YA PLASTIC CORP. EXTERIOR DOORS OR THE | | | MANUFACTURER CAN APPLY FOR LOCAL PRODUCT APPROVAL IN | | | ACCORDANCE WITH RULE 9B-72. | | | | | | 44) THE WEATHERSHIELD LEGACY FIXED WINDDOW NOA NO. | | | 05-0420.04 IS MISSING SHEET 4 OF 4 FROM DRAWING NO. | | | 1071. | | | | | | 45) THE NOA NO. 03-1105.01 FOR THE PGT PW-701 WINDOW | | | HAS BEEN REVISED BY NOA NO. 07-0418.06. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2009-09-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-09-28 |
Time |
13:09 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-09-28 |
Time |
13:09 |
Sent To |
PC |
|
| Notes |
| 2009-09-28 13:11:33 | ** REDLINED PLANS | | | | | | 110.26 FOR A/C DISCONNECT | | | 250.122 FOR MISSING EQUIPMENT GROUNDING CONDUCTOR AFTER | | | MAIN DISCONNECT. | | | SUCCESSOR ARCHITECT TO BE COMPLETED BY ARCHITECT PER | | | FLORIDA ADMINSTRATIVE CODE 61G1-16. LETTER SUBMITTED | | | ONLY LISTED NEW ARCHITECT AS TAKING OVER. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2009-07-20 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-07-20 |
Time |
14:40 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-07-20 |
Time |
14:40 |
Sent To |
|
|
| Notes |
| 2009-07-20 14:40:50 | | | | | | | ** DENIED REVISION ** | | | | | | ** THE TITLE BLOCKS INDICATE THERE HAVE BEEN THREE | | | REVISIONS SINCE THE LAST REVIEW DONE IN THIS OFFICE | | | SINCE 12/03/07 HOWEVER TO DATE NO ELECTRICAL REVISIONS | | | HAVE BEEN SUBMITTED FOR BASE BUILDING PLANS. | | | THE SERVICE HAS COMPLETELY BEEN REVISED ALONG WITH MANY | | | OTHER ITEMS. | | | | | | | | | 1) NOTE: PLANS SUBMITTED ARE NOT REVISED BY THE | | | ENGINEER OF RECORD PER FS 471.025 | | | FAC 61G15-23 | | | | | | 2) NOTE: PLEASE UPDATE LOAD CALCULATIONS FOR RECESSED | | | LIGHTING LOADS PER 220.3B4. THE AMOUNT OF RECESSED | | | LIGHTING SHOWN ON PLANS IS ABOVE THE GENERAL LIGHTING | | | LOADS. PLEASE ALSO BE SURE THE ADDITIONAL LOADS ON THE | | | LIGHTING PANEL IS COORDINATED. | | | | | | 3) NOTE: PLEASE LOOK AT THE NEW 600AMP DISTRIBUTION | | | PANEL. ALL PANELS ARE SHOWING FEEDER CONDUCTORS AND | | | LOADS WELL BELOW ANY MINIMUMS BY CODE. 240.4,310.16 ETC | | | FOR EXAMPLE: PANEL *A* IS SHOWING A 225AMP BREAKER WITH | | | #10 CONDUCTORS AS THE FEEDERS WITH A LOAD OF 4.5 KW. | | | THIS IS NOT POSSIBLE. ALL OTHER PANELS ON THIS SAME | | | 600AMP MDP IS THE SAME. CONDUCTORS ARE TOO SMALL AND | | | LOADS ARE NOT ACCURATE. | | | | | | 4) NOTE: PANELS FOR ALL LOADS NEED TO BE SUBMITTED AND | | | COMPLETE. NO PANEL SCHEDULE FOR EXAMPLE WAS SUBMITTED | | | FOR THE NEW POOL PANEL SO LOADS, BRANCH CIRCUITS ETC | | | CAN NOT BE VERIFIED AS CODE COMPLIANT. | | | 408.4,220,310, ETC | | | | | | 5) NOTE: THE RISER HAS BEEN COMPLETELY REVISED FOR A | | | NEW 600AMP SERVICE HOWEVER THE PLANS ON SHEETS E- STILL | | | INDICATES THE ORIGINAL 400AMP SERVICE, 400AMP MAIN AND | | | 400AMP TRANSFER SWITCH. | | | PLEASE COORDINATE PLANS. | | | 215.5,230.70,230.71,ETC | | | | | | 6) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT | | | SHEETS FOR THE NEW TRANSFER SWITCH WHICH APPEARS TO BE | | | UPDATED FROM THE PREVIOUS PLANS. | | | 110.3, 90.7 | | | | | | 7) NOTE: PLEASE SEE SAFE ROOM WHICH WAS/IS THE MASTER | | | BEDROOM CLOSET. THE PLANS INDICATE WHAT APPEAR TO BE | | | WALL SCONCES. PLEASE SEE 410.8 FOR MINIMUM CLEARANCES | | | FROM SHELVING. | | | | | | | | | | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2007-12-20 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-12-03 |
Time |
13:18 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-12-03 |
Time |
13:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2007-10-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-10-06 |
Time |
16:56 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-10-06 |
Time |
15:00 |
Sent To |
M |
|
| Notes |
| 2007-10-06 16:56:20 | | | | *** DENIED2ND REVIEW *** | | | | | | ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW STILL | | | NEED TO BE ADDRESSED. | | | ** PLEASE SEE NEW NOTE DUE TO CHANGE IN NOTE ON PLANS. | | | | | | 1) NOTE: PLEASE KNOW ONCE ADDRESS HAS BEEN DETERMINED | | | BY THE ADDRESSING REVIEWER THE NEW ADDRESS SHOULD BE | | | PLACED ON THE TITLE BLOCKS. | | | FBC ADMIN SECT 110.1.2, 106.1.2 | | | FAC 61G1-16.004, 61G15-23.002 | | | | | | 2) NOTE:THIS IS THE SAME COMMENT FROM PREVIOUS | | | REVIEW. | | | PLEASE SEE THE ARCHITECTURAL FIRM IS STILL MISSING THE | | | REQUIRED LICENSE INFORMATION. | | | ** THIS IS REQUIRED. IF PLANS COME BACK WITHOUT THE | | | REQUIRED INFORMATION THIS OFFICE WILL HAVE NO CHOICE | | | BUT TO TURN THIS OVER TO THE STATE. | | | PLEASE ADDRESS. | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SEE MISSING LICENSE INFORMATION ON THE TITLE | | | BLOCKS FOR THE ARCHITECTURAL FIRM. | | | PLEASE KNOW THAT THE MISSING CERTIFICATE OF | | | AUTHORIZATION AS REQUIRED FOR THE FIRM WHICH IS | | | REQUIRED TO BE ON THE TITLE BLOCK IS IN FACT DELINQUENT | | | WITH THE STATE. PLEASE SEE THE ATTACHED PRINT OUT FROM | | | THE DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION | | | WHICH INDICATES THIS AS OF THIS REVIEW. | | | PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G1-16.004 AND | | | FLORIDA STATUTES 481.219 | | | ** PLEASE KNOW THIS IS REQUIRED FOR ALL TRADES AND ALL | | | SHEETS WHICH CONTAIN THIS TITLE BLOCK WHETHER OR NOT | | | COMMENT IS MADE BY OTHER TRADE(S). | | | | | | 3) NOTE: PLEASE SEE THE PLANS ARE NOW CONTAINING A NOTE | | | WHICH MENTIONS THE ATS AND GENERATOR WILL BE UNDER | | | SEPARATE PERMITS, HOWEVER PLEASE SEE THE PLANS AND | | | RISER STILL INDICATE THE ATS BEIGN INSTALLED AT THIS | | | TIME. | | | IF ONLY THE ATS WILL BE INSTALLED AT THIS TIME WITH THE | | | ELECTRICAL FOR THE MAIN HOUSE SERVICE, THEN PLEASE | | | SUBMIT THE MANUFACTURES SPECS/CUT SHEETS FOR THIS | | | UNIT. | | | SOME OTHER SHEETS STILL SHOW THE GENERATOR. | | | FBC 106.1.1, 106.1.2, | | | NEC 110.3, 90.7 | | | | | | 4) NOTE: PLEASE SEE THE ARC FAULT PROTECTION NOTE ON | | | THE BOTTOM OF THE PANEL SCHEDULE MENTIONS THIS IS | | | REQUIRED FOR *RECEPTACLE CIRCUITS* HOWEVER THIS IS | | | REQUIRED FOR ALL AS LISTED ON PREVIOUS REVIEW NOTE FOR | | | *ALL*OUTLETS IN THE SLEEPING ROOMS INCLUSIVE OF SMOKE | | | ALARMS, FANS, LIGHTING ETC. | | | PLEASE SEE 210.12 | | | | | | 5) NOTE: PLEASE SEE THE REVISED ITEMS WERE NOT CLOUDED | | | OR INDICATED ON THE PLANS. THE NOTES ON THE LOWER RIGHT | | | HAND CORNER DO NOT ACTUALLY RESPOND TO ALL PREVIOUS | | | NOTES. | | | | | | 6) NOTE: PLEASE SEE NOTE #16 FROM PREVIOUS REVIEW WHICH | | | REQUESTED FOR COMPLETION OF THE PANEL SCHEDULE TO SHOW | | | THE REQUIRED MINIMUM BRANCH CIRCUIT CONDUCTORS, HOWEVER | | | THIS WAS NOT DONE. | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE COMPLETE PANEL SCHEDULES WITH THE BRANCH | | | CIRCUIT CONDUCTOR SIZES. | | | 408.4, 240.4, 310.16. | | | FBC 106.1.2, 106.3.5.4 | | | | | | 7) NOTE:NO INFORMATION ON LIGHTING CONTROL | | | PANEL(S)/SYSTEM AS NOTED ON PREVIOUS NOTE #17. | | | PLEASE KNOW THAT ANY LIGHTING SYSTEMS OR CONTROLS WHICH | | | ARE INSTALLED WHICH AFFECT THE BASE CODE DESIGNED BY | | | THE DESIGNER OF RECORD WILL BE REQUIRED TO GO THROUGH | | | THE RESPONSIBLE DESIGNER OF RECORD. THESE *FUTURE* | | | PLANS WILL BE REQUIRED TO CONTAIN A *SHOP DRAWING* | | | REVIEW STAMP IF PLANS ARE NOT DONE BY THE DESIGNER OF | | | RECORD. PLEASE ALSO KNOW THAT ANY INSTALLATION OF THESE | | | ITEMS WILL ALSO BE REQUIRED TO BE REVISED ON BASE HOUSE | | | PLANS FOR REFERENCE OF SYSTEM. | | | | | | **PREVIOUS REVIEW NOTE ** | | | PLEASE SUBMIT MORE INFORMATION ON THE PROPOSED LIGHTING | | | CONTROL PANELS AND SYSTEM. PLEASE SEE 110.3, 90.7 AS | | | VERIFICATION OF THE TYPE OF SYSTEM, LISTING FROM A | | | NRTL, LOCATIONS AND TYPE OF WIRING BEING INSTALLED. | | | | | | 8) NOTE: PLEASE PROVIDE A NOTE ON PLANS FOR THE TYPE OF | | | RECESSED LIGHTING AS REQUIRED PER FBC | | | 13-606-1.ABC.1.2.4. | | | | | | PLEASE KNOW THAT A TYPED WRITTEN RESPONSE WILL HELP IN | | | THE REVIEW PROCESS. THIS IS NOT REQUIRED AND ONLY A | | | SUGGESTION. | | | PLEASE ALSO SEE THE PREVIOUS REVIEW WHICH MENTIONED IF | | | THERE ARE ANY QUESTIONS OR COMMENTS TO PLEASE CONTACT | | | THIS REVIEW. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | | DELAYS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-08-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-08-31 |
Time |
10:20 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-08-29 |
Time |
19:55 |
Sent To |
M |
|
| Notes |
| 2007-08-31 10:20:56 | 2007-08-31 10:20:56 | | | | | | ** DENIED** | | | | | | | | | | | | 1) NOTE: PLEASE SEE THE ARCHITECTURAL PLANS DO NOT | | | CONTAIN AN ORIGINAL SIGNATURE AND DATE AS REQUIRED PER | | | FLORIDA STATUTES 481.221. | | | THE PLANS ARE REQUIRED TO BE SIGNED AS ORIGINAL. | | | PLACING A RAISED SEAL OVER AN *IMAGED* SIGNATURE IS NOT | | | ACCEPTABLE PER THE MINIMUM REQUIREMENTS OF THE FAC AND | | | FS. | | | **THIS IS REQUIRED FOR ALL SHEETS AND ALL TRADES | | | WHETHER OR NOT COMMENT IS MADE BY OTHER REVIEWS. | | | | | | 2) NOTE: PLEASE SEE MISSING LICENSE INFORMATION ON THE | | | TITLE BLOCKS FOR THE ARCHITECTURAL FIRM. | | | PLEASE KNOW THAT THE MISSING CERTIFICATE OF | | | AUTHORIZATION AS REQUIRED FOR THE FIRM WHICH IS | | | REQUIRED TO BE ON THE TITLE BLOCK IS IN FACT DELINQUENT | | | WITH THE STATE. PLEASE SEE THE ATTACHED PRINT OUT FROM | | | THE DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION | | | WHICH INDICATES THIS AS OF THIS REVIEW. | | | PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G1-16.004 AND | | | FLORIDA STATUTES 481.219 | | | ** PLEASE KNOW THIS IS REQUIRED FOR ALL TRADES AND ALL | | | SHEETS WHICH CONTAINS THIS TITLE BLOCK WHETHER OR NOT | | | COMMENT IS MADE BY OTHER TRADE(S). | | | | | | 3) NOTE: PLEASE SEE THE TITLE BLOCK FOR THE ENGINEER | | | AND FIRM AS SHOWN IS ALSO MISSING INFORMATION. PLEASE | | | SEE THE MISSING PRINTED NAME, PRINTED LICENSE NUMBER | | | AND MISSING CERTIFICATE OF AUTHORIZATION NUMBER. | | | **PLEASE KNOW THIS IS REQUIRED FOR ALL MEP SHEETS | | | WHETHER OR NOT COMMENT IS MADE BY OTHER TRADE(S). | | | | | | 4) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS | | | WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES | | | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. | | | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO | | | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. | | | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY | | | AFFECT DESIGNS FOR ALL TRADES. | | | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS | | | REVIEWER AT A MINIMUM. | | | 2004 FBC W/ 2006 REVISIONS | | | 2005 NFPA-70 | | | 2002 NFPA-72 | | | 2003 NFPA-101 | | | | | | | | | 5) NOTE: PLEASE SEE THE PLANS ARE SHOWING A NEW | | | GENERATOR AND ATS BEING INCLUDED WITH THE SCOPE OF WORK | | | FOR HOUSE HOWEVER PLEASE SUBMIT THE MANUFACTURES | | | SPEC/CUT SHEETS FOR BOTH.IF THE GENERATOR WILL BE | | | UNDER A SEPARATE PERMIT PLEASE ADJUST PLANS TO INDICATE | | | THIS. | | | PLEASE KNOW THE GENERATOR SPECS/CUT SHEETS ARE TO | | | INDICATE THE MINIMUM CLEARANCES FOR UNIT. | | | PLEASE SUBMIT AND SEE COMMENTS FROM OTHER TRADES FROM | | | ZONING, BUILDING AND PLUMBING. | | | FBC 106.1.1, 106.1.2, | | | NEC 110.3, 90.7 | | | | | | 6) NOTE: PLEASE SEE THERE ARE SEVERAL SPECIFIC | | | DEDICATED APPLIANCE LOADS AND MOTORS LOADS ON THE | | | ELECTRICAL PANEL SCHEDULES WHERE THE LOADS ARE NOT | | | INCLUDED IN THE LOAD CALCULATIONS. | | | PLEASE GO OVER CALCULATIONS AND ADJUST AS NEEDED. | | | PLEASE SEE FOR EXAMPLE MISSING, WATER PUMP, | | | REFRIGERATOR, WASHER, CENTRAL VACUUM, GARAGE DOOR | | | OPENER ETC. | | | PLEASE SEE NEC 220 AND SEE SOME COMMENTS BELOW FOR SOME | | | OTHER LOADS. | | | | | | 7) NOTE:PLEASE SEE 210. 52C2 AND 220.53 FOR MINIMUM | | | LOADS FOR THE WASHER/LAUNDRY LOADS AS REQUIRED. PLEASE | | | SEE THE PANEL SCHEDULE DOES NOT INDICATE THE MINIMUM OF | | | 1500VA FOR EACH OF THESE AS SHOWN AND LISTED. PLEASE | | | ALSO SEE THE LOADS SHOWN ON THE LOAD CALCULATIONS ON | | | THE SERVICE INDICATE (2) LAUNDRY LOADS HOWEVER THE TWO | | | ARE SHOWN WITH A TOTAL OF 4500VA? | | | IT IS UNCLEAR HOW THESE LOADS ARE BEING DETERMINED AS | | | THE PANEL SCHEDULE AND OTHER LOADS ARE NOT THE SAME. | | | PLEASE SEE THE SECTIONS AS NOTED FOR THE MINIMUM | | | LOADS. | | | PLEASE ADJUST. | | | | | | 8) NOTE: PLEASE SEE MISSING ARC FAULT PROTECTION FRO | | | ALL OUTLETS IN THE SLEEPING ROOMS INCLUSIVE OF SMOKE | | | ALARMS, FANS, LIGHTING ETC. | | | PLEASE SEE 210.12 | | | | | | 9) NOTE: PLEASE SEE MINIMUM LOADS TO BE FIGURED FOR | | | RECESSED LIGHTING. PLEASE SEE THAT THE WATTAGE BASED ON | | | THE AMOUNT OF EACH OF THESE TYPES OF FIXTURES DO EXCEED | | | THE 3VA PER SQ FT.THIS WAS CONFIRMED BY THE CODE | | | PANELIST AND THE AHJ IS THE DETERMINING AUTHORITY. | | | PLEASE SEE THE FOLLOWING TEXT WHICH IS TAKEN DIRECTLY | | | FROM THE 2005 NEC AND SOME COMMENTARY FROM THE | | | HANDBOOK. | | | | | | *D) LUMINAIRES (LIGHTING FIXTURES) AN OUTLET SUPPLYING | | | LUMINAIRE(S) [LIGHTING FIXTURE(S)] SHALL BE CALCULATED | | | BASED ON THE MAXIMUM VOLT-AMPERE RATING OF THE | | | EQUIPMENT AND LAMPS FOR WHICH THE LUMINAIRE(S) | | | [FIXTURE(S)] IS RATED. | | | IN GENERAL, NO ADDITIONAL CALCULATION IS REQUIRED FOR | | | LUMINAIRES (RECESSED AND SURFACE MOUNTED) INSTALLED IN | | | OR ON A DWELLING UNIT, BECAUSE THE LOAD OF SUCH | | | LUMINAIRES IS COVERED IN THE 3 VOLT-AMPERES PER SQUARE | | | FOOT CALCULATION SPECIFIED BY TABLE 220.12. WHERE THE | | | RATING OF THE LUMINAIRES INSTALLED FOR GENERAL LIGHTING | | | EXCEEDS THE MINIMUM LOAD PROVIDED FOR IN TABLE 220.12, | | | THE MINIMUM GENERAL LIGHTING LOAD FOR THAT PREMISES IS | | | TO BE BASED ON THE INSTALLED LUMINAIRES. DISTINGUISHING | | | BETWEEN THE LUMINAIRES INSTALLED FOR GENERAL LIGHTING | | | VERSUS THOSE INSTALLED FOR ACCENT, SPECIALTY OR DISPLAY | | | LIGHTING IS MUCH EASIER TO DELINEATE IN COMMERCIAL | | | (PARTICULARLY MERCANTILE) OCCUPANCIES. | | | | | | AS STATED, *IN GENERAL* AN ADDITIONAL AMOUNT IS NOT | | | NEEDED ONLY WHEN THE FIXTURES ARE USED FOR NORMAL | | | GENERAL LIGHTING. WHEN THE FIXTURES EXCEED THE GENERAL | | | LIGHTING USE AS THIS IS DONE ON THIS PLAN, THEN THE | | | ADDITIONAL SHALL BE FIGURED. | | | PLEASE SEE THIS SECTION IN THE 2002 NEC WAS 220.3B4 | | | | | | 10) NOTE: PLEASE SEE NFPA-72 FOR DEFINITIONS FOR SMOKE | | | DETECTION DEVICES.PLEASE SEE THAT SMOKE DETECTORS ARE | | | DEVICES WHICH ONLY DETECT AND DO NOT SOUND AND ALARM | | | WHEREAS SMOKE ALARMS ARE DEVICES WHICH DETECT AND SOUND | | | AN ALARM. | | | AS THE PLAN INDICATES SD FOR SMOKE DETECTORS THIS SEEMS | | | IT SHOULD BE SA FOR SMOKE ALARMS. | | | PLEASE SEE THE 2002 NFPA-72 | | | | | | 11) NOTE: PLEASE SEE THE PLANS DO NOT SHOW ANY OF THE | | | MAINS AS SHOWN ON RISER ON THE OUTSIDE OF THE HOUSE. | | | ONLY THE METER AND ATS IS SHOWN. | | | PLEASE COORDINATE. | | | FBC 106.1.2 | | | | | | 12) NOTE: PLEASE SEE THE POOL PANEL DOES NOT MEET THE | | | MINIMUM CLEARANCE REQUIREMENTS PER 110.26. | | | | | | 13) NOTE: PLEASE SEE THE HOT WATER HEATERS ARE BEING | | | SHOWN AS CONNECTED BY MEANS OF RECEPTACLES WHICH ARE | | | NOT PERMITTED. | | | PLEASE SEE 422.30, 422.31. | | | PLEASE INDICATE ON PLANS. | | | | | | 14) NOTE: PLEASE SEE 422.13 AS THE LOADS FOR THE WATER | | | HEATERS ARE TO BE FIGURED AT 125% FOR CONTINUOUS | | | LOADS. | | | THIS WAS REVISED IN THE 2005 NEC AND PLEASE SEE CODE | | | COMMENTARY IN THE NEC HANDBOOK. | | | | | | 15) NOTE: PLEASE GO OVER FIXTURES AND LOCATIONS IN ALL | | | STORAGE CLOSETS FOR MINIMUM CLEARANCES FOR FIXTURES | | | FROM CLOSET SHELVING PER 410.8 | | | PLEASE SEE THERE ARE SOME ON PLANS WHICH AS SHOWN ARE | | | TOO CLOSE TO SHELVES. | | | | | | 16) NOTE: PLEASE COMPLETE PANEL SCHEDULES WITH THE | | | BRANCH CIRCUIT CONDUCTOR SIZES. | | | 408.4, 240.4, 310.16. | | | FBC 106.1.2, 106.3.5.4 | | | | | | 17) NOTE: PLEASE SUBMIT MORE INFORMATION ON THE | | | PROPOSED LIGHTING CONTROL PANELS AND SYSTEM. PLEASE SEE | | | 110.3, 90.7 AS VERIFICATION OF THE TYPE OF SYSTEM, | | | LISTING FROM A NRTL, LOCATIONS AND TYPE OF WIRING BEING | | | INSTALLED. | | | | | | 18) NOTE: PLEASE SEE SOME 3-WAY SWITCHING LOCATIONS ARE | | | SHOWING A S3, (3-WAY DEVICE AT EITHER END WHICH IS OK, | | | HOWEVER PLEASE CLARIFY THAT BOTH ENDS ARE SHOWN AS | | | BEING DIMMERS? | | | IN 3-WAY AND OR 4-WAY WIRING SYSTEMS THE DIMMERS ARE | | | TYPICALLY ONLY AT ONE LOCATION BASED ON STANDARD | | | DEVICES WHICH IS WHAT IS BEING SHOWN. | | | PLEASE SEE THE NOTE #16 ABOVE AS THESE MAY BE A PART OF | | | THE LIGHTING CONTROL SYSTEM WHICH IS NOT KNOWN AT THIS | | | TIME. | | | | | | 19) NOTE: PLEASE SEE THE LOADS FOR THE AIR HANDLERS ARE | | | IN QUESTION. THE A/C DETAILS INDICATE LOADS IN KW WHICH | | | ARE SUBSTANTIALLY HIGHER THAN THAT OF THE LOAD SHOWN ON | | | THE LOAD CALCULATIONS. | | | PLEASE SEE 220.60 AS THE LARGER OF THE HEATING AND | | | COOLING LOADS ARE TO BE FIGURED. | | | | | | 20) NOTE: PLEASE KNOW AS FOR INFORMATION THE LOW | | | VOLTAGE AS SHOWN ON PLANS WILL BE REQUIRED TO BE UNDER | | | SEPARATE PERMITS. THESE PLANS WHICH CONTAIN ITEMS FOR | | | MANY LV ITEMS MAY BE USED AS A REFERENCE FOR TURN | | | AROUND PERMITS HOWEVER SEPARATE APPLICATION AND FEES | | | WILL BE DUE BASED ON THE SEPARATE VALUATIONS OF THESE | | | SYSTEMS. | | | *ANY LOW VOLTAGE SECURITY IS ALSO UNDER A SEPARATE | | | PERMIT. THESE DO NOT NEED PLANS UNLESS CAMERA OR ACCESS | | | CONTROL SYSTEMS ARE BEING INSTALLED. THE DEVICE | | | LOCATIONS INCLUDING THE LOCATION OF SECURITY PANELS DO | | | NOTNEED TO BE INCLUDED ON ANY PANELS. | | | THE LV FOR ALARM SYSTEMS IS UNDER SEPARATE FEES BASED | | | ON THAT SCOPE OF WORK. | | | THIS IS ONLY NOTED FOR INFORMATION AND NO INFORMATION | | | AND CHANGES NEED TO BE MADE ON PLANS. | | | ** IF THERE IS ANY CLARIFICATION NEEDED PLEASE CONTACT | | | THIS OFFICE/REVIEWER. | | | | | | 21) NOTE: PLEASE SEE THE PLANS INDICATE THE RECEPTACLE | | | BEING NOTED FOR THE WINE COOLER (MAIN) BEING CIRCUITED | | | TO OTHER GENERAL PURPOSE RECEPTACLES IN THE DWELLING. | | | PLEASE CLARIFY THIS AS SHOWN. | | | PLEASE VERIFY LOAD AND PROVIDE INFORMATION FOR ANY | | | CHANGES WITH ANY MOTOR LOADS ON THE GENERAL PURPOSE | | | BRANCH RECEPTACLES. | | | FBC 106.1.2. | | | 430.6 AND SEVERAL OTHER CODES IN 430 FOR INFORMATION | | | INCLUDING 430.148 | | | | | | 22) NOTE: PLEASE SEE THE A/C CLOSET DETAILS ON SHEET | | | FOR SECOND FLOOR. THE DISCONNECT SHOWN FOR ONE O OF THE | | | AIR HANDLER UNITS DO NOT SEEM TO MEET 110.26. | | | | | | 23) NOTE: PLEASE SEE THE PLANS NOTES *BREAKER LOCK | | | DEVICES* FOR SMOKE ALARMS. | | | PLEASE KNOW AS NOTED ABOVE THESE REQUIRE ARC FAULT | | | PROTECTION REQUIRED, THESE SMOKE DEVICES MAY BE PLACED | | | ON THE LIGHTING/RECEPTACLE CIRCUITS FOR BEDROOMS. | | | | | | 24) NOTE: PLEASE PROVIDE A NOTE ON PLANS FOR THE TYPE | | | OF RECESSED LIGHTING AS REQUIRED PER FBC | | | 13-606-1.ABC.1.2.4. | | | | | | ** PLEASE SEE ANY COMMENTS FROM OTHER TRADES WHICH MAY | | | OR MAY NOT AFFECT ELECTRICAL PLANS. | | | | | | | | | | | | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | 2007-08-31 07:58:21 | 2007-08-31 07:58:21 | | | | | | REVIEW CONTINUED | | 2007-08-29 20:50:20 | 2007-08-29 20:50:20 | | | | | | ELECTRICAL REVIEW WILL BE PROCESSED INTO A *F* STATUS | | | AND NOTES WILL FOLLOW ONCE REVIEW IS COMPLETED ON 8/30 | | 2007-08-29 19:55:58 | 2007-08-29 19:55:58 | | | IN ELEC FOR REVIEW |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
14 |
Status |
N |
Date |
2009-09-22 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2009-09-17 |
Time |
10:59 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2009-09-17 |
Time |
10:59 |
Sent To |
|
|
| Notes |
| 2009-09-22 11:00:40 | GAVE TO DEWEY, ROUTED ON 9/22 LM |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
13 |
Status |
N |
Date |
2009-07-15 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2009-07-15 |
Time |
08:55 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2009-07-15 |
Time |
08:55 |
Sent To |
|
|
| Notes |
| 2009-07-15 08:55:25 | TO DP DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
12 |
Status |
N |
Date |
2009-04-20 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2009-04-20 |
Time |
11:37 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2009-04-20 |
Time |
11:37 |
Sent To |
|
|
| Notes |
| 2009-04-20 11:37:48 | TO RM DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
11 |
Status |
N |
Date |
2009-04-10 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2009-04-10 |
Time |
13:04 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2009-04-10 |
Time |
13:04 |
Sent To |
B |
|
| Notes |
| 2009-04-10 13:04:45 | TO "RMCDOUGAL" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
10 |
Status |
N |
Date |
2008-09-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-09-23 |
Time |
15:43 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-09-23 |
Time |
15:43 |
Sent To |
M |
|
| Notes |
| 2008-09-23 15:43:54 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
9 |
Status |
N |
Date |
2008-04-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-04-02 |
Time |
14:11 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-04-02 |
Time |
14:11 |
Sent To |
P |
|
| Notes |
| 2008-04-02 14:12:27 | TO "P" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2008-03-26 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-03-26 |
Time |
13:53 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-03-26 |
Time |
13:53 |
Sent To |
P |
|
| Notes |
| 2008-03-26 13:54:05 | TO "P" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2008-02-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-02-06 |
Time |
11:10 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-02-06 |
Time |
11:10 |
Sent To |
B |
|
| Notes |
| 2008-02-06 11:10:33 | TO "RMCDOUGAL" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2008-01-29 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-01-29 |
Time |
08:31 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-01-29 |
Time |
08:31 |
Sent To |
M |
|
| Notes |
| 2008-01-29 08:31:35 | TO "M" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2008-01-11 |
|
|
Cont ID |
|
| Sent By |
spalmer |
Date |
2008-01-11 |
Time |
|
Rev Time |
0.00 |
| Received By |
spalmer |
Date |
2008-01-11 |
Time |
10:32 |
Sent To |
M |
|
| Notes |
| 2008-01-11 10:33:24 | TO TOM GORDONS DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2008-01-10 |
|
|
Cont ID |
|
| Sent By |
mmiller |
Date |
2008-01-10 |
Time |
19:09 |
Rev Time |
0.00 |
| Received By |
mmiller |
Date |
2008-01-10 |
Time |
19:09 |
Sent To |
|
|
| Notes |
| 2008-01-10 19:10:18 | NEED TO SPEAK WITH DEWEY PALMER REGARDING THESE PLANS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-11-30 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-11-30 |
Time |
14:38 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-11-30 |
Time |
14:38 |
Sent To |
Z |
|
| Notes |
| 2007-11-30 14:38:42 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-10-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-10-02 |
Time |
10:37 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-10-02 |
Time |
10:37 |
Sent To |
Z |
|
| Notes |
| 2007-10-02 10:37:51 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-09-18 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2007-09-18 |
Time |
14:45 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2007-08-22 |
Time |
16:14 |
Sent To |
|
|
| Notes |
| 2007-08-22 16:14:53 | TO "SFR" "Z" |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
P |
Date |
2008-09-25 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-09-25 |
Time |
15:26 |
Rev Time |
0.45 |
| Received By |
tgordon |
Date |
2008-09-25 |
Time |
15:26 |
Sent To |
|
|
| Notes |
| 2008-09-25 15:27:35 | RVISION TO MECH. PLANS M-1 AND M-2. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2008-01-29 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-01-29 |
Time |
09:21 |
Rev Time |
0.45 |
| Received By |
tgordon |
Date |
2008-01-29 |
Time |
09:21 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2008-01-11 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-01-11 |
Time |
13:41 |
Rev Time |
1.30 |
| Received By |
tgordon |
Date |
2008-01-11 |
Time |
13:41 |
Sent To |
B |
|
| Notes |
| 2008-01-11 14:04:27 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) ONLY ONE SET OF THE MECHANICAL PLANS PAGE M-1 AND | | | M-2 WERE SUBMITTED FOR REVIEW, TWO SETS MUST BE | | | SUBMITTED, SEE 2004 FBC/WPB AMEND. 106.1. | | | | | | 2) COOLING LOAD CALCULATIONS ARE CALLING FOR 121,173 | | | TOTAL COOLING BTU'S, MECHANICAL PLANS ARE SHOWING | | | 156,400 TOTAL COOLING BTU'S, THE PLANS CAN ONLY CALL | | | FOR 15% MORE THAN THE COOLING LOAD CALCULATIONS, SEE | | | 2004 FBC 13-607.1.ABC.1.1. 13 TONS OF AIR CONDITIONING | | | APPEARS TO BE TO MUCH, PLEASE CORRECT. | | | | | | 3) A/C SYSTEM 1 AND 2 ARI CERTIFICATION HAS BEEN | | | DISCONTINUED (SEE ATTACHED COPY), SEE 2004 FBC | | | 13-607.1.ABC.3.1.1, PLEASE CORRECT. | | | | | | 4) THE FIRST FLOOR CLOTHES DRYER VENT MAY NOT DISCHARGE | | | ON OR TERMINATE NEAR THE A/C CONDENSER UNIT, SEE 2004 | | | FBC/R M303.4.2, PLEASE CORRECT. | | | | | | 5) PLEASE ADD JOB ADDRESS TO ANY NEW MECHANICAL PLANS, | | | SEE 2004 FBC/WPB AMEND. 106.1.3. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] . |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2007-12-03 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-12-03 |
Time |
14:58 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2007-12-03 |
Time |
14:57 |
Sent To |
P |
|
| Notes |
| 2007-12-03 15:03:00 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) COMPLETE MECHANICAL REVIEW COULD NOT BE DONE AS | | | MECHANICAL PLANS PAGES M.1 AND M.2 WERE NOT SUBMITTED | | | WITH REVISED PLANS. SEE 2004 W.P.B AMEND. 106.3.5.4 | | | (10) SUBMIT MECHANICAL PLANS FOR REVIEW. | | | | | | 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT | | | ALSO, PER 2004 FBC 13-600.3.ABC.2. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2007-10-10 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-10-10 |
Time |
12:06 |
Rev Time |
0.45 |
| Received By |
tgordon |
Date |
2007-10-10 |
Time |
12:06 |
Sent To |
P |
|
| Notes |
| 2007-10-10 12:29:56 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | | PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA | | | ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS). | | | | | | *** DENIED *** | | | | | | 1) AS NOTED IN LAST REVIEW 9/6/07. MECHANICAL PLANS, | | | INFORMATION MISSING IN TITLE BLOCK FOR ARCHITECT | | | (ARCHITECT FIRM LICENSE NUMBER AA0002936). | | | PER FAC 61G1-16.004 TITLE BLOCK. | | | | | | 2) AS NOTED IN LAST REVIEW 9/6/07 NOTE #3. PLEASE | | | SUBMIT COOLING LOAD CALCULATIONS, SEE FBC | | | 13-407.1.ABC.1. | | | | | | 3) AS NOTED IN LAST REVIEW 9/6/07 NOTE #4. ENERGY | | | CALCULATIONS LINE 13A, AND B SHOW THE A/C SYSTEMS AS | | | HEAT PUMP SYSTEMS. THE ARI DIRECTORY SHOWS THE UNITS | | | ARE STRAIGHT COOL SYSTEMS, PLEASE CORRECT ENERGY CAL'S. | | | OR MODEL NUMBERS ON MECHANICAL PLANS. | | | | | | 4) AS NOTED IN LAST REVIEW 9/6/07 NOTE #6. PLEASE | | | SUBMIT DETAILED MANUFACTURER'S SPECIFICATION'S AND | | | INSTALLATION INSTRUCTIONS FOR THE GAS BBQ GRILL AND | | | HOOD, GAS FIRE PLACES, AND GAS LOG LIGHTERS IF USED. | | | | | | 5) AS NOTED IN LAST REVIEW NOTE #7. PLEASE SUBMIT | | | PRODUCT APPROVAL FOR O/A LOUVER FOR SAFE ROOM, SEE FS | | | 553.842(1) AND FAC RULE 9B-72, 9B-72.005, AND FAC | | | 9B-72.010(31)(G). | | | | | | **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION | | | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE | | | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE | | | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. | | | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT | | | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT | | | HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR | | | LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE | | | 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG. | | | | | | 6) WASHER/DRYER DETAIL ON PAGE DMP-1 STATES PER I.M.C. | | | 2003304.6.1. ALL WORK PERMITTED IN THE CITY OF W.P.B. | | | MUST COMPLY WITH THE "2004 F.B.C.", PLEASE CORRECT. | | | | | | 7) SEE ATTACHED NOTICE FS 553.80 (2) (B) REGARDING FOUR | | | TIMES THE FEE. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2007-09-06 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-09-06 |
Time |
08:43 |
Rev Time |
1.30 |
| Received By |
tgordon |
Date |
2007-09-06 |
Time |
08:43 |
Sent To |
P |
|
| Notes |
| 2007-09-06 09:33:01 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | | PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA | | | ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS). | | | | | | *** DENIED *** | | | 1) MECHANICAL PLANS, INFORMATION MISSING FROM TITLE | | | BLOCK (ENGINEERS PRINTED NAME AND LICENSE NUMBER WHO | | | SEALED THE PLAN, AND THE ENGINEERING BUSINESS | | | CERTIFICATE OF AUTHORIZATION NUMBER). | | | SEE FAC 61G15-23.002 (2)A TITLE BLOCK ON EACH SHEET | | | CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE | | | NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND | | | LICENSE NUMBER OF THE ENGINEER, AND THE NAME, ADDRESS | | | AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE | | | ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT. | | | | | | 2) MECHANICAL PLANS, INFORMATION MISSING IN TITLE BLOCK | | | FOR ARCHITECT (ARCHITECT FIRM LICENSE NUMBER, AND JOB | | | ADDRESS). | | | SEE FAC 61G1-16.004 TITLE BLOCK. A TITLE BLOCK MUST | | | APPEAR ON ALL ARCHITECTURAL OR INTERIOR DESIGN DRAWINGS | | | AND SPECIFICATION IDENTIFICATION SHEETS. THE TITLE | | | BLOCK MUST, AT A MINIMUM, CONTAIN THE FOLLOWING | | | INFORMATION: | | | (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. | | | (2) FIRM LICENSE NUMBER. | | | (3) NAME OR IDENTIFICATION OF PROJECT. ("JOB ADDRESS" | | | SEE CITY WPB AMEND. 106.1.1). | | | (4) DATE PREPARED. | | | (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. | | | (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING | | | THE DOCUMENT. | | | | | | 3) PLEASE SUBMIT COOLING LOAD CALCULATIONS, SEE FBC | | | 13-407.1.ABC.1. | | | | | | 4) ENERGY CALCULATIONS LINE 13A, AND B SHOW THE A/C | | | SYSTEMS AS HEAT PUMP SYSTEMS. THE ARI DIRECTORY SHOWS | | | THE UNITS ARE STRAIGHT COOL SYSTEMS, PLEASE CORRECT | | | ENERGY CAL'S. OR MODEL NUMBERS ON MECHANICAL PLANS. | | | | | | 4) PAGE DMP-1 DETAIL OF CONDENSATE DISCHARGE TO GRADE, | | | DRAIN NEEDS TO DISCHARGE 12" FROM THE BUILDING, SEE | | | RES. R320.7. PLEASE CORRECT. | | | | | | 5) PAGES M-1 AND M-2 DUCT SCHEDULE ZONES 2, 3, AND 4 DO | | | NOT SHOW ALL THE DUCT SIZES (SEE YELLOW HIGH LIGHT ON | | | PLAN) PLEASE CORRECT. | | | | | | 6) PLEASE SUBMIT DETAILED MANUFACTURER'S | | | SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR THE | | | GAS BBQ GRILL AND HOOD, GAS FIRE PLACES, AND GAS LOG | | | LIGHTERS IF USED. | | | | | | 7) PLEASE SUBMIT PRODUCT APPROVAL FOR O/A LOUVER FOR | | | SAFE ROOM, SEE FS 553.842(1) AND FAC RULE 9B-72, | | | 9B-72.005, AND FAC 9B-72.010(31)(G). | | | | | | **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION | | | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE | | | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE | | | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. | | | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT | | | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT | | | HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR | | | LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE | | | 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG. | | | | | | *** INFORNATIONAL: PAGE A.01 SHOWS A GENERATOR NEAR A | | | 8X8" VENT BLOCK TO THE GARAGE NFPA 37 REQUIRES | | | GENERATORS TO BE FIVE FEET FROM BUILDING OPENINGS. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2008-04-14 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2008-04-14 |
Time |
08:10 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2008-04-14 |
Time |
08:00 |
Sent To |
|
|
| Notes |
| 2008-04-14 08:11:06 | PLUMBING AS-BUILTS |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2008-03-27 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-03-27 |
Time |
10:22 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-03-27 |
Time |
10:22 |
Sent To |
PC |
|
| Notes |
| 2008-03-27 10:29:55 | PLUMBING PLAN REVIEW: | | | REVISION DENIED: | | | | | | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | 1. SHEET P.01 MASTER BATH SANITARY PLUMBING RISER: THE | | | BIDET IS NOT VENTED. PER FBC PLUMBING SECTION 901.2.1 | | | VENTING REQUIRED. | | | | | | ********IMPORTANT INFORMATION******** | | | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION | | | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | NOTE: THERE IS ONLY ONE CORRECTED DRAWING | | | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS | | | EXAMINER FOR REFERENCE FOR THE | | | RESUBMITTAL. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | PHONE= (561) 805-6730 | | | FAX= (561) 805-6731 | | | E-MAIL= [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2007-12-14 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-12-14 |
Time |
09:52 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-12-14 |
Time |
08:33 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2007-10-16 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-10-16 |
Time |
08:31 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-10-16 |
Time |
08:01 |
Sent To |
B |
|
| Notes |
| 2007-10-16 08:51:55 | DENIED; | | | 1.SEE MECHANICAL NOTE #1. ARCHITECT FIRM LICENSE IS | | | REQUIRED ON THE TITLE BLOCK. | | | 2. SANITARY RISER DIAGRAM, CLEANOUT'S REQUIRED ON | | | AUTOMATIC CLOTHES WASHER VENT AT 48" ABOVE FINISH | | | FLOOR. | | | 3. DISHWASHERS TO DISCHARGE INDIRECTLY INTO BUILDING | | | DRAIN. SECTION 802.1.6. | | | 4. 1/2 BATH FIRST FLOOR TOILET NOT VENTED AS DRAWN | | | CANNOT DISCHARGE INTO THE 2ND FLOOR BRANCH DRAIN. | | | 5. WATER SANITARY RISER DIAGRAM WATER HAMMER ARRESTORS | | | ARE REQUIRED ON ALL QUICK CLOSING VALVES PER 604.9 SHOW | | | ON PLANS. | | | 6. 2 WATER HEATERS SHOWN ON FLOOR PLANS 80 GAL ON 1ST | | | FLOOR60 GAL ON 2ND FLOOR, ONLY ONE MODEL # SHOWN ON | | | PAGE DMP-1. | | | 7. SHOW LOCATION OF IN-LINE PUMP FOR MATER SHOWER. THIS | | | PUMP MUST BE ACCESSABLE WITH A SHUTOFF VALVE UP STREAM. | | | | | | PLUMBING PLAN REVIEW BY | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-09-11 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-09-11 |
Time |
08:50 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-09-11 |
Time |
08:24 |
Sent To |
B |
|
| Notes |
| 2007-09-11 09:11:09 | DENIED; | | | SEE ELECTRICAL PLAN REVIEW NOTES 1 THRU 5. | | | 1.SHOW ON PLANS, BACKFLOW PREVENTOR REQUIRED. CITY | | | UTILITY ORD. RPZ REQUIRED IF HOUSE HAS A POOL. | | | 2. ( ONE SHEET DMP-2) MARKED IN RED, SHOWER NOT VENTED. | | | SINK TO DISCHARGE DOWN STREAM OF BATHROOM GROUP, | | | SECTION 909.1. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2007-11-30 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-11-30 |
Time |
16:24 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-11-30 |
Time |
16:24 |
Sent To |
E |
|
| Notes |
| 2007-11-30 15:46:13 | *** APPROVED- RESUB #2*** | | | | | | | | | | | | SENT TO "E" - DP |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2007-10-05 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-10-05 |
Time |
12:11 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-10-05 |
Time |
12:11 |
Sent To |
E |
|
| Notes |
| 2007-10-05 12:12:41 | ***FAILED - RESUB #1*** | | | | | | | | | REPEAT COMMENTS: | | | | | | 1)EXCEEDS MAXIMUM BUILDING HEIGHT.DEVELOPMENT | | | REGULATIONS FOR BEAR LAKES ALLOW A MAXIMUM BUILDING | | | HEIGHT OF 35' (MEASURED FROM GRADE TO THE MIDPOINT OF | | | THE ROOF'S PITCH), WITH AN ALLOWABLE 10% FOR | | | ACCESSORIES.YIELDING A MAXIMUM HEIGHT FOR ALL | | | ACCESSORIES (NON-HABITABLE TOWERS) OF 38.5' . | | | | | | 2)AS THE FRONT SITE WALL (COLUMNS) FALLS WITHIN THE | | | FRONT UTILITY EASEMENT, ADDITIONAL EASEMENT CONSENT | | | FORMS SHALL BE PROVIDED FROM:FP&L, COMCAST/ADELPHIA, | | | FLA PUBLIC UTILITIES, AND BELLSOUTH. | | | | | | NEW COMMENTS: | | | | | | 1)INDICATE SETBACK DIMENSIONS FROM TRELLIS TO REAR | | | PROPERTY LINE. | | | | | | 2)PURSUANT TO SECTION 94-302(B)(1) OF THE ZONING AND | | | LAND DEVELOPMENT REGULATIONS:RESIDENTIAL FENCE, | | | HEDGE, AND WALL LIMITATIONS. | | | (1)MAXIMUM HEIGHT.IN RESIDENTIAL DISTRICTS, NO | | | FENCE OR WALL SHALL EXCEED SIX FEET IN HEIGHT WITHIN | | | REQUIRED SIDE AND REAR SETBACKS. FENCES OR WALLS SHALL | | | NOT BE IN EXCESS OF 48 INCHES IN HEIGHT WITHIN THE | | | REQUIRED FRONT SETBACK. HEDGES SHALL NOT EXCEED TEN | | | FEET IN HEIGHT IN ANY REQUIRED SETBACK. | | | | | | NOTE:PALM TREES DO NOT COUNT TOWARDS THE REQUIRED | | | FLOWERING/FRUIT TREE REQUIREMENT FOR OPEN SPACE.CHECK | | | THAT REQUIREMENT IS STILL SATISFIED. | | | | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING | | | TECHNICIAN | | | (561)805-6720 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2007-08-24 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-08-24 |
Time |
11:12 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-08-24 |
Time |
11:12 |
Sent To |
E |
|
| Notes |
| 2007-08-24 11:24:13 | ***FAILED*** | | | | | | | | | 1)EXCEEDS MAXIMUM BUILDING HEIGHT.DEVELOPMENT | | | REGULATIONS FOR BEAR LAKES ALLOW A MAXIMUM BUILDING | | | HEIGHT OF 35' (MEASURED FROM GRADE TO THE MIDPOINT OF | | | THE ROOF'S PITCH), WITH AN ALLOWABLE 10% FOR | | | ACCESSORIES.YIELDING A MAXIMUM HEIGHT FOR ALL | | | ACCESSORIES (NON-HABITABLE TOWERS) OF 38.5' . | | | | | | 2)PROVIDE A LANDSCAPE PLAN SHOWING COMPLIANCE WITH | | | SECTION 94-442 OF THE CITY OF WEST PALM BEACH ZONING | | | AND LAND DEVELOPMENT REGULATIONS. | | | | | | 3)SHEET AS.0 SHOWS A GENERATOR AND POOL EQUIPMENT. | | | PLANS SHALL REFLECT THESE TO BE PERMITTED SEPARATELY. | | | | | | 4)SHEET AS.0 APPEARS TO SHOW A FRONT SITE WALL.IF | | | INCLUDED IN SCOPE OF WORK FOR THIS PERMIT, AN ELEVATION | | | OF PROPOSED WALL SHALL BE SHOWN AND AN EASEMENT CONSENT | | | FORM FROM THE CITY OF WEST PALM BEACH DEPARTMENT OF | | | PUBLIC UTILITIES SHALL BE APPROVED AND SUBMITTED. NOTE: | | | IF SITE WALL FALLS WITHIN THE FRONT UTILITY EASEMENT, | | | ADDITIONAL EASEMENT CONSENT FORMS SHALL BE PROVIDED | | | FROM:FP&L, COMCAST/ADELPHIA, FLA PUBLIC UTILITIES, | | | AND BELLSOUTH. | | | | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING | | | TECHNICIAN | | | (561)805-6720 |
|
|