Plan Review Details - Permit 07080572
Plan Review Stops For Permit 07080572
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2007-10-16 Cont ID  
Sent By lursu Date 2007-10-16 Time 14:47 Rev Time 0.00
Received By lursu Date 2007-10-16 Time 14:47 Sent To  
Notes
2007-10-16 14:50:44THE RECORDED UNITY OF TITLE FOR THESE TWO PARCELS WAS
 RECEIVED AND A NEW SITE ADDRESS : 2671 DAKOTA CIR ,WEST
 PALM BEACH, FL 33409 IS ASSIGNED TO THE NEW SINGLE
 HOUSE.BASED ON THE UOT A NEW PARCEL CONTROL NUMBER WILL
 BE ISSUED BY THE PROPERTY APPRAISER'S OFFICE .
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2007-08-31 Cont ID  
Sent By lursu Date 2007-08-31 Time 11:27 Rev Time 0.00
Received By lursu Date 2007-08-31 Time 11:27 Sent To  
Notes
2007-08-31 11:36:08PRIOR OF ISSUING THE NEW SITE ADDRESS FOR THE NEW HOUSE
 , THE UNITY OF TITLE FOR THE TWO PARCELS MUST BE
 RECORDED .THE PROPERTY APPRAISER'S OFFICE WILL ISSUE A
 NEW PARCEL CONTROL NUMBER FOR THE UNIFIED PROPERTIES
 AND BASED ON THE NEW PCN, THE CITY WILL ISSUE THE NEW
 SITE ADDRESS.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2009-04-30 Cont ID  
Sent By rmcdouga Date 2009-04-30 Time 08:37 Rev Time 0.00
Received By rmcdouga Date 2009-04-30 Time 08:37 Sent To  
Notes
2009-04-30 09:32:26REVISION TO REPLACE GARAGE SIDE DOOR WITH ONE OF A KIND
 SITE SPECIFIC DOOR IS OK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2009-04-15 Cont ID  
Sent By rmcdouga Date 2009-04-15 Time 10:04 Rev Time 0.00
Received By rmcdouga Date 2009-04-15 Time 10:04 Sent To  
Notes
2009-04-15 10:41:03REVISION DENIED BY BUILDING
  
  
 1) THE REVISION TO CHANGE FRONT DOOR IS OK. FL. PRODUCT
 APPROVALS WERE SUBMITTED. PLACE COPY OF STAMPED PRODUCT
 APPROVAL WITH THE PLANS.
  
 2) THE REVISION TO CHANGE SIDE DOOR IS DENIED. THIS
 DOOR DOES NOT HAVE STATE PRODUCT APPROVAL. LOCAL/SITE
 SPECIFIC ENGINEERING IS REQUIRED IN ACCORDANCE WITH DCA
 RULE 9B-72. ORIGINAL SIGNED AND SEALED DOCUMENTS FROM
 THE ENGINEER ARE REQUIRED. NOTE: THE DESIGN PRESSURES
 IN THE SUBMITTAL OF +36.0 PSF, -39.3 PSF ARE TOO LOW.
 THE STRUCTURE IS LOCATED IN EXPOSURE CATEGORY C THE
 OPENING PRESSURE OF +47.5 PSF, -51.8 PSF ARE SPECIFIED
 ON SHEET S3.02 OF THE PLANS FOR A 20 SQFT OPENING. THE
 STREET NAME ON THE LETTER IS INCORRECT, IT IS DAKOTA
 CIRCLE. PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2008-02-11 Cont ID  
Sent By rmcdouga Date 2008-02-11 Time 11:05 Rev Time 0.00
Received By rmcdouga Date 2008-02-11 Time 11:05 Sent To  
Notes
2008-02-11 11:07:15CONTRACTOR SUBMITTED PRODUCT APPROVAL FOR GARAGE DOORS
 WITH ADEQUATE DESIGN PRESSURES AS REQUESTED IN THE
 BUILDING PROVISO.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-01-31 Cont ID  
Sent By rmcdouga Date 2008-01-31 Time 15:38 Rev Time 0.00
Received By rmcdouga Date 2008-01-31 Time 07:01 Sent To  
Notes
2008-01-31 15:38:42 
 BUILDING PROVISO
  
 SUBMIT PRODUCT APPROVALS FOR THE 9' X 8' OVERHEAD
 GARAGE DOORS WITH DESIGN PRESSURES GREATER THAN + 43.7
 / -49.5 PSF.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-01-17 Cont ID  
Sent By rmcdouga Date 2008-01-17 Time 11:29 Rev Time 0.00
Received By rmcdouga Date 2008-01-16 Time 11:27 Sent To  
Notes
2008-01-17 11:41:102004 FBC W/2007 SUPPLEMENTS
 NSFR
  
 DENIED BY BUILDING
  
 1) COMPLIED
  
 2) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED. WORK MUST COMMENCE WITHIN 90 DAYS
 OF THE DATE THE NOC IS RECORDED. FS 713.13. THE ONE
 THAT WAS SUBMITTED IS EXPIRED.
  
 3) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED. SUBMIT COPY OF
 THE PAID RECEIPT FOR THE IMPACT FEES.
  
 4) COMPLIED
  
 5)COMPLIED
  
 6) COMPLIED
  
 7) COMPLIED
  
 8) COMPLIED
  
 9)NOTE THAT THE DEFINITION FOR EXPOSURE C HAS CHANGED
 EFFECTIVE DECEMBER 8, 2006 (2006 AMENDMENTS TO THE
 FBC), FBC1609.4, FBC R301.2.1.4.
 EXPOSURE C. OPEN TERRAIN WITH SCATTERED
 OBSTRUCTIONS, INCLUDING SURFACE UNDULATIONS OR OTHER
 IRREGULARITIES, HAVING HEIGHTS GENERALLY LESS THAN 30
 FEET (9144 MM) EXTENDING MORE THAN 1,500 FEET (457.2 M)
 FROM THE BUILDING SITE IN ANY QUADRANT. THIS EXPOSURE
 SHALL ALSO APPLY TO ANY BUILDING LOCATED WITHIN
 EXPOSURE B-TYPE TERRAIN WHERE THE BUILDING IS DIRECTLY
 ADJACENT TO OPEN AREAS OF EXPOSURE C-TYPE TERRAIN IN
 ANY QUADRANT FOR A DISTANCE OF MORE THAN 600 FEET
 (182.9 M). THE STRUCTURE IS LOCATED ADJACENT TO A GOLF
 COURSE WHICH MAY REQUIRE IT TO BE DESIGNED AS EXPOSURE
 C. PLEASE REVISE PLANS OR INDICATE WHY THE EXPOSURE
 CATEGORY SHOULD NOT BE CHANGED. ADDITIONAL COMMENTS:
 THE INFORMATION THAT WAS SUBMITTED DOES NOT CONSIDER
 THE TERRAIN IN THE ENTIRE REAR QUADRANT, WHICH INCLUDES
 THE TERRAIN FOR 45 DEGREES EITHER SIDE OF THE WIND
 DIRECTION BEING CONSIDERED. SEE ASCE 7-02 SECTION
 6.5.6.1. ALSO SEE ATTACHED COPIES OF THE 2004 FBC
 RESIDENTIAL CODE COMMENTARY AND ASCE 7-02.
  
 10) COMPLIED
  
 11) COMPLIED
  
 12) COMPLIED
  
 13) COMPLIED
  
 14) COMPLIED
  
 15) COMPLIED
  
 16) COMPLIED
  
 17)COMPLIED
  
 18) COMPLIED
  
 19) COMPLIED
  
 20) COMPLIED
  
 21) COMPLIED
  
 22)COMPLIED
  
 23) COMPLIED
  
 24) COMPLIED
  
 25) REVISE COMPONENT AND CLADDING PRESSURES TO EXPOSURE
 CATEGORY 'C'. SEE ITEM #9.
  
 26) COMPLIED
  
 27) COMPLIED
  
 28) COMPLIED
  
 29) COMPLIED
  
 30) N/A
  
 31) COMPLIED
  
 32) COMPLIED
  
 33) COMPLIED
  
 34) CORRECTED
  
 35) COMPLIED
  
 36) COMPLIED
  
 37) COMPLIED
  
 38) COMPLIED
  
 39) CORRECTED
  
 40) COMPLIED
  
 41) COMPLIED
  
 42)COMPLIED
  
 43)COMPLIED
  
 44) COMPLIED
  
 45) CORRECTED
  
 46) COMPLIED
  
 47)COMPLIED
  
 48) COMPLIED
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-12-20 Cont ID  
Sent By rmcdouga Date 2007-12-20 Time 13:10 Rev Time 0.00
Received By rmcdouga Date 2007-12-19 Time 07:22 Sent To  
Notes
2007-12-20 13:10:302004 FBC W/2007 SUPPLEMENTS
 NSFR
  
 DENIED BY BUILDING
  
 1) COMPLIED
  
 2) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED. WORK MUST COMMENCE WITHIN 90 DAYS
 OF THE DATE THE NOC IS RECORDED. FS 713.13.
  
 3) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 4) COMPLIED
  
 5)FBC R401.4AREA OF QUESTIONABLE
 SOIL.SUBMIT A GEOTECHNICAL REPORT
 TO VERIFY THE SAFE BEARING CAPACITY OF
 THE SOIL. SUBMIT 2 SIGNED AND SEALED COPIES.
  
 6) COMPLIED
  
 7) THE FLOOD ZONE DESIGNATION ON THE SURVEY IS
 SPECIFIED AS A8, WHICH IS INCORRECT. THIS AREA IS
 INCLUDED IN THE LETTER OF MAP REVISION (LOMR) FOR THE
 VILLAGES OF PALM BEACH LAKES AND SPENCER LAKES PLATS
 1,2 AND 3 DATED DECEMBER 3, 1983. PLEASE CORRECT.
 SUBMIT REVISED SURVEY.
  
 8) THE ENERGY CALCULATIONS LIST THE CONDITIONED FLOOR
 AREA AS 8000 SQFT AND THE PLANS SPECIFY 8327 SQFT.
 PLEASE CORRECT. FBC R CHAPTER 11 AND FBC CHAPTER 13.
 THE NEW FORMS HAVE NOT BEEN SIGNED BY THE OWNER/AGENT
 AS REQUIRED BY FBC 13-600.
  
 9)NOTE THAT THE DEFINITION FOR EXPOSURE C HAS CHANGED
 EFFECTIVE DECEMBER 8, 2006 (2006 AMENDMENTS TO THE
 FBC), FBC1609.4, FBC R301.2.1.4.
 EXPOSURE C. OPEN TERRAIN WITH SCATTERED
 OBSTRUCTIONS, INCLUDING SURFACE UNDULATIONS OR OTHER
 IRREGULARITIES, HAVING HEIGHTS GENERALLY LESS THAN 30
 FEET (9144 MM) EXTENDING MORE THAN 1,500 FEET (457.2 M)
 FROM THE BUILDING SITE IN ANY QUADRANT. THIS EXPOSURE
 SHALL ALSO APPLY TO ANY BUILDING LOCATED WITHIN
 EXPOSURE B-TYPE TERRAIN WHERE THE BUILDING IS DIRECTLY
 ADJACENT TO OPEN AREAS OF EXPOSURE C-TYPE TERRAIN IN
 ANY QUADRANT FOR A DISTANCE OF MORE THAN 600 FEET
 (182.9 M). THE STRUCTURE IS LOCATED ADJACENT TO A GOLF
 COURSE WHICH MAY REQUIRE IT TO BE DESIGNED AS EXPOSURE
 C. PLEASE REVISE PLANS OR INDICATE WHY THE EXPOSURE
 CATEGORY SHOULD NOT BE CHANGED. NOTE: ALTHOUGH THE
 GENERAL NOTES (C) (3) ON A.09 HAVE BEEN REVISED TO
 EXPOSURE CATEGORY 'C', THE COMPONENT AND CLADDING
 PRESSURES IN THE TABLE ON S3.02 HAVE NOT BEEN REVISED
 TO CATEGORY 'C'. PLEASE CORRECT.
  
 10) THE WALLS OF THE WINE ROOM ARE REQUIRED TO BE
 WATERPROOFED IN ACCORDANCE WITH FBC R406. INDICATE HOW
 THIS WILL BE ACCOMPLISHED ON THE PLANS. THE SPRAY FOAM
 INSULATION DOES NOT COMPLY WITH THE REQUIREMENTS OF FBC
 R406.
  
 11) COMPLIED
  
 12) COMPLIED
  
 13) COMPLIED
  
 14) COMPLIED
  
 15) COMPLIED
  
 16) COMPLIED
  
 17)COMPLIED
  
 18) COMPLIED
  
 19) COMPLIED
  
 20) COMPLIED
  
 21) COMPLIED
  
 22)COMPLIED
  
 23) COMPLIED
  
 24) COMPLIED
  
 25) REVISE COMPONENT AND CLADDING PRESSURES TO EXPOSURE
 CATEGORY 'C'. SEE ITEM #9.
  
 26) COMPLIED
  
 27) COMPLIED
  
 28) COMPLIED
  
 29) THE SIMPSON H10 OR USP RT16 "R" IN SCHEDULE ON
 S2.02) WILL NOT WORK FOR ATTACHING THE FLOOR TRUSSES TO
 THE LEDGERS. THE FLOOR TRUSSES ARE 3-1/2" WIDE AND THE
 CONNECTORS HAVE A 1-9/16" OPENING FOR THE TRUSS. PLEASE
 CORRECT.
  
 30) N/A
  
 31) COMPLIED
  
 32) COMPLIED
  
 33) COMPLIED
  
 34) CORRECTED
  
 35) THE TRUSS LAYOUT IS REQUIRED TO BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR THE
 STRUCTURE. SEE R802.1.6, FBC106.1.1.2* CITY AMENDMENTS
 AND FAC 61G15-31.003.
  
 36) THE ROOF TRUSSES ARE REQUIRED TO HAVE A MINIMUM
 BOTTOM CORD LIVE LOAD OF 10 PSF. SEE TABLE R301.5.
 PLEASE CORRECT.
  
 37) THE TRUSS DRAWING SUBMITTAL DOES NOT MEET THE
 REQUIREMENTS OF FAC 61G-15-31.003. PLEASE SEPARATE THE
 DRAWINGS AND PLACE THEM WITH THE APPROPRIATE COVER
 SHEETS AND NUMBER THE DRAWINGS TO CORRESPOND TO THE
 NUMBERING ON THE COVERSHEETS. SEE ATTACHMENT.
  
 38) COMPLIED
  
 39)CORRECTED
  
 40) FBC 106.3* CITY AMENDMENTS PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 41) COMPLIED
  
 42)THE GENERIC PRESSURES IN THE SCHEDULE ON S3.02 MAY
 BE TOO HIGH FOR THE GARAGE DOORS WHEN THEY ARE
 INCREASED TO EXPOSURE 'C'. SEE TABLE R301.2(4). PLEASE
 INDICATE THE REQUIRED OPENING PRESSURES FOR THE GARAGE
 DOORS ON THE PLANS.
  
 43)COMPLIED
  
 44) COMPLIED. HOWEVER, PLEASE CLARIFY WHICH WINDOWS THE
 PRODUCT APPROVALS FOR THE WEATHER SHIELD "LEGACY" FIXED
 CASEMENT WINDOWS ARE FOR. THERE DOES NOT TO BE ANY OF
 THESE SPECIFIED ON THE PLANS.
  
 45) CORRECTED
  
 46) COMPLIED
  
 47)COMPLIED
  
 48) COMPLIED
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-10-23 Cont ID  
Sent By rmcdouga Date 2007-10-23 Time 09:52 Rev Time 0.00
Received By rmcdouga Date 2007-10-23 Time 09:52 Sent To  
Notes
2007-10-23 09:51:552004 FBC W/2007 SUPPLEMENTS
 NSFR
  
 DENIED BY BUILDING
  
 1) COMPLIED
  
 2) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED. WORK MUST COMMENCE WITHIN 90 DAYS
 OF THE DATE THE NOC IS RECORDED. FS 713.13.
  
 3) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 4)THE PLANS SPECIFY TYPE III UNPROTECTED
 CONSTRUCTION, WHICH UNDER THE 2004 CODE IS TYPE III-B.
 PLEASE SPECIFY A OR B ON THE PLANS. SEE FBC CHAPTER 6.
 NOTE: TYPE III CONSTRUCTION REQUIRES EXTERIOR WALLS TO
 HAVE A TWO HOUR FIRE RATING IN ADDITION TO OTHER
 REQUIREMENTS. SEE TABLES 601 AND 602. NOTE: THIS
 STRUCTURE COULD BE DECLARED TYPE V-B CONSTRUCTIONAND
 IT WOULD STILL COMPLY WITH THE HEIGHT AND AREA
 REQUIREMENTS OF TABLE 503. TYPE V-B CONSTRUCTION DOES
 NOT REQUIRE THE EXTERIOR WALLS TO BE FIRE RATED. IF YOU
 ARE SPECIFYING TYPE III CONSTRUCTION SUBMIT
 CALCULATIONS AS TO HOW THE 2 HOUR FIRE RATING WILL BE
 OBTAINED. SUBMIT A LETTER FROM THE CONCRETE BLOCK
 SUPPLIER THAT SPECIES THE THICKNESS AND AGGREGATE IN
 THE BLOCK AND THE FIRE RESISTANCE RATING IN HOURS.
  
 5)FBC R401.4AREA OF QUESTIONABLE
 SOIL.SUBMIT A GEOTECHNICAL REPORT
 TO VERIFY THE SAFE BEARING CAPACITY OF
 THE SOIL. SUBMIT 2 SIGNED AND SEALED COPIES.
  
 6) THE PLANS ARE REQUIRED TO HAVE THE CERTIFICATE OF
 AUTHORIZATION NUMBERS OF THE ENGINEERING AND
 ARCHITECTURAL FIRMS. SEE FS 471 AND 481. ALSO SEE THE
 ELECTRICAL REVIEW COMMENTS.
  
 7) THE FLOOD ZONE DESIGNATION ON THE SURVEY IS
 SPECIFIED AS A8, WHICH IS INCORRECT. THIS AREA IS
 INCLUDED IN THE LETTER OF MAP REVISION (LOMR) FOR THE
 VILLAGES OF PALM BEACH LAKES AND SPENCER LAKES PLATS
 1,2 AND 3 DATED DECEMBER 3, 1983. PLEASE CORRECT.
  
 8) THE ENERGY CALCULATIONS LIST THE CONDITIONED FLOOR
 AREA AS 8000 SQFT AND THE PLANS SPECIFY 8327 SQFT.
 PLEASE CORRECT. FBC R CHAPTER 11 AND FBC CHAPTER 13
  
 9)NOTE THAT THE DEFINITION FOR EXPOSURE C HAS CHANGED
 EFFECTIVE DECEMBER 8, 2006 (2006 AMENDMENTS TO THE
 FBC), FBC1609.4, FBC R301.2.1.4.
 EXPOSURE C. OPEN TERRAIN WITH SCATTERED
 OBSTRUCTIONS, INCLUDING SURFACE UNDULATIONS OR OTHER
 IRREGULARITIES, HAVING HEIGHTS GENERALLY LESS THAN 30
 FEET (9144 MM) EXTENDING MORE THAN 1,500 FEET (457.2 M)
 FROM THE BUILDING SITE IN ANY QUADRANT. THIS EXPOSURE
 SHALL ALSO APPLY TO ANY BUILDING LOCATED WITHIN
 EXPOSURE B-TYPE TERRAIN WHERE THE BUILDING IS DIRECTLY
 ADJACENT TO OPEN AREAS OF EXPOSURE C-TYPE TERRAIN IN
 ANY QUADRANT FOR A DISTANCE OF MORE THAN 600 FEET
 (182.9 M). THE STRUCTURE IS LOCATED ADJACENT TO A GOLF
 COURSE WHICH MAY REQUIRE IT TO BE DESIGNED AS EXPOSURE
 C. PLEASE REVISE PLANS OR INDICATE WHY THE EXPOSURE
 CATEGORY SHOULD NOT BE CHANGED.
  
 10) THE WALLS OF THE WINE ROOM ARE REQUIRED TO BE
 WATERPROOFED IN ACCORDANCE WITH FBC R406. INDICATE HOW
 THIS WILL BE ACCOMPLISHED ON THE PLANS.
  
 11) PROVIDE DETAILS OF THE MASONRY FIREPLACES AND
 CHIMNEYS IN THE LIVING ROOM AND AT THE COVERED PATIO.
 SEE SECTIONS R1001 AND R1003.SPECIFY REINFORCING,
 ETC.
  
 12) PROVIDE DETAILS FOR THE PRE-FAB FIREPLACE AND
 CHIMNEY. SUBMIT THE MANUFACTURER'S SPECIFICATIONS AND
 LISTING INFORMATION FOR THE FIREPLACE AND CHIMNEY. FBC
 R1002 AND R1004
  
 13) PROVIDE DETAILS FOR THE CHIMNEY CAPS. SPECIFY
 MATERIALS, ATTACHMENTS, FASTENERS, ETC. FBC 106.1.1
 CITY AMENDMENTS.
  
 14) PROVIDE STRUCTURAL DETAILS FOR THE WOOD FRAME FALSE
 CHIMNEY. SPECIFY MATERIALS, CONNECTIONS, ETC. FBC
 106.1.1 CITY AMENDMENTS.
  
 15) AT INTERIOR STAIRS AND SECOND FLOOR LANDING SHOW
 COMPLIANCE WITH R312.2 GUARD OPENING LIMITATIONS.
 REQUIRED GUARDS ON OPEN SIDES OF STAIRWAYS, RAISED
 FLOOR AREAS, BALCONIES AND PORCHES SHALL HAVE
 INTERMEDIATE RAILS OR ORNAMENTAL CLOSURES WHICH DO NOT
 ALLOW PASSAGE OF A SPHERE 4 INCHES (102MM) OR MORE IN
 DIAMETER.
  
 16) SHOW COMPLIANCE WITH R807.1 ATTIC ACCESS .
 IN BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF
 CONSTRUCTION, AN ATTIC ACCESS OPENING SHALL BE PROVIDED
 TO ATTIC AREAS THAT EXCEED 30 SQUARE FEET (2.8 M 2 )
 AND HAVE A VERTICAL HEIGHT OF 30 INCHES (762 MM) OR
 GREATER. THE ROUGH-FRAMED OPENING SHALL NOT BE LESS
 THAN 22 INCHES BY 30 INCHES (559 MM BY 762 MM) AND
 SHALL BE LOCATED IN A HALLWAY OR OTHER READILY
 ACCESSIBLE LOCATION. NO ATTIC ACCESS IS SPECIFIED ON
 THE SECOND FLOOR.
  
 17)COMPLIED
  
 18) SUBMIT THE MANUFACTURER'S SPECIFICATIONS AND
 LISTING FOR THE OUTDOOR BBQ ON THE COVERED PORCH.
 INCLUDE SPECS. AND LISTING FOR HOOD IF ONE IS REQUIRED.
 FBC 106.1.1 CITY AMENDMENTS.
  
 19) SPECIFY THE CEILING FINISHES FOR THE FRONT PORCH,
 LOGGIA AND COVERED PATIO. FBC 106.1.1 CITY AMENDMENTS.
  
 20) THE ROOF/FLOOR DRAIN AT THE FRONT PORCH IS REQUIRED
 TO DISCHARGE AT LEAST 1 FOOT AWAY FROM THE STRUCTURE IN
 ACCORDANCE WITH R320.7. SPECIFY ON THE PLANS.
  
 21) SHOW COMPLIANCE WITH R502.1.2 DRAFTSTOPPING
 REQUIRED.
 WHEN THERE IS USABLE SPACE BOTH ABOVE AND BELOW THE
 CONCEALED SPACE OF A FLOOR/CEILING ASSEMBLY, DRAFTSTOPS
 SHALL BE INSTALLED SO THAT THE AREA OF THE CONCEALED
 SPACE DOES NOT EXCEED 1,000 SQUARE FEET (92.9 M 2 ).
 DRAFTSTOPPING SHALL DIVIDE THE CONCEALED SPACE INTO
 APPROXIMATELY EQUAL AREAS. WHERE THE ASSEMBLY IS
 ENCLOSED BY A FLOOR MEMBRANE ABOVE AND A CEILING
 MEMBRANE BELOW DRAFTSTOPPING SHALL BE PROVIDED IN
 FLOOR/CEILING ASSEMBLIES UNDER THE FOLLOWING
 CIRCUMSTANCES:
 1.CEILING IS SUSPENDED UNDER THE FLOOR FRAMING. 2.
 FLOOR FRAMING IS CONSTRUCTED OF TRUSS-TYPE OPEN-WEB OR
 PERFORATED MEMBERS.
 R502.1.2.1 MATERIALS.
 DRAFTSTOPPING MATERIALS SHALL NOT BE LESS THAN 1/2-INCH
 (12.7 MM) GYPSUM BOARD, 3 / 8 -INCH (9.5 MM) WOOD
 STRUCTURAL PANELS, 3 / 8 -INCH (9.5 MM) TYPE 2-M-W
 PARTICLEBOARD OR OTHER APPROVED MATERIALS ADEQUATELY
 SUPPORTED. DRAFTSTOPPING SHALL BE INSTALLED PARALLEL TO
 THE FLOOR FRAMING MEMBERS UNLESS OTHERWISE APPROVED BY
 THE BUILDING OFFICIAL. THE INTEGRITY OF ALL DRAFTSTOPS
 SHALL BE MAINTAINED.
 SPECIFY THE MATERIAL THAT WILL BE USED AND LOCATIONS ON
 THE PLANS.
  
 22)COMPLIED
  
 23) REVISE GENERAL NOTE E(2) ON A9 TO SPECIFY ACI
 315-02 AND NOTE F(2) FROM SBC TO FBC. WHICH ARE THE
 CORRECT REFERENCES PER 2004 FBC RESIDENTIAL CHAPTER
 43.
  
 24) ON SHEET S1.01, NOTE 2 INCORRECTLY LISTS S3.01 AS
 THE SHEET CONTAINING THE WINDOW AND DOOR PRESSURES. THE
 TABLE IS LOCATED ON S 3.02.
  
 25) PLEASE SPECIFY THE COMPONENT AND CLADDING PRESSURES
 AT EACH OF THE OPENINGS ON THE PLANS BASED ON THE
 OPENING SIZES, EXPOSURE CATEGORY AND LOCATIONS. FBC *
 106.1.2
  
 26) COMPLIED
  
 27) ON SHEET A.01 THE STAIR CALCULATIONS ARE INCORRECT.
 THE SUM OF THE 2 RISERS AND A TREAD IS 23.95" NOT 24"
 AS SPECIFIED, WHICH IS NOT BETWEEN 24 AND 25 INCHES.
 SEE FBC R311.5.3.2 PLEASE CORRECT.
  
 28) THE (2)LB-3 BEAMS SPECIFIED AT THE COVERED PORCH
 ON SHEET S2.01 ARE NOT LISTED IN THE SECOND BEAM
 SCHEDULE ON SHEET S2.01. PLEASE CORRECT. FBC 106.1.2
 CITY AMENDMENTS
  
 29) THE SIMPSON H10 OR USP RT16 "R" IN SCHEDULE ON
 S2.02) WILL NOT WORK FOR ATTACHING THE FLOOR TRUSSES TO
 THE LEDGERS. THE FLOOR TRUSSES ARE 3-1/2" WIDE AND THE
 CONNECTORS HAVE A 1-9/16" OPENING FOR THE TRUSS. PLEASE
 CORRECT.
  
 30) N/A
  
 31) CONNECTOR "L" IN THE SCHEDULE ON S2.02A SIMPSON
 MTSM 20,REQUIRES 4 CONCRETE SCREWS TO ACHIEVE THE
 UPLIFT SPECIFIED. ONLY 3 FASTENERS ARE SPECIFIED IN THE
 SCHEDULE. PLEASE CORRECT.
  
 32) CONNECTOR "N" ON S2.O2 , THE SIMPSON HTT22 IS
 INCORRECTLY SPECIFIED WITH 3/4" DIA. ANCHORS AND THE
 SIMPSON CATALOG SPECS. 5/8" DIA ANCHORS. PLEASE
 CORRECT.
  
 33) NOTE #4 ON SHEETS S2.01 AND S2.02 STATE SEE PLYWOOD
 NAILING SCHEDULE ON THIS SHEET AND THE SCHEDULE IS ON
 SHEET S3.02. PLEASE CORRECT.
  
 34) CORRECTED
  
 35) THE TRUSS LAYOUT IS REQUIRED TO BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR THE
 STRUCTURE. R802.1.6 AND FBC106.1.1.2 CITY AMENDMENTS
  
 36) THE ROOF TRUSSES ARE REQUIRED TO HAVE A MINIMUM
 BOTTOM CORD LIVE LOAD OF 10 PSF. SEE TABLE R301.5.
 PLEASE CORRECT.
  
 37) THE TRUSS DRAWING SUBMITTAL DOES NOT MEET THE
 REQUIREMENTS OF FAC 61G-15-31.003. PLEASE SEPARATE THE
 DRAWINGS AND PLACE THEM WITH THE APPROPRIATE COVER
 SHEETS AND NUMBER THE DRAWINGS TO CORRESPOND TO THE
 NUMBERING ON THE COVERSHEETS.
  
 38) THE PLYWOOD SHEATHING FASTENING SCHEDULE FOR WALLS
 AND ROOFS ON S 3.02 SPECIFIES #8 SCREWS AND THE NOTE
 CALLS FOR 2-1/2" SELF DRILLING SCREWS FOR ATTACHING TO
 A METAL DECK.THE SHEATHING AND FRAMING FOR THIS
 PROJECT IS WOOD. PLEASE CORRECT. FBC R803.2.3.1
 REQUIRES 8D RING SHANK NAILS IN ALL ROOF ZONES. PLEASE
 CORRECT.
  
 39)CORRECTED
  
 40) FBC 106.3* CITY AMENDMENTS PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 41) SPECIFY THE METHOD OF ATTACHMENT THAT WILL BE USED
 TO INSTALL THE ROOF TILES. PLEASE CIRCLE THE
 APPROPRIATE METHOD FROM THOSE LISTED IN THE PRODUCT
 APPROVAL NOA. FBC 106.1.2 CITY AMENDMENTS.
  
 42)THE GENERIC PRESSURES IN THE SCHEDULE ON S3.02 ARE
 TOO HIGH FOR THE GARAGE DOORS. SEE TABLE R301.2(4).
 PLEASE INDICATE THE REQUIRED OPENING PRESSURES FOR THE
 GARAGE DOORS ON THE PLANS.
  
 43)SUBMIT THE PRODUCT EVALUATION REPORT AND
 INSTALLATION INSTRUCTIONS FOR THE NAN YA PLASTIC CORP.
 EXTERIOR DOORS IN ACCORDANCE WITH FAC RULE 9B-72.
  
 44) SUBMIT PRODUCT APPROVALS FOR THE FIXED WINDOWS AS
 REQUIRED BY FAC RULE 9B-72.
  
 45) CORRECTED
  
 46) THE LOCAL PRODUCT APPROVAL APPLICATION FOR THE
 "SIGNATURE DOOR INC." EXTERIOR DOORS IS INCOMPLETE.
 SUBMIT THE EVALUATION REPORT, INSTALLATION
 INSTRUCTIONS, ETC. REQUIRED BY FAC RULE 9B-72.
  
 47)ON THE FIRST FLOOR PLAN SHEET A.01, THERE IS A
 WALL TYPE 6 SPECIFIED. HOWEVER, THIS WALL TYPE IS NOT
 LISTED IN THE WALL SCHEDULE. PLEASE CORRECT. FBC
 106.1.2 CITY AMENDMENTS.
  
 48) IN ORDER TO EXPEDITE PLAN REVIEW AND HELP AVOID
 ADDITIONAL PLAN REVIEWS, PLEASE INCLUDE A RESPONSE
 LETTER SPECIFYING HOW THE COMMENTS HAVE BEEN
 ADDRESSED.
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-18 Cont ID  
Sent By rmcdouga Date 2007-09-18 Time 14:45 Rev Time 0.00
Received By rmcdouga Date 2007-09-12 Time 18:04 Sent To  
Notes
2007-09-17 17:26:362004 FBC W/2007 SUPPLEMENTS
 NSFR
  
 DENIED BY BUILDING
  
 1) UNITY OF TITLE FOR THE LOTS MUST BE COMPLETED AND
 ADDRESS ASSIGNED BEFORE PERMIT IS ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 4)THE PLANS SPECIFY TYPE III UNPROTECTED
 CONSTRUCTION, WHICH UNDER THE 2004 CODE IS TYPE III-B.
 PLEASE SPECIFY A OR BE ON THE PLANS. SEE FBC CHAPTER 6.
 NOTE: TYPE III CONSTRUCTION REQUIRES EXTERIOR WALLS TO
 HAVE A TWO HOUR FIRE RATING IN ADDITION TO OTHER
 REQUIREMENTS. SEE TABLES 601 AND 602. NOTE: THIS
 STRUCTURE COULD BE DECLARED TYPE V-B CONSTRUCTIONAND
 IT WOULD STILL COMPLY WITH THE HEIGHT AND AREA
 REQUIREMENTS OF TABLE 503. TYPE V-B CONSTRUCTION DOES
 NOT REQUIRE THE EXTERIOR WALLS TO BE FIRE RATED. IF YOU
 ARE SPECIFYING TYPE III CONSTRUCTION SUBMIT
 CALCULATIONS AS TO HOW THE 2 HOUR FIRE RATING WILL BE
 OBTAINED. SUBMIT A LETTER FROM THE CONCRETE BLOCK
 SUPPLIER THAT SPECIES THE THICKNESS AND AGGREGATE IN
 THE BLOCK AND THE FIRE RESISTANCE RATING IN HOURS.
  
 5)FBC R401.4AREA OF QUESTIONABLE
 SOIL.SUBMIT A GEOTECHNICAL REPORT
 TO VERIFY THE SAFE BEARING CAPACITY OF
 THE SOIL. SUBMIT 2 SIGNED AND SEALED COPIES.
  
 6) THE PLANS ARE REQUIRED TO HAVE THE ORIGINAL
 SIGNATURE OF THE ENGINEER AND ARCHITECT IN ADDITION TO
 THE LICENSE NUMBERS OF THE ENGINEERING AND
 ARCHITECTURAL FIRMS. SEE FS 471 AND 481. SEE THE
 ELECTRICAL REVIEW COMMENTS.
  
 7) THE FLOOD ZONE DESIGNATION ON THE SURVEY IS
 SPECIFIED AS A8, WHICH IS INCORRECT. THIS AREA IS
 INCLUDED IN THE LETTER OF MAP REVISION (LOMR) FOR THE
 VILLAGES OF PALM BEACH LAKES AND SPENCER LAKES PLATS
 1,2 AND 3 DATED DECEMBER 3, 1983. PLEASE CORRECT.
  
 8) THE ENERGY CALCULATIONS LISTS THE CONDITIONED FLOOR
 AREA AS 8000 SQFT AND THE PLANS SPECIFY 8327 SQFT.
 PLEASE CORRECT.
  
 9)NOTE THAT THE DEFINITION FOR EXPOSURE C HAS CHANGED
 EFFECTIVE DECEMBER 8, 2006 (2006 AMENDMENTS TO THE
 FBC), FBC1609.4, FBC R301.2.1.4.
 EXPOSURE C. OPEN TERRAIN WITH SCATTERED
 OBSTRUCTIONS, INCLUDING SURFACE UNDULATIONS OR OTHER
 IRREGULARITIES, HAVING HEIGHTS GENERALLY LESS THAN 30
 FEET (9144 MM) EXTENDING MORE THAN 1,500 FEET (457.2 M)
 FROM THE BUILDING SITE IN ANY QUADRANT. THIS EXPOSURE
 SHALL ALSO APPLY TO ANY BUILDING LOCATED WITHIN
 EXPOSURE B-TYPE TERRAIN WHERE THE BUILDING IS DIRECTLY
 ADJACENT TO OPEN AREAS OF EXPOSURE C-TYPE TERRAIN IN
 ANY QUADRANT FOR A DISTANCE OF MORE THAN 600 FEET
 (182.9 M). THE STRUCTURE IS LOCATED ADJACENT TO A GOLF
 COURSE WHICH MAY REQUIRE IT TO BE DESIGNED AS EXPOSURE
 C. PLEASE REVISE PLANS OR INDICATE WHY THE EXPOSURE
 CATEGORY SHOULD NOT BE CHANGED.
  
 10) THE WALLS OF THE WINE ROOM ARE REQUIRED TO BE
 WATERPROOFED IN ACCORDANCE WITH FBC R406.
  
 11) PROVIDE DETAILS OF THE MASONRY FIREPLACES AND
 CHIMNEYS IN THE LIVING ROOM AND AT THE COVERED PATIO.
 SEE SECTIONS R1001 AND R1003. COORDINATE WITH THE
 STRUCTURAL ENGINEER FOR THE FOUNDATION REQUIREMENTS.
 SPECIFY REINFORCING, ETC.
  
 12) PROVIDE DETAILS FOR THE PRE-FAB FIREPLACE AND
 CHIMNEY. SUBMIT THE MANUFACTURER'S SPECIFICATIONS AND
 LISTING INFORMATION FOR THE FIREPLACE AND CHIMNEY.
  
 13) PROVIDE DETAILS FOR THE CHIMNEY CAPS. SPECIFY
 MATERIALS, ATTACHMENTS, FASTENERS, ETC.
  
 14) PROVIDE STRUCTURAL DETAILS FOR THE WOOD FRAME FAKE
 CHIMNEY. SPECIFY MATERIALS, CONNECTIONS, ETC.
  
 15) AT INTERIOR STAIRS AND SECOND FLOOR LANDING SHOW
 COMPLIANCE WITH R312.2 GUARD OPENING LIMITATIONS.
 REQUIRED GUARDS ON OPEN SIDES OF STAIRWAYS, RAISED
 FLOOR AREAS, BALCONIES AND PORCHES SHALL HAVE
 INTERMEDIATE RAILS OR ORNAMENTAL CLOSURES WHICH DO NOT
 ALLOW PASSAGE OF A SPHERE 4 INCHES (102MM) OR MORE IN
 DIAMETER.
  
 16) SHOW COMPLIANCE WITH R807.1 ATTIC ACCESS .
 IN BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF
 CONSTRUCTION, AN ATTIC ACCESS OPENING SHALL BE PROVIDED
 TO ATTIC AREAS THAT EXCEED 30 SQUARE FEET (2.8 M 2 )
 AND HAVE A VERTICAL HEIGHT OF 30 INCHES (762 MM) OR
 GREATER. THE ROUGH-FRAMED OPENING SHALL NOT BE LESS
 THAN 22 INCHES BY 30 INCHES (559 MM BY 762 MM) AND
 SHALL BE LOCATED IN A HALLWAY OR OTHER READILY
 ACCESSIBLE LOCATION.
  
 17)SHOW COMPLIANCE WITH R310 FOR EMERGENCY ESCAPE AND
 RESCUE OPENINGS AT THE SLEEPING ROOMS. SPECIFY THE
 SECOND FLOOR EGRESS WINDOWS ON THE PLANS.
  
 18) SUBMIT THE MANUFACTURER'S SPECIFICATIONS AND
 LISTING FOR THE OUTDOOR BBQ ON THE COVERED PORCH.
 INCLUDE SPECS. AND LISTING FOR HOOD IF ONE IS
 REQUIRED.
  
 19) SPECIFY THE CEILING FINISHES FOR THE FRONT PORCH,
 LOGGIA AND COVERED PATIO.
  
 20) THE ROOF/FLOOR DRAIN AT THE FRONT PORCH IS REQUIRED
 TO DISCHARGE AT LEAST 1 FOOT AWAY FROM THE STRUCTURE IN
 ACCORDANCE WITH R320.7.
  
 21) SHOW COMPLIANCE WITH R502.1.2 DRAFTSTOPPING
 REQUIRED.
 WHEN THERE IS USABLE SPACE BOTH ABOVE AND BELOW THE
 CONCEALED SPACE OF A FLOOR/CEILING ASSEMBLY, DRAFTSTOPS
 SHALL BE INSTALLED SO THAT THE AREA OF THE CONCEALED
 SPACE DOES NOT EXCEED 1,000 SQUARE FEET (92.9 M 2 ).
 DRAFTSTOPPING SHALL DIVIDE THE CONCEALED SPACE INTO
 APPROXIMATELY EQUAL AREAS. WHERE THE ASSEMBLY IS
 ENCLOSED BY A FLOOR MEMBRANE ABOVE AND A CEILING
 MEMBRANE BELOW DRAFTSTOPPING SHALL BE PROVIDED IN
 FLOOR/CEILING ASSEMBLIES UNDER THE FOLLOWING
 CIRCUMSTANCES:
 1.CEILING IS SUSPENDED UNDER THE FLOOR FRAMING. 2.
 FLOOR FRAMING IS CONSTRUCTED OF TRUSS-TYPE OPEN-WEB OR
 PERFORATED MEMBERS.
 R502.1.2.1 MATERIALS.
 DRAFTSTOPPING MATERIALS SHALL NOT BE LESS THAN ?-INCH
 (12.7 MM) GYPSUM BOARD, 3 / 8 -INCH (9.5 MM) WOOD
 STRUCTURAL PANELS, 3 / 8 -INCH (9.5 MM) TYPE 2-M-W
 PARTICLEBOARD OR OTHER APPROVED MATERIALS ADEQUATELY
 SUPPORTED. DRAFTSTOPPING SHALL BE INSTALLED PARALLEL TO
 THE FLOOR FRAMING MEMBERS UNLESS OTHERWISE APPROVED BY
 THE BUILDING OFFICIAL. THE INTEGRITY OF ALL DRAFTSTOPS
 SHALL BE MAINTAINED.
 SPECIFY THE MATERIAL AND LOCATIONS ON THE PLAN.
  
 22)REVISE THE TYPICAL DOOR JAMB DETAIL 7 ON A9. THE
 2X OR 1X BUCKS ARE REQUIRED TO BE THE FULL WIDTH OF THE
 JAMB. SEE R613.6.1.1
  
 23) REVISE GENERAL NOTE E(2) ON A9 TO SPECIFY ACI
 315-02 AND NOTE F(2) FROM SBC TO FBC. WHICH ARE THE
 CORRECT REFERENCES PER 2004 FBC RESIDENTIAL CHAPTER
 43.
  
 24) ON SHEET S1.01, NOTE 2 INCORRECTLY LISTS S3.01 AS
 THE SHEET CONTAINING THE WIDOW AND DOOR PRESSURES. THE
 TABLE IS LOCATED ON S 3.02.
  
 25) PLEASE SPECIFY THE COMPONENT AND CLADDING PRESSURES
 AT EACH OF THE OPENINGS ON THE PLANS BASED ON THE
 OPENING SIZES, EXPOSURE CATEGORY AND LOCATIONS. FBC *
 106.1.2
  
 26) ON SHEET S1.01 THE NOTE FOR CAP PLATE C REFERS TO
 DETAIL 8 ON S3.01, WHICH IS NOT CORRECT. PLEASE
 CORRECT. SEE 8 ON S3.02.
  
 27) ON PAGE A1 THE SUM OF 2 RISERS AND A TREAD IS
 23.95", WHICH IS NOT BETWEEN 24 AND 25 INCHES. PLEASE
 CORRECT.
  
 28) THE LB-3 BEAMS ARE NOT LISTED IN THE SECOND BEAM
 SCHEDULE ON SHEET S2.01.
  
 29) THE SIMPSON H10 OR USP RT16 ("R" IN SCHEDULE ON
 S2.02) WILL NOT WORK FOR ATTACHING THE FLOOR TRUSSES TO
 THE LEDGERS. THE FLOOR TRUSSES ARE 3-1/2" WIDE AND THE
 CONNECTORS HAVE A 1-9/16" OPENING FOR THE TRUSS.
  
 30) THE SCHEDULE SPECIFIES CONNECTOR "W" WHICH IS TWO
 SIMPSON H10 OR TWO USP RT16 TRUSS ANCHORS. SOME OF THE
 TRUSSES THAT HAVE THESE CONNECTORS SPECIFIED DO NOT
 EXTEND PAST THE 2 X 6 WALL SO THEY CAN NOT BE APPLIED
 TO EACH SIDE OF THE WALL AND THE TRUSS.
  
 31) CONNECTOR "L" IN THE SCHEDULE ON S2.02A SIMPSON
 MTSM 20,REQUIRES 4 CONCRETE SCREWS TO ACHIEVE THE
 UPLIFT SPECIFIED. ONLY 3 FASTENERS ARE SPECIFIED IN THE
 SCHEDULE. PLEASE CORRECT.
  
 32) CONNECTOR "N" ON S2.O2 , THE SIMPSON HTT22 IS
 INCORRECTLY SPECIFIED WITH 3/4" DIA. ANCHORS AND THE
 SIMPSON CATALOG SPECS. 5/8" DIA ANCHORS. PLEASE
 CORRECT.
  
 33) NOTE #4 ON SHEETS S2.01 AND S2.02 STATE SEE PLYWOOD
 NAILING SCHEDULE ON THIS SHEET AND THE SCHEDULE IS ON
 SHEET S3.02. PLEASE CORRECT.
  
 34) ALL OF THE DETAILS ON SHEET S3.02 ARE INCORRECTLY
 LABELED AS BEING ON S3.01.
  
 35) THE TRUSS LAYOUT IS REQUIRED TO BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR THE
 STRUCTURE.
  
 36) THE ROOF TRUSSES ARE REQUIRED TO HAVE A MINIMUM
 BOTTOM CORD LIVE LOAD OF 10 PSF. SEE TABLE R301.5.
  
 37) THE TRUSS DRAWING SUBMITTAL DOES NOT MEET THE
 REQUIREMENTS OF 61G-15-31.003. PLEASE SEPARATE THE
 DRAWINGS AND PLACE THEM WITH THE APPROPRIATE COVER
 SHEETS AND NUMBER THE DRAWINGS TO CORRESPOND TO THE
 NUMBERING ON THE COVERSHEETS.
  
 38) THE PLYWOOD SHEATHING FASTENING SCHEDULE FOR WALLS
 AND ROOFS ON S 3.02 SPECIFIES #8 SCREWS AND THE NOTE
 CALLS FOR 2-1/2" SELF DRILLING SCREWS FOR ATTACHING TO
 A METAL DECK.THE SHEATHING AND FRAMING FOR THIS
 PROJECT IS WOOD. PLEASE CORRECT. FBC R803.2.3.1
 REQUIRES 8D RING SHANK NAILS IN ALL ROOF ZONES.
  
 39)PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE.
  
 40)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 41) CIRCLE THE METHOD OF ATTACHMENT THAT WILL BE USED
 TO INSTALL THE ROOF TILE ON THE NOA.
  
 42)THE GENERIC PRESSURES IN THE SCHEDULE ON S3.02 ARE
 TOO HIGH FOR THE GARAGE DOORS. SEE TABLE R301.2(4).
  
 43)SUBMIT STATE OR MIAMI-DADE PRODUCT APPROVALS FOR
 THE NAN YA PLASTIC CORP. EXTERIOR DOORS OR THE
 MANUFACTURER CAN APPLY FOR LOCAL PRODUCT APPROVAL IN
 ACCORDANCE WITH RULE 9B-72.
  
 44) THE WEATHERSHIELD LEGACY FIXED WINDDOW NOA NO.
 05-0420.04 IS MISSING SHEET 4 OF 4 FROM DRAWING NO.
 1071.
  
 45) THE NOA NO. 03-1105.01 FOR THE PGT PW-701 WINDOW
 HAS BEEN REVISED BY NOA NO. 07-0418.06.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2009-09-28 Cont ID  
Sent By dpalmer Date 2009-09-28 Time 13:09 Rev Time 0.00
Received By dpalmer Date 2009-09-28 Time 13:09 Sent To PC
Notes
2009-09-28 13:11:33** REDLINED PLANS
  
 110.26 FOR A/C DISCONNECT
 250.122 FOR MISSING EQUIPMENT GROUNDING CONDUCTOR AFTER
 MAIN DISCONNECT.
 SUCCESSOR ARCHITECT TO BE COMPLETED BY ARCHITECT PER
 FLORIDA ADMINSTRATIVE CODE 61G1-16. LETTER SUBMITTED
 ONLY LISTED NEW ARCHITECT AS TAKING OVER.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2009-07-20 Cont ID  
Sent By dpalmer Date 2009-07-20 Time 14:40 Rev Time 0.00
Received By dpalmer Date 2009-07-20 Time 14:40 Sent To  
Notes
2009-07-20 14:40:50 
  
 ** DENIED REVISION **
  
 ** THE TITLE BLOCKS INDICATE THERE HAVE BEEN THREE
 REVISIONS SINCE THE LAST REVIEW DONE IN THIS OFFICE
 SINCE 12/03/07 HOWEVER TO DATE NO ELECTRICAL REVISIONS
 HAVE BEEN SUBMITTED FOR BASE BUILDING PLANS.
 THE SERVICE HAS COMPLETELY BEEN REVISED ALONG WITH MANY
 OTHER ITEMS.
  
  
 1) NOTE: PLANS SUBMITTED ARE NOT REVISED BY THE
 ENGINEER OF RECORD PER FS 471.025
 FAC 61G15-23
  
 2) NOTE: PLEASE UPDATE LOAD CALCULATIONS FOR RECESSED
 LIGHTING LOADS PER 220.3B4. THE AMOUNT OF RECESSED
 LIGHTING SHOWN ON PLANS IS ABOVE THE GENERAL LIGHTING
 LOADS. PLEASE ALSO BE SURE THE ADDITIONAL LOADS ON THE
 LIGHTING PANEL IS COORDINATED.
  
 3) NOTE: PLEASE LOOK AT THE NEW 600AMP DISTRIBUTION
 PANEL. ALL PANELS ARE SHOWING FEEDER CONDUCTORS AND
 LOADS WELL BELOW ANY MINIMUMS BY CODE. 240.4,310.16 ETC
 FOR EXAMPLE: PANEL *A* IS SHOWING A 225AMP BREAKER WITH
 #10 CONDUCTORS AS THE FEEDERS WITH A LOAD OF 4.5 KW.
 THIS IS NOT POSSIBLE. ALL OTHER PANELS ON THIS SAME
 600AMP MDP IS THE SAME. CONDUCTORS ARE TOO SMALL AND
 LOADS ARE NOT ACCURATE.
  
 4) NOTE: PANELS FOR ALL LOADS NEED TO BE SUBMITTED AND
 COMPLETE. NO PANEL SCHEDULE FOR EXAMPLE WAS SUBMITTED
 FOR THE NEW POOL PANEL SO LOADS, BRANCH CIRCUITS ETC
 CAN NOT BE VERIFIED AS CODE COMPLIANT.
 408.4,220,310, ETC
  
 5) NOTE: THE RISER HAS BEEN COMPLETELY REVISED FOR A
 NEW 600AMP SERVICE HOWEVER THE PLANS ON SHEETS E- STILL
 INDICATES THE ORIGINAL 400AMP SERVICE, 400AMP MAIN AND
 400AMP TRANSFER SWITCH.
 PLEASE COORDINATE PLANS.
 215.5,230.70,230.71,ETC
  
 6) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE NEW TRANSFER SWITCH WHICH APPEARS TO BE
 UPDATED FROM THE PREVIOUS PLANS.
 110.3, 90.7
  
 7) NOTE: PLEASE SEE SAFE ROOM WHICH WAS/IS THE MASTER
 BEDROOM CLOSET. THE PLANS INDICATE WHAT APPEAR TO BE
 WALL SCONCES. PLEASE SEE 410.8 FOR MINIMUM CLEARANCES
 FROM SHELVING.
  
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-12-20 Cont ID  
Sent By dpalmer Date 2007-12-03 Time 13:18 Rev Time 0.00
Received By dpalmer Date 2007-12-03 Time 13:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-10-06 Cont ID  
Sent By dpalmer Date 2007-10-06 Time 16:56 Rev Time 0.00
Received By dpalmer Date 2007-10-06 Time 15:00 Sent To M
Notes
2007-10-06 16:56:20 
 *** DENIED2ND REVIEW ***
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW STILL
 NEED TO BE ADDRESSED.
 ** PLEASE SEE NEW NOTE DUE TO CHANGE IN NOTE ON PLANS.
  
 1) NOTE: PLEASE KNOW ONCE ADDRESS HAS BEEN DETERMINED
 BY THE ADDRESSING REVIEWER THE NEW ADDRESS SHOULD BE
 PLACED ON THE TITLE BLOCKS.
 FBC ADMIN SECT 110.1.2, 106.1.2
 FAC 61G1-16.004, 61G15-23.002
  
 2) NOTE:THIS IS THE SAME COMMENT FROM PREVIOUS
 REVIEW.
 PLEASE SEE THE ARCHITECTURAL FIRM IS STILL MISSING THE
 REQUIRED LICENSE INFORMATION.
 ** THIS IS REQUIRED. IF PLANS COME BACK WITHOUT THE
 REQUIRED INFORMATION THIS OFFICE WILL HAVE NO CHOICE
 BUT TO TURN THIS OVER TO THE STATE.
 PLEASE ADDRESS.
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING LICENSE INFORMATION ON THE TITLE
 BLOCKS FOR THE ARCHITECTURAL FIRM.
 PLEASE KNOW THAT THE MISSING CERTIFICATE OF
 AUTHORIZATION AS REQUIRED FOR THE FIRM WHICH IS
 REQUIRED TO BE ON THE TITLE BLOCK IS IN FACT DELINQUENT
 WITH THE STATE. PLEASE SEE THE ATTACHED PRINT OUT FROM
 THE DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION
 WHICH INDICATES THIS AS OF THIS REVIEW.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G1-16.004 AND
 FLORIDA STATUTES 481.219
 ** PLEASE KNOW THIS IS REQUIRED FOR ALL TRADES AND ALL
 SHEETS WHICH CONTAIN THIS TITLE BLOCK WHETHER OR NOT
 COMMENT IS MADE BY OTHER TRADE(S).
  
 3) NOTE: PLEASE SEE THE PLANS ARE NOW CONTAINING A NOTE
 WHICH MENTIONS THE ATS AND GENERATOR WILL BE UNDER
 SEPARATE PERMITS, HOWEVER PLEASE SEE THE PLANS AND
 RISER STILL INDICATE THE ATS BEIGN INSTALLED AT THIS
 TIME.
 IF ONLY THE ATS WILL BE INSTALLED AT THIS TIME WITH THE
 ELECTRICAL FOR THE MAIN HOUSE SERVICE, THEN PLEASE
 SUBMIT THE MANUFACTURES SPECS/CUT SHEETS FOR THIS
 UNIT.
 SOME OTHER SHEETS STILL SHOW THE GENERATOR.
 FBC 106.1.1, 106.1.2,
 NEC 110.3, 90.7
  
 4) NOTE: PLEASE SEE THE ARC FAULT PROTECTION NOTE ON
 THE BOTTOM OF THE PANEL SCHEDULE MENTIONS THIS IS
 REQUIRED FOR *RECEPTACLE CIRCUITS* HOWEVER THIS IS
 REQUIRED FOR ALL AS LISTED ON PREVIOUS REVIEW NOTE FOR
 *ALL*OUTLETS IN THE SLEEPING ROOMS INCLUSIVE OF SMOKE
 ALARMS, FANS, LIGHTING ETC.
 PLEASE SEE 210.12
  
 5) NOTE: PLEASE SEE THE REVISED ITEMS WERE NOT CLOUDED
 OR INDICATED ON THE PLANS. THE NOTES ON THE LOWER RIGHT
 HAND CORNER DO NOT ACTUALLY RESPOND TO ALL PREVIOUS
 NOTES.
  
 6) NOTE: PLEASE SEE NOTE #16 FROM PREVIOUS REVIEW WHICH
 REQUESTED FOR COMPLETION OF THE PANEL SCHEDULE TO SHOW
 THE REQUIRED MINIMUM BRANCH CIRCUIT CONDUCTORS, HOWEVER
 THIS WAS NOT DONE.
 ** PREVIOUS REVIEW NOTE **
 PLEASE COMPLETE PANEL SCHEDULES WITH THE BRANCH
 CIRCUIT CONDUCTOR SIZES.
 408.4, 240.4, 310.16.
 FBC 106.1.2, 106.3.5.4
  
 7) NOTE:NO INFORMATION ON LIGHTING CONTROL
 PANEL(S)/SYSTEM AS NOTED ON PREVIOUS NOTE #17.
 PLEASE KNOW THAT ANY LIGHTING SYSTEMS OR CONTROLS WHICH
 ARE INSTALLED WHICH AFFECT THE BASE CODE DESIGNED BY
 THE DESIGNER OF RECORD WILL BE REQUIRED TO GO THROUGH
 THE RESPONSIBLE DESIGNER OF RECORD. THESE *FUTURE*
 PLANS WILL BE REQUIRED TO CONTAIN A *SHOP DRAWING*
 REVIEW STAMP IF PLANS ARE NOT DONE BY THE DESIGNER OF
 RECORD. PLEASE ALSO KNOW THAT ANY INSTALLATION OF THESE
 ITEMS WILL ALSO BE REQUIRED TO BE REVISED ON BASE HOUSE
 PLANS FOR REFERENCE OF SYSTEM.
  
 **PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT MORE INFORMATION ON THE PROPOSED LIGHTING
 CONTROL PANELS AND SYSTEM. PLEASE SEE 110.3, 90.7 AS
 VERIFICATION OF THE TYPE OF SYSTEM, LISTING FROM A
 NRTL, LOCATIONS AND TYPE OF WIRING BEING INSTALLED.
  
 8) NOTE: PLEASE PROVIDE A NOTE ON PLANS FOR THE TYPE OF
 RECESSED LIGHTING AS REQUIRED PER FBC
 13-606-1.ABC.1.2.4.
  
 PLEASE KNOW THAT A TYPED WRITTEN RESPONSE WILL HELP IN
 THE REVIEW PROCESS. THIS IS NOT REQUIRED AND ONLY A
 SUGGESTION.
 PLEASE ALSO SEE THE PREVIOUS REVIEW WHICH MENTIONED IF
 THERE ARE ANY QUESTIONS OR COMMENTS TO PLEASE CONTACT
 THIS REVIEW.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-08-31 Cont ID  
Sent By dpalmer Date 2007-08-31 Time 10:20 Rev Time 0.00
Received By dpalmer Date 2007-08-29 Time 19:55 Sent To M
Notes
2007-08-31 10:20:562007-08-31 10:20:56
  
 ** DENIED**
  
  
  
 1) NOTE: PLEASE SEE THE ARCHITECTURAL PLANS DO NOT
 CONTAIN AN ORIGINAL SIGNATURE AND DATE AS REQUIRED PER
 FLORIDA STATUTES 481.221.
 THE PLANS ARE REQUIRED TO BE SIGNED AS ORIGINAL.
 PLACING A RAISED SEAL OVER AN *IMAGED* SIGNATURE IS NOT
 ACCEPTABLE PER THE MINIMUM REQUIREMENTS OF THE FAC AND
 FS.
 **THIS IS REQUIRED FOR ALL SHEETS AND ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY OTHER REVIEWS.
  
 2) NOTE: PLEASE SEE MISSING LICENSE INFORMATION ON THE
 TITLE BLOCKS FOR THE ARCHITECTURAL FIRM.
 PLEASE KNOW THAT THE MISSING CERTIFICATE OF
 AUTHORIZATION AS REQUIRED FOR THE FIRM WHICH IS
 REQUIRED TO BE ON THE TITLE BLOCK IS IN FACT DELINQUENT
 WITH THE STATE. PLEASE SEE THE ATTACHED PRINT OUT FROM
 THE DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION
 WHICH INDICATES THIS AS OF THIS REVIEW.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G1-16.004 AND
 FLORIDA STATUTES 481.219
 ** PLEASE KNOW THIS IS REQUIRED FOR ALL TRADES AND ALL
 SHEETS WHICH CONTAINS THIS TITLE BLOCK WHETHER OR NOT
 COMMENT IS MADE BY OTHER TRADE(S).
  
 3) NOTE: PLEASE SEE THE TITLE BLOCK FOR THE ENGINEER
 AND FIRM AS SHOWN IS ALSO MISSING INFORMATION. PLEASE
 SEE THE MISSING PRINTED NAME, PRINTED LICENSE NUMBER
 AND MISSING CERTIFICATE OF AUTHORIZATION NUMBER.
 **PLEASE KNOW THIS IS REQUIRED FOR ALL MEP SHEETS
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADE(S).
  
 4) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
  
 5) NOTE: PLEASE SEE THE PLANS ARE SHOWING A NEW
 GENERATOR AND ATS BEING INCLUDED WITH THE SCOPE OF WORK
 FOR HOUSE HOWEVER PLEASE SUBMIT THE MANUFACTURES
 SPEC/CUT SHEETS FOR BOTH.IF THE GENERATOR WILL BE
 UNDER A SEPARATE PERMIT PLEASE ADJUST PLANS TO INDICATE
 THIS.
 PLEASE KNOW THE GENERATOR SPECS/CUT SHEETS ARE TO
 INDICATE THE MINIMUM CLEARANCES FOR UNIT.
 PLEASE SUBMIT AND SEE COMMENTS FROM OTHER TRADES FROM
 ZONING, BUILDING AND PLUMBING.
 FBC 106.1.1, 106.1.2,
 NEC 110.3, 90.7
  
 6) NOTE: PLEASE SEE THERE ARE SEVERAL SPECIFIC
 DEDICATED APPLIANCE LOADS AND MOTORS LOADS ON THE
 ELECTRICAL PANEL SCHEDULES WHERE THE LOADS ARE NOT
 INCLUDED IN THE LOAD CALCULATIONS.
 PLEASE GO OVER CALCULATIONS AND ADJUST AS NEEDED.
 PLEASE SEE FOR EXAMPLE MISSING, WATER PUMP,
 REFRIGERATOR, WASHER, CENTRAL VACUUM, GARAGE DOOR
 OPENER ETC.
 PLEASE SEE NEC 220 AND SEE SOME COMMENTS BELOW FOR SOME
 OTHER LOADS.
  
 7) NOTE:PLEASE SEE 210. 52C2 AND 220.53 FOR MINIMUM
 LOADS FOR THE WASHER/LAUNDRY LOADS AS REQUIRED. PLEASE
 SEE THE PANEL SCHEDULE DOES NOT INDICATE THE MINIMUM OF
 1500VA FOR EACH OF THESE AS SHOWN AND LISTED. PLEASE
 ALSO SEE THE LOADS SHOWN ON THE LOAD CALCULATIONS ON
 THE SERVICE INDICATE (2) LAUNDRY LOADS HOWEVER THE TWO
 ARE SHOWN WITH A TOTAL OF 4500VA?
 IT IS UNCLEAR HOW THESE LOADS ARE BEING DETERMINED AS
 THE PANEL SCHEDULE AND OTHER LOADS ARE NOT THE SAME.
 PLEASE SEE THE SECTIONS AS NOTED FOR THE MINIMUM
 LOADS.
 PLEASE ADJUST.
  
 8) NOTE: PLEASE SEE MISSING ARC FAULT PROTECTION FRO
 ALL OUTLETS IN THE SLEEPING ROOMS INCLUSIVE OF SMOKE
 ALARMS, FANS, LIGHTING ETC.
 PLEASE SEE 210.12
  
 9) NOTE: PLEASE SEE MINIMUM LOADS TO BE FIGURED FOR
 RECESSED LIGHTING. PLEASE SEE THAT THE WATTAGE BASED ON
 THE AMOUNT OF EACH OF THESE TYPES OF FIXTURES DO EXCEED
 THE 3VA PER SQ FT.THIS WAS CONFIRMED BY THE CODE
 PANELIST AND THE AHJ IS THE DETERMINING AUTHORITY.
 PLEASE SEE THE FOLLOWING TEXT WHICH IS TAKEN DIRECTLY
 FROM THE 2005 NEC AND SOME COMMENTARY FROM THE
 HANDBOOK.
  
 *D) LUMINAIRES (LIGHTING FIXTURES) AN OUTLET SUPPLYING
 LUMINAIRE(S) [LIGHTING FIXTURE(S)] SHALL BE CALCULATED
 BASED ON THE MAXIMUM VOLT-AMPERE RATING OF THE
 EQUIPMENT AND LAMPS FOR WHICH THE LUMINAIRE(S)
 [FIXTURE(S)] IS RATED.
 IN GENERAL, NO ADDITIONAL CALCULATION IS REQUIRED FOR
 LUMINAIRES (RECESSED AND SURFACE MOUNTED) INSTALLED IN
 OR ON A DWELLING UNIT, BECAUSE THE LOAD OF SUCH
 LUMINAIRES IS COVERED IN THE 3 VOLT-AMPERES PER SQUARE
 FOOT CALCULATION SPECIFIED BY TABLE 220.12. WHERE THE
 RATING OF THE LUMINAIRES INSTALLED FOR GENERAL LIGHTING
 EXCEEDS THE MINIMUM LOAD PROVIDED FOR IN TABLE 220.12,
 THE MINIMUM GENERAL LIGHTING LOAD FOR THAT PREMISES IS
 TO BE BASED ON THE INSTALLED LUMINAIRES. DISTINGUISHING
 BETWEEN THE LUMINAIRES INSTALLED FOR GENERAL LIGHTING
 VERSUS THOSE INSTALLED FOR ACCENT, SPECIALTY OR DISPLAY
 LIGHTING IS MUCH EASIER TO DELINEATE IN COMMERCIAL
 (PARTICULARLY MERCANTILE) OCCUPANCIES.
  
 AS STATED, *IN GENERAL* AN ADDITIONAL AMOUNT IS NOT
 NEEDED ONLY WHEN THE FIXTURES ARE USED FOR NORMAL
 GENERAL LIGHTING. WHEN THE FIXTURES EXCEED THE GENERAL
 LIGHTING USE AS THIS IS DONE ON THIS PLAN, THEN THE
 ADDITIONAL SHALL BE FIGURED.
 PLEASE SEE THIS SECTION IN THE 2002 NEC WAS 220.3B4
  
 10) NOTE: PLEASE SEE NFPA-72 FOR DEFINITIONS FOR SMOKE
 DETECTION DEVICES.PLEASE SEE THAT SMOKE DETECTORS ARE
 DEVICES WHICH ONLY DETECT AND DO NOT SOUND AND ALARM
 WHEREAS SMOKE ALARMS ARE DEVICES WHICH DETECT AND SOUND
 AN ALARM.
 AS THE PLAN INDICATES SD FOR SMOKE DETECTORS THIS SEEMS
 IT SHOULD BE SA FOR SMOKE ALARMS.
 PLEASE SEE THE 2002 NFPA-72
  
 11) NOTE: PLEASE SEE THE PLANS DO NOT SHOW ANY OF THE
 MAINS AS SHOWN ON RISER ON THE OUTSIDE OF THE HOUSE.
 ONLY THE METER AND ATS IS SHOWN.
 PLEASE COORDINATE.
 FBC 106.1.2
  
 12) NOTE: PLEASE SEE THE POOL PANEL DOES NOT MEET THE
 MINIMUM CLEARANCE REQUIREMENTS PER 110.26.
  
 13) NOTE: PLEASE SEE THE HOT WATER HEATERS ARE BEING
 SHOWN AS CONNECTED BY MEANS OF RECEPTACLES WHICH ARE
 NOT PERMITTED.
 PLEASE SEE 422.30, 422.31.
 PLEASE INDICATE ON PLANS.
  
 14) NOTE: PLEASE SEE 422.13 AS THE LOADS FOR THE WATER
 HEATERS ARE TO BE FIGURED AT 125% FOR CONTINUOUS
 LOADS.
 THIS WAS REVISED IN THE 2005 NEC AND PLEASE SEE CODE
 COMMENTARY IN THE NEC HANDBOOK.
  
 15) NOTE: PLEASE GO OVER FIXTURES AND LOCATIONS IN ALL
 STORAGE CLOSETS FOR MINIMUM CLEARANCES FOR FIXTURES
 FROM CLOSET SHELVING PER 410.8
 PLEASE SEE THERE ARE SOME ON PLANS WHICH AS SHOWN ARE
 TOO CLOSE TO SHELVES.
  
 16) NOTE: PLEASE COMPLETE PANEL SCHEDULES WITH THE
 BRANCH CIRCUIT CONDUCTOR SIZES.
 408.4, 240.4, 310.16.
 FBC 106.1.2, 106.3.5.4
  
 17) NOTE: PLEASE SUBMIT MORE INFORMATION ON THE
 PROPOSED LIGHTING CONTROL PANELS AND SYSTEM. PLEASE SEE
 110.3, 90.7 AS VERIFICATION OF THE TYPE OF SYSTEM,
 LISTING FROM A NRTL, LOCATIONS AND TYPE OF WIRING BEING
 INSTALLED.
  
 18) NOTE: PLEASE SEE SOME 3-WAY SWITCHING LOCATIONS ARE
 SHOWING A S3, (3-WAY DEVICE AT EITHER END WHICH IS OK,
 HOWEVER PLEASE CLARIFY THAT BOTH ENDS ARE SHOWN AS
 BEING DIMMERS?
 IN 3-WAY AND OR 4-WAY WIRING SYSTEMS THE DIMMERS ARE
 TYPICALLY ONLY AT ONE LOCATION BASED ON STANDARD
 DEVICES WHICH IS WHAT IS BEING SHOWN.
 PLEASE SEE THE NOTE #16 ABOVE AS THESE MAY BE A PART OF
 THE LIGHTING CONTROL SYSTEM WHICH IS NOT KNOWN AT THIS
 TIME.
  
 19) NOTE: PLEASE SEE THE LOADS FOR THE AIR HANDLERS ARE
 IN QUESTION. THE A/C DETAILS INDICATE LOADS IN KW WHICH
 ARE SUBSTANTIALLY HIGHER THAN THAT OF THE LOAD SHOWN ON
 THE LOAD CALCULATIONS.
 PLEASE SEE 220.60 AS THE LARGER OF THE HEATING AND
 COOLING LOADS ARE TO BE FIGURED.
  
 20) NOTE: PLEASE KNOW AS FOR INFORMATION THE LOW
 VOLTAGE AS SHOWN ON PLANS WILL BE REQUIRED TO BE UNDER
 SEPARATE PERMITS. THESE PLANS WHICH CONTAIN ITEMS FOR
 MANY LV ITEMS MAY BE USED AS A REFERENCE FOR TURN
 AROUND PERMITS HOWEVER SEPARATE APPLICATION AND FEES
 WILL BE DUE BASED ON THE SEPARATE VALUATIONS OF THESE
 SYSTEMS.
 *ANY LOW VOLTAGE SECURITY IS ALSO UNDER A SEPARATE
 PERMIT. THESE DO NOT NEED PLANS UNLESS CAMERA OR ACCESS
 CONTROL SYSTEMS ARE BEING INSTALLED. THE DEVICE
 LOCATIONS INCLUDING THE LOCATION OF SECURITY PANELS DO
 NOTNEED TO BE INCLUDED ON ANY PANELS.
 THE LV FOR ALARM SYSTEMS IS UNDER SEPARATE FEES BASED
 ON THAT SCOPE OF WORK.
 THIS IS ONLY NOTED FOR INFORMATION AND NO INFORMATION
 AND CHANGES NEED TO BE MADE ON PLANS.
 ** IF THERE IS ANY CLARIFICATION NEEDED PLEASE CONTACT
 THIS OFFICE/REVIEWER.
  
 21) NOTE: PLEASE SEE THE PLANS INDICATE THE RECEPTACLE
 BEING NOTED FOR THE WINE COOLER (MAIN) BEING CIRCUITED
 TO OTHER GENERAL PURPOSE RECEPTACLES IN THE DWELLING.
 PLEASE CLARIFY THIS AS SHOWN.
 PLEASE VERIFY LOAD AND PROVIDE INFORMATION FOR ANY
 CHANGES WITH ANY MOTOR LOADS ON THE GENERAL PURPOSE
 BRANCH RECEPTACLES.
 FBC 106.1.2.
 430.6 AND SEVERAL OTHER CODES IN 430 FOR INFORMATION
 INCLUDING 430.148
  
 22) NOTE: PLEASE SEE THE A/C CLOSET DETAILS ON SHEET
 FOR SECOND FLOOR. THE DISCONNECT SHOWN FOR ONE O OF THE
 AIR HANDLER UNITS DO NOT SEEM TO MEET 110.26.
  
 23) NOTE: PLEASE SEE THE PLANS NOTES *BREAKER LOCK
 DEVICES* FOR SMOKE ALARMS.
 PLEASE KNOW AS NOTED ABOVE THESE REQUIRE ARC FAULT
 PROTECTION REQUIRED, THESE SMOKE DEVICES MAY BE PLACED
 ON THE LIGHTING/RECEPTACLE CIRCUITS FOR BEDROOMS.
  
 24) NOTE: PLEASE PROVIDE A NOTE ON PLANS FOR THE TYPE
 OF RECESSED LIGHTING AS REQUIRED PER FBC
 13-606-1.ABC.1.2.4.
  
 ** PLEASE SEE ANY COMMENTS FROM OTHER TRADES WHICH MAY
 OR MAY NOT AFFECT ELECTRICAL PLANS.
  
  
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-08-31 07:58:212007-08-31 07:58:21
  
 REVIEW CONTINUED
2007-08-29 20:50:202007-08-29 20:50:20
  
 ELECTRICAL REVIEW WILL BE PROCESSED INTO A *F* STATUS
 AND NOTES WILL FOLLOW ONCE REVIEW IS COMPLETED ON 8/30
2007-08-29 19:55:582007-08-29 19:55:58
 IN ELEC FOR REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2009-09-22 Cont ID  
Sent By lmartine Date 2009-09-17 Time 10:59 Rev Time 0.00
Received By lmartine Date 2009-09-17 Time 10:59 Sent To  
Notes
2009-09-22 11:00:40GAVE TO DEWEY, ROUTED ON 9/22 LM

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2009-07-15 Cont ID  
Sent By shill Date 2009-07-15 Time 08:55 Rev Time 0.00
Received By shill Date 2009-07-15 Time 08:55 Sent To  
Notes
2009-07-15 08:55:25TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2009-04-20 Cont ID  
Sent By shill Date 2009-04-20 Time 11:37 Rev Time 0.00
Received By shill Date 2009-04-20 Time 11:37 Sent To  
Notes
2009-04-20 11:37:48TO RM DESK

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2009-04-10 Cont ID  
Sent By adarroug Date 2009-04-10 Time 13:04 Rev Time 0.00
Received By adarroug Date 2009-04-10 Time 13:04 Sent To B
Notes
2009-04-10 13:04:45TO "RMCDOUGAL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2008-09-23 Cont ID  
Sent By adarroug Date 2008-09-23 Time 15:43 Rev Time 0.00
Received By adarroug Date 2008-09-23 Time 15:43 Sent To M
Notes
2008-09-23 15:43:54TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-04-02 Cont ID  
Sent By adarroug Date 2008-04-02 Time 14:11 Rev Time 0.00
Received By adarroug Date 2008-04-02 Time 14:11 Sent To P
Notes
2008-04-02 14:12:27TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-03-26 Cont ID  
Sent By adarroug Date 2008-03-26 Time 13:53 Rev Time 0.00
Received By adarroug Date 2008-03-26 Time 13:53 Sent To P
Notes
2008-03-26 13:54:05TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-02-06 Cont ID  
Sent By adarroug Date 2008-02-06 Time 11:10 Rev Time 0.00
Received By adarroug Date 2008-02-06 Time 11:10 Sent To B
Notes
2008-02-06 11:10:33TO "RMCDOUGAL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-01-29 Cont ID  
Sent By adarroug Date 2008-01-29 Time 08:31 Rev Time 0.00
Received By adarroug Date 2008-01-29 Time 08:31 Sent To M
Notes
2008-01-29 08:31:35TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-01-11 Cont ID  
Sent By spalmer Date 2008-01-11 Time   Rev Time 0.00
Received By spalmer Date 2008-01-11 Time 10:32 Sent To M
Notes
2008-01-11 10:33:24TO TOM GORDONS DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-01-10 Cont ID  
Sent By mmiller Date 2008-01-10 Time 19:09 Rev Time 0.00
Received By mmiller Date 2008-01-10 Time 19:09 Sent To  
Notes
2008-01-10 19:10:18NEED TO SPEAK WITH DEWEY PALMER REGARDING THESE PLANS

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-11-30 Cont ID  
Sent By adarroug Date 2007-11-30 Time 14:38 Rev Time 0.00
Received By adarroug Date 2007-11-30 Time 14:38 Sent To Z
Notes
2007-11-30 14:38:42TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-02 Cont ID  
Sent By adarroug Date 2007-10-02 Time 10:37 Rev Time 0.00
Received By adarroug Date 2007-10-02 Time 10:37 Sent To Z
Notes
2007-10-02 10:37:51TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-09-18 Cont ID  
Sent By rmcdouga Date 2007-09-18 Time 14:45 Rev Time 0.00
Received By rmcdouga Date 2007-08-22 Time 16:14 Sent To  
Notes
2007-08-22 16:14:53TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2008-09-25 Cont ID  
Sent By tgordon Date 2008-09-25 Time 15:26 Rev Time 0.45
Received By tgordon Date 2008-09-25 Time 15:26 Sent To  
Notes
2008-09-25 15:27:35RVISION TO MECH. PLANS M-1 AND M-2.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2008-01-29 Cont ID  
Sent By tgordon Date 2008-01-29 Time 09:21 Rev Time 0.45
Received By tgordon Date 2008-01-29 Time 09:21 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2008-01-11 Cont ID  
Sent By tgordon Date 2008-01-11 Time 13:41 Rev Time 1.30
Received By tgordon Date 2008-01-11 Time 13:41 Sent To B
Notes
2008-01-11 14:04:27PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ONLY ONE SET OF THE MECHANICAL PLANS PAGE M-1 AND
 M-2 WERE SUBMITTED FOR REVIEW, TWO SETS MUST BE
 SUBMITTED, SEE 2004 FBC/WPB AMEND. 106.1.
  
 2) COOLING LOAD CALCULATIONS ARE CALLING FOR 121,173
 TOTAL COOLING BTU'S, MECHANICAL PLANS ARE SHOWING
 156,400 TOTAL COOLING BTU'S, THE PLANS CAN ONLY CALL
 FOR 15% MORE THAN THE COOLING LOAD CALCULATIONS, SEE
 2004 FBC 13-607.1.ABC.1.1. 13 TONS OF AIR CONDITIONING
 APPEARS TO BE TO MUCH, PLEASE CORRECT.
  
 3) A/C SYSTEM 1 AND 2 ARI CERTIFICATION HAS BEEN
 DISCONTINUED (SEE ATTACHED COPY), SEE 2004 FBC
 13-607.1.ABC.3.1.1, PLEASE CORRECT.
  
 4) THE FIRST FLOOR CLOTHES DRYER VENT MAY NOT DISCHARGE
 ON OR TERMINATE NEAR THE A/C CONDENSER UNIT, SEE 2004
 FBC/R M303.4.2, PLEASE CORRECT.
  
 5) PLEASE ADD JOB ADDRESS TO ANY NEW MECHANICAL PLANS,
 SEE 2004 FBC/WPB AMEND. 106.1.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected] .

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-12-03 Cont ID  
Sent By tgordon Date 2007-12-03 Time 14:58 Rev Time 0.30
Received By tgordon Date 2007-12-03 Time 14:57 Sent To P
Notes
2007-12-03 15:03:00PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) COMPLETE MECHANICAL REVIEW COULD NOT BE DONE AS
 MECHANICAL PLANS PAGES M.1 AND M.2 WERE NOT SUBMITTED
 WITH REVISED PLANS. SEE 2004 W.P.B AMEND. 106.3.5.4
 (10) SUBMIT MECHANICAL PLANS FOR REVIEW.
  
 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-10-10 Cont ID  
Sent By tgordon Date 2007-10-10 Time 12:06 Rev Time 0.45
Received By tgordon Date 2007-10-10 Time 12:06 Sent To P
Notes
2007-10-10 12:29:56PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA
 ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS).
  
 *** DENIED ***
  
 1) AS NOTED IN LAST REVIEW 9/6/07. MECHANICAL PLANS,
 INFORMATION MISSING IN TITLE BLOCK FOR ARCHITECT
 (ARCHITECT FIRM LICENSE NUMBER AA0002936).
 PER FAC 61G1-16.004 TITLE BLOCK.
  
 2) AS NOTED IN LAST REVIEW 9/6/07 NOTE #3. PLEASE
 SUBMIT COOLING LOAD CALCULATIONS, SEE FBC
 13-407.1.ABC.1.
  
 3) AS NOTED IN LAST REVIEW 9/6/07 NOTE #4. ENERGY
 CALCULATIONS LINE 13A, AND B SHOW THE A/C SYSTEMS AS
 HEAT PUMP SYSTEMS. THE ARI DIRECTORY SHOWS THE UNITS
 ARE STRAIGHT COOL SYSTEMS, PLEASE CORRECT ENERGY CAL'S.
 OR MODEL NUMBERS ON MECHANICAL PLANS.
  
 4) AS NOTED IN LAST REVIEW 9/6/07 NOTE #6. PLEASE
 SUBMIT DETAILED MANUFACTURER'S SPECIFICATION'S AND
 INSTALLATION INSTRUCTIONS FOR THE GAS BBQ GRILL AND
 HOOD, GAS FIRE PLACES, AND GAS LOG LIGHTERS IF USED.
  
 5) AS NOTED IN LAST REVIEW NOTE #7. PLEASE SUBMIT
 PRODUCT APPROVAL FOR O/A LOUVER FOR SAFE ROOM, SEE FS
 553.842(1) AND FAC RULE 9B-72, 9B-72.005, AND FAC
 9B-72.010(31)(G).
  
 **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG.
  
 6) WASHER/DRYER DETAIL ON PAGE DMP-1 STATES PER I.M.C.
 2003304.6.1. ALL WORK PERMITTED IN THE CITY OF W.P.B.
 MUST COMPLY WITH THE "2004 F.B.C.", PLEASE CORRECT.
  
 7) SEE ATTACHED NOTICE FS 553.80 (2) (B) REGARDING FOUR
 TIMES THE FEE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-09-06 Cont ID  
Sent By tgordon Date 2007-09-06 Time 08:43 Rev Time 1.30
Received By tgordon Date 2007-09-06 Time 08:43 Sent To P
Notes
2007-09-06 09:33:01PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA
 ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS).
  
 *** DENIED ***
 1) MECHANICAL PLANS, INFORMATION MISSING FROM TITLE
 BLOCK (ENGINEERS PRINTED NAME AND LICENSE NUMBER WHO
 SEALED THE PLAN, AND THE ENGINEERING BUSINESS
 CERTIFICATE OF AUTHORIZATION NUMBER).
 SEE FAC 61G15-23.002 (2)A TITLE BLOCK ON EACH SHEET
 CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE
 NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND
 LICENSE NUMBER OF THE ENGINEER, AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT.
  
 2) MECHANICAL PLANS, INFORMATION MISSING IN TITLE BLOCK
 FOR ARCHITECT (ARCHITECT FIRM LICENSE NUMBER, AND JOB
 ADDRESS).
 SEE FAC 61G1-16.004 TITLE BLOCK. A TITLE BLOCK MUST
 APPEAR ON ALL ARCHITECTURAL OR INTERIOR DESIGN DRAWINGS
 AND SPECIFICATION IDENTIFICATION SHEETS. THE TITLE
 BLOCK MUST, AT A MINIMUM, CONTAIN THE FOLLOWING
 INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT. ("JOB ADDRESS"
 SEE CITY WPB AMEND. 106.1.1).
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  
 3) PLEASE SUBMIT COOLING LOAD CALCULATIONS, SEE FBC
 13-407.1.ABC.1.
  
 4) ENERGY CALCULATIONS LINE 13A, AND B SHOW THE A/C
 SYSTEMS AS HEAT PUMP SYSTEMS. THE ARI DIRECTORY SHOWS
 THE UNITS ARE STRAIGHT COOL SYSTEMS, PLEASE CORRECT
 ENERGY CAL'S. OR MODEL NUMBERS ON MECHANICAL PLANS.
  
 4) PAGE DMP-1 DETAIL OF CONDENSATE DISCHARGE TO GRADE,
 DRAIN NEEDS TO DISCHARGE 12" FROM THE BUILDING, SEE
 RES. R320.7. PLEASE CORRECT.
  
 5) PAGES M-1 AND M-2 DUCT SCHEDULE ZONES 2, 3, AND 4 DO
 NOT SHOW ALL THE DUCT SIZES (SEE YELLOW HIGH LIGHT ON
 PLAN) PLEASE CORRECT.
  
 6) PLEASE SUBMIT DETAILED MANUFACTURER'S
 SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR THE
 GAS BBQ GRILL AND HOOD, GAS FIRE PLACES, AND GAS LOG
 LIGHTERS IF USED.
  
 7) PLEASE SUBMIT PRODUCT APPROVAL FOR O/A LOUVER FOR
 SAFE ROOM, SEE FS 553.842(1) AND FAC RULE 9B-72,
 9B-72.005, AND FAC 9B-72.010(31)(G).
  
 **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG.
  
 *** INFORNATIONAL: PAGE A.01 SHOWS A GENERATOR NEAR A
 8X8" VENT BLOCK TO THE GARAGE NFPA 37 REQUIRES
 GENERATORS TO BE FIVE FEET FROM BUILDING OPENINGS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 5 Status P Date 2008-04-14 Cont ID  
Sent By jleech Date 2008-04-14 Time 08:10 Rev Time 0.00
Received By jleech Date 2008-04-14 Time 08:00 Sent To  
Notes
2008-04-14 08:11:06PLUMBING AS-BUILTS

Review Stop P PLUMBING
Rev No 4 Status F Date 2008-03-27 Cont ID  
Sent By mperson Date 2008-03-27 Time 10:22 Rev Time 0.00
Received By mperson Date 2008-03-27 Time 10:22 Sent To PC
Notes
2008-03-27 10:29:55PLUMBING PLAN REVIEW:
 REVISION DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 1. SHEET P.01 MASTER BATH SANITARY PLUMBING RISER: THE
 BIDET IS NOT VENTED. PER FBC PLUMBING SECTION 901.2.1
 VENTING REQUIRED.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-12-14 Cont ID  
Sent By jleech Date 2007-12-14 Time 09:52 Rev Time 0.00
Received By jleech Date 2007-12-14 Time 08:33 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-10-16 Cont ID  
Sent By jleech Date 2007-10-16 Time 08:31 Rev Time 0.00
Received By jleech Date 2007-10-16 Time 08:01 Sent To B
Notes
2007-10-16 08:51:55DENIED;
 1.SEE MECHANICAL NOTE #1. ARCHITECT FIRM LICENSE IS
 REQUIRED ON THE TITLE BLOCK.
 2. SANITARY RISER DIAGRAM, CLEANOUT'S REQUIRED ON
 AUTOMATIC CLOTHES WASHER VENT AT 48" ABOVE FINISH
 FLOOR.
 3. DISHWASHERS TO DISCHARGE INDIRECTLY INTO BUILDING
 DRAIN. SECTION 802.1.6.
 4. 1/2 BATH FIRST FLOOR TOILET NOT VENTED AS DRAWN
 CANNOT DISCHARGE INTO THE 2ND FLOOR BRANCH DRAIN.
 5. WATER SANITARY RISER DIAGRAM WATER HAMMER ARRESTORS
 ARE REQUIRED ON ALL QUICK CLOSING VALVES PER 604.9 SHOW
 ON PLANS.
 6. 2 WATER HEATERS SHOWN ON FLOOR PLANS 80 GAL ON 1ST
 FLOOR60 GAL ON 2ND FLOOR, ONLY ONE MODEL # SHOWN ON
 PAGE DMP-1.
 7. SHOW LOCATION OF IN-LINE PUMP FOR MATER SHOWER. THIS
 PUMP MUST BE ACCESSABLE WITH A SHUTOFF VALVE UP STREAM.
  
 PLUMBING PLAN REVIEW BY
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-09-11 Cont ID  
Sent By jleech Date 2007-09-11 Time 08:50 Rev Time 0.00
Received By jleech Date 2007-09-11 Time 08:24 Sent To B
Notes
2007-09-11 09:11:09DENIED;
 SEE ELECTRICAL PLAN REVIEW NOTES 1 THRU 5.
 1.SHOW ON PLANS, BACKFLOW PREVENTOR REQUIRED. CITY
 UTILITY ORD. RPZ REQUIRED IF HOUSE HAS A POOL.
 2. ( ONE SHEET DMP-2) MARKED IN RED, SHOWER NOT VENTED.
 SINK TO DISCHARGE DOWN STREAM OF BATHROOM GROUP,
 SECTION 909.1.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 3 Status P Date 2007-11-30 Cont ID  
Sent By choops Date 2007-11-30 Time 16:24 Rev Time 0.00
Received By choops Date 2007-11-30 Time 16:24 Sent To E
Notes
2007-11-30 15:46:13*** APPROVED- RESUB #2***
  
  
  
 SENT TO "E" - DP

Review Stop Z ZONING
Rev No 2 Status F Date 2007-10-05 Cont ID  
Sent By choops Date 2007-10-05 Time 12:11 Rev Time 0.00
Received By choops Date 2007-10-05 Time 12:11 Sent To E
Notes
2007-10-05 12:12:41***FAILED - RESUB #1***
  
  
 REPEAT COMMENTS:
  
 1)EXCEEDS MAXIMUM BUILDING HEIGHT.DEVELOPMENT
 REGULATIONS FOR BEAR LAKES ALLOW A MAXIMUM BUILDING
 HEIGHT OF 35' (MEASURED FROM GRADE TO THE MIDPOINT OF
 THE ROOF'S PITCH), WITH AN ALLOWABLE 10% FOR
 ACCESSORIES.YIELDING A MAXIMUM HEIGHT FOR ALL
 ACCESSORIES (NON-HABITABLE TOWERS) OF 38.5' .
  
 2)AS THE FRONT SITE WALL (COLUMNS) FALLS WITHIN THE
 FRONT UTILITY EASEMENT, ADDITIONAL EASEMENT CONSENT
 FORMS SHALL BE PROVIDED FROM:FP&L, COMCAST/ADELPHIA,
 FLA PUBLIC UTILITIES, AND BELLSOUTH.
  
 NEW COMMENTS:
  
 1)INDICATE SETBACK DIMENSIONS FROM TRELLIS TO REAR
 PROPERTY LINE.
  
 2)PURSUANT TO SECTION 94-302(B)(1) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS:RESIDENTIAL FENCE,
 HEDGE, AND WALL LIMITATIONS.
 (1)MAXIMUM HEIGHT.IN RESIDENTIAL DISTRICTS, NO
 FENCE OR WALL SHALL EXCEED SIX FEET IN HEIGHT WITHIN
 REQUIRED SIDE AND REAR SETBACKS. FENCES OR WALLS SHALL
 NOT BE IN EXCESS OF 48 INCHES IN HEIGHT WITHIN THE
 REQUIRED FRONT SETBACK. HEDGES SHALL NOT EXCEED TEN
 FEET IN HEIGHT IN ANY REQUIRED SETBACK.
  
 NOTE:PALM TREES DO NOT COUNT TOWARDS THE REQUIRED
 FLOWERING/FRUIT TREE REQUIREMENT FOR OPEN SPACE.CHECK
 THAT REQUIREMENT IS STILL SATISFIED.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2007-08-24 Cont ID  
Sent By choops Date 2007-08-24 Time 11:12 Rev Time 0.00
Received By choops Date 2007-08-24 Time 11:12 Sent To E
Notes
2007-08-24 11:24:13***FAILED***
  
  
 1)EXCEEDS MAXIMUM BUILDING HEIGHT.DEVELOPMENT
 REGULATIONS FOR BEAR LAKES ALLOW A MAXIMUM BUILDING
 HEIGHT OF 35' (MEASURED FROM GRADE TO THE MIDPOINT OF
 THE ROOF'S PITCH), WITH AN ALLOWABLE 10% FOR
 ACCESSORIES.YIELDING A MAXIMUM HEIGHT FOR ALL
 ACCESSORIES (NON-HABITABLE TOWERS) OF 38.5' .
  
 2)PROVIDE A LANDSCAPE PLAN SHOWING COMPLIANCE WITH
 SECTION 94-442 OF THE CITY OF WEST PALM BEACH ZONING
 AND LAND DEVELOPMENT REGULATIONS.
  
 3)SHEET AS.0 SHOWS A GENERATOR AND POOL EQUIPMENT.
 PLANS SHALL REFLECT THESE TO BE PERMITTED SEPARATELY.
  
 4)SHEET AS.0 APPEARS TO SHOW A FRONT SITE WALL.IF
 INCLUDED IN SCOPE OF WORK FOR THIS PERMIT, AN ELEVATION
 OF PROPOSED WALL SHALL BE SHOWN AND AN EASEMENT CONSENT
 FORM FROM THE CITY OF WEST PALM BEACH DEPARTMENT OF
 PUBLIC UTILITIES SHALL BE APPROVED AND SUBMITTED. NOTE:
 IF SITE WALL FALLS WITHIN THE FRONT UTILITY EASEMENT,
 ADDITIONAL EASEMENT CONSENT FORMS SHALL BE PROVIDED
 FROM:FP&L, COMCAST/ADELPHIA, FLA PUBLIC UTILITIES,
 AND BELLSOUTH.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720