Plan Review Details - Permit 07080565
Plan Review Stops For Permit 07080565
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-12-14 Cont ID  
Sent By mjacobs Date 2007-12-14 Time 11:08 Rev Time 0.00
Received By mjacobs Date 2007-12-14 Time 10:07 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-06 Cont ID  
Sent By mjacobs Date 2007-09-06 Time 10:24 Rev Time 0.00
Received By mjacobs Date 2007-09-06 Time 05:48 Sent To  
Notes
2007-09-06 09:54:24BUILDING PLAN REVIEW
 PERMIT: 07080565
 ADD: 450 S. AUSTRALIAN AVE SUITE 6,7,8,9
 CONT: FRANKLIN CONTRACTORS INC.
 TEL: (954)491-6662
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 3) FBC 1004. INDICATE THE OCCUPANT LOAD OF THE SPACE ON
 THE DRAWINGS.
  
 4)FBC 1016.1 CORRIDORS SHALL BE FIRE-RESISTANCE RATED
 IN ACCORDANCE WITH TABLE 1016.1. THE WALLS SHALL COMPLY
 WITH SECTION 708 FOR FIRE PARTITIONS. INDICATE THE NEW
 WALL FIRE RATING AND THE UL ASSEMBLY.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-12-11 Cont ID  
Sent By dpalmer Date 2007-12-11 Time 15:50 Rev Time 0.00
Received By dpalmer Date 2007-12-11 Time 15:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-09-04 Cont ID  
Sent By dpalmer Date 2007-09-04 Time 07:31 Rev Time 0.00
Received By dpalmer Date 2007-09-04 Time 07:05 Sent To  
Notes
2007-09-04 07:31:33 
  
 ** DENIED**
  
 1) NOTE: PLEASE BE SURE ELECTRICAL AND ARCHITECTURAL
 SHEETS STATE THE FOLLOWING MINIMUM CODES.
 2006 FBC W/2006 REVISIONS.
 2005 NFPA-70.
 2003 NFPA-101
 2002 NFPA-72
  
 ** THE FBC IS ALREADY ON SOME SHEETS.
  
 2) NOTE: PLEASE SEE THE SEAL IN USE BY THE ENGINEER AS
 LISTED ON THE MECHANICAL AND ELECTRICAL SHEETS IS NO
 LONGER VALID FOR USE IN THE STATE OF FLORIDA.
 PLEASE SEE RULING FROM THE FLORIDA BOARD OF ENGINEERS
 DATED FEB *04* WHICH REQUIRED ALL SEALS FOR ENGINEERS
 TO CHANGE FROM THE WORDING OF *CERTIFICATE* TO THE
 *LICENSE* IN SAID SEAL. AN EXTENSION IN TIME WAS GIVEN
 HOWEVER THAT WAS ONLY UNTIL DECEMBER 31ST, 2005.THIS
 RULING WAS OVER THREE YEARS AGO AND THE SEAL ON PLANS
 IS NO LONGER ACCEPTABLE. PLEASE OBTAIN NEW SEAL AND
 RE-SIGN, DATE AND SEAL PLANS.
 FAC 61G15-23.001, FS 471.025
  
 ** THIS IS REQUIRE FOR ALL SHEETS AND TRADES WHETHER OR
 NOT COMMENT IS MADE BY OTHER TRADE REVIEWER(S).
  
 3) NOTE: PLEASE PROVIDE INFORMATION ON THE
 EGRESS/ACCESS CONTROL FOR FAIL SAFE OPERATION. PLEASE
 SEE IF THE POWER TO THE LOCAL EM PANEL WHICH IS BEING
 NOTED FOR CIRCUITING FAILS OR ONLY A SINGLE BRANCH
 CIRCUIT FAILS, THERE WILL BE NO POWER TO UNITS WHICH
 WOULD NOT PROVIDE EGRESS UNDER AN EMERGENCY CONDITION.
 PLEASE KNOW THE GENERATOR WILL ONLY PROVIDE BACK UP IN
 THE EVENT THE POWER FAILS FOR THE ENTIRE BUILDING NOT
 PARTS OF THE BUILDING.
 PLEASE SEE LS 101 CHAPTER 7.2.1, 7.2.1.5, 7.2.1.6.2
 ** PLEASE SEE POSSIBLE COMMENTS FROM THE FIRE MARSHAL.
  
 4) NOTE: PLEASE CLARIFY THE CIRCUITING OF EMERGENCY AND
 EXIT LIGHTING PER 700.12F OF THE NEC.
 PLEASE SEE THE NOTE MENTIONS TO THE EM PANELS, HOWEVER
 HOW THE LIGHTING WILL COME ON IF THE NORMAL LIGHTING IN
 THE AREA WHICH IS FED FROM A LOCAL PANEL OR LOCAL
 CIRCUIT FAILS. PLEASE SEE EXCERPT FROM THE NEC.
 *THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL BE
 THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES.*
  
 5) NOTE: PLEASE PROVIDE NOTE INFORMATION TO VERIFY THE
 LEVELS OF THE STROBES, HORN DEVICES MEETING THE MINIMUM
 LEVELS PER FBC FOR ADA. 11-4.28.1,.2, AND .3(4).
  
  
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-12-12 Cont ID  
Sent By mwennerg Date 2007-12-12 Time 11:08 Rev Time 0.00
Received By mwennerg Date 2007-12-12 Time 11:08 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-09-07 Cont ID  
Sent By mwennerg Date 2007-09-07 Time 15:31 Rev Time 0.00
Received By mwennerg Date 2007-09-07 Time 15:31 Sent To  
Notes
2007-09-07 15:42:42***DENIED***
  
 1) PLEASE SEE OTHER REVIEW COMMENTS REGARDING FS AND
 FAC REQUIREMENTS FOR PLANS.
  
 2) PLEASE PROVIDE ADDITIONAL INFORMATION FOR CARD
 READING EQUIPMENT AND SHOW COMPLIANCE WITH NFPA 101,
 2003 EDITION SEC,. 7.2.1.6.2.
  
 3) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM REMODEL WHERE APPLICABLE.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-12-06 Cont ID  
Sent By adarroug Date 2007-12-06 Time 09:52 Rev Time 0.00
Received By adarroug Date 2007-12-06 Time 09:52 Sent To  
Notes
2007-12-10 16:10:14TO "BOB"#11
2007-12-06 09:52:52WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-09-07 Cont ID  
Sent By mwennerg Date 2007-09-07 Time 15:47 Rev Time 0.00
Received By mwennerg Date 2007-08-21 Time 15:20 Sent To  
Notes
2007-08-31 10:45:30TO "BOB"#2
2007-08-21 15:25:45WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-12-11 Cont ID  
Sent By tgordon Date 2007-12-11 Time 08:55 Rev Time 0.25
Received By tgordon Date 2007-12-11 Time 08:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-09-06 Cont ID  
Sent By tgordon Date 2007-09-06 Time 11:31 Rev Time 0.25
Received By tgordon Date 2007-09-06 Time 11:31 Sent To  
Notes
2007-09-06 11:34:08PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA
 ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS).
  
 *** DENIED ***
 1) SEE ELECTRICAL REVIEW NOTE #2 REGARDING SEAL BEING
 USED, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2007-09-05 Cont ID  
Sent By choops Date 2007-09-05 Time 10:47 Rev Time 0.00
Received By choops Date 2007-09-05 Time 10:47 Sent To  
Notes
2007-09-05 10:47:25*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.