| 2007-09-04 07:31:33 | |
| | |
| | ** DENIED** |
| | |
| | 1) NOTE: PLEASE BE SURE ELECTRICAL AND ARCHITECTURAL |
| | SHEETS STATE THE FOLLOWING MINIMUM CODES. |
| | 2006 FBC W/2006 REVISIONS. |
| | 2005 NFPA-70. |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | |
| | ** THE FBC IS ALREADY ON SOME SHEETS. |
| | |
| | 2) NOTE: PLEASE SEE THE SEAL IN USE BY THE ENGINEER AS |
| | LISTED ON THE MECHANICAL AND ELECTRICAL SHEETS IS NO |
| | LONGER VALID FOR USE IN THE STATE OF FLORIDA. |
| | PLEASE SEE RULING FROM THE FLORIDA BOARD OF ENGINEERS |
| | DATED FEB *04* WHICH REQUIRED ALL SEALS FOR ENGINEERS |
| | TO CHANGE FROM THE WORDING OF *CERTIFICATE* TO THE |
| | *LICENSE* IN SAID SEAL. AN EXTENSION IN TIME WAS GIVEN |
| | HOWEVER THAT WAS ONLY UNTIL DECEMBER 31ST, 2005.THIS |
| | RULING WAS OVER THREE YEARS AGO AND THE SEAL ON PLANS |
| | IS NO LONGER ACCEPTABLE. PLEASE OBTAIN NEW SEAL AND |
| | RE-SIGN, DATE AND SEAL PLANS. |
| | FAC 61G15-23.001, FS 471.025 |
| | |
| | ** THIS IS REQUIRE FOR ALL SHEETS AND TRADES WHETHER OR |
| | NOT COMMENT IS MADE BY OTHER TRADE REVIEWER(S). |
| | |
| | 3) NOTE: PLEASE PROVIDE INFORMATION ON THE |
| | EGRESS/ACCESS CONTROL FOR FAIL SAFE OPERATION. PLEASE |
| | SEE IF THE POWER TO THE LOCAL EM PANEL WHICH IS BEING |
| | NOTED FOR CIRCUITING FAILS OR ONLY A SINGLE BRANCH |
| | CIRCUIT FAILS, THERE WILL BE NO POWER TO UNITS WHICH |
| | WOULD NOT PROVIDE EGRESS UNDER AN EMERGENCY CONDITION. |
| | PLEASE KNOW THE GENERATOR WILL ONLY PROVIDE BACK UP IN |
| | THE EVENT THE POWER FAILS FOR THE ENTIRE BUILDING NOT |
| | PARTS OF THE BUILDING. |
| | PLEASE SEE LS 101 CHAPTER 7.2.1, 7.2.1.5, 7.2.1.6.2 |
| | ** PLEASE SEE POSSIBLE COMMENTS FROM THE FIRE MARSHAL. |
| | |
| | 4) NOTE: PLEASE CLARIFY THE CIRCUITING OF EMERGENCY AND |
| | EXIT LIGHTING PER 700.12F OF THE NEC. |
| | PLEASE SEE THE NOTE MENTIONS TO THE EM PANELS, HOWEVER |
| | HOW THE LIGHTING WILL COME ON IF THE NORMAL LIGHTING IN |
| | THE AREA WHICH IS FED FROM A LOCAL PANEL OR LOCAL |
| | CIRCUIT FAILS. PLEASE SEE EXCERPT FROM THE NEC. |
| | *THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL BE |
| | THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL |
| | LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL |
| | SWITCHES.* |
| | |
| | 5) NOTE: PLEASE PROVIDE NOTE INFORMATION TO VERIFY THE |
| | LEVELS OF THE STROBES, HORN DEVICES MEETING THE MINIMUM |
| | LEVELS PER FBC FOR ADA. 11-4.28.1,.2, AND .3(4). |
| | |
| | |
| | |
| | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |