| Plan Review Stops For Permit 07080559 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2007-08-31 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2007-08-31 |
Time |
10:57 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2007-08-31 |
Time |
10:57 |
Sent To |
|
|
| Notes |
| 2007-08-31 11:01:40 | ***PROVISO*** | | | | | | 1) PLANS DON'T CLEARLY SPECIFY IF ONLY EXISTING | | | SPRINKLERS ARE TO BE RELOCATED. IF NEW HEADS ARE | | | INSTALLED, SPECIFICATION SHEETS SHALL BE SUBMITTED. | | | | | | 2) PLEASE INCLUDE ADOPTED EDITION WHEN REFERENCING | | | CODES, NFPA 13, 2002. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-08-31 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2007-08-31 |
Time |
11:10 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2007-08-21 |
Time |
15:47 |
Sent To |
|
|
| Notes |
| 2007-08-21 15:47:48 | TO "F" BOX |
|
|
|