Plan Review Details - Permit 07080551
Plan Review Stops For Permit 07080551
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-11-05 Cont ID  
Sent By shill Date 2007-11-05 Time 17:18 Rev Time 0.00
Received By shill Date 2007-11-05 Time 17:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-10-19 Cont ID  
Sent By shill Date 2007-10-19 Time 15:49 Rev Time 0.00
Received By shill Date 2007-10-19 Time 15:49 Sent To  
Notes
2007-10-19 15:50:13****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 1.)NOTES REFER TO ASCE7-98; CORRECT REFERENCE IS
 ASCE7-02, FBC35.
  
 2.)SECOND COMMENT WAS ADDRESSED BY CONTRACTOR
 REVISING APPLICATION TO STATE THAT THE PAD WILL BE
 POURED.NOTE THAT IF THE CONTRACTOR WISHES TO USE A
 PREFAB SLAB, CALCULATIONS WILL BE REQUIRED.
 (INFORMATIONAL; NOT REQUIRED TO BE ADDRESSED.)
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-17 Cont ID  
Sent By shill Date 2007-09-17 Time 14:11 Rev Time 0.00
Received By shill Date 2007-09-17 Time 14:11 Sent To  
Notes
2007-09-17 14:13:43****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)NOTES REFER TO ASCE7-98; CORRECT REFERENCE IS
 ASCE7-02, FBC35.
  
 2.)NOTES FOR GENERATOR STATE THAT THE SLAB WILL BE
 POURED.APPLICATION STATES EITHER POURED OR PRECAST.
 A PRECAST SLAB REQUIRES ENGINEERING FOR THE SLAB AND
 ANCHORING, AND MUST BE CONSISTENT WITH THE ENGINEER'S
 DESIGN.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-10-10 Cont ID  
Sent By btrobaug Date 2007-10-05 Time 15:57 Rev Time 0.00
Received By btrobaug Date 2007-10-05 Time 07:43 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-09-14 Cont ID  
Sent By tgordon Date 2007-09-14 Time 11:30 Rev Time 0.00
Received By btrobaug Date 2007-09-14 Time 11:29 Sent To P
Notes
2007-10-10 16:10:14 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} IT IS THE DETERMINATION OF THIS OFFICE THAT LOADS
 BEING TRANSFERRED AUTOMATICALLY ARE THE LOADS SELECTED
 UNDER ARTICLE 702.5. UTILITY POWER CAN BE DISRUPTED AT
 ANY TIME, POSSIBLY IN THE OWNERS ABSENCE. THEREFORE ALL
 CONNECTED LOADS WILL BE ENERGIZED AS THERE IS NO ONE TO
 "SELECT" WHICH CIRCUITS WILL BE ENERGIZED. THEREFORE
 ALL CONNECTED LOADS WILL BE ENERGIZED AS THERE IS NOONE
 TO "SELECT"WHICH CIRCUITS WILL BE ENERGIZED. THE
 CALCULATION GIVEN WOULD INCLUDE THE "LOAD SHEDDING
 JUSTIFICATION" OF THE WHIRLPOOL EQUIPMENT AS THEY ARE
 IN THE SELECTED PANEL. THE ACCEPTABLE LOAD WILL DEPEND
 ON THE GENERATOR SPECIFICATIONS, SEE COMMENT #2.
  
 2}PROVIDE MANUFACTURERS SPECIFICATIONS INDICATING
 RECOMMENDED SETBACKS AND ELECTRICAL SPEC'S FOR THE
 GENERATOR AND TRANSFER SWITCH.
  
 3} PLEASE LOCATE ALL SERVICE AND GENERATOR EQUIPMENT ON
 A SITE PLAN, NOT THE SURVEY, METER ENCLOSURE,
 DISCONNECTS, ATS AND PANELS, SO THAT COMPLIANCE WITH
 ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2007-11-02 Cont ID  
Sent By mperson Date 2007-11-02 Time 11:09 Rev Time 0.00
Received By mperson Date 2007-11-02 Time 11:09 Sent To B
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2007-10-16 Cont ID  
Sent By mperson Date 2007-10-16 Time 08:57 Rev Time 0.00
Received By mperson Date 2007-10-16 Time 08:57 Sent To B
Notes
2007-10-16 09:21:06DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE (FAC).
 ** FLORIDA STATUTES (FS).
  
 1. THERE ARE TWO DIFFERENT SETS OF GAS RISER DIAGRAMS
 IN THE RESUBMITTAL. ONE THAT IS SIGNED AND SEALED BY
 JAMES L. MAKO P.E. #54111 USING 1 INCH COPPER PIPE AND
 ONE BY FLORIDA PUBLIC UTILITIES CO. USING 3/4 INCH PE
 PIPE UNDERGROUND AND 3/4 INCH SCH. 40 GALV. PIPE ABOVE
 GROUND. PLEASE NOTE THAT THE SUBMITTED DRAWINGS BY
 FLORIDA PUBLIC UTILITIES CO. ARE CORRECT IN THAT THEY
 INDICATE THE ENTIRE GAS SYSTEM PIPING AND BTU LOAD
 (WHICH IS REQUIRED BY CITY REQUIREMENTS). THE SIGNED
 AND SEALED PLANS DO NOT INDICATE THIS. PLEASE CORRELATE
 THE RESUBMITTAL WITH ONLY ONE SET OF GAS RISER
 DIAGRAMS.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-09-14 Cont ID  
Sent By mperson Date 2007-09-14 Time 16:38 Rev Time 0.00
Received By mperson Date 2007-09-14 Time 16:38 Sent To B
Notes
2007-09-14 16:52:11DENIED
 REFERENCE:
 ** FBC-2004 FUEL GAS WITH 2006 REVISIONS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1.SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 NOTE: PLEASE SUBMIT MANUFACTURER SPECIFICATIONS ON THE
 GENERATOR WITH THE MAKE, MODEL NUMBER, GAS TYPE/BTU
 LOAD AND A LISTING FROM A NATIONALLY RECOGNIZED TESTING
 LABORATORY (NRTL) ALSO PLEASE SUBMIT MANUFACTURER
 SPECIFICATION SHEETS ON THE REGULATOR FOR THE GENERATOR
 WITH THE MAKE, MODEL NUMBER, BTU LOAD CAACITY AND A
 LISTING FROM A NATIONALLY RECOGNIZED TESTING LABORATORY
 (NRTL).
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-10-22 Cont ID  
Sent By adarroug Date 2007-10-22 Time 11:08 Rev Time 0.00
Received By adarroug Date 2007-10-22 Time 11:08 Sent To G
Notes
2007-10-22 11:08:52TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-03 Cont ID  
Sent By adarroug Date 2007-10-03 Time 15:52 Rev Time 0.00
Received By adarroug Date 2007-10-03 Time 15:52 Sent To E
Notes
2007-10-03 15:52:31TO "BTROBAUGH" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-09-17 Cont ID  
Sent By shill Date 2007-09-17 Time 14:13 Rev Time 0.00
Received By shill Date 2007-08-21 Time 09:13 Sent To  
Notes
2007-08-21 09:13:57TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-08-22 Cont ID  
Sent By tgordon Date 2007-08-22 Time 11:19 Rev Time 0.20
Received By tgordon Date 2007-08-22 Time 11:19 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2007-08-21 Cont ID  
Sent By choops Date 2007-08-21 Time 16:51 Rev Time 0.00
Received By choops Date 2007-08-21 Time 16:51 Sent To E
Notes
2007-08-21 16:52:02APPROVED GENERATOR LOCATION ONLY.PROVISO:MUST BE A
 MINIMUM OF 3.5' FROM SIDE PROPERTY LINE.