| Plan Review Stops For Permit 07080551 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2007-11-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-11-05 |
Time |
17:18 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-11-05 |
Time |
17:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-10-19 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-10-19 |
Time |
15:49 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-10-19 |
Time |
15:49 |
Sent To |
|
|
| Notes |
| 2007-10-19 15:50:13 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | FROM PREVIOUS LIST: | | | | | | 1.)NOTES REFER TO ASCE7-98; CORRECT REFERENCE IS | | | ASCE7-02, FBC35. | | | | | | 2.)SECOND COMMENT WAS ADDRESSED BY CONTRACTOR | | | REVISING APPLICATION TO STATE THAT THE PAD WILL BE | | | POURED.NOTE THAT IF THE CONTRACTOR WISHES TO USE A | | | PREFAB SLAB, CALCULATIONS WILL BE REQUIRED. | | | (INFORMATIONAL; NOT REQUIRED TO BE ADDRESSED.) | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-09-17 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-09-17 |
Time |
14:11 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-09-17 |
Time |
14:11 |
Sent To |
|
|
| Notes |
| 2007-09-17 14:13:43 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.)NOTES REFER TO ASCE7-98; CORRECT REFERENCE IS | | | ASCE7-02, FBC35. | | | | | | 2.)NOTES FOR GENERATOR STATE THAT THE SLAB WILL BE | | | POURED.APPLICATION STATES EITHER POURED OR PRECAST. | | | A PRECAST SLAB REQUIRES ENGINEERING FOR THE SLAB AND | | | ANCHORING, AND MUST BE CONSISTENT WITH THE ENGINEER'S | | | DESIGN. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2007-10-10 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-10-05 |
Time |
15:57 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-10-05 |
Time |
07:43 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-09-14 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-09-14 |
Time |
11:30 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-09-14 |
Time |
11:29 |
Sent To |
P |
|
| Notes |
| 2007-10-10 16:10:14 | | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} IT IS THE DETERMINATION OF THIS OFFICE THAT LOADS | | | BEING TRANSFERRED AUTOMATICALLY ARE THE LOADS SELECTED | | | UNDER ARTICLE 702.5. UTILITY POWER CAN BE DISRUPTED AT | | | ANY TIME, POSSIBLY IN THE OWNERS ABSENCE. THEREFORE ALL | | | CONNECTED LOADS WILL BE ENERGIZED AS THERE IS NO ONE TO | | | "SELECT" WHICH CIRCUITS WILL BE ENERGIZED. THEREFORE | | | ALL CONNECTED LOADS WILL BE ENERGIZED AS THERE IS NOONE | | | TO "SELECT"WHICH CIRCUITS WILL BE ENERGIZED. THE | | | CALCULATION GIVEN WOULD INCLUDE THE "LOAD SHEDDING | | | JUSTIFICATION" OF THE WHIRLPOOL EQUIPMENT AS THEY ARE | | | IN THE SELECTED PANEL. THE ACCEPTABLE LOAD WILL DEPEND | | | ON THE GENERATOR SPECIFICATIONS, SEE COMMENT #2. | | | | | | 2}PROVIDE MANUFACTURERS SPECIFICATIONS INDICATING | | | RECOMMENDED SETBACKS AND ELECTRICAL SPEC'S FOR THE | | | GENERATOR AND TRANSFER SWITCH. | | | | | | 3} PLEASE LOCATE ALL SERVICE AND GENERATOR EQUIPMENT ON | | | A SITE PLAN, NOT THE SURVEY, METER ENCLOSURE, | | | DISCONNECTS, ATS AND PANELS, SO THAT COMPLIANCE WITH | | | ARTICLES 225 AND 230 CAN BE REVIEWED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2007-11-02 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-11-02 |
Time |
11:09 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2007-11-02 |
Time |
11:09 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2007-10-16 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-10-16 |
Time |
08:57 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2007-10-16 |
Time |
08:57 |
Sent To |
B |
|
| Notes |
| 2007-10-16 09:21:06 | DENIED 2ND TIME | | | REFERENCE: | | | ** FBC-2004 WITH 05 & 06 REVISIONS, FUEL GAS. | | | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION | | | REQUIREMENTS. | | | ** FBC-2004 CHAPTER 1, THE CITY OF | | | WEST PALM BEACH AMENDMENTS. | | | ** FLORIDA ADMINISTRATIVE CODE (FAC). | | | ** FLORIDA STATUTES (FS). | | | | | | 1. THERE ARE TWO DIFFERENT SETS OF GAS RISER DIAGRAMS | | | IN THE RESUBMITTAL. ONE THAT IS SIGNED AND SEALED BY | | | JAMES L. MAKO P.E. #54111 USING 1 INCH COPPER PIPE AND | | | ONE BY FLORIDA PUBLIC UTILITIES CO. USING 3/4 INCH PE | | | PIPE UNDERGROUND AND 3/4 INCH SCH. 40 GALV. PIPE ABOVE | | | GROUND. PLEASE NOTE THAT THE SUBMITTED DRAWINGS BY | | | FLORIDA PUBLIC UTILITIES CO. ARE CORRECT IN THAT THEY | | | INDICATE THE ENTIRE GAS SYSTEM PIPING AND BTU LOAD | | | (WHICH IS REQUIRED BY CITY REQUIREMENTS). THE SIGNED | | | AND SEALED PLANS DO NOT INDICATE THIS. PLEASE CORRELATE | | | THE RESUBMITTAL WITH ONLY ONE SET OF GAS RISER | | | DIAGRAMS. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2007-09-14 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-09-14 |
Time |
16:38 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2007-09-14 |
Time |
16:38 |
Sent To |
B |
|
| Notes |
| 2007-09-14 16:52:11 | DENIED | | | REFERENCE: | | | ** FBC-2004 FUEL GAS WITH 2006 REVISIONS. | | | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION | | | REQUIREMENTS. | | | ** FBC-2004 CHAPTER 1, THE CITY OF | | | WEST PALM BEACH AMENDMENTS. | | | ** FLORIDA ADMINISTRATIVE CODE. | | | ** FLORIDA STATUTES. | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | GAS PLAN REVIEW TO MEET CODE COMPLIANCE: | | | | | | 1.SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | NOTE: PLEASE SUBMIT MANUFACTURER SPECIFICATIONS ON THE | | | GENERATOR WITH THE MAKE, MODEL NUMBER, GAS TYPE/BTU | | | LOAD AND A LISTING FROM A NATIONALLY RECOGNIZED TESTING | | | LABORATORY (NRTL) ALSO PLEASE SUBMIT MANUFACTURER | | | SPECIFICATION SHEETS ON THE REGULATOR FOR THE GENERATOR | | | WITH THE MAKE, MODEL NUMBER, BTU LOAD CAACITY AND A | | | LISTING FROM A NATIONALLY RECOGNIZED TESTING LABORATORY | | | (NRTL). | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-10-22 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-10-22 |
Time |
11:08 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-10-22 |
Time |
11:08 |
Sent To |
G |
|
| Notes |
| 2007-10-22 11:08:52 | TO "G" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-10-03 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-10-03 |
Time |
15:52 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-10-03 |
Time |
15:52 |
Sent To |
E |
|
| Notes |
| 2007-10-03 15:52:31 | TO "BTROBAUGH" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-09-17 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-09-17 |
Time |
14:13 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-08-21 |
Time |
09:13 |
Sent To |
|
|
| Notes |
| 2007-08-21 09:13:57 | TO "Z" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2007-08-22 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-08-22 |
Time |
11:19 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2007-08-22 |
Time |
11:19 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2007-08-21 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-08-21 |
Time |
16:51 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-08-21 |
Time |
16:51 |
Sent To |
E |
|
| Notes |