| 2007-09-12 16:59:56 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 FUEL GAS WITH 2006 REVISIONS. |
| | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| | REQUIREMENTS. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE. |
| | ** FLORIDA STATUTES. |
| | |
| | 1. THIS GAS PERMIT CAN NOT BE ISSUED BEFORE THE MASTER |
| | PERMIT #07040733 IS ISSUED. IT HAS PRESENTLY FAILED |
| | PLAN REVIEW TWO (2) TIMES. IT IS SUGGESTED THAT YOU DO |
| | NOT RESUBMIT UNTIL THE MASTER PERMIT HAS BEEN ISSUED. |
| | |
| | 2. THE VALUE OF THE PROPOSED GAS SYSTEM IS WAY TO LOW, |
| | PLEASE KEEP IN MIND THE FOLLOWING ABOUT THE VALUE WHEN |
| | RESUBMITTING. PER FBC-2004, CHAPTER 1, SECTION 108.3, |
| | BUILDING PERMIT VALUATION: IF IN THE OPINION OF THE |
| | BUILDING OFFICIAL, THE CLAIMED VALUATION OF THE |
| | BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, |
| | MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE |
| | UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE |
| | DENIED. FOR |
| | PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS |
| | SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, NORMAL |
| | SITE WORK (EXCAVATION AND BACKFILL FOR BUILDINGS), |
| | ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, |
| | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL |
| | CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT, |
| | MEANS ECT.) WITH REGIONAL ADJUSTMENTS FOR LOCATION AS |
| | PUBLISHED BY INTERNATIONAL CODE |
| | CONGRESS. |
| | NOTE: IF THE MASTER PERMIT DOES NOT REFLECT THE GAS |
| | SYSTEM THEN THE GAS PERMIT MUST REFLECT THE TOTAL COST |
| | OF THE JOB INCLUDING THE APPLIANCES. |
| | |
| | 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2 |
| | NOTE: PLEASE PROVIDE MANUFACTURER CUT SHEETS FOR THE |
| | FOLLOWING APPLIANCES THAT INDICATE THE MAKE, MODEL |
| | NUMBER, BTU'S AND A LISTING FROM A NATIONALLY |
| | RECOGNIZED TESTING LABORATORY. |
| | |
| | A} 80,000 BTU GRILL. |
| | |
| | B} 270,000 BTU RANGE. |
| | |
| | C} 105,000 BTU FRYER |
| | |
| | D} 105,000 BTU FRYER. |
| | |
| | E} 90,000 BTU CANDY POT. |
| | |
| | F} 200,000 BTU OVEN. |
| | |
| | 4. PLEASE CLARIFY WHAT "ON A BLOCK SYSTEM" IS ON THE |
| | RESUBMITTAL. |
| | |
| | 5. PLEASE CEARLY INDICATE ON THE RESUBMITTAL THAT THE |
| | EMERGENCY HOOD SHUT DOWN VALVE (1-1/2" ANSAL VALVE) IS |
| | LOCATED BELOW THE CEILING. |
| | |
| | 6. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | |
| | 7. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES |
| | PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 6.6.1. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL: [email protected] |