Plan Review Details - Permit 07080543
Plan Review Stops For Permit 07080543
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-18 Cont ID  
Sent By tgordon Date 2007-10-18 Time 10:45 Rev Time 0.00
Received By tgordon Date 2007-10-05 Time 10:37 Sent To  
Notes
2007-10-05 10:37:58TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-10-19 Cont ID  
Sent By tgordon Date 2007-10-19 Time 12:19 Rev Time 0.30
Received By tgordon Date 2007-10-19 Time 12:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-10-18 Cont ID  
Sent By tgordon Date 2007-10-18 Time 10:37 Rev Time 0.25
Received By tgordon Date 2007-10-18 Time 10:37 Sent To  
Notes
2007-10-18 10:45:23PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) THE MECHANICAL PLANS NEED THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN, AND
 CONTRACTOR INFORMATION IF APPLICABLE ON THEM, SEE
 W.P.B. AMEND. 106.1.3.
  
 *** BE ADVISED THE ORIGANAL PERMIT WAS FOR REPAIRING
 DUCT WORK NOT TO REPLACE ALL DUCT WORK THAT WOULD MAKE
 THIS A REVISION AND A FEE WILL NEED TO BE PAID.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]