Plan Review Details - Permit 07080520
Plan Review Stops For Permit 07080520
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-08-27 Cont ID  
Sent By rmcdouga Date 2007-08-27 Time 07:40 Rev Time 0.00
Received By rmcdouga Date 2007-08-27 Time 07:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-08-17 Cont ID  
Sent By rmcdouga Date 2007-08-17 Time 10:29 Rev Time 0.00
Received By rmcdouga Date 2007-08-17 Time 10:29 Sent To  
Notes
2007-08-17 11:38:432004 FBC
 REROOF- FLAT
  
 DENIED BY BUILDING
  
 1) SPECIFY WHICH ONE OF THE APPROVED ASSEMBLIES LISTED
 IN THE NOA WILL BE INSTALLED.
  
 2) SPECIFY THE FASTENING OPTION AND CORRESPONDING
 DESIGN PRESSURE THAT WILL BE USED FOR THE ASSEMBLY.
  
 3) THE REQUIRED UPLIFT PRESSURES ARE -59.2 FOR THE
 PERIMETER ROOF AREAS AND -89.0 FOR THE CORNER ROOF
 AREAS. IF THE DESIGN PRESSURES ARE TOO LOW, SEE GENERAL
 LIMITATION #7 ON PAGE 21 OF THE NOA. SUBMIT RAS 117
 CALCULATIONS FOR ENHANCED FASTENING.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]