Plan Review Details - Permit 07080476
Plan Review Stops For Permit 07080476
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-10-09 Cont ID  
Sent By rmcdouga Date 2007-10-09 Time 13:06 Rev Time 0.00
Received By rmcdouga Date 2007-10-09 Time 13:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-09-24 Cont ID  
Sent By rmcdouga Date 2007-09-24 Time 13:26 Rev Time 0.00
Received By rmcdouga Date 2007-09-24 Time 12:36 Sent To  
Notes
2007-09-24 14:55:25FASTENER SPECIFIED ON NOA IS NOT FOR WOOD DECK. CALLED
 MANUFACTURER AND THEY ARE GOING TO CONTACT MIAMI-DADE
 AND GET BACK WITH ME.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-09-05 Cont ID  
Sent By kconrad Date 2007-09-05 Time 16:59 Rev Time 0.00
Received By kconrad Date 2007-09-05 Time 15:28 Sent To B
Notes
2007-09-05 15:52:34MET WITH ROOFER TO DETERMINE IF A ROOF RECOVER WILL
 COMPLY WITH THE FEBC , SECTION 511.3. A ROOF CUT WAS
 TAKEN OF THE EXISTING ROOF SYSTEM AND INDICATED ONE
 ROOF APPLICATION. THE ROOF RECOVER PERMIT MAY BE ISSUED
 UPON APPROVAL BY PLAN REVIEW. ALSO ADVISED THE
 CONTRACTOR THAT A HVAC PERMIT SHALL BE OBTAINED SINCE
 THEEXISTING ROOF EQUIPMENT WILL BE REMOVED AND
 RELOCATED ON STANDS. DETAILS SHALL BE SUBMITTED FOR
 PLAN REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-08-16 Cont ID  
Sent By rmcdouga Date 2007-08-16 Time 19:06 Rev Time 0.00
Received By rmcdouga Date 2007-08-16 Time 19:06 Sent To  
Notes
2007-08-17 07:30:37ROOF OVER/RECOVER DECK
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE CONDITION OF THE EXISTING ROOF WILL BE REQUIRED
 TO BE INSPECTED BY THE CONSTRUCTION SERVICES DEPT.
  
 3) THE FASTENERS SPECIFIED IN THE PRODUCT APPROVAL NOA
 ARE REQUIRED TO BE USED. THEY CAN NOT BE CHANGED BY
 ANYONE EXCEPT MIAMI-DADE PRODUCT CONTROL. SEE PAGE 74
 OF THE NOA.
  
 4) THE APPROVEDASSEMBLY SPECIFIED HAS A DESIGN
 PRESSURE OF -60 PSF WHICH IS TOO LOW FOR THE CORNER
 AREAS THAT REQUIRE -89 PSF. HOWEVER GENERAL LIMITATION
 NUMBER 7 ALLOWS FOR ENHANCED FASTENING TO INCREASE THE
 DESIGN PRESSUREUSING RAS 117 CALCULATIONS. SEE PAGE 85.
 THE NOA REQUIRES THESE CALCULATIONS TO BE DONE BY A
 FLORIDA LICENSED ENGINEER, ARCHITECT OR REGISTERED ROOF
 CONSULTANT. SUBMIT SIGNED AND SEALED RAS 117
 CALCULATIONS.
  
 5)SUBMIT THE FIRST 14 PAGES OF THE NOA WHICH LIST THE
 MATERIALS, FASTENERS, ETC.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-09-24 Cont ID  
Sent By adarroug Date 2007-09-24 Time 08:13 Rev Time 0.00
Received By adarroug Date 2007-09-24 Time 08:13 Sent To B
Notes
2007-09-24 08:14:33TO "RMCDOUGAL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-08-17 Cont ID  
Sent By rmcdouga Date 2007-08-17 Time 07:30 Rev Time 0.00
Received By rmcdouga Date 2007-08-16 Time 10:13 Sent To  
Notes
2007-08-16 10:22:37TO "SHILL" DESK/ROOF