Plan Review Details - Permit 07080456
Plan Review Stops For Permit 07080456
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-10-26 Cont ID  
Sent By rmcdouga Date 2007-10-26 Time 08:37 Rev Time 0.00
Received By rmcdouga Date 2007-10-26 Time 06:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-12 Cont ID  
Sent By rmcdouga Date 2007-09-12 Time 12:50 Rev Time 0.00
Received By rmcdouga Date 2007-09-12 Time 07:04 Sent To  
Notes
2007-09-12 12:47:042004 FBC W/2007 SUPPLEMENT
 LEVEL 2 ALTERATION AND ADDITION
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) SPECIFY THE APPLICABLE CODES AND EDITIONS ON THE
 PLANS. SPECIFY WHICH METHODS OF STRUCTURAL DESIGNARE
 BEING USED FOR THIS PROJECT.
  
 4) SHOW COMPLIANCE WITHR806.1 VENTILATION REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN. VENTILATING OPENINGS SHALL BE
 PROVIDED WITH CORROSION-RESISTANT WIRE MESH, WIT H 1 /
 8 INCH (3.2 MM) MINIMUM TO1/4 INCH (6.4 MM) MAXIMUM
 OPENINGS. SPECIFY THE LOCATIONS AND SIZES OF THE ATTIC
 VENTS.
  
 5) SPECIFY THE SIZE OF THE ATTIC ACCESS AS REQUIRED BY
 FBC R807.1.
  
 6) SPECIFY THE CLADDING THAT WILL BE INSTALLED ON THE
 SOFFITS. IF ALUMINUM, VINYL OR OTHER TYPE OF CLADDING
 REQUIRING PRODUCT APPROVALS IS USED, SUBMIT THEIR
 PRODUCT APPROVALS.
  
 7) PROVIDE A SIDE ELEVATION WITH DIMENSIONS FOR THE
 STEEL COLUMN TOP UNDER WOOD GIRDER #2. THE SECTION THRU
 TRUSS ON SHEET 4 APPEARS TO SHOW THIS COLUMN TOP.
 PLEASE CLARIFY THIS BY LABELING IT TO TIE TO THE ROOF
 FRAMING PLAN. SPECIFY THE WELD TYPE FOR THIS COLUMN
 CAP.
  
 8) THE OWNER/AGENT IS REQUIRED BY FBC CHAPTER 13 TO
 SIGN THE ENERGY CALCULATION FORMS.
  
 9) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 10) SUBMIT PRODUCT APPROVALS FOR THE GLASS BLOCK AND
 THE 8" WIDE LINTELS.
  
 11)THE NOA THAT WAS SUBMITTED FOR THE PGT SINGLE HUNG
 WINDOWS HAS BEEN REVISED BY NOA NO. 07-0322.06. SUBMIT
 CURRENT PRODUCT APPROVAL.
  
 12) PLEASE CIRCLE THE ATTACHMENT METHODS THAT WILL BE
 USED TO INSTALL THE MONIER ROOF TILE ON THE PRODUCT
 APPROVAL NOA. REFER TO SHEET 3 OF THE PLANS.
  
 13) ADDITIONAL FEES OF $ 5.64 ARE DUE TO THE CITY FOR
 RADON FEES.
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-10-10 Cont ID  
Sent By btrobaug Date 2007-10-10 Time 09:14 Rev Time 0.00
Received By btrobaug Date 2007-10-10 Time 07:58 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-08-22 Cont ID  
Sent By btrobaug Date 2007-08-22 Time 13:24 Rev Time 0.00
Received By btrobaug Date 2007-08-22 Time 10:52 Sent To P
Notes
2007-08-22 13:23:55 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} INDICATE IF THE SERVICE IS EXISTING OR PART OF THIS
 APPLICATION.
  
 2} REGARDING SMOKE DETECTORS, SEE R313.1.1 ALTERATIONS,
 REPAIRS AND ADDITIONS.
 WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE
 ALARMS SHALL BE INTERCONNECTED AND HARD WIRED. LOCATE
 ON THE PLANS.ALSO SEE THE DEFINITION OF "SMOKE
 DETECTORS" 11.8.2.1 NFPA-72, CLARIFY IF USING DETECTORS
 OR ALARMS, TO AVOID CONFUSION IN THE FIELD. IF USING
 DETECTORS INDICATE THE LOCATIONS OF THE SOUNDING
 DEVICES.
  
 3} 210.52(A)(2)(2) REQUIRES FLOOR RECEPTACLES IN THE
 DINING ROOM FOR SPACING REQUIREMENTS OF 210.52(A).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-02-01 Cont ID  
Sent By adarroug Date 2008-02-01 Time 15:39 Rev Time 0.00
Received By adarroug Date 2008-02-01 Time 15:39 Sent To M
Notes
2008-02-01 15:39:33TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-04 Cont ID  
Sent By adarroug Date 2007-10-04 Time 10:52 Rev Time 0.00
Received By adarroug Date 2007-10-04 Time 10:52 Sent To Z
Notes
2007-10-04 10:53:08TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-09-12 Cont ID  
Sent By rmcdouga Date 2007-09-12 Time 12:50 Rev Time 0.00
Received By rmcdouga Date 2007-08-15 Time 15:09 Sent To  
Notes
2007-08-15 15:10:10TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-02-04 Cont ID  
Sent By tgordon Date 2008-02-04 Time 08:22 Rev Time 0.25
Received By tgordon Date 2008-02-04 Time 08:22 Sent To  
Notes
2008-02-04 08:23:29REVISION TO MECH. PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-10-25 Cont ID  
Sent By tgordon Date 2007-10-25 Time 08:31 Rev Time 0.25
Received By tgordon Date 2007-10-25 Time 08:31 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-08-17 Cont ID  
Sent By tgordon Date 2007-08-17 Time 12:05 Rev Time 0.30
Received By tgordon Date 2007-08-17 Time 12:05 Sent To E
Notes
2007-08-17 12:18:14PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2005, 2006 REVISIONS, AND CHAPTER
 1 CITY OF WEST PALM BEACH AMENDMENTS.
  
 *** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 2) SHOW ON THE MECHANICAL PLAN EQUIPMENT LISTING THE
 HEATER KW OR IF NO HEAT STATE SO ON PLAN.
  
 3) ELECTRICAL PLAN SHOWS EXHAUST FANS IN THE MASTER
 BATHROOM AND THE MAIN BATHROOM, IF THEY ARE BEING
 INSTALLED SHOW THEM ON THE MECHANICAL PLAN WITH THE
 CFM'S. IF NOT BEING INSTALLED REMOVE FROM ELECTRICAL
 PLAN, SEE RES. R303.3 EXEPT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL: [email protected].

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-10-25 Cont ID  
Sent By jleech Date 2007-10-25 Time 08:04 Rev Time 0.00
Received By jleech Date 2007-10-25 Time 08:04 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-09-11 Cont ID  
Sent By jleech Date 2007-09-11 Time 08:07 Rev Time 0.00
Received By jleech Date 2007-09-11 Time 08:07 Sent To B
Notes
2007-09-11 08:12:44DENIED;
 1.SANITARY RISER DIAGRAM, MASTER SHOWER IS NOT VENTED.
 THE VENT SHOULD BE BETWEEN THE TOILET AND THE SHOWER.
 2. FBC-2004 PLUMBING TABLE 403.1 R-3 MINIMUM FIXTURES
 REQUIRES A AUTOMATIC CLOTHS WASHER.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2007-10-09 Cont ID  
Sent By choops Date 2007-10-09 Time 14:53 Rev Time 0.00
Received By choops Date 2007-10-09 Time 14:53 Sent To E
Notes
2007-10-09 14:54:56***APPROVED - RESUB #1***
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 1 Status F Date 2007-08-16 Cont ID  
Sent By choops Date 2007-08-16 Time 09:25 Rev Time 0.00
Received By choops Date 2007-08-16 Time 09:25 Sent To E
Notes
2007-08-16 09:31:10***FAILED***
  
  
 1)AS THE VALUE OF THE PROPOSED WORK EXCEEDS 50% OF
 THE STRUCTURE'S VALUE LANDSCAPING SHALL BE BROUGHT TO
 COMPLIANCE (IF NOT ALREADY) WITH THE CITY OF WEST PALM
 BEACH ZONING AND LAND DEVELOPMENT REGULATIONS, SECTION
 94-442.PLEASE PROVIDE A LANDSCAPE PLAN INDICATING
 SUCH, WITH A DATA TABLE SHOWING REQUIRED LANDSCAPING
 AND PROVIDED LANDSCAPING.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720


Account Summary | Usage Policy | Privacy Policy