| Plan Review Stops For Permit 07080456 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2007-10-26 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2007-10-26 |
Time |
08:37 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2007-10-26 |
Time |
06:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-09-12 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2007-09-12 |
Time |
12:50 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2007-09-12 |
Time |
07:04 |
Sent To |
|
|
| Notes |
| 2007-09-12 12:47:04 | 2004 FBC W/2007 SUPPLEMENT | | | LEVEL 2 ALTERATION AND ADDITION | | | | | | DENIED BY BUILDING | | | | | | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT | | | MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2) IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY, PLANS STAMPED BY THEM AND | | | COPY OF RECEIPT SUBMITTED TO CITY OF | | | WEST PALM BEACH BUILDING DEPARTMENT, | | | BEFORE A BUILDING PERMIT CAN BE ISSUED. | | | | | | 3) SPECIFY THE APPLICABLE CODES AND EDITIONS ON THE | | | PLANS. SPECIFY WHICH METHODS OF STRUCTURAL DESIGNARE | | | BEING USED FOR THIS PROJECT. | | | | | | 4) SHOW COMPLIANCE WITHR806.1 VENTILATION REQUIRED. | | | ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE | | | CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF | | | RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE | | | SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE | | | ENTRANCE OF RAIN. VENTILATING OPENINGS SHALL BE | | | PROVIDED WITH CORROSION-RESISTANT WIRE MESH, WIT H 1 / | | | 8 INCH (3.2 MM) MINIMUM TO1/4 INCH (6.4 MM) MAXIMUM | | | OPENINGS. SPECIFY THE LOCATIONS AND SIZES OF THE ATTIC | | | VENTS. | | | | | | 5) SPECIFY THE SIZE OF THE ATTIC ACCESS AS REQUIRED BY | | | FBC R807.1. | | | | | | 6) SPECIFY THE CLADDING THAT WILL BE INSTALLED ON THE | | | SOFFITS. IF ALUMINUM, VINYL OR OTHER TYPE OF CLADDING | | | REQUIRING PRODUCT APPROVALS IS USED, SUBMIT THEIR | | | PRODUCT APPROVALS. | | | | | | 7) PROVIDE A SIDE ELEVATION WITH DIMENSIONS FOR THE | | | STEEL COLUMN TOP UNDER WOOD GIRDER #2. THE SECTION THRU | | | TRUSS ON SHEET 4 APPEARS TO SHOW THIS COLUMN TOP. | | | PLEASE CLARIFY THIS BY LABELING IT TO TIE TO THE ROOF | | | FRAMING PLAN. SPECIFY THE WELD TYPE FOR THIS COLUMN | | | CAP. | | | | | | 8) THE OWNER/AGENT IS REQUIRED BY FBC CHAPTER 13 TO | | | SIGN THE ENERGY CALCULATION FORMS. | | | | | | 9) WPB ADMIN CODE 106.3* PRODUCT | | | APPROVALS. THOSE PRODUCT WHICH ARE | | | REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL | | | FOR JURISDICTIONAL APPROVAL. | | | | | | 10) SUBMIT PRODUCT APPROVALS FOR THE GLASS BLOCK AND | | | THE 8" WIDE LINTELS. | | | | | | 11)THE NOA THAT WAS SUBMITTED FOR THE PGT SINGLE HUNG | | | WINDOWS HAS BEEN REVISED BY NOA NO. 07-0322.06. SUBMIT | | | CURRENT PRODUCT APPROVAL. | | | | | | 12) PLEASE CIRCLE THE ATTACHMENT METHODS THAT WILL BE | | | USED TO INSTALL THE MONIER ROOF TILE ON THE PRODUCT | | | APPROVAL NOA. REFER TO SHEET 3 OF THE PLANS. | | | | | | 13) ADDITIONAL FEES OF $ 5.64 ARE DUE TO THE CITY FOR | | | RADON FEES. | | | | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2007-10-10 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-10-10 |
Time |
09:14 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-10-10 |
Time |
07:58 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-08-22 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-08-22 |
Time |
13:24 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-08-22 |
Time |
10:52 |
Sent To |
P |
|
| Notes |
| 2007-08-22 13:23:55 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} INDICATE IF THE SERVICE IS EXISTING OR PART OF THIS | | | APPLICATION. | | | | | | 2} REGARDING SMOKE DETECTORS, SEE R313.1.1 ALTERATIONS, | | | REPAIRS AND ADDITIONS. | | | WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS | | | REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING | | | ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE | | | INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE | | | ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE | | | ALARMS SHALL BE INTERCONNECTED AND HARD WIRED. LOCATE | | | ON THE PLANS.ALSO SEE THE DEFINITION OF "SMOKE | | | DETECTORS" 11.8.2.1 NFPA-72, CLARIFY IF USING DETECTORS | | | OR ALARMS, TO AVOID CONFUSION IN THE FIELD. IF USING | | | DETECTORS INDICATE THE LOCATIONS OF THE SOUNDING | | | DEVICES. | | | | | | 3} 210.52(A)(2)(2) REQUIRES FLOOR RECEPTACLES IN THE | | | DINING ROOM FOR SPACING REQUIREMENTS OF 210.52(A). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2008-02-01 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-02-01 |
Time |
15:39 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-02-01 |
Time |
15:39 |
Sent To |
M |
|
| Notes |
| 2008-02-01 15:39:33 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-10-04 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-10-04 |
Time |
10:52 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-10-04 |
Time |
10:52 |
Sent To |
Z |
|
| Notes |
| 2007-10-04 10:53:08 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-09-12 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2007-09-12 |
Time |
12:50 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2007-08-15 |
Time |
15:09 |
Sent To |
|
|
| Notes |
| 2007-08-15 15:10:10 | TO "SFR" "Z" |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2008-02-04 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-02-04 |
Time |
08:22 |
Rev Time |
0.25 |
| Received By |
tgordon |
Date |
2008-02-04 |
Time |
08:22 |
Sent To |
|
|
| Notes |
| 2008-02-04 08:23:29 | REVISION TO MECH. PLANS. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2007-10-25 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-10-25 |
Time |
08:31 |
Rev Time |
0.25 |
| Received By |
tgordon |
Date |
2007-10-25 |
Time |
08:31 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2007-08-17 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-08-17 |
Time |
12:05 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2007-08-17 |
Time |
12:05 |
Sent To |
E |
|
| Notes |
| 2007-08-17 12:18:14 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2005, 2006 REVISIONS, AND CHAPTER | | | 1 CITY OF WEST PALM BEACH AMENDMENTS. | | | | | | *** DENIED *** | | | 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT | | | ALSO, PER 2004 FBC 13-600.3.ABC.2. | | | | | | 2) SHOW ON THE MECHANICAL PLAN EQUIPMENT LISTING THE | | | HEATER KW OR IF NO HEAT STATE SO ON PLAN. | | | | | | 3) ELECTRICAL PLAN SHOWS EXHAUST FANS IN THE MASTER | | | BATHROOM AND THE MAIN BATHROOM, IF THEY ARE BEING | | | INSTALLED SHOW THEM ON THE MECHANICAL PLAN WITH THE | | | CFM'S. IF NOT BEING INSTALLED REMOVE FROM ELECTRICAL | | | PLAN, SEE RES. R303.3 EXEPT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL: [email protected]. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2007-10-25 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-10-25 |
Time |
08:04 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-10-25 |
Time |
08:04 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-09-11 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-09-11 |
Time |
08:07 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-09-11 |
Time |
08:07 |
Sent To |
B |
|
| Notes |
| 2007-09-11 08:12:44 | DENIED; | | | 1.SANITARY RISER DIAGRAM, MASTER SHOWER IS NOT VENTED. | | | THE VENT SHOULD BE BETWEEN THE TOILET AND THE SHOWER. | | | 2. FBC-2004 PLUMBING TABLE 403.1 R-3 MINIMUM FIXTURES | | | REQUIRES A AUTOMATIC CLOTHS WASHER. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2007-10-09 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-10-09 |
Time |
14:53 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-10-09 |
Time |
14:53 |
Sent To |
E |
|
| Notes |
| 2007-10-09 14:54:56 | ***APPROVED - RESUB #1*** | | | | | | SENT TO "E" - BT |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2007-08-16 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-08-16 |
Time |
09:25 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-08-16 |
Time |
09:25 |
Sent To |
E |
|
| Notes |
| 2007-08-16 09:31:10 | ***FAILED*** | | | | | | | | | 1)AS THE VALUE OF THE PROPOSED WORK EXCEEDS 50% OF | | | THE STRUCTURE'S VALUE LANDSCAPING SHALL BE BROUGHT TO | | | COMPLIANCE (IF NOT ALREADY) WITH THE CITY OF WEST PALM | | | BEACH ZONING AND LAND DEVELOPMENT REGULATIONS, SECTION | | | 94-442.PLEASE PROVIDE A LANDSCAPE PLAN INDICATING | | | SUCH, WITH A DATA TABLE SHOWING REQUIRED LANDSCAPING | | | AND PROVIDED LANDSCAPING. | | | | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING | | | TECHNICIAN | | | (561)805-6720 |
|
|