Plan Review Details - Permit 07080451
Plan Review Stops For Permit 07080451
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-10-03 Cont ID  
Sent By mjacobs Date 2007-10-03 Time 06:56 Rev Time 0.00
Received By mjacobs Date 2007-10-03 Time 05:59 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-08-31 Cont ID  
Sent By mjacobs Date 2007-08-31 Time 10:03 Rev Time 0.00
Received By mjacobs Date 2007-08-31 Time 06:49 Sent To  
Notes
2007-08-31 10:03:17BUILDING PLAN REVIEW
 PERMIT:
 ADD:
 CONT:
 TEL: (561)###-####
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 2)2004 FBC EXISTING
 301.5A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 3)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR RECORD KEEPING
 A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT
 IS DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM ISPROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 . -------------------------------------
 ) NUMBER OF UNITS
 ) NUMBER OF FLOORS
 ) NUMBER OF ROOMS
 ) NUMBER OF BEDROOMS
 ) SQ. FT. LIV SPACE/ FL
 ) SQ. FT. FOOTPRINT
  
 4))PROVIDE A DETAIL DRAWING OF EACH TYPE OF WALL
 CORRESPONDING WITH THE WALL LEGEND. THE DRAWINGS SHALL
 INDICATE ALL MATERIALS FOR THE CONSTRUCTION OF EACH
 WALL.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-05-13 Cont ID  
Sent By btrobaug Date 2008-05-13 Time 13:06 Rev Time 0.00
Received By btrobaug Date 2008-05-13 Time 11:29 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-09-28 Cont ID  
Sent By dpalmer Date 2007-09-28 Time 18:36 Rev Time 0.00
Received By dpalmer Date 2007-09-28 Time 18:36 Sent To  
Notes
2007-09-28 18:37:11** PROVISO/REVISION NEEDED **
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEWS ARE
 STILL IN NEED OF ADDRESSING.
 THE *PROVISO* WILL REQUIRE THESE ITEMS TO BE REVISED ON
 PLANS ALONG WITH ANY OTHER REVISIONS DONE ON THE
 PROJECT.
 ** IF PLANS COME BACK WITH ANY OTHER COMMENTS, PLEASE
 MAKE CORRECTIONS AT THIS TIME. THIS WILL HELP TO AVOID
 ANY REVISION FEES AT A LATER DATE.
  
 1) NOTE: PLEASE SEE COMMENTS FROM PREVIOUS REVIEW WHICH
 REQUESTED THE ARC FAULT PROTECTED CIRCUITS TO BE LISTED
 ON PANEL SCHEDULE FOR ROOMS AND AREAS IN WHICH THEY
 FEED.
 PLANS ARE REQUIRED TO SHOW DETAILED CODE COMPLIANCE.
 QUOTING THE CONTRACTOR IS RESPONSIBLE TO PROVIDE AFCI
 BREAKERS IS NOT SHOWING CODE COMPLIANCE AS REQUIRED PER
 FLORIDA STATUTES 553.73
 NEC 210.12 AND FBC 106.3.5.1.2, 106.1.2, 110.1.2
  
 2) NOTE: PLEASE SEE AS NOTED ON PREVIOUS REVIEW; PLEASE
 SEE THE AMPERAGE LOAD SHOWN ON THE PANEL SCHEDULE CAN
 NOT POSSIBLY BE THE 2KVA AS LISTED ON LOAD
 CALCULATIONS.
 PLEASE RE-CALCULATE AS 2KVA DIVIDED BY THE VOLTAGE DOES
 NOT EQUATE TO THE AMPERAGE AS LISTED ON PANEL SCHEDULE.
  
  
 3) NOTE: PLEASE SEE CIRCUIT NUMBER 21 WHICH IS PART OF
 210.52B1, HOWEVER BASED ON THE AMPERAGE SHOWN ON PANEL
 SCHEDULE THIS DOES NOT MEET THE MINIMUM LOAD AS
 REQUIRED PER 210.11C1 AND 220.53
  
 4) NOTE: PLEASE SEE PANEL SCHEDULE CIRCUIT #14 WHICH
 STILL INDICATES SMOKE DETECTORS WHEN PLANS SHOW SMOKE
 ALARMS. THIS COMMENT IS MINOR AND WAS REDLINED ON
 PLANS.
 THIS CAN BE REVISED WHEN REVISING PLANS FOR OTHER ITEMS
 AS THIS SEEMS TO BE A MISPRINT.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-08-27 Cont ID  
Sent By dpalmer Date 2007-08-27 Time 20:14 Rev Time 0.00
Received By dpalmer Date 2007-08-27 Time 20:14 Sent To  
Notes
2007-08-27 20:14:472007-08-27 20:14:47
  
 ** DENIED **
  
 1) NOTE: PLEASE SEE THE SMOKE DEVICES AS SHOWN ARE
 BEING INDICATED AS SD, WHERE THE PLANS ALSO CALL FOR
 THESE AS 120V UNITS. IF THESE ARE DEVICES WHICH DETECT
 AND SOUND AN ALARM, THEY ARE IN FACT SMOKE ALARMS (SA)
 AND NOT SMOKE DETECTORS. PLEASE SEE NFPA-72 DEFINITIONS
 AS THE SD ONLY DETECT AND DO NOT PROVIDE AN AUDIBLE
 ALARM.
 PLEASE SEE NFPA-72 11.8.3 WHICH REQUIRES ALL SMOKE
 DETECTION DEVICES TO BE A MINIMUM OF 20FT AWAY FROM
 COOKING APPLIANCES. THERE IS AN EXCEPTION TO THIS AS
 LONG AS ONE OF TWO SPECIFIC TYPES OF UNITS IS
 INSTALLED. PLEASE SPECIFY
 PLEASE ADJUST.
  
 2) NOTE: PLEASE SEE THE REQUIRED DEDICATED BATH CIRCUIT
 FOR THE GFI IS BEING SHOWN ON THE SAME CIRCUIT AS THE
 SMOKE DETECTION DEVICES WHICH ARE NOT PERMITTED. PLEASE
 SEE 210.52D,210.11C3.
 (MUST BE 20AMP AND #12).
  
 3) NOTE: PLEASE SEE THE MISSING LOAD TO BE FIGURED IN
 THE LOAD CALCULATIONS FOR THE DINING ROOM RECEPTACLES
 PER 210.52B1, 210.11C1, AND 220.53.
 (1500VA MIN)
  
 4) NOTE: PLEASE SEE THERE ARE SEVERAL ITEMS ON THE LOAD
 CALCULATIONS WHICH DO NOT MATCH WITH THE AMPERAGE LOADS
 BEING SHOWN ON THE PANEL SCHEDULE.
 FOR EXAMPLE:
 PLEASE SEE THE MICROWAVE/HOOD ON SCHEDULE SHOWS
 13.5AMPS. THIS AT 120V IS MUCH HIGHER THAN THE 900VA
 SHOWN ON THE LOAD CALCULATIONS.
 THIS IS THE SAME FOR OTHER LOADS SUCH AS WINE COOLER
 JACUZZI ETC.
 PLEASE SEE THE LOAD FOR THE A/C CAN NOT POSSIBLY BE THE
 2KVA AS SHOWN ON LOAD CALCULATIONS WITH AN AMPERAGE
 LOAD OF 18.8AMPS.
 PLEASE SEE SOME LOADS ON THE LOAD CALCULATIONS ARE TO
 COORDINATE WITH THE LOADS ON PANELS.
 NEC 220, 408.4, 240.4, 310.16 TO DETERMINE CIRCUITS.
 FBC 106.3.5.4
 106.1.2, 106.1.1
  
 5) NOTE: PLEASE LIST THE REQUIRED ARC FAULT PROTECTED
 CIRCUITS PER 210.12. 408.4
 THIS IS REQUIRED FOR ALL OUTLETS, INCLUSIVE OF SMOKE
 DEVICES (120V), RECEPTACLES, LIGHTS, FANS ETC.
  
 6) NOTE: PLEASE SEE MISSING GFI RECEPTACLE ALONG
 KITCHEN COUNTER SPACE WHICH IS REQUIRED PER 210.52C1,
 210.8A6.
 THE PLANS STATE A SCALE OF 3/8 INCH PER FT, AND BASED
 ON THE LENGTH OF COUNTER SPACE ALONG WALL NEAR LIVING
 ROOM, AN ADDITIONAL GFI IS NEEDED
  
 7) NOTE: PLEASE SEE ANY RECEPTACLES WITHIN 6FT OF WET
 BAR SINKS ARE REQUIRED TO BE GFIOR GFI PROTECTED PER
 210.8A7 (DINING ROOM)
  
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-10-01 Cont ID  
Sent By mawillia Date 2007-10-01 Time 11:59 Rev Time 0.00
Received By mawillia Date 2007-10-01 Time 11:48 Sent To  
Notes
2007-10-01 11:55:05*****APPROVED*****
  
  
 PLAN SHEETS A-1 AND E-1 WERE STAMPED, INITIALED, AND
 DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2007-08-30 Cont ID  
Sent By mawillia Date 2007-08-30 Time 12:41 Rev Time 0.00
Received By mawillia Date 2007-08-30 Time 12:01 Sent To  
Notes
2007-08-30 12:41:46*****PROVISO*****
  
  
 THE APPROPIATE PLAN SHEET(S) TO BE FIRE-STAMPED WHEN
 THE OTHER REVIEWERS HAVE BEEN SATISFIED.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-05-27 Cont ID  
Sent By adarroug Date 2008-05-27 Time 14:55 Rev Time 0.00
Received By adarroug Date 2008-05-27 Time 14:55 Sent To M
Notes
2008-05-27 14:58:07TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-05-08 Cont ID  
Sent By adarroug Date 2008-05-08 Time 16:48 Rev Time 0.00
Received By adarroug Date 2008-05-08 Time 16:48 Sent To  
Notes
2008-05-08 16:48:35TO "BOB"#7

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-09-18 Cont ID  
Sent By adarroug Date 2007-09-18 Time 15:25 Rev Time 0.00
Received By adarroug Date 2007-09-18 Time 15:25 Sent To  
Notes
2007-09-18 15:25:20WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-09-10 Cont ID  
Sent By jleech Date 2007-09-10 Time 10:09 Rev Time 0.00
Received By jleech Date 2007-08-15 Time 13:34 Sent To  
Notes
2007-08-27 13:55:22TO "BOB"#17
2007-08-15 13:36:26WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-05-28 Cont ID  
Sent By tgordon Date 2008-05-28 Time 08:43 Rev Time 0.30
Received By tgordon Date 2008-05-28 Time 08:43 Sent To  
Notes
2008-05-28 08:44:06REVISION TO MECH. PLAN PAGE M-1.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-05-09 Cont ID  
Sent By tgordon Date 2008-05-09 Time 14:12 Rev Time 0.30
Received By tgordon Date 2008-05-09 Time 14:12 Sent To  
Notes
2008-05-09 14:13:11REVISION TO MECH. PLAN M-1.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-08-30 Cont ID  
Sent By tgordon Date 2007-08-30 Time 14:03 Rev Time 0.25
Received By tgordon Date 2007-08-30 Time 14:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-05-12 Cont ID  
Sent By jleech Date 2008-05-12 Time 08:39 Rev Time 0.00
Received By jleech Date 2008-05-12 Time 08:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2007-09-10 Cont ID  
Sent By jleech Date 2007-09-10 Time 10:07 Rev Time 0.00
Received By jleech Date 2007-09-10 Time 10:07 Sent To  
Notes
2007-09-10 10:09:10PLUMBING FIXTURE CHANGE OUT. WATER TEST REQUIRED FOR
 SHOWER AND TUB.

Review Stop Z ZONING
Rev No 1 Status N Date 2007-08-27 Cont ID  
Sent By choops Date 2007-08-27 Time 15:19 Rev Time 0.00
Received By choops Date 2007-08-27 Time 15:19 Sent To  
Notes
2007-08-27 15:19:56*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.