| | ** DENIED 2ND REVIEW** |
| | |
| | ** PLEASE SEE NOTES FROM PREVIOUS REVIEW. |
| | |
| | 1) NOTE: AS STATED ON PREVIOUS REVIEW, ALL CURRENT |
| | RELEVANT CODES SHALL BE STATED ON PLANS. |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2004 FBC W/2006 REVS. |
| | |
| | 2) NOTE: THE VALUE WAS CHANGED ON PERMIT APPLICATION |
| | PER RE-SUB COVER SHEET. THIS WAS NOT CHANGED ON |
| | APPLICATION BY CONTRACTOR ONLY ON RE-SUB COVER SHEET. |
| | ** THIS IS NOTED FOR INFORMATIONAL PURPOSE TO |
| | CONTRACTOR ONLY. |
| | |
| | 3) NOTE: PLEASE SEE CIRCUITING ON PANEL SCHEDULE |
| | SUBMITTED IS NOT ACCEPTABLE USING *GENERAL LIGHTS* AND |
| | *RECEPTACLES*. |
| | PLEASE SEE 408.4 AND THE FOLLOWING TEXT EXTRACTED FROM |
| | COMMENTARY. |
| | *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE |
| | THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| | PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| | THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| | CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| | AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| | BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| | DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| | CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| | ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| | ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR |
| | RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT |
| | OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| | ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT |
| | PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| | SECTION.* |
| | 408.4, 310.16, 240.4 ETC |
| | FBC 106.3.5.4, FBC 106.1.2 |
| | |
| | 4) NOTE: PLEASE SEE NFPA-72 FOR DEFINITIONS OF SMOKE |
| | DETECTION DEVICES. THESE ARE SHOWN AS SD FOR SMOKE |
| | DETECTORS. IF THESE ARE SMOKE DETECTORS BY DEFINITION, |
| | PLEASE INCLUDE SYSTEM WHICH INCLUDE FIRE ALARM PANEL, |
| | HORN DEVICES ETC. |
| | IF THESE ARE SMOKE ALARMS WHICH DETECT AND SOUND AND |
| | ALARM, PLEASE ADJUST TO SA. |
| | PLEASE ALSO SEE THE STUDY WHICH IS AN ADAPTABLE |
| | SLEEPING ROOM IS REQUIRED TO CONTAIN SMOKE DETECTION |
| | DEVICE INSIDE AND OUTSIDE THIS ROOM. |
| | NFPA-72 , 11.5.1.1.1, 11.8.3 |
| | |
| | 5) NOTE: PLEASE CLARIFY 210.12 FOR ARC FAULT |
| | PROTECTION. PLEASE LIST. |
| | |
| | 6) NOTE: RISER INDICATES *OPTIONAL* FOR REQUIRED |
| | ELECTRICAL CODE ITEMS. |
| | PLANS MAY NOT CONTAIN *OPTIONAL* FOR FINAL RECORD SETS |
| | OF DRAWINGS. THE DOCUMENT MUST SHOW AN ACCURATE RECORD |
| | OF WORK DONE/INSTALLED. |
| | FBC 106.1.2, 106.5, 110.1.2 ETC. |
| | |
| | 7) NOTE: PLEASE ALSO THE EQUIPMENT GROUNDING CONDUCTOR |
| | IS LISTED AS *OPTIONAL* BEFORE AND AFTER MAIN. PLEASE |
| | SEE 250.6, 250.24B AS AN EQUIPMENT GROUNDING CONDUCTOR |
| | IS REQUIRED AFTER THE FIRST MEANS OF DISCONNECTAND |
| | SHALL NOT BE INSTALLED BEFORE THE FIRST MEANS OF |
| | DISCONNECT. |
| | |
| | 8) NOTE: PLANS SHOW HOT WATER HEATER AS BEING PLUGGED |
| | IN WHICH IS NOT PERMITTED. |
| | 422.30, 422.31 |
| | |
| | 9) NOTE: PLEASE SEE 210.8A6 AS ALL RECEPTACLES SERVING |
| | KITCHEN COUNTER SPACE SHALL BE GFI. |
| | |
| | 10) NOTE: PLEASE BE SURE PLANS ARE DETAILED TO ALL |
| | ITEMS WHICH ARE GOING TO BE NEW AND WHICH ARE GOING TO |
| | REMAIN AS EXISTING. AS THE SCOPE OF WORK APPEARS THE |
| | ENTIRE HOUSE IS BEING REWIRED, MUST COMPLY WITH CURRENT |
| | NEC 2005 ETC AS NOTED ABOVE. |
| | THERE ARE ITEMS WHICH COULD NOT BE COMMENTED ON AS THE |
| | SCOPE OF WORK IS NOT CLEARLY DEFIED. |
| | |
| | 11) NOTE: PLEASE INCLUDE THE TYPE OF RECESSED LIGHTING |
| | FIXTURES TO MEET FBC 13-606.1.ABC.1.2.4 |
| | |
| | 12) NOTE: PLEASE SEE THERE ARE SYMBOLS ON PLANS WHICH |
| | ARE NOT ON ELECTRICAL SYMBOL LEGEND. PLEASE COORDINATE |
| | AND COMPLETE. |
| | FOR EXAMPLE: RECESSED LIGHTS, WATER HEATER ETC. FBC |
| | 106.1.2 ADDITIONAL INFORMATION/COORDINATION. |
| | |
| | 13) NOTE: PANEL SCHEDULE INDICATES A SPRINKLER PUMP |
| | HOWEVER THERE IS NO PUMP AND DISCONNECT ON PLANS. |
| | PLEASE SHOW. FBC 106.1.2, 106.3.5.4 |
| | |
| | 14) NOTE: PLEASE SEE THERE ARE SEVERAL CIRCUITS ON |
| | PANEL SCHEDULE WHICH SHOW #2 FOR THE WIRE SIZE. THIS |
| | APPEARS TO BE A MISPRINT FOR #12? |
| | 408.4, 310.16, FBC 106.1.2, 106.3.5.4 |
| | |
| | 15) NOTE: PLEASE SEE MISSING RECEPTACLE(S) ALONG |
| | COUNTER SPACE AS REQUIRED PER 210.52C1 (DISHWASHER |
| | COUNTER). |
| | |
| | 16) NOTE: PLEASE SEE MISSING RECEPTACLE(S) PER 210.52. |
| | |
| | 2FT OR MORE OF WALL SPACE. |
| | |
| | 17) NOTE: PLEASE SEE NEC 220 AS THE HEAT LOAD ON |
| | CALCULATIONS MENTIONS TO BE DONE AT 100 PERCENT OR 40 |
| | PERCENT. WHERE DOES THE CODE PERMIT THIS TO BE DONE AT |
| | 40 PERCENT FOR THIS DWELLING UNIT FOR ONE A/C SYSTEM? |
| | PLEASE SEE 220, 220.60, 220.80 ETC. |
| | |
| | 18) NOTE: PLEASE SEE 210.70 AND LS 101 7.8 AS A LIGHT |
| | FIXTURE OF SOME TYPE WILL BE REQUIRED AT THE REAR |
| | EGRESS. |
| | |
| | 19) NOTE: PLEASE SEE 210.52B1, 210.11C1, 220.53 AS THE |
| | NOOK RECEPTACLES SHALL BE PART OF ONE OR *MORE* OF THE |
| | SMALL APPLIANCE CIRCUITS. THIS AREA IS THE SAME AS THE |
| | DINING ROOM WHICH INDICATES THE ADDITIONAL CIRCUIT WITH |
| | LOAD AT 1500VA. |
| | |
| | |
| | ** AS THERE ARE SOME ITEMS NOT YET ON PLANS AND OR |
| | SHOWN THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW |
| | WHICH CAN NOT BE MADE AT THIS TIME. |
| | |
| | IF THERE ARE ANY QUESTIONS, PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |