Plan Review Details - Permit 07080406
Plan Review Stops For Permit 07080406
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2008-02-12 Cont ID  
Sent By lursu Date 2008-02-12 Time 08:05 Rev Time 0.00
Received By lursu Date 2008-02-12 Time 08:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-12-10 Cont ID  
Sent By jwitmer Date 2008-12-10 Time 08:38 Rev Time 1.11
Received By jwitmer Date 2008-12-10 Time 08:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-10-07 Cont ID  
Sent By jwitmer Date 2008-10-07 Time 08:44 Rev Time 3.33
Received By jwitmer Date 2008-10-07 Time 08:44 Sent To  
Notes
2008-10-07 08:49:05BUILDING PLAN REVIEW
 PERMIT: 07080406
 ADD: 2027 SPRUCE
 CONT: JAW CONSTRUCTION
 TEL: (561)333-6738
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW TUES OCT 07/08
 ACTION: DENIED
  
 1) PLANS APPEAR TO BE CODE COMPLIANT, WILL NEED TO GO
 TO PALM BEACH COUNTY BUILDING DEPARTMENT FOR REVIEW FOR
 IMPACT FEES (ASSEMBLY OCCUPANCY). ONCE PLANS ARE
 REVIEWED AND STAMPED FOR IMPACT FEES
 THE BUILDING REVIEW WILL BE CHANGED TO A PASS, THIS
 DOES NOT CONSTITUTE AS ANOTHER REVIEW.
  
 BUILDING PLAN REVIEW
 PERMIT: 07080406
 ADD: 2027 SPRUCE
 CONT: JAW CONSTRUCTION
 TEL: (561)333-6738
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-04-22 Cont ID  
Sent By jwitmer Date 2008-04-22 Time 16:25 Rev Time 2.22
Received By jwitmer Date 2008-04-22 Time 16:25 Sent To  
Notes
2008-04-22 16:25:40BUILDING PLAN REVIEW
 PERMIT: 07080406
 ADD: 2027 SPRUCE
 CONT: JAW CONSTRUCTION
 TEL: (561)333-6738
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1-6) COMPLIED.
  
 7) 3RD REQUEST, ROOFING SYSTEMS- THE SUB-SYSTEM
 HIGHLIGHTED ON PAGES 14-15 LIST A MAXIMUM DESIGN
 PRESSURE OF -45 WITH LIMITATION# 7. NOTE UNDER
 LIMITATION# 7 DOES ALLOW ENHANCED FASTENING IN ZONES 2
 & 3 TO THE CALCULATION RAS 117. PLEASE HAVE YOUR DESIGN
 PROFESSIONAL PROVIDE THE RAS 117 FOR THE ENHANCED
 FASTENING IN ZONES 2& 3.
 FIRST OFF THE PROBLEM WITH THE LETTER FROM TURQUOISE
 ENGINEERING IS THIS IS A COPY NOT AN ORIGINAL SIGNED
 AND SEALED ORIGINAL. THE SECOND ISSUE WITH THE PROPERTY
 BEING IN EITHER A "B" ZONE OR "C" ZONE, YES I DID STATE
 THIS PROPERTY LIES IN A "B" ZONE BUT THE ENGINEER OF
 RECORD WOULD NEED TO CHANGE THEIR PLAN TO INDICATE A
 "B" ZONE. SHEET S100 THE STRUCTURAL DESIGNER OR
 ENGINEER JOSE A TOLEDO HAS ELECTED TO DESIGN THIS
 BUILDING TO A MORE RESTRICTIVE "C" ZONE WITH THE HIGHER
 ASSCIATED PRESSURES. MR. TOLEDO HAS ALSO USED THE
 HIGHER "C" VALUES FOR THE MOMENT OF OVER TURNING FOR
 THE CALCULATIONS FOR THE A/C UNITS. PLEASE EITHER HAVE
 THE DESIGN PROFESSIONAL IN CHARGE OF THE PROJECT CHANGE
 FROM THE CZONE AND ASSOCIATED PRESSURES OR PROVIDE RAS
 117 CALCYULATIONS FOR THE "C" ZONE. NOTE ALSO INEITHER
 CASE IF ANOTHER ENGINNER IS BROUGHT IN FOR THE ROOFING
 APPROVALS, THE ENGINEER OF RECORD WILL NEED TO REVIEW
 THE DESIGN AND CALCULATIONS BEFORE SUBMITTING TO THE
 BUILDING DEPARTMENT.
  
 8) 3RD REQUEST, SEMI-COMPLIED: HURRICANE SHUTTERS,
 SEMI- COMPLIED. PLEASE SEE THE ADDTIONAL INFORMATION
 THAT IS REQUIRED FOR USE OF STORM PANELS. A SAMPLE OF
 AN INSTALLATION SCHEDULE IS ATTACHED.
 NOTE MANY OF THE WINDOWS SUBMITTED ARE A FIN TYPE
 WINDOW THAT WILL REQUIRE THE STORM SHUTTERS TO BE SET
 AWAY FROM THE GLAZING BECAUSE OF THE DEFLECTION OF THE
 STORM PANEL DURING A HIGH WIND EVENT. HIGHLIGHT OR
 CIRCLE WHICH TYPE OF INSTALLATION WILL BE USED AND TYPE
 OF FASTENERS.
  
 PROVIDE STORM PANEL INFORMATION WITH INSTALLATION
 SCHEDULE AND KEY PLAN WITH SPECIFIC ANCHORS AND
 MOUNTING TO BE USED FOR ALL NON-IMPACT GLAZING. FBC
 1609.1.4. FL BLD CODE 2004 SECTION 106.3.3, 1609.1.4,
 1714.5.1 & EXIST BUILD CODE 507.3. PROCEDURES: 1(B) A
 COMPLETE INSTALLATION SCHEDULE SUMMARIZING &
 IDENTIFYING OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM BAR REINFORCING
 REQUIREMENTS, WALL PRESSURE ZONES, SLAT TYPES, ETC.,
 SHALL BE SUBMITTED AT TIME OF PERMIT APPLICATION TO
 FACILITATE PLAN REVIEW AND PERMIT ISSUANCE.
  
 9-21) COMPLIED.
  
 22) AGAIN SEE ELECTRICAL COMMENTS ABOUT THE ENERGY
 CALCULATIONS.
  
 23-25) COMPLIED.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.)
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-02-14 Cont ID  
Sent By jwitmer Date 2008-02-14 Time 16:46 Rev Time 3.33
Received By jwitmer Date 2008-02-14 Time 16:46 Sent To  
Notes
2008-02-14 16:47:33BUILDING PLAN REVIEW
 PERMIT: 07080406
 ADD: 2027 SPRUCE
 CONT: JAW CONSTRUCTION
 TEL: (561)333-6738
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B) INFORMATIONAL,PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C)INFORMATIONAL,106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2007 SUPPLEMENTS. PLEASE INCORPORATE
 INTO PLAN DATA.
  
 2-5)COMPLIED FROM FIRST REVIEW.
  
 6) SEMI-COMPLIED. PLANS A302 INDICATE THE USE OF 1 HOUR
 FIRE RATED WINDOW SYSTEMS AT THE EXTERIOR STAIRS. THERE
 HAS BEEN NO PRODUCT APPROVAL INFORMATION SUBMITTED FOR
 THE FIRE RATED WINDOWS, NOTE THESE WINDOW WILL REQUIRE
 STORM SHUTTERS THE MANUFACTURERS DO NOT MAKE A FIRE
 RATED LARGE MISSLE RATED ASSEMBLY.
  
 7) ROOFING SYSTEMS- THE SUB-SYSTEM HIGHLIGHTED ON PAGES
 14-15 LIST A MAXIMUM DESIGN PRESSURE OF -45 WITH
 LIMITATION# 7. NOTE UNDER LIMITATION# 7 DOES ALLOW
 ENHANCED FASTENING IN ZONES 2 & 3 TO THE CALCULATION
 RAS 117. PLEASE HAVE YOUR DESIGN PROFESSIONAL PROVIDE
 THE RAS 117 FOR THE ENHANCED FASTENING IN ZONES 2& 3.
  
 8) HURRICANE SHUTTERS, SEMI- COMPLIED. PLEASE SEE THE
 ADDTIONAL INFORMATION THAT IS REQUIRED FOR USE OF STORM
 PANELS.PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH SPECIFIC
 ANCHORS AND MOUNTING TO BE USED FOR ALL NON-IMPACT
 GLAZING. FBC 1609.1.4.FL BLD CODE 2004 SECTION
 106.3.3, 1609.1.4, 1714.5.1 & EXIST BUILD CODE 507.3.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION SCHEDULE
 SUMMARIZING & IDENTIFYING OPENING SIZES, STORY HEIGHTS,
 UNIT MARK NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM BAR
 REINFORCING REQUIREMENTS, WALL PRESSURE ZONES, SLAT
 TYPES, ETC., SHALL BE SUBMITTED AT TIME OF PERMIT
 APPLICATION TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 9-21) COMPLIED.
  
 22) PLEASE SEE ELECTRICAL NOTES ON ENERGY
 CALCULATIONS.
  
 NEW COMMENTS
  
 23)2-29-08 COMPLIED. EXCEPTION TO 302.3.2 FOR FIRE
 SPRINKLERS 1 HR REDUCTION BUT NOT LESS THAN 1 HR.OK
  
 24) SHOWER STALLS- 11-4.23.2 DOORS SHALL NOT SWING INTO
 THE CLEAR FLOOR SPACE REQUIRED FOR FIXTURES. THE MAIN
 DOOR TO THE RESTROOM OVERLAYS THE CLEAR FLOOR SPACE
 REQUIRED FORTHE SHOWER.
  
 25) 11-4.13.7 DOORS IN SERIES PLEASE REVIEW THE
 RESTROOM ENTRY DOOR AND THE ACCESSIBLE STALL DOOR.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-21 Cont ID  
Sent By jjohnsto Date 2007-09-21 Time 13:04 Rev Time 4.00
Received By jjohnsto Date 2007-09-21 Time 8:00 Sent To  
Notes
2007-09-21 13:07:55CONSTRUCTION SERVICES DEPARTMENT
 200 SECOND STREET, 3RD FLOOR, WEST PALM BEACH,
 FLORIDA33401
 TEL:561-805-6713FAX:
 561-805-6731
  
 JAMES JOHNSTON, PERMIT NO 07080406
 BUILDING PLAN EXAMINERII PROJECT MASONIC LODGE
 E-MAIL:JJOHNSTON @WPB.ORG ADDRESS 2027 SPRUCE
 AVENUE
  CONTRACTOR WPB HOUSING AUTHORITY
  DATE SEPTEMBER 19, 2007
  
  
 STRUCTURALPLANREVIEW
  
  
  
  FBC 1604.5 IMPORTANCE FACTOR.
 1 THE VALUE FOR WIND LOAD IMPORTANCE FACTOR SHALL BE
 DETERMINED IN ACCORDANCE WITH TABLE 1604.5 .
 COMMENT -IDENTIFY WIND IMPORTANCE FACTOR SHEET CS100
  
 2 FBC CHAPTER 3IDENTIFY RESIDENTIAL OCCUPANCYR-3
  
 COMMENT- IDENTIFY OCCUPANCIES ON CS100R-3 AND A-3
  
 3 FBC1004.1 DESIGN OCCUPANT LOAD.
 IN DETERMINING MEANS OF EGRESS REQUIREMENTS, THE NUMBER
 OF OCCUPANTS FOR WHOM MEANS OF EGRESS FACILITIES SHALL
 BE PROVIDED SHALL BE ESTABLISHED BY THE LARGEST NUMBER
 COMPUTED IN ACCORDANCE WITH SECTIONS 1004.1.1 THROUGH
 1004.1.3 .
 COMMENT-ASSEMBLY -CHAIRS ONLY 116 OCCUPANTS
  
 4 FBC1004.3 POSTING OF OCCUPANT LOAD.
 EVERY ROOM OR SPACE THAT IS AN ASSEMBLY OCCUPANCY SHALL
 HAVE THE OCCUPANT LOAD OF THE ROOM OR SPACE POSTED IN A
 CONSPICUOUS PLACE, NEAR THE MAIN EXIT OR EXIT ACCESS
 DOORWAY FROM THE ROOM OR SPACE. POSTED SIGNS SHALL BE
 OF AN APPROVED LEGIBLE PERMANENT DESIGN AND SHALL BE
 MAINTAINED BY THE OWNER OR AUTHORIZED AGENT.
 COMMENT -IDENTIFY SIGNAGE IN AREA OF OCCUPANT LOAD
  
 5. 1.3.3 LOCATION OF ROOF INSULATION.
 THE ROOF INSULATION SHALL NOT BE INSTALLED ON A
 SUSPENDED CEILING WITH REMOVABLE CEILING PANELS.
 THIS IS LOCATED IN THE FBC ENERGY REQUIREMENTS.SHEET
 A-400DETAIL 1-A 400 SUGGEST THIS AS AN OPTION
  
 6. WINDOW SCHEDULE
 PLEASE NOTE ON SHEET A-500 WINDOW SCHEDULE THE IMPACT
 WINDOW DESIGNATION VS. THE NON-IMPACT DESIGNATION
  
  
  
  
  
 PRODUCT APPROVALS
  
 7 ROOF SYSTEM PRODUCT APPROVAL
 COMMENT -HIGHLIGHT THE COMPONENTS TO BE USED IN THIS
 SYSTEM
  
 8 HURRICANE SHUTTER PRODUCT APPROVAL
 COMMENT -APPROVAL EXPIRED AUGUST 22, 2007
  
 9 WINDOW PRODUCT APPROVAL
 PGT INDUSTRIESALUMINUM FIXED WINDOW
 COMMENT -APPROVAL WILL EXPIRE OCTOBER 3, 2007
  
  
 FBCEXISTING CHAPTER 2 ? DEFINITION WORK AREA.
 THAT PORTION OR PORTIONS OF A BUILDING CONSISTING OF
 ALL RECONFIGURED ELEMENTS, SYSTEMS OR SPACES AS
 INDICATED ON THE CONSTRUCTION DOCUMENTS. WORK AREA
 EXCLUDES OTHER PORTIONS OF THE BUILDING WHERE
 INCIDENTAL WORK ENTAILED BY THE INTENDED WORK MUST BE
 PERFORMED AND PORTIONS OF THE BUILDING WHERE WORK NOT
 INITIALLY INTENDED BY THE OWNER IS SPECIFICALLY
 REQUIRED BY THIS CODE.
  
 10 FBCEXISTING605.4.3 DOOR CLOSING.
 IN ANY WORK AREA, ALL DOORS OPENING ONTO AN EXIT
 PASSAGEWAY AT GRADE OR AN EXIT STAIR SHALL BE
 SELF-CLOSING OR AUTOMATICALLY CLOSING BY LISTED CLOSING
 DEVICES.
 COMMENT ?ND 35,ND 01
  
 11 FBC EXISTING607.3 NEW STRUCTURAL MEMBERS.
 NEW STRUCTURAL MEMBERS IN ALTERATIONS, INCLUDING
 CONNECTIONS AND ANCHORAGE, SHALL COMPLY WITH THE
 FLORIDA BUILDING CODE, BUILDING.
 COMMENT - THIS INCLUDES ROOF SYSTEM/ELEVATOR SHAFT/
 INTERIOR AND EXTERIOR COMPONENTS
  
 12 FBC1604.8.1 GENERAL.
 ANCHORAGE OF THE ROOF TO WALLS AND COLUMNS, AND OF
 WALLS AND COLUMNS TO FOUNDATIONS, SHALL BE PROVIDED TO
 RESIST THE UPLIFT AND SLIDING FORCES THAT RESULT FROM
 THE APPLICATION OF THE PRESCRIBED LOADS.
 COMMENT - ELEVATOR SHAFT ENCLOSURE
  
  
 13 SHEETS-200? STRUCTURAL NOTES ?
 COMMENTS
 7-SIDENTIFY SLEEVE ANCHOR EMBEDMENT INTO CONCRETE
  
 10-SIDENTIFY # 4 DOWEL EMBEDMENT INTO CONCRETE.
  
 SHEET S-100IDENTIFY TIE BEAM ELEVATIONS ON SCHEDULE
  
  
 FBC EXISTING812.5 ACCESSIBILITY.
 EXISTING BUILDINGS OR PORTIONS THEREOF THAT UNDERGO A
 CHANGE OF GROUP OR OCCUPANCY CLASSIFICATION SHALL
 COMPLY WITH CHAPTER 11 OF THE FLORIDA BUILDING CODE,
 BUILDING.
  
 14 FBC ACCESSIBILITY 11-4.10 ELEVATORS
 COMMENTPLEASE PROVIDE NOTE ON PLAN ELEVATOR MUST
 COMPLY WITH THIS SECTION
  
  
  
 15 FBC11-4.10.9 FLOOR PLAN OF ELEVATOR CARS.
 THE FLOOR AREA OF ELEVATOR CARS SHALL PROVIDE SPACE FOR
 WHEELCHAIR USERS TO ENTER THE CAR, MANEUVER WITHIN
 REACH OF CONTROLS, AND EXIT FROM THE CAR. ACCEPTABLE
 DOOR OPENING AND INSIDE DIMENSIONS
 THE CLEARANCE BETWEEN THE CAR PLATFORM SILL AND THE
 EDGE OF ANY HOIST WAY LANDING SHALL BE NO GREATER THAN
 1 1 / 4 INCHES (32 MM).
  
 16 ELEVATOR PIT
 COMMENTIDENTIFY THE DEPTH OF THE PIT FROM FINISHED
 FLOOR AND ALL OTHER REQUIRED MEASUREMENTS
  
 17 FBC3006.2 VENTING.
 ELEVATOR MACHINE ROOMS THAT CONTAIN SOLID-STATE
 EQUIPMENT FOR ELEVATOR OPERATION SHALL BE PROVIDED WITH
 AN INDEPENDENT VENTILATION OR AIR-CONDITIONING SYSTEM
 TO PROTECT AGAINST THE OVERHEATING OF THE ELECTRICAL
 EQUIPMENT. THE SYSTEM SHALL BE CAPABLE OF MAINTAINING
 TEMPERATURES WITHIN THE RANGE ESTABLISHED FOR THE
 ELEVATOR EQUIPMENT.
 COMMENT -WILL THIS SECTION APPLY?
  
  
 18 FBC1807.3.2 WALLS. ELEVATOR SHAFT WALLS
 WALLS REQUIRED TO BE WATERPROOFED SHALL BE OF CONCRETE
 OR MASONRY AND SHALL BE DESIGNED AND CONSTRUCTED TO
 WITHSTAND THE HYDROSTATIC PRESSURES AND OTHER LATERAL
 LOADS TO WHICH THE WALLS WILL BE SUBJECTED.
 COMMENTTHE WALLS OF THE ELEVATOR PIT ARE SUBJECT TO
 GROUND WATER/MOISTURE INTRUSION. PLEASE DEFINE A
 WATERPROOFING SYSTEM (NEGATIVE SIDE) OR IF NOT
 REQUIRED, A SOIL TEST REPORT ON THE GROUND WATER
 CONDITION
  
  
 FBCRESIDENTIALENERGY CALCULATIONS13-6
  
 PERFORMANCE METHOD ABASE / AS-BUILT
  
 19 GLASS TYPES
 EAST WALLAREA WITHOUT DEDUCTING FRAME 52.17 S.F.
 YOUR CALCULATIONS WITH FRAME DEDUCTION 38.5 S.F.
 PLEASE EXPLAINTHIS.
  
 20 DOOR TYPES
 EXTERIOR DOOR STEEL.YOUR CALCULATIONS BASED ON WOOD.
 PLEASE EXPLAIN THIS
  
 21 CEILING TYPES
 AREA UNDER ATTIC HAS NO INSULATION. THERE IS A
 CONDITIONED SECOND FLOOR ABOVE THIS RESIDENCE.YOUR
 CALCULATIONS STATE R 19. PLEASE EXPLAIN THIS.
  
  
 FBCENERGY CALCULATIONS13-6METHOD A WHOLE
 BUILDING PERFORMANCE
  
 SIGNATURE PAGE 3
 22 SIGNATURES ARE MISSING FOR THE ARCHITECT AND
 ELECTRICAL DESIGNER

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2008-12-15 Cont ID  
Sent By dpalmer Date 2008-12-15 Time 14:17 Rev Time 0.00
Received By dpalmer Date 2008-12-15 Time 14:17 Sent To M
Notes
2008-12-15 14:18:10NEW FORM B UNDER CORRECT VERSION 2.5 BROUGHT IN.

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2008-12-05 Cont ID  
Sent By dpalmer Date 2008-12-05 Time 14:43 Rev Time 0.00
Received By dpalmer Date 2008-12-05 Time 14:43 Sent To  
Notes
2008-12-05 14:44:04 
 ** FAILED REVIEW 5TH TIME. **
  
 ** A CALL WAS PLACED TO THE ELECTRICAL ENGINEER AND
 LEFT MESSAGE ON VOICE-MAIL TO RETURN CALL AS SOON AS
 POSSIBLE TO GO OVER NOTE BELOW.
  
 1) NOTE: THE SUBMITTED FLA-COM CALCULATIONS ARE NOW
 METHOD*B* WHICH IS DIFFERENT FROM PREVIOUS SUBMITTED
 CALCULATIONS. PLEASE SEE SECTION 13-400.B.3 OF THE
 FLORIDA BUILDING CODE. THE VERSION SUBMITTED IS NOT
 ADOPTED BY THE STATE OF FLORIDA. THIS HAS BEEN
 DISCUSSED AND CONFIRMED ON MORE THAN ONE OCCASION WITH
 MO MADANI WITH DEPARTMENT OF COMMUNITY AFFAIRS. THE
 ADOPTED VERSION IS 2.5.
 PLEASE SEE THE FOLLOWING WORDING WHICH IS TAKEN
 DIRECTLY FROM THE ENERGY GAUGE WEBSITE. PLEASE BE SURE
 TO READ THE LAST LINE IN PARENTHESIS. YOU WILL SEE IT
 STATES **VERSION 2.5**.
 IT IS IMPORTANT TO KNOW THAT IT IS THE UNDERSTANDING TO
 THIS OFFICE THAT THERE IS A FREE PATCH ON THEIR WEBSITE
 IN ORDER TO OBTAIN CORRECT VERSION. IT IS ALSO THE
 UNDERSTANDING OF THIS REVIEWER/OFFICE FROM NUMEROUS
 OTHER DESIGNERS WHO HAVE HAD TO DO THIS IS THERE IS NO
 FEE ASSOCIATED WITH PATCH.
  
 ***BUILDING OFFICIALS: ENERGYGAUGE SUMMIT VERSION 3.00
 THROUGH 3.14 SATISFIES THE REQUIREMENTS IN 13-400.3.A
 AND 13-400.3.B (GENERATED BY FLA/COM-2004 COMPUTER
 PROGRAM, VERSION 2.5).***
  
  
  
  
 THERE WILL BE COMMENTS FROM OTHER TRADES WITH RESPECT
 TO OTHER COMPONENTS ON THE INPUT DATA REPORT OF THE
 SUBMITTED CALCULATIONS. AS A *HEADS-UP* TO OTHER
 POSSIBLE CONFLICTS PLEASE SEE THE OTHER
 ITEMS/COMPONENTS WHICH ARE NOT PLACED IN THE IDR AS
 REQUIRED.
 METHOD *B* IS FOR ENVELOP TRADE-OFF COMPLIANCE.
  
 A) TYPE OF ROOF IS NOT CALLED OUT IT SIMPLY STATES
 *ROOF* UNDER TYPE OF ROOF.
 B) NO FLOORS IN THE IDR.
 C) NO INFORMATION ON HOT WATER PIPE INSULATION.
 ETC.
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-10-03 Cont ID  
Sent By dpalmer Date 2008-10-03 Time 15:50 Rev Time 0.00
Received By dpalmer Date 2008-10-03 Time 15:50 Sent To  
Notes
2008-10-03 15:50:43 
 ** DENIED 4TH REVIEW **
 3RD REVIEW UNDER PERMIT APPLICATION.
  
 1) NOTE: PLEASE SEE THE SUBMITTED FORM *C* IS NOT IN
 COMPLIANCE WITH FBC 13-415.2,13-415.2.ABC.1.1,.1.2,
 .1.3.
 THE FORM *C* NOW NOTES THREE SEPARATE SPACES WHICH MAY
 NOT BE USED AS FORM *C* IS FOR A SPECIFIC USE OR
 OCCUPANCY. IF USING A SPACE BY SPACE THEN TABLE *B* IS
 REQUIRED TO BE USED. PLEASE SEE THE SECTIONS ABOVE
 ALONG WITH SECTION 202 OF CHAPTER 13 FOR THE
 DEFINITIONS OF A RENOVATION. THE FORM *C* DOES NOT SHOW
 COMPLIANCE FOR EXTERIOR LIGHTING AS NOTED IN
 13-415.2.ABC.1.3 NOTED INALL REVIEWS.
 COMPLIANCE WITH THE SPECIFIC CODES ABOVE HAS NOT BEEN
 DEMONSTRATED. THE RESPONSE LETTER MENTIONS THIS IS NOT
 AN ELECTRICAL COMMENT. HOWEVER PLEASE SEE STATEMENTS
 ISSUED BY THE FLORIDA BUILDING COMMISSION WHICH ARE
 AVAILABLE ON-LINE WHICH STATE: * THE INTENT FOR REVIEW
 OF THE CALCULATIONS AND CHAPTER 13 IS FOR EACH TRADE
 REVIEWER TO REVIEW THAT PARTICULAR TRADE.
 A CALLED WAS PLACED TO THE ELECTRICAL ENGINEER AS OF
 THIS REVIEW AND A MESSAGE WAS LEFT ON VOICEMAIL TO
 RETURN CALL.
 THE CALCULATIONS ON FORM *C* AS SUBMITTED ALONG WITH
 ELECTRICAL PLANS WILL BE RETAINED BY THIS OFFICE.
 BASED ON THE *C* SUBMITTED AND OCCUPANCY DESIGN WATTAGE
 IS OVER THE ALLOWANCES PERMITTED. THIS IS NOT
 LODGE/HOTEL/TRANSIENT LODGING. THIS IS A ASSEMBLY
 OCCUPANCY BASED ON ARCHITECTURAL PLANS OCCUPANCY
 DESIGNATION. PLEASE CONTACT THIS OFFICE/REVIEW TO GO
 OVER HOWEVER THE CODE COMPLIANCE CAN BE SHOWN.
  
  
 2) NOTE: PLEASE SEE THE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENT FOR CODE COMPLIANCES. THE SPECIFIC
 SECTIONS OF THE CODE HAVE BEEN GIVEN NOW FOR FOUR
 REVIEWS THREE OF WHICH ARE UNDER PERMIT APPLICATION.
 THE STATUTORY REQUIREMENT IS THAT A FEE BE ASSESSED.
 THIS IS NOT A LOCAL ORDINANCE, REGULATION, OR
 ADMINISTRATIVE AMENDMENT. THIS IS A FLORIDA STATUTE
 REQUIRED FEE. THIS OFFICE HAS PLACED THE CONTACT
 INFORMATION FOR ANY QUESTIONS OR COMMENTS ON ALL
 REVIEWS TO GO OVER PLANS HOWEVER CONTACT HAS NOT YET
 BEEN MADE.
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-04-03 Cont ID  
Sent By dpalmer Date 2008-04-03 Time 18:43 Rev Time 0.00
Received By dpalmer Date 2008-04-03 Time 18:43 Sent To  
Notes
2008-04-03 18:43:28** DENIED 3RD REVIEW **
 ** ONLY 2ND REVIEW UNDER ACTUAL PERMIT APPLICATION.
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING ALONG WITH SOME NEW
 COMMENTS BASED ON CHANGES MADE TO PLANS AND/OR
 DOCUMENTS SUBMITTED.
  
 1) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS
 FOR COMMERCIAL PORTION OF BUILDING NEEDS TO MEET CODE
 AND COORDINATE WITH PLANS. PLEASE BE SURE TO SEE
 13-415.2, 13-415.2.ABC.1.1, .1.2 AND .1.3.
 FOR EXAMPLE:
 PLEASE BE SURE TO SEE THE CALCULATIONS STATED ON SHEET
 E-3 STATES THIS BUILDING AS A "LODGE". HOW IS THIS
 POSSIBLE? THE SUBMITTED ENERGY CALCULATIONS CLEARLY
 STATE "OFFICE".
 FOR EXAMPLE:
 PLEASE SEE THE INPUT DATA REPORT WHICH DOES NOT SHOW
 ANY EXTERIOR LIGHT FIXTURES YET THE PLANS CLEARLY SHOW
 EXTERIOR LIGHTING. HOW IS THIS POSSIBLE?
 FOR EXAMPLE:
 PLEASE SEE ONLY TWO TYPES OF FIXTURES ARE SHOWN FOR
 FIRST FLOOR ZONE HOWEVER THE PLANS CONTAINS A MINIMUM
 OF FOUR DIFFERENT TYPES OF FIXTURES. (THIS IS NOT
 NOTING THE SEPARATE ELEVATOR ZONE)
 FOR EXAMPLE:
 PLEASE SEE UPPER FLOOR ZONE FOR AHU3. WHERE ARE K
 FIXTURES, WHERE ARE THE FIXTURES IN BATHROOMS SHOWN FOR
 SHOWERS? WHERE ARE THE WALL SCONCES?
  
 ** PLEASE ALSO BE SURE THE OWNER AGENT IS SIGNED ON THE
 CERTIFICATION SHEET WHEN RESUBMITTING. FBC 13-103.1
  
 2) NOTE: PLEASE SEE THE TAPPED CONDUCTORS FROM THE
 320AMP METER CAN SHALL TERMINATE IN OVER CURRENT
 PROTECTION HOWEVER THE RISER ONLY SHOWS A 30AMP 2-POLE
 DISCONNECT AT BOTH THE SERVICE MAIN LOCATION AND THE
 ELEVATOR DISCONNECT.
 PLEASE KNOW THE FIRST ITEM IS THIS 30AMP DISCONNECT IS
 ONE OF THE SERVICE MAINS YET NO LABELING OF THIS IS
 SHOWN. 230.2E (ALL)
 PLEASE SEE THE SECOND ITEM IS THAT THIS 30AMP
 DISCONNECT SHALL BE SERVICE EQUIPMENT RATED AND SERVICE
 ENTRANCE RATED FOR A MAIN. 230.70, 230.71, 110.7, 90.7
 PLEASE VERIFY THIS.
 PLEASE SEE FOR THE THIRD ITEM; PLEASE SEE 240.21,
 310.16 AND 240.4 AS THE TAPPED CONDUCTORS SHALL
 TERMINATE IN OVER CURRENT PROTECTION.
  
 3) NOTE: PLEASE SEE THE OVER CURRENT PROTECTION SHOWN
 ON ELECTRICAL PANEL SCHEDULES AND MECHANICAL PLANS ARE
 NOT CODE COMPLIANT.
 PLEASE SEE THE CODE REQUIRES MINIMUM OVER CURRENT
 PROTECTION OF 125% PER 424.3B. PLEASE SEE ONE OF THE
 5KW AH UNITS STATES 60AMP OCP.
 PLEASE SEE THE AC SHEETS AS THESE STATES THE MINIMUM
 CIRCUIT AMPACITY OF THE 5KW UNITS IS 13AMPS AND THE MAX
 OCP ID 20AMPS. THIS CAN NOT BE POSSIBLE AS THE LOAD OF
 5KW AT 240V IS OVER 20AMPS. THIS IS BEFORE THE MINIMUM
 125% WHICH IS REQUIRED BY CODE.
 PLEASE SEE THE UNIT WHICH SHOWS A 12.9 KW HEAT STRIP
 SHOWS MINIMUM CIRCUIT LOAD OF 20AMPS AND THE MAXIMUM
 OCP AT 40AMPS. THIS IS ALSO NOT POSSIBLE AS THE LOAD ON
 THIS UNIT BEFORE 125% IS SUBSTANTIALLY HIGHER THAN THE
 40AMP BREAKER OR CIRCUIT.
 PLEASE SEE 424.3B, 240.4, 310.16 ETC.
  
 ** PLEASE SEE THE ARCHITECTURAL PLANS STATE AND SHOW A
 AHU #4, WHEREAS THE MECHANICAL PLANS SHOWS THE AHU#3 IN
 THE SAME LOCATION.
  
 4) NOTE: PLEASE SEE THE MINIMUM PHOTO-METRIC LEVELS ON
 THE OUTSIDE STAIRS DO NOT MEET THE LIFE SAFETY CODE FOR
 COMPLIANCE.
 PLEASE SEE 7.8.1.3 AS THIS REQUIRES A *MINIMUM* OF
 10FOOT CANDLES. THE PLANS SHOWS ABOUT HALF OF THE
 NEEDED FOR NORMAL LIGHTING LEVELS.
  
 5) NOTE: PLEASE SEE A NOTICE TO FS 553.80(2)(B) IS NOW
 BEING GIVEN. THERE ARE REPEAT COMMENTS FOR CODE
 COMPLIANCE WHICH HAS BEEN MADE ON THE LAST TWO REVIEWS
 WHICH ARE BEING REPEATED ONCE AGAIN. THE INITIAL REVIEW
 DOES NOT APPLY AS PLANS WERE ONLY SUBMITTED FOR *PLAN
 REVIEW* AND WERE NOT SUBMITTED FOR PERMIT APPLICATION.
  
 PLEASE BE SURE ALL COMMENTS ARE ADDRESSED ON THE THIRD
 REVIEW UNDER PERMIT AND FORTH REVIEW FOR PROJECT. ONCE
 AGAIN AS STATED ON PREVIOUS REVIEWS IF THERE ARE
 QUESTIONS OR COMMENTS PLEASE CONTACT THIS REVIEWER.
 PLANS AND CALCULATIONS MAY BE RETAINED BY THIS OFFICE
 DUE TO THE REPEAT COMMENTS FOR CODE COMPLIANCE.
  
  
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-01-22 Cont ID  
Sent By dpalmer Date 2008-01-22 Time 12:04 Rev Time 0.00
Received By dpalmer Date 2008-01-18 Time 16:46 Sent To  
Notes
2008-01-22 12:05:11 
  
 ** DENIED 2NDREVIEW **
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
  
 1) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENTS WITH
 RESPECT TO FBC CHAPTER 13 FOR LIGHTING PERFORMANCE
 CALCULATIONS/ENERGY CALCULATIONS.
 PLEASE SEE ONCE AGAIN THE SUBMITTED ENERGY CALCULATIONS
 MAY NOT BE USED AS SHOW. PLEASE SEE IN FACT THESE ARE
 THE SAME AS PREVIOUSLY SUBMITTED. ONE SET IS FORM 600
 FOR WHOLE BUILDING RESIDENTIAL WHICH THIS IS NOT A
 WHOLE RESIDENTIAL BUILDING BY DEFINITION. THIS 600A
 FORM ALSO STATES AN ADDRESS OF 2037 SPRUCE WHICH IS NOT
 THE BUILDING ADDRESSING OF THIS APPLIED SCOPE OF WORK.
 PLEASE SEE THE OTHER METHOD SUBMITTED IS THE SAME
 METHOD *A* FROM PREVIOUS REVIEW. THIS MAY ALSO NOT BE
 USED AS SUBMITTED.
 PLEASE SEE THE INFORMATION ON THE COVER SHEET, SUMMARY
 SHEETS AND THE INPUT DATA REPORTS DO NOT CORRELATE WITH
 PLANS.
 THE AMOUNT OF LIGHT FIXTURES, THE WATTAGE, THE TYPES
 AND THE METHOD OF CONTROLS ALL NEED TO MEET 13-415.2.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AS THE SQ FT ON
 CALCULATIONS IS STATING THE BUILDING IS 8K PLUS SQ FT.
 PLEASE KNOW IF A/C IS BEING ADDED, PLEASE SEE
 MECHANICAL REVIEW COMMENTS.
 PLEASE SUBMIT THE ABOVE INFORMATION.
  
 2) NOTE: PLEASE SEE PREVIOUS REVIEW REQUESTED
 COORDINATION OF ALL SERVICE ENTRANCE CONDUCTORS AND
 FEEDERS WITH THAT OF WHICH IS SINGLE PHASE AND THREE
 PHASE. MOST OF THESE WERE DONE BUT PLEASE SEE THERE IS
 NO NEUTRAL CONDUCTOR BEING SHOWN TO THE ELEVATOR
 SERVICE DISCONNECT WHICH IS REQUIRED.
 PLEASE ADJUST THE SERVICE ENTRANCE CONDUCTORS TO THIS
 FIRST MEANS OF DISCONNECT.
 230.42C, 250.24C, 250.6 ETC
  
 3) NOTE: PLEASE SEE PREVIOUS REVIEW REQUEST TO CLEARLY
 DESIGNATE THE SMOKE DETECTION DEVICES. SYMBOL LEGEND
 STILL CALLS FOR SMOKE DETECTORS AND THEN ALSO NOTES
 SMOKE ALARMS.
 PLEASE SHOW WHICH ONE AS THESE ARE DIFFERENT BY
 DEFINITION.
 PLEASE SEE NFPA-72
  
 4) NOTE: PLEASE SEE PREVIOUS REQUEST FOR PHOTO-METRIC
 LEVELS UNDER NORMAL AND EMERGENCY CONDITIONS.
 LS 101 7.8.1.3, 7.9.2.2
 PLANS SEEM TO INDICATE LEVEL UNDER EMERGENCY ONLY.
  
 5) NOTE: PLEASE SEE PREVIOUS REVIEW WITH RESPECT TO
 SEAL NO BEING CLEAR AND VISIBLE WITH ALL INFORMATION ON
 SAID SEAL.
 PLEASE SEE THE LICENSE NUMBER ON SEAL IS MISSING THE
 LAST DIGIT AND CAN NOT CLEARLY SEE THIS.
 A LEAD RUB WAS USED AND INFORMATION WAS STILL NOT CLEAR
 AND VISIBLE.
 PLEASE SEE FS 471.025 AND ADJUST.
  
 6) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE.
 THIS IS ONLY A NOTICE GIVEN AT THIS TIME.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-09-13 Cont ID  
Sent By dpalmer Date 2007-09-13 Time 11:20 Rev Time 0.00
Received By dpalmer Date 2007-09-13 Time 08:52 Sent To  
Notes
2007-09-13 11:20:40 
 ** DENIED **
  
 *** IMPORTANT**
 PLANS HAVE ONLY BEEN SUBMITTED FOR PLAN REVIEW AND HAVE
 NOT BEEN SUBMITTED FOR PERMIT APPLICATION.
 PLEASE KNOW EVEN ONCE ALL CODE COMMENTS ARE ADDRESSED
 AND PERMIT HAS NOT BEEN APPLIED FOR BY A LICENSED
 CONTRACTOR, THE REVIEW WILL STILL REMAIN INA *F*
 STATUS UNTIL APPLICATION IS MADE. ALL LICENSING FOR
 CONTRACTORS, DESIGNERS WILL BE VERIFIED AT THAT TIME
 BEFORE PERMIT ISSUANCE.
  
  
 1) NOTE: PLEASE CLARIFY EXISTING OCCUPANCY.
  
 2) NOTE: PLEASE SEE CERTIFICATE OF AUTHORIZATION NUMBER
 SHOWN ON TITLE BLOCKS FOR ARCHITECTURAL FIRM IS NOT
 THAT AS LISTED WITH THE DEPARTMENT OF BUSINESS AND
 PROFESSIONAL REGULATION. PLEASE SEE THE ATTACHED PRINT
 OUT AS OF THIS REVIEW.
 PLEASE SEE FAC 61G1-16.004 AND FLORIDA STATUTES
 481.219
  
 3) NOTE: PLEASE BE SURE THE RAISED/EMBOSSED SEAL ON THE
 ELECTRICAL SHEETS IS CLEAR AND VISIBLE WITH ALL
 INFORMATION ON SAID SEAL. SOMEARE VERY FAINT AND NOT
 EASILY READ.
 FS 471.025, FAC 61G15-23.001
  
 4) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 5) NOTE: PLEASE SEE MECHANICAL REVIEW COMMENTS AS THE
 ADDITIONAL A/C BEING ADDED TO SPACE MAY REQUIRED ENERGY
 CALCULATIONS BY METHOD AS SPECIFIED IN 13-415.1.B,
 13-415.1.C.
 PLEASE SEE THE LIGHTING ON THE INPUT DATA REPORT DO NOT
 CORRELATE WITH PLANS AND FIXTURE LEGEND. THE IDR ONLY
 INDICATES 3 FIXTURES TOTAL?
 PLEASE ALSO SEE METHOD A BEING SUBMITTED.
 PLEASE KNOW THAT LIGHTING PERFORMANCE CALCULATIONS ARE
 STILL REQUIRED PER 13-415.2. PLEASE SEE TABLES
 415.2.C.1, 415.2.B.1.
 PLEASE BE SURE TO COORDINATE ALL OF THESE ITEMS.
 FBC 106.1.2, 106.3.5.1.2
  
 6) NOTE: PLEASE INDICATE THE AIC RATINGS FOR NEW MAINS
 AND SERVICE EQUIPMENT AS SHOWN ON RISER.
 110.9. SOME ARE SHOWN BUT NOT ALL.
 FBC 106.3.5.1.2, 106.1.2
  
 7) NOTE: PLEASE SEE THE RISER IS SHOWING *EQUIPMENT
 GROUNDING CONDUCTORS* AHEAD OF MAINS WHICH IS NOT
 PERMITTED. AS THE NEUTRAL/GROUNDED CONDUCTOR IS BONED
 AT THE FIRST MEANS OF DISCONNECT, IF AN *EQUIPMENT
 GROUNDING CONDUCTOR * WAS INSTALLED AHEAD OF MAINS,
 THIS WOULD CREATE OBJECTIONABLE CURRENTS PER 250.6,
 250.24
 PLEASE REMOVE.
  
 8) NOTE: PLEASE SEE 310.16, 110.14, 240.4 AS THE 1/0
 CONDUCTORS ARE NOT RATED FOR THE 175AMP BREAKER/OVER
 CURRENT PROTECTION TO PANEL *B*.
  
 9) NOTE: PLEASE SEE LS 200 WHICH MENTIONS THE EMERGENCY
 FIXTURES ON AN EMERGENCY CIRCUIT, YET THERE IS NO
 GENERATOR BACK UP ON PLANS?
 PLEASE VERIFY AS THE ELECTRICAL PLANS INDICATES THE
 CIRCUITING CORRECTLY PER 700.12F.
  
 10) NOTE: PLEASE CORRELATE PLANS WITH RISER FOR ALL
 FEEDERS. PLEASE SEE THE RISER SHOWS SERVICE ENTRANCE
 CONDUCTORS AND FEEDERS FOR THREE PHASE TO PANEL *A* YET
 PANEL *A* IS SHOWN AS SINGLE PAHSE. PLEASE CORRELATE
 AND ADJUST.
 FBC 106.1.2 FOR COORDINATION.
  
 11) NOTE: PLEASE CORRELATE FEEDERS ON RISER AND PANEL
 SCHEDULE FOR PANEL *B* AS PANEL INDICATES 2/0 AND THE
 RISER SHOWS 1/0. PLEASE SEE PREVIOUS NOTE ABOVE #7 AS
 THE 1/0 CONDUCTORS ARE NOT RATED FOR THE 175AMPS.
 PLEASE CORRELATE AND ADJUST.
 FBC 106.1.2, 106.3.5.1.2, ETC
  
 12) NOTE: PLEASE SEE THE RISER WHICH INDICATES BUILDING
 STEEL AS PART OF THE GROUNDING ELECTRODE SYSTEM. THIS
 IS BEING ASSUMED THIS IS ACTUALLY *FOOTER STEEL*? IN
 EITHER CASE PLEASE KNOW AS THIS IS AN EXISTING BUILDING
 THE FOOTER STEEL WOULD NOT REQUIRE AN ATTACHMENT AS
 THIS MAY CREATE AN ADVERSE AFFECT ON THE STRUCTURAL
 INTEGRITY OF THE FOUNDATION.
 (IF SHOWN ON RISER, THEN THIS WOULD BE REQUIRED AS THIS
 IS BEING SPECIFIED.)
 PLEASE SEE MISSING GAS LINE BOND AS REQUIRED. 250.50,
 250.104.
  
 13) NOTE: PLEASE SEE NEC 422.13 AS THE WATER HEATER IS
 REQUIRED TO BE FIGURED AT 125% FOR LOAD. PLEASE KNOW
 THIS WAS A CHANGE IN THE 2005 NEC.
 230.42, 215.3, 422.13 ETC
  
 14) NOTE: PLEASE SUBMIT PHOTO-METRICS FOR THE MINIMUM
 LIGHTING LEVELS UNDER NORMAL AND EMERGENCY CONDITIONS
 PER NFPA-101 7.8.1.3, 7.9.2.2 FOR STAIRS/DESIGNATED
 EGRESS PATHS.
 FLORIDA ADMINISTRATIVE CODE 61G15-33.004
  
 15) NOTE: PLEASE INDICATE THE SIZE/AMPERAGE OF METER
 CANS.
 PLEASE VERIFY RISER AS SHOWN WITH AN ADDITIONAL GUTTER
 ON THE SECONDARY SIDE OF THE METER.
 FBC106.1.2
  
 16) NOTE: PLEASE SEE PANEL SCHEDULES NEED TO BE
 SPECIFIC TO THE ROOMS AND AREAS IN WHICH THEY FEED.
 PLEASE SEE THE FOLLOWING TEXT WHICH IS TAKEN DIRECTLY
 FROM THE NEC.
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 17) NOTE: PLEASE VERIFY THE SMOKE DETECTION DEVICES,
 TYPES AND DESIGNATIONS ON PLANS.
 PLEASE SEE NFPA-72 AS SMOKE DETECTORS ARE ONLY DEVICES
 WHICH DETECT AND DO NOT SOUND AN ALARM AND SMOKE ALARMS
 DETECT AND SOUND AN ALARM.
 IF TWO DIFFERENT TYPES OF DEVICES ARE BEING USED AS IT
 SEEMS, PLEASE ADJUST DESIGNATIONS.
  
 18) NOTE: PLEASE SEE 210.12 AS ALL *OUTLETS* IN
 SLEEPING ROOMS REQUIRE ARC FAULT PROTECTION.
 PLEASE KNOW THIS INCLUDES RECEPTACLES, LIGHTS, SMOKE
 ALARMS, FANS ETC.
  
 19) NOTE: PLEASE SEE MISSING CIRCUITS/LIGHTS/GFI PER
 620.24.
 PLEASE ALSO SEE HANDBOOK REFERENCES THE ANSI/ASME 2004
 ELEVATOR SAFETY CODE FOR MINIMUM LIGHTING LEVELS IN PIT
 AREA. (5FT CANDLES) PLEASE ALSO SEE ANY MINIMUM
 REQUIREMENTS FROM THE STATE OF FLORIDA AND STATE
 ELEVATOR CODE WHICH MAY BE MORE RESTRICTIVE.
  
 20) NOTE: PLEASE SPECIFY ALL LIGHTING FOR
 CLOSETS/LOCKERS AS THEY ARE REQUIRED TO MEET 410.8.
 PLEASE KNOW THIS IS ALSO REQUIRED OF THE DWELLING UNIT
 CLOSET. *(PLANS NOTE LIGHT FIXTURES TO BE OWNER CHOSEN,
 HOWEVER NEED TO MEET MINIMUM LIFE SAFETY CODE AT THIS
 TIME.)
  
 21) NOTE: PLEASE SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT THE ELECTRICAL PLANS AND/OR DESIGN FOR
 BUILDING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2008-12-15 Cont ID  
Sent By mwennerg Date 2008-12-15 Time 13:58 Rev Time 0.00
Received By mwennerg Date 2008-12-15 Time 13:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2008-10-20 Cont ID  
Sent By mawillia Date 2008-10-20 Time 15:32 Rev Time 0.00
Received By mawillia Date 2008-10-20 Time 15:01 Sent To  
Notes
2008-10-20 15:32:25*****UNSAT*****
  
 "THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE ADDRESSED:"
  
 9. KNOX LOCKING CAPS WILL BE REQUIRED FOR THE FIRE
 DEPARTMENT CONNECTIONS. FOR APPLICATIONS, CONTACT WEST
 PALM BEACH FIRE PREVENTION BUREAU AT 561-804-4724. ADD
 COMMENT TO SHEET FS-2
  
 "THE FOLLOWING NEW COMMENT STILL NEEDS TO BE
 ADDRESSED:"
  
 C. ON SHEET FS-2, REFERENCES ARE MADE TO MIAMI DADE
 FIRE RESCUE DEPARTMENT AND MIAMI AND MIAMI-DADE WATER &
 SEWER. PLEASE PROVIDE FLOW TEST DATA AS PER WEST PALM
 BEACH FIRE PREVENTION AND WATER SUPPLY CHARACTERISTICS
 AS PER CITY OF WEST PALM BEACH WATER UTILITIES
 DEPARTMENT.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2008-05-01 Cont ID  
Sent By mwennerg Date 2008-05-01 Time 13:56 Rev Time 0.00
Received By mwennerg Date 2008-05-01 Time 13:56 Sent To  
Notes
2008-05-01 14:08:03***DENIED***
  
 MOST OF THE COMMENTS HAVE BEEN ADDRESSED. PLEASE SEE
 THE FOLLOWING PAST COMMENTS AND A NEW COMMENT:
  
 9) KNOX LOCKING CAPS WILL BE REQUIRED FOR THE FIRE
 DEPARTMENT CONNECTIONS. FOR APPLICATIONS, CONTACT WEST
 PALM BEACH FIRE PREVENTION BURAEU AT (561) 804-4724.
 ADD COMMENT TO SHEET FS-2.
  
 B) PLEASE EXPLAIN THE ADDITION OF APT. 101 IN THE
 PROJECT SITE ADDRESS SHOWN IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET.
  
 C) ON SHEET FS-2, REFERENCES ARE MADE TO MIAMI DADE
 FIRE RESCUE DEPARTMENT AND MIAMI AND MIAMI-DADE WATER
 AND SEWER. PLEASE PROVIDE FLOW TEST DATA AS PER WEST
 PALM BEACH FIRE PREVENTION AND WATER SUPPLY
 CHARACTERISTICS AS PER CITY OF WEST PALM BEACH WATER
 UTILITIES DEPARTMENT.
  
 NEW COMMENT:
  
 1) SHEET CS 100 REFERENCES SPRINKLER SYSTEM TO COMPLY
 WITH 2004 NFPA 101, SECTION 9.7. NOTE SHOULD REFERENCE
 2003 EDITION.
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS
 ADDRESSED.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-02-19 Cont ID  
Sent By mawillia Date 2008-02-19 Time 12:12 Rev Time 0.00
Received By mawillia Date 2008-02-19 Time 11:10 Sent To  
Notes
2008-02-19 12:11:46*****DENIED*****
  
 "THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE ADDRESSED:"
  
 3. OUTSIDE STAIRS AND LANDINGS SHALL BE OF SLIP
 RESISTANT SURFACES AND DESIGNED TO MINIMIZE WATER
 ACCUMULATION ON THEIR SURFACES. ADD COMMENT TO AN
 APPROPIATE PLAN SHEET
  
 4. THE NEW ELEVATOR SHALL BE IN ACCORDANCE WITH ASME
 A17.1, SAFETY CODE FOR ELEVATORS AND ESCALATORS. ADD
 COMMENT TO AN APPROPIATE PLAN SHEET
  
 5. BUILDING ELEMENTS SHALL BE USED TO RESTRICT WATER
 EXPOSURE OF ELEVATOR EQUIPMENT. ADD COMMENT TO AN
 APPROPIATE PLAN SHEET
  
 6. IN REFERENCE TO THE DWELLING UNIT ON SHEET E-1,
 AMEND ELECTRICAL LEGEND ON SHEET E-3 TO REFLECT SMOKE
 ALARMS INSTEAD OF SMOKE DETECTORS. SMOKE DETECTORS ARE
 TIED INTO THE BUILDING FIRE ALARM SYSTEM, WHEREAS SMOKE
 ALARMS ALERT THE OCCUPANTS OF THE SAID UNIT. TO PREVENT
 CONFUSION, DELETE SMOKE DETECTOR REFERENCE
  
 9. KNOX LOCKING CAPS WILL BE REQUIRED FOR THE FIRE
 DEPARTMENT CONNECTIONS. FOR APPLICATIONS, CONTACT WEST
 PALM BEACH FIRE PREVENTION BUREAU AT 561-804-4724. ADD
 COMMENT TO SHEET FS-2
  
 "THE FOLLOWING NEW COMMENTS ARE TO BE ADDRESSED:"
  
 A. THE UPPER LEFT HAND CORNER OF SHEET CS100 LIST THE
 ADDRESS AS 2027 SPRUCE AVENUE.
  
 B. PLEASE EXPLAIN THE ADDITION OF APT. 101 IN THE
 PROJECT SITE ADDRESS SHOWN IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET.
  
 C. ON SHEET FS-2, REFERENCES ARE MADE TO MIAMI DADE
 FIRE RESCUE DEPARTMENT AND MIAMI AND MIAMI-DADE WATER &
 SEWER. PLEASE PROVIDE FLOW TEST DATA AS PER WEST PALM
 BEACH FIRE PREVENTION AND WATER SUPPLY CHARACTERISTICS
 AS PER CITY OF WEST PALM BEACH WATER UTILITIES
 DEPARTMENT.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-10-22 Cont ID  
Sent By mawillia Date 2007-10-22 Time 16:55 Rev Time 0.00
Received By mawillia Date 2007-10-22 Time 15:04 Sent To  
Notes
2007-10-22 15:19:32*****DENIED*****
  
  
 01.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.I.E. ON SHEET LSP200 LISTS 2004
  
 02.POST/SHOW THE NUMERICAL ADDRESS OF THE BUILDING ON
 THE APPROPIATE EXTERIOR ELEVATION WHICH FRONTS SPRUCE
 AVENUE.AS PER WEST PALM BEACH CODE, THE NUMBERS SHALL
 BE NO LESS THAN SIX INCHES IN HEIGHT AND NO LESS THAN
 ONE INCH IN WIDTH.
  
 03.OUTSIDE STAIRS AND LANDINGS SHALL BE OF SLIP
 RESISTANT SURFACES AND DESIGNED TO MINIMIZE WATER
 ACCUMULATION ON THEIR SURFACES.
  
 04.THE NEW ELEVATOR SHALL BE IN ACCORDANCE WITH ASME
 A17.1, SAFETY CODE FOR ELEVATORS AND ESCALATORS.
  
 05.BUILDING ELEMENTS SHALL BE USED TO RESTRICT WATER
 EXPOSURE OF ELEVATOR EQUIPMENT.
  
 06.IN REFERENCE TO THE DWELLING UNIT ON SHEET E-1,
 AMEND ELECTRICAL LEGEND ON SHEET E-3 TO REFLECT SMOKE
 ALARMS INSTEAD OF SMOKE DETECTORS.SMOKE DETECTORS ARE
 TIED INTO THE BUILDING FIRE ALARM SYSTEM, WHEREAS SMOKE
 ALARMS ALERT THE OCCUPANTS OF THE SAID UNIT.
  
 07.IN NEW CONSTRUCTION, WHERE TWO OR MORE SMOKE
 ALARMS ARE REQUIRED WITHIN A DWELLING UNIT, THEY SHALL
 BE ARRANGED SO THAT OPERATION OF ANY SMOKE ALARM SHALL
 CAUSE THE ALARM IN ALL THE OTHER SMOKE ALARMS TO
 SOUND.
  
 08.AMEND ON SHEET FA-02 UNDER DUCT DETECTOR, DUCT
 SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE ALARM (AS
 PER LOCAL CODE).
  
 09. KNOX LOCKING CAPS WILL BE REQUIRED FOR THE FIRE
 DEPARTMENT CONNECTIONS.FOR APPLICATIONS, CONTACT WEST
 PALM BEACH FIRE PREVENTION BUREAU AT 561-804-4724.
  
 10.ELECTRONIC SWITCHES, CHAIN AND LOCK SHALL BE
 REQUIRED ON THE FIRE LINE BAK FLOW DEVICE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLANEACH COMMENT WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-11-24 Cont ID  
Sent By adarroug Date 2008-11-24 Time 08:31 Rev Time 0.00
Received By adarroug Date 2008-11-24 Time 08:31 Sent To  
Notes
2008-11-24 08:31:31TO "COMM" BD#63

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-09-19 Cont ID  
Sent By adarroug Date 2008-09-19 Time 14:24 Rev Time 0.00
Received By adarroug Date 2008-09-19 Time 14:21 Sent To  
Notes
2008-10-14 15:10:0910/14/08--TAKEN FROM BD AND ROUTED TO MIKE WILLIAMS
 DESK
2008-09-19 14:29:05TO "COMM" BD#39

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-04-02 Cont ID  
Sent By adarroug Date 2008-04-02 Time 16:39 Rev Time 0.00
Received By adarroug Date 2008-04-02 Time 16:39 Sent To  
Notes
2008-04-02 16:43:48TO "COMM" BD#9

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-01-14 Cont ID  
Sent By adarroug Date 2008-01-14 Time 14:36 Rev Time 0.00
Received By adarroug Date 2008-01-14 Time 14:36 Sent To  
Notes
2008-01-14 14:38:40TO "COMM" BD#56

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-22 Cont ID  
Sent By mawillia Date 2007-10-22 Time 15:04 Rev Time 0.00
Received By mawillia Date 2007-08-15 Time 10:40 Sent To  
Notes
2007-09-10 16:59:15TO "COMM" BD#12
2007-08-15 10:40:34WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2008-12-16 Cont ID  
Sent By rregueir Date 2008-12-16 Time 20:54 Rev Time 0.00
Received By rregueir Date 2008-12-16 Time 20:54 Sent To PC
Notes
2008-12-16 20:55:09CORRECTED ENERGY CALCS SUBMITTED. REVIEW NOW IN PASSED
 STATUS. PLANS SENT FOR PROCESSING/PERMIT ISSUANCE

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2008-12-13 Cont ID  
Sent By rregueir Date 2008-12-13 Time 11:02 Rev Time 0.00
Received By rregueir Date 2008-12-13 Time 10:54 Sent To  
Notes
2008-12-13 11:01:46**NOTE**
 MECHANICAL REVIEW WAS PREVIOUSLY PASSED, BUT NOW THE
 ENERGY CALCULATIONS HAVE BEEN REDONE WITH SEVERAL
 DEFICIENCIES. PLEASE SEE ELECTRICAL PLAN REVIEW DATED
 12/5/08 FOR A MOR DETAILED DESCRIPTION. MECHANICAL
 REVIEW WILL BE PASSED ONCE CORRECT ENERGY CODE
 COMPLIANCE DATA IS SUBMITTED.
 THE PREVIOUSLY PASSED MECHANICAL REVIEW STATUS WILL BE
 CHANGED TO FAIL PENDING SATISFACTIRY RESOLUTION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2008-12-13 Cont ID  
Sent By rregueir Date 2008-10-01 Time 14:50 Rev Time 0.00
Received By rregueir Date 2008-10-01 Time 14:17 Sent To  
Notes
2008-12-13 11:04:06**NOTE**
 THIS MECHANICAL REVIEW WAS PREVIOUSLY PASSED, BUT NOW
 (12/13/08) THE ENERGY CALCULATIONS HAVE BEEN REDONE
 WITH SEVERAL DEFICIENCIES. PLEASE SEE ELECTRICAL PLAN
 REVIEW DATED 12/5/08 FOR A MORE DETAILED DESCRIPTION.
 MECHANICAL REVIEW WILL BE PASSED ONCE CORRECT ENERGY
 CODE COMPLIANCE DATA IS SUBMITTED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2008-04-25 Cont ID  
Sent By rregueir Date 2008-04-25 Time 10:00 Rev Time 0.00
Received By rregueir Date 2008-04-24 Time 17:29 Sent To  
Notes
2008-04-25 10:00:24REVIEW #: 3RD
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 COMMENTS 1-4 OK
  
 5. FRC SECTION M1501.1 EXCEPTION 1: "WHERE A CLOTHES
 DRYER BOOSTER FAN IS INSTALLED AND LISTED AND LABELED
 FOR THE APPLICATION, THE MAXIMUM LENGTH OF THE EXHAUST
 DUCT, INCLUDING ANY TRANSITION DUCT, SHALL BE PERMITTED
 TO BE IN ACCORDANCE WITH THE BOOSTER FAN MANUFACTURER?S
 INSTALLATION INSTRUCTIONS."
 NO DRYER BOOSTER FAN LISTING OR INSTALLATION
 INSTRUCTIONS HAVE BEEN PROVIDED. NOTE THAT THIS SECTION
 REQUIRES THE BOOSTER FAN TO BE LISTED FOR USE IN A
 DOMESTIC CLOTHES DRYER APPLICATION. IF THIS EXCEPTION
 IS TO BE USED, PROVIDE ALL REQUIRED INFORMATION TO BE
 INCLUDED IN THE PERMIT DOCUMENTATION PRIOR TO PERMIT
 ISSUANCE.
 FRC SECTION M1501.1 EXCEPTION 2: "WHERE THE MAKE AND
 MODEL OF THE CLOTHES DRYER TO BE INSTALLED IS KNOWN AND
 THE MANUFACTURER?S INSTALLATION INSTRUCTIONS FOR SUCH
 DRYER ARE PROVIDED TO THE BUILDING OFFICIAL, THE
 MAXIMUM LENGTH OF THE EXHAUST DUCT, INCLUDING ANY
 TRANSITION DUCT, SHALL BE PERMITTED TO BE IN ACCORDANCE
 WITH THE DRYER MANUFACTURER?S INSTALLATION
 INSTRUCTIONS."
 NO DRYER MODEL OR INSTALLATION INSTRUCTIONS HAVE BEEN
 PROVIDED. IF THIS EXCEPTION IS TO BE USED, PROVIDE ALL
 REQUIRED INFORMATION TO BE INCLUDED IN THE PERMIT
 DOCUMENTATION PRIOR TO PERMIT ISSUANCE.
  
 NOTE: THE CLOTHES DRYER SHALL BE INSTALLED AND
 TRANSITION DUCT CONNECTED FOR FINAL MECHANICAL
 INSPECTION.
  
 NOTE: PLEASE ADDRESS ELECTRICAL REVIEW COMMENTS RELATED
 TO ELECTRICAL RATINGS OF A/C APPLIANCES, SHOWING
 COORDINATION BETWEEN MANUFACTURER'S REQUIREMENTS,
 ELECTRICAL PLANS AND A/C UNIT SCHEDULE ON PG AC-2.
  
 ALL OTHER MECHANICAL COMMENTS HAVE BEEN ADEQUATELY
 ADDRESSED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-02-11 Cont ID  
Sent By rregueir Date 2008-02-11 Time 15:29 Rev Time 0.00
Received By rregueir Date 2008-02-11 Time 14:31 Sent To  
Notes
2008-02-11 15:28:54REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1 THROUGH 4: OK
  
 5. BOOSTER FAN HAS BEEN ADDED TO ACCOMMODATE NEW DRYER
 EXHAUST OUTLET LOCATION. CLOTHES DRYERS SHALL BE
 EXHAUSTED IN ACCORDANCE WITH THE MANUFACTURER?S
 INSTRUCTIONS PER FBC, M 504.1. A BOOSTER FAN MAY ONLY
 BE USED IF ALLOWED BY DRYER MANUFACTURER?S INSTALLATION
 INSTRUCTIONS.
 NOTE: WHERE THE MAKE AND MODEL OF THE CLOTHES DRYER TO
 BE INSTALLED IS KNOWN AND THE MANUFACTURER?S
 INSTALLATION INSTRUCTIONS FOR SUCH DRYER ARE PROVIDED
 TO THE CODE OFFICIAL, THE MAXIMUM LENGTH OF THE EXHAUST
 DUCT, INCLUDING ANY TRANSITION DUCT, SHALL BE PERMITTED
 TO BE IN ACCORDANCE WITH THE DRYER MANUFACTURER?S
 INSTALLATION INSTRUCTIONS PER FBC 504.6.1 EXCEPTION.
 THE DRYER MANUFACTURER MAY ALLOW DRYER DUCT LENGTHS
 WHICH WILL MAKE A BOOSTER FAN UNNECESSARY. PROVIDE
 MANUFACTURER?S INSTRUCTIONS.
  
 6 AND 7: OK
  
 8. VENTILATION RATE FOR DWELLING UNIT TO BE DETERMINED
 PER THE RATIO OF OPENABLE WINDOW AND DOOR AREA TO FLOOR
 AREA IN ACCORDANCE WITH FRC 303.1. PROVIDE CALCULATIONS
 CONTAINING THIS DATA SHOWING COMPLIANCE WITH THIS
 SECTION. ASHRAE 62-89 IS NOT APPLICABLE IN THIS
 SITUATION UNDER THIS CODE AS IT IS NOT A REFERENCE
 STANDARD FOR THE FRC ACCORDING TO FRC CHAPTER 43.
  
 9. NO INFORMATION COULD BE FOUND ON PLANS REGARDING
 THIS COMMENT. THIS ISSUE CAN BE ADDRESSED BY FIELD
 INSPECTION. HOWEVER, ADDRESSING THIS NOW WITH DETAILED
 INFORMATION COULD AVOID DELAYS AND FAILED INSPECTIONS
 IN THE FUTURE.
  
 10. WIND LOAD CALCULATIONS SUBJECT TO BUILDING PLAN
 REVIEW.
  
 11. OK
  
 12. FIRESTOP DETAIL FOR REFRIGERANT PIPES SHOWN ON
 PLANS, CAJ 1047, DOES NOT MAKE PROVISIONS FOR PIPE
 INSULATION AND THEREFORE IS NOT APPROPRIATE FOR A
 REFRIGERANT PIPE APPLICATION. PROVIDE A
 THROUGH-PENETRATION FIRESTOP SYSTEM WHICH IS
 APPROPRIATE FOR THE PIPING SYSTEM BEING USED PER FBC
 712.3.
  
 NOTE: PLEASE PROVIDE WRITTEN RESPONSE TO REVIEW
 COMMENTS TO ASSIST IN SUBSEQUENT REVIEWS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-09-18 Cont ID  
Sent By rregueir Date 2007-09-18 Time 15:48 Rev Time 0.00
Received By rregueir Date 2007-09-17 Time 19:58 Sent To  
Notes
2007-09-18 15:48:53REVIEW #: 1
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. THE DESIGNER OR OWNER MUST SELECT THE LEVEL OF
 ALTERATION BEING PROPOSED PER FBC,EB 301.5.
  
 2. IS THIS A CHANGE OF OCCUPANCY? SEE FBC,EB 301.4 AND
 306.1.
  
 3. VALUE OF WORK HAS NOT BEEN DECLARED. FOR PURPOSE OF
 FBC CH,13 COMPLIANCE, IT IS ASSUMED THAT THE WORK
 QUALIFIES AS A RENOVATION AS DEFINED IN FBC 13-202.
  
 4. AC-1: LOCATION OF CU-2 APPEARS TO BE IN CONFLICT
 WITH STAIR LANDING ON WEST ELEVATION. VERIFY REQUIRED
 CLEARANCES FOR CU PER FBC,M 304.1.
  
 5. AC-1: BATH AND DRYER EXHAUST FROM RESIDENCE WILL BE
 DISCHARGING ONTO THE STAIR SHOWN ON WEST ELEVATION.
 EXHAUST AIR SHALL NOT BE DIRECTED ONTO WALKWAYS PER
 FBC,M 401.5.2.
  
 6. AC-1: REFRIGERANT LINES FOR CU-2/AHU-2, IF THEY ARE
 TO RUN ABOVE CEILING, THEY MAY BE IN CONFLICT WITJ
 STAIR ON WEST ELEVATION WHEN THEY LEAVE THE BUILDING.
 PLEASE VERIFY THERE IS NO CONFLICT. FBC 106.1.2.
  
 7. PG LSP200 SHOWS AHU IN CLOSET ON 2ND FL NEXT TO
 JANITOR'S CLOSET. PG AC-1 DOES NOT. PLEASE COORDINATE
 PLANS. FBC 106.1.1 AND 106.1.3.
  
 8. AC-1: PLEASE PROVIDE CALCULATIONS SHOWING HOW THE
 VENTILATION REQUIREMENTS OF FRC 303.1 ARE BEING MET FOR
 THE RESIDENCE.
  
 9. AC-1: ALL A/C CLOSETS SHALL BE LINED WITH A
 CONTINUOUS, NON-POPOUS, APPROVED AIR BARRIER AND
 EXTERIOR WALLS USED AS A PLENUM SHALL BE INSULATED TO
 MIN. R-8 PER FBC,M 603.8 AND 603.9.
  
 10. PG AC-1: CONDENSER MOUNTING DETAIL, FBC,M 301.13.1
 ONLY APPLIES TO R-3 OCCUPANCIES AND 5 TONS OR LESS. THE
 PRESCRIPTIVE METHOD OF 301.13.1 ONLY APPLIES TO CU-2.
 PROVIDE ENGINEERING FOR WIND LOADS AND ATTACHMNENTS FOR
 OTHER CU'S PER FBC,M 301.13 AND FBC CH.16.
  
 11. AC-1: NOTE #14, CONDENSATE DRAIN LINES SHALL BE OF
 NON COMBUSTIBLE MATERIALS PER FBC,M 602.2.1.
  
 12. AC-1: PROVIDE DETAIL AND LISTING OF
 THROUGH-PENETRATION FIRESTOP SYSTEM FOR LINES
 PENETRATING THE RATED STORAGE ROOM PER FBC 712.3.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-09-23 Cont ID  
Sent By kstevens Date 2008-09-23 Time 10:59 Rev Time 0.00
Received By kstevens Date 2008-09-23 Time 10:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-04-14 Cont ID  
Sent By kstevens Date 2008-04-14 Time 07:52 Rev Time 0.00
Received By kstevens Date 2008-04-14 Time 07:52 Sent To  
Notes
2008-04-14 07:53:05PASSED/PROVISO--RPZV BACKFLOW REQUIRE ON THE WATER
 SERVICE.

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-02-08 Cont ID  
Sent By kstevens Date 2008-02-08 Time 09:17 Rev Time 0.00
Received By kstevens Date 2008-02-07 Time 15:50 Sent To  
Notes
2008-02-08 09:36:43DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
 2. OK
 3. OK
  
 4. SHT A700 WOMENS TOILET ROOM STALL SHALL BE
 ACCESSIBLE AND SHALL MEET THE REQUIREMENTS OF FIGURE
 11-30E.--EACH WATER CLOSET UTILIZED BY THE PUBLIC
 OR EMPLOYEES SHALL OCCUPY A SEPARATE COMPARTMENT WITH
 WALLS OR PARTITIIONS AND A DOOR ENCLOSING THE FIXTURES
 TO ENSURE PRIVACY. SECTION 310.4. SHOW THE ACCESSIBLE
 TOILET AND LAV IN THE STALL/COMPARTMENT.
 ****RESPONSE NOTED, BUT THE ACCESSIBLE STALL DOES NOT
 COMPLY WITH FIG 11-30E. THE CLEAR FLOOR SPACE FOR THE
 W/C IS NOT INDICATED ON THE FLOOR PLAN, AND THE SIDE OF
 THE LAV IS LESS THAN 5' OFF THE WALL ADJACENT TO THE OF
 THE W/C AS REQUIRED IN FIG 11-30E.
  
 5. OK
  
 6. SHT A700 MENS TOILET ROOM SHALL BE ACCESSIBLE AND
 SHALL MEET THE REQUIREMENTS OF FIGURE 11-30E.-- EACH
 WATER CLOSET UTILIZED BY THE PUBLIC OR EMPLOYEES SHALL
 OCCUPY A SEPARATE COMPARTMENT WITH WALLS OR PARTITIIONS
 AND A DOOR ENCLOSING THE FIXTURES TO ENSURE PRIVACY.
 SECTION 310.4. SHOW THE ACCESSIBLE TOILET AND LAV IN
 THE STALL/COMPARTMENT.
 ****RESPONSE NOTED, BUT THE ACCESSIBLE STALL DOES NOT
 COMPLY WITH FIG 11-30E. THE CLEAR FLOOR SPACE FOR THE
 W/C IS NOT INDICATED ON THE FLOOR PLAN, AND THE SIDE OF
 THE LAV IS LESS THAN 5' OFF THE WALL ADJACENT TO THE OF
 THE W/C AS REQUIRED IN FIG 11-30E.
  
 7. OK
  
 8. SHT A700 PLEASE SHOW COMPLIANCE FOR THE FOLLOWING:
 ___W/C'S
 A. 11-4.16.5 FLUSH CONTROLS
 ****NOT ADDRESSED
 ___URINAL
 A. 11-4.18.2 HEIGHT
 ****NOT ADDRESSED
 B. 11-4.18.3 CLEAR FLOOR SPACE
 ****NOT ADDRESSED
 C. 11-4.18.4 FLUSH CONTROLS
 ****NOT ADDRESSED
 ___ FOR LAVS
 A. 11-4.19.5 FAUCETS
 ___SHOWERS
 A. 11-4.21.2 SIZE & CLEARANCES
 ****NOT ADDRESSED, SHOWS 3'-10-5/8"
 B. OK
 C. OK
 D. OK
 C. OK
 E. OK
  
 9. OK
 10. OK
 11. OK
 12. OK
  
 13. SHT P-2 WATER RISER DIAGRAM. AN RPZV BACKFLOW IS
 REQUIRED ON THE WATER SERVICE TO THE COMMERCIAL
 OCCUPANCY. SECTION 608.13.2. PLEASE INDICATE ON THE
 RISER DIAGRAM.
 ****RESPONSE NOTED, BUT THE CIVIL PLANS HAVE NOT BEEN
 SUBMITTED.
  
 14. OK
  
 15. THE ENERGY EFFICIENCY CODE SYSTEM COMPLIANCE REPORT
 DOES NOT REFLECT WHAT IS SHOWN ON SHT P-3. REPORT
 INDICATES NONE FOR THE WATER HEATER, BUT SHT P-3
 INDICATES TYPICAL WATER HEATER 80 GAL, 4.5KW, 208V.
 PLEASE CORRELATE.--INPUT DATA REPORT ALSO SHOWS NO
 INFORMATION FOR THE WATER HEATER.--THE RESIDENTIAL
 WHOLE BUILDING PERFORMANCE METHOD A INDICATES A 50 GAL
 CAP. WATER HEATER WHICH DOES NOT RELFECT THE 80 GAL
 SHOWN ON SHT P-3. PLEASE CORRELATE INFORMATION. SECTION
 13-103.
 ****NO RESPONSE, NOT ADDRESSED. (ALSO SEE COMMENT
 NUMBER ONE OF THE ELECTRICAL PLAN REVIEW).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-09-27 Cont ID  
Sent By kstevens Date 2007-09-27 Time 10:44 Rev Time 0.00
Received By kstevens Date 2007-09-26 Time 18:57 Sent To  
Notes
2007-09-27 16:26:37DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS WITH DALIMA STUDIO TITLE BLOCK. THE FIRMS
 LICENSE NUMBER, (CERTIFICATE OF AUTHORIZATION), IS
 REQUIRED ON EACH SHEET. FAC 61G1-16.004(2) & FS
 481.219, 481.2055. PLEASE INDICATE FIRM LICENSE NUMBER
 IN THE TITLE BLOCK ON EACH SHEET.
  
 2. SHT A200. THE A-3 OCCUPANCY REQUIRES A DRINKING
 FOUNTAIN, BUT A BOTTLED WATER COOLER IS SHOWN. THIS IS
 NOT APPROVED. BOTTLED WATER DISPENSERS SHALL BE
 PERMITTED TO BE SUBSTITUTED FOR NOT MORE THAN 50% OF
 THE REQUIRED DRINKING FOUNTAINS. SINCE ONLY ONE
 DRINKING FOUNTAIN IS REQUIRED, THE BOTTLED WATER
 DISPENSER IS BEING SUBSTITUTED FOR 100% OF THE REQUIRED
 FIXTURES. TABLE 403.1 AND SECTION 410.1. PLEASE
 INDICATE THE LOCATION OF THE DRINKING FOUNTAIN.
  
 3. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN SHOWING
 COMPLIANCE WITH SECTION 11-4.15 AND ALL SUBSECTIONS AS
 WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE
 WHO HAVE DIFFICULTY BENDING OR STOOPING.
  
 4. SHT A700 WOMENS TOILET ROOM STALL SHALL BE
 ACCESSIBLE AND SHALL MEET THE REQUIREMENTS OF FIGURE
 11-30E.--EACH WATER CLOSET UTILIZED BY THE PUBLIC
 OR EMPLOYEES SHALL OCCUPY A SEPARATE COMPARTMENT WITH
 WALLS OR PARTITIIONS AND A DOOR ENCLOSING THE FIXTURES
 TO ENSURE PRIVACY. SECTION 310.4. SHOW THE ACCESSIBLE
 TOILET AND LAV IN THE STALL/COMPARTMENT.
  
 5. SHT A700 WOMENS TOILET ROOM WILL REQUIRE ANOTHER LAV
 FOR THE W/C OUTSIDE THE ACCESSIBLE STALL. SECTION
 405.3.2.. PLEASE SHOW THE LOCATION OF THE LAV OUTSIDE
 THE ACCESSIBLE STALL.
  
 6. SHT A700 MENS TOILET ROOM SHALL BE ACCESSIBLE AND
 SHALL MEET THE REQUIREMENTS OF FIGURE 11-30E.-- EACH
 WATER CLOSET UTILIZED BY THE PUBLIC OR EMPLOYEES SHALL
 OCCUPY A SEPARATE COMPARTMENT WITH WALLS OR PARTITIIONS
 AND A DOOR ENCLOSING THE FIXTURES TO ENSURE PRIVACY.
 SECTION 310.4. SHOW THE ACCESSIBLE TOILET AND LAV IN
 THE STALL/COMPARTMENT.
  
 7. SHT A700 WOMENS TOILET ROOM WILL REQUIRE ANOTHER LAV
 FOR THE URINAL OUTSIDE THE ACCESSIBLE STALL. SECTION
 405.3.2.. PLEASE SHOW THE LOCATION OF THE LAV OUTSIDE
 THE ACCESSIBLE STALL.
  
 8. SHT A700 PLEASE SHOW COMPLIANCE FOR THE FOLLOWING:
 ___W/C'S
 A. 11-4.16.5 FLUSH CONTROLS
 ___URINAL
 A. 11-4.18.2 HEIGHT
 B. 11-4.18.3 CLEAR FLOOR SPACE
 C. 11-4.18.4 FLUSH CONTROLS
 ___ FOR LAVS
 A. 11-4.19.5 FAUCETS
 ___SHOWERS
 A. 11-4.21.2 SIZE & CLEARANCES
 B. 11-4.21.3 SEATS
 C. 11-4.21.4 GRAB BARS
 D. 11-4.21.5 CONTROLS
 C. 11-4.21.6 SHOWER UNITS
 E. 11-4.21.7 CURBS
 PLEASE SUBMIT DETAILS OR ELEVATIONS AND ADJUST DETAILS
 ALREADY SUBMITTED. SEE SECTION 11-4.23AND ALL
 SUBSECTIONS.
  
 9. SHT P-1 DETAIL 1 THE SHOWER IN BATHROOM #2. PER
 TABLE 906.1 THE MAXIMUM DISTANCE FROM THE TRAP TO THE
 VENT FOR 2" IS 6FT. PER THE FLOOR PLAN, THIS SCALES OUT
 TO 8FT. PLEASE CHECK DISTANCE FROM TRAP TO VENT FOR THE
 SHOWER.
  
 10. SHT P-1 DETAIL 1 APPLIANCE P-6 IS NOT INDICATED ON
 THE PLUMBING FIXTURE SCHEDULE FOUND ON SHT P-3. PLEASE
 INDICATE WHAT TYPE OF FIXTURE THIS IS. SECTION
 106.1.1.
  
 11. SHT P-1 DETAIL 1 BATHROOM 3 IS INDICATED AS CLOSET
 NO.3. PLEASE CLARIFY. (ALSO SEE OTHER SHEETS). SECTION
 106.1.1.
  
 12. SHT P-2 SANITARY RISER DIAGRAM. ITEM P-6. IF THE
 ITEM IS A WASH MACHINE, THEN 3" IS REQUIRED FOR THE
 BRANCH DRAIN AND STACK SECTION 406.3--ALSO A
 STANDPIPE IS REQUIRED FOR THE W/M PER SECTIONS 1002.1 &
 802.4.--A CLEANOUT SHALL BE INSTALLED AT LEAST 4FT
 ABOVE THE FLOOR PER SECTION 708.9. PLEASE SHOW ON THE
 ISOMETRIC IF P-6 IS THE WASH MACHINE.
  
 13. SHT P-2 WATER RISER DIAGRAM. AN RPZV BACKFLOW IS
 REQUIRED ON THE WATER SERVICE TO THE COMMERCIAL
 OCCUPANCY. SECTION 608.13.2. PLEASE INDICATE ON THE
 RISER DIAGRAM.
  
 14. SHT P-3 PLEASE SUBMIT THE CALCULATIONS FOR THE
 EXPANSION TANK. PLEASE SUBMIT THE MANUF. SPECIFICATION
 SHEETS FOR THE EXPANSION TANK AND INDICATE THE MODEL
 NUMBER. SECTION 607.3.2.
  
 15. THE ENERGY EFFICIENCY CODE SYSTEM COMPLIANCE REPORT
 DOES NOT REFLECT WHAT IS SHOWN ON SHT P-3. REPORT
 INDICATES NONE FOR THE WATER HEATER, BUT SHT P-3
 INDICATES TYPICAL WATER HEATER 80 GAL, 4.5KW, 208V.
 PLEASE CORRELATE.--INPUT DATA REPORT ALSO SHOWS NO
 INFORMATION FOR THE WATER HEATER.--THE RESIDENTIAL
 WHOLE BUILDING PERFORMANCE METHOD A INDICATES A 50 GAL
 CAP. WATER HEATER WHICH DOES NOT RELFECT THE 80 GAL
 SHOWN ON SHT P-3. PLEASE CORRELATE INFORMATION. SECTION
 13-103.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date 2008-10-03 Cont ID  
Sent By kdfreema Date 2008-10-03 Time 11:54 Rev Time 0.00
Received By kdfreema Date 2008-10-03 Time 11:54 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2008-04-04 Cont ID  
Sent By choops Date 2008-04-04 Time 10:27 Rev Time 0.00
Received By choops Date 2008-04-04 Time 10:27 Sent To  
Notes
2008-04-04 10:27:59***APPROVAL PER AJV***

Review Stop Z ZONING
Rev No 2 Status P Date 2008-01-17 Cont ID  
Sent By choops Date 2008-01-17 Time 15:28 Rev Time 0.00
Received By choops Date 2008-01-17 Time 15:28 Sent To  
Notes
2008-01-17 15:29:09***APPROVAL PER AJV***

Review Stop Z ZONING
Rev No 1 Status F Date 2007-09-18 Cont ID  
Sent By choops Date 2007-09-18 Time 16:32 Rev Time 0.00
Received By choops Date 2007-09-18 Time 16:32 Sent To  
Notes
2007-09-18 16:32:54PLAN REVIEW - NO COMMENTS AT THIS TIME PER AJV.FINAL
 APPROVAL SHALL BE MADE UPON SUBMITTAL FOR PERMIT.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved