| Plan Review Stops For Permit 07080406 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2008-02-12 |
|
|
Cont ID |
|
| Sent By |
lursu |
Date |
2008-02-12 |
Time |
08:05 |
Rev Time |
0.00 |
| Received By |
lursu |
Date |
2008-02-12 |
Time |
08:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2008-12-10 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-12-10 |
Time |
08:38 |
Rev Time |
1.11 |
| Received By |
jwitmer |
Date |
2008-12-10 |
Time |
08:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2008-10-07 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-10-07 |
Time |
08:44 |
Rev Time |
3.33 |
| Received By |
jwitmer |
Date |
2008-10-07 |
Time |
08:44 |
Sent To |
|
|
| Notes |
| 2008-10-07 08:49:05 | BUILDING PLAN REVIEW | | | PERMIT: 07080406 | | | ADD: 2027 SPRUCE | | | CONT: JAW CONSTRUCTION | | | TEL: (561)333-6738 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW TUES OCT 07/08 | | | ACTION: DENIED | | | | | | 1) PLANS APPEAR TO BE CODE COMPLIANT, WILL NEED TO GO | | | TO PALM BEACH COUNTY BUILDING DEPARTMENT FOR REVIEW FOR | | | IMPACT FEES (ASSEMBLY OCCUPANCY). ONCE PLANS ARE | | | REVIEWED AND STAMPED FOR IMPACT FEES | | | THE BUILDING REVIEW WILL BE CHANGED TO A PASS, THIS | | | DOES NOT CONSTITUTE AS ANOTHER REVIEW. | | | | | | BUILDING PLAN REVIEW | | | PERMIT: 07080406 | | | ADD: 2027 SPRUCE | | | CONT: JAW CONSTRUCTION | | | TEL: (561)333-6738 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2008-04-22 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-04-22 |
Time |
16:25 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2008-04-22 |
Time |
16:25 |
Sent To |
|
|
| Notes |
| 2008-04-22 16:25:40 | BUILDING PLAN REVIEW | | | PERMIT: 07080406 | | | ADD: 2027 SPRUCE | | | CONT: JAW CONSTRUCTION | | | TEL: (561)333-6738 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW | | | ACTION: DENIED | | | | | | 1-6) COMPLIED. | | | | | | 7) 3RD REQUEST, ROOFING SYSTEMS- THE SUB-SYSTEM | | | HIGHLIGHTED ON PAGES 14-15 LIST A MAXIMUM DESIGN | | | PRESSURE OF -45 WITH LIMITATION# 7. NOTE UNDER | | | LIMITATION# 7 DOES ALLOW ENHANCED FASTENING IN ZONES 2 | | | & 3 TO THE CALCULATION RAS 117. PLEASE HAVE YOUR DESIGN | | | PROFESSIONAL PROVIDE THE RAS 117 FOR THE ENHANCED | | | FASTENING IN ZONES 2& 3. | | | FIRST OFF THE PROBLEM WITH THE LETTER FROM TURQUOISE | | | ENGINEERING IS THIS IS A COPY NOT AN ORIGINAL SIGNED | | | AND SEALED ORIGINAL. THE SECOND ISSUE WITH THE PROPERTY | | | BEING IN EITHER A "B" ZONE OR "C" ZONE, YES I DID STATE | | | THIS PROPERTY LIES IN A "B" ZONE BUT THE ENGINEER OF | | | RECORD WOULD NEED TO CHANGE THEIR PLAN TO INDICATE A | | | "B" ZONE. SHEET S100 THE STRUCTURAL DESIGNER OR | | | ENGINEER JOSE A TOLEDO HAS ELECTED TO DESIGN THIS | | | BUILDING TO A MORE RESTRICTIVE "C" ZONE WITH THE HIGHER | | | ASSCIATED PRESSURES. MR. TOLEDO HAS ALSO USED THE | | | HIGHER "C" VALUES FOR THE MOMENT OF OVER TURNING FOR | | | THE CALCULATIONS FOR THE A/C UNITS. PLEASE EITHER HAVE | | | THE DESIGN PROFESSIONAL IN CHARGE OF THE PROJECT CHANGE | | | FROM THE CZONE AND ASSOCIATED PRESSURES OR PROVIDE RAS | | | 117 CALCYULATIONS FOR THE "C" ZONE. NOTE ALSO INEITHER | | | CASE IF ANOTHER ENGINNER IS BROUGHT IN FOR THE ROOFING | | | APPROVALS, THE ENGINEER OF RECORD WILL NEED TO REVIEW | | | THE DESIGN AND CALCULATIONS BEFORE SUBMITTING TO THE | | | BUILDING DEPARTMENT. | | | | | | 8) 3RD REQUEST, SEMI-COMPLIED: HURRICANE SHUTTERS, | | | SEMI- COMPLIED. PLEASE SEE THE ADDTIONAL INFORMATION | | | THAT IS REQUIRED FOR USE OF STORM PANELS. A SAMPLE OF | | | AN INSTALLATION SCHEDULE IS ATTACHED. | | | NOTE MANY OF THE WINDOWS SUBMITTED ARE A FIN TYPE | | | WINDOW THAT WILL REQUIRE THE STORM SHUTTERS TO BE SET | | | AWAY FROM THE GLAZING BECAUSE OF THE DEFLECTION OF THE | | | STORM PANEL DURING A HIGH WIND EVENT. HIGHLIGHT OR | | | CIRCLE WHICH TYPE OF INSTALLATION WILL BE USED AND TYPE | | | OF FASTENERS. | | | | | | PROVIDE STORM PANEL INFORMATION WITH INSTALLATION | | | SCHEDULE AND KEY PLAN WITH SPECIFIC ANCHORS AND | | | MOUNTING TO BE USED FOR ALL NON-IMPACT GLAZING. FBC | | | 1609.1.4. FL BLD CODE 2004 SECTION 106.3.3, 1609.1.4, | | | 1714.5.1 & EXIST BUILD CODE 507.3. PROCEDURES: 1(B) A | | | COMPLETE INSTALLATION SCHEDULE SUMMARIZING & | | | IDENTIFYING OPENING SIZES, STORY HEIGHTS, UNIT MARK | | | NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM BAR REINFORCING | | | REQUIREMENTS, WALL PRESSURE ZONES, SLAT TYPES, ETC., | | | SHALL BE SUBMITTED AT TIME OF PERMIT APPLICATION TO | | | FACILITATE PLAN REVIEW AND PERMIT ISSUANCE. | | | | | | 9-21) COMPLIED. | | | | | | 22) AGAIN SEE ELECTRICAL COMMENTS ABOUT THE ENERGY | | | CALCULATIONS. | | | | | | 23-25) COMPLIED. | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE.) | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2008-02-14 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-02-14 |
Time |
16:46 |
Rev Time |
3.33 |
| Received By |
jwitmer |
Date |
2008-02-14 |
Time |
16:46 |
Sent To |
|
|
| Notes |
| 2008-02-14 16:47:33 | BUILDING PLAN REVIEW | | | PERMIT: 07080406 | | | ADD: 2027 SPRUCE | | | CONT: JAW CONSTRUCTION | | | TEL: (561)333-6738 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW | | | ACTION: DENIED | | | | | | 1A)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | | ANTICIPATED COOPERATION. | | | | | | 1B) INFORMATIONAL,PLEASE SUBMIT 2 OF ALL SURVEYS, | | | PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR | | | SUBMITTALS FOR REVIEW FOR PERMIT. | | | IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF | | | YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A | | | THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID | | | DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1* | | | /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH | | | ADMINISTRATIVE CODE. | | | | | | 1C)INFORMATIONAL,106.1.1* W.P.B. ADMINISTRATIVE | | | CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN | | | INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO | | | THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO | | | CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION | | | SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE | | | CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR | | | ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC | | | INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE | | | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND | | | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT | | | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS | | | DETERMINED BY THE BUILDING OFFICIAL. | | | | | | 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE | | | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT | | | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) | | | AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC | | | BUILDING WITH THE2007 SUPPLEMENTS. PLEASE INCORPORATE | | | INTO PLAN DATA. | | | | | | 2-5)COMPLIED FROM FIRST REVIEW. | | | | | | 6) SEMI-COMPLIED. PLANS A302 INDICATE THE USE OF 1 HOUR | | | FIRE RATED WINDOW SYSTEMS AT THE EXTERIOR STAIRS. THERE | | | HAS BEEN NO PRODUCT APPROVAL INFORMATION SUBMITTED FOR | | | THE FIRE RATED WINDOWS, NOTE THESE WINDOW WILL REQUIRE | | | STORM SHUTTERS THE MANUFACTURERS DO NOT MAKE A FIRE | | | RATED LARGE MISSLE RATED ASSEMBLY. | | | | | | 7) ROOFING SYSTEMS- THE SUB-SYSTEM HIGHLIGHTED ON PAGES | | | 14-15 LIST A MAXIMUM DESIGN PRESSURE OF -45 WITH | | | LIMITATION# 7. NOTE UNDER LIMITATION# 7 DOES ALLOW | | | ENHANCED FASTENING IN ZONES 2 & 3 TO THE CALCULATION | | | RAS 117. PLEASE HAVE YOUR DESIGN PROFESSIONAL PROVIDE | | | THE RAS 117 FOR THE ENHANCED FASTENING IN ZONES 2& 3. | | | | | | 8) HURRICANE SHUTTERS, SEMI- COMPLIED. PLEASE SEE THE | | | ADDTIONAL INFORMATION THAT IS REQUIRED FOR USE OF STORM | | | PANELS.PROVIDE STORM PANEL INFORMATION WITH | | | INSTALLATION SCHEDULE AND KEY PLAN WITH SPECIFIC | | | ANCHORS AND MOUNTING TO BE USED FOR ALL NON-IMPACT | | | GLAZING. FBC 1609.1.4.FL BLD CODE 2004 SECTION | | | 106.3.3, 1609.1.4, 1714.5.1 & EXIST BUILD CODE 507.3. | | | PROCEDURES: 1(B) A COMPLETE INSTALLATION SCHEDULE | | | SUMMARIZING & IDENTIFYING OPENING SIZES, STORY HEIGHTS, | | | UNIT MARK NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM BAR | | | REINFORCING REQUIREMENTS, WALL PRESSURE ZONES, SLAT | | | TYPES, ETC., SHALL BE SUBMITTED AT TIME OF PERMIT | | | APPLICATION TO FACILITATE PLAN REVIEW AND PERMIT | | | ISSUANCE. | | | | | | 9-21) COMPLIED. | | | | | | 22) PLEASE SEE ELECTRICAL NOTES ON ENERGY | | | CALCULATIONS. | | | | | | NEW COMMENTS | | | | | | 23)2-29-08 COMPLIED. EXCEPTION TO 302.3.2 FOR FIRE | | | SPRINKLERS 1 HR REDUCTION BUT NOT LESS THAN 1 HR.OK | | | | | | 24) SHOWER STALLS- 11-4.23.2 DOORS SHALL NOT SWING INTO | | | THE CLEAR FLOOR SPACE REQUIRED FOR FIXTURES. THE MAIN | | | DOOR TO THE RESTROOM OVERLAYS THE CLEAR FLOOR SPACE | | | REQUIRED FORTHE SHOWER. | | | | | | 25) 11-4.13.7 DOORS IN SERIES PLEASE REVIEW THE | | | RESTROOM ENTRY DOOR AND THE ACCESSIBLE STALL DOOR. | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-09-21 |
|
|
Cont ID |
|
| Sent By |
jjohnsto |
Date |
2007-09-21 |
Time |
13:04 |
Rev Time |
4.00 |
| Received By |
jjohnsto |
Date |
2007-09-21 |
Time |
8:00 |
Sent To |
|
|
| Notes |
| 2007-09-21 13:07:55 | CONSTRUCTION SERVICES DEPARTMENT | | | 200 SECOND STREET, 3RD FLOOR, WEST PALM BEACH, | | | FLORIDA33401 | | | TEL:561-805-6713FAX: | | | 561-805-6731 | | | | | | JAMES JOHNSTON, PERMIT NO 07080406 | | | BUILDING PLAN EXAMINERII PROJECT MASONIC LODGE | | | E-MAIL:JJOHNSTON @WPB.ORG ADDRESS 2027 SPRUCE | | | AVENUE | | | CONTRACTOR WPB HOUSING AUTHORITY | | | DATE SEPTEMBER 19, 2007 | | | | | | | | | STRUCTURALPLANREVIEW | | | | | | | | | | | | FBC 1604.5 IMPORTANCE FACTOR. | | | 1 THE VALUE FOR WIND LOAD IMPORTANCE FACTOR SHALL BE | | | DETERMINED IN ACCORDANCE WITH TABLE 1604.5 . | | | COMMENT -IDENTIFY WIND IMPORTANCE FACTOR SHEET CS100 | | | | | | 2 FBC CHAPTER 3IDENTIFY RESIDENTIAL OCCUPANCYR-3 | | | | | | COMMENT- IDENTIFY OCCUPANCIES ON CS100R-3 AND A-3 | | | | | | 3 FBC1004.1 DESIGN OCCUPANT LOAD. | | | IN DETERMINING MEANS OF EGRESS REQUIREMENTS, THE NUMBER | | | OF OCCUPANTS FOR WHOM MEANS OF EGRESS FACILITIES SHALL | | | BE PROVIDED SHALL BE ESTABLISHED BY THE LARGEST NUMBER | | | COMPUTED IN ACCORDANCE WITH SECTIONS 1004.1.1 THROUGH | | | 1004.1.3 . | | | COMMENT-ASSEMBLY -CHAIRS ONLY 116 OCCUPANTS | | | | | | 4 FBC1004.3 POSTING OF OCCUPANT LOAD. | | | EVERY ROOM OR SPACE THAT IS AN ASSEMBLY OCCUPANCY SHALL | | | HAVE THE OCCUPANT LOAD OF THE ROOM OR SPACE POSTED IN A | | | CONSPICUOUS PLACE, NEAR THE MAIN EXIT OR EXIT ACCESS | | | DOORWAY FROM THE ROOM OR SPACE. POSTED SIGNS SHALL BE | | | OF AN APPROVED LEGIBLE PERMANENT DESIGN AND SHALL BE | | | MAINTAINED BY THE OWNER OR AUTHORIZED AGENT. | | | COMMENT -IDENTIFY SIGNAGE IN AREA OF OCCUPANT LOAD | | | | | | 5. 1.3.3 LOCATION OF ROOF INSULATION. | | | THE ROOF INSULATION SHALL NOT BE INSTALLED ON A | | | SUSPENDED CEILING WITH REMOVABLE CEILING PANELS. | | | THIS IS LOCATED IN THE FBC ENERGY REQUIREMENTS.SHEET | | | A-400DETAIL 1-A 400 SUGGEST THIS AS AN OPTION | | | | | | 6. WINDOW SCHEDULE | | | PLEASE NOTE ON SHEET A-500 WINDOW SCHEDULE THE IMPACT | | | WINDOW DESIGNATION VS. THE NON-IMPACT DESIGNATION | | | | | | | | | | | | | | | | | | PRODUCT APPROVALS | | | | | | 7 ROOF SYSTEM PRODUCT APPROVAL | | | COMMENT -HIGHLIGHT THE COMPONENTS TO BE USED IN THIS | | | SYSTEM | | | | | | 8 HURRICANE SHUTTER PRODUCT APPROVAL | | | COMMENT -APPROVAL EXPIRED AUGUST 22, 2007 | | | | | | 9 WINDOW PRODUCT APPROVAL | | | PGT INDUSTRIESALUMINUM FIXED WINDOW | | | COMMENT -APPROVAL WILL EXPIRE OCTOBER 3, 2007 | | | | | | | | | FBCEXISTING CHAPTER 2 ? DEFINITION WORK AREA. | | | THAT PORTION OR PORTIONS OF A BUILDING CONSISTING OF | | | ALL RECONFIGURED ELEMENTS, SYSTEMS OR SPACES AS | | | INDICATED ON THE CONSTRUCTION DOCUMENTS. WORK AREA | | | EXCLUDES OTHER PORTIONS OF THE BUILDING WHERE | | | INCIDENTAL WORK ENTAILED BY THE INTENDED WORK MUST BE | | | PERFORMED AND PORTIONS OF THE BUILDING WHERE WORK NOT | | | INITIALLY INTENDED BY THE OWNER IS SPECIFICALLY | | | REQUIRED BY THIS CODE. | | | | | | 10 FBCEXISTING605.4.3 DOOR CLOSING. | | | IN ANY WORK AREA, ALL DOORS OPENING ONTO AN EXIT | | | PASSAGEWAY AT GRADE OR AN EXIT STAIR SHALL BE | | | SELF-CLOSING OR AUTOMATICALLY CLOSING BY LISTED CLOSING | | | DEVICES. | | | COMMENT ?ND 35,ND 01 | | | | | | 11 FBC EXISTING607.3 NEW STRUCTURAL MEMBERS. | | | NEW STRUCTURAL MEMBERS IN ALTERATIONS, INCLUDING | | | CONNECTIONS AND ANCHORAGE, SHALL COMPLY WITH THE | | | FLORIDA BUILDING CODE, BUILDING. | | | COMMENT - THIS INCLUDES ROOF SYSTEM/ELEVATOR SHAFT/ | | | INTERIOR AND EXTERIOR COMPONENTS | | | | | | 12 FBC1604.8.1 GENERAL. | | | ANCHORAGE OF THE ROOF TO WALLS AND COLUMNS, AND OF | | | WALLS AND COLUMNS TO FOUNDATIONS, SHALL BE PROVIDED TO | | | RESIST THE UPLIFT AND SLIDING FORCES THAT RESULT FROM | | | THE APPLICATION OF THE PRESCRIBED LOADS. | | | COMMENT - ELEVATOR SHAFT ENCLOSURE | | | | | | | | | 13 SHEETS-200? STRUCTURAL NOTES ? | | | COMMENTS | | | 7-SIDENTIFY SLEEVE ANCHOR EMBEDMENT INTO CONCRETE | | | | | | 10-SIDENTIFY # 4 DOWEL EMBEDMENT INTO CONCRETE. | | | | | | SHEET S-100IDENTIFY TIE BEAM ELEVATIONS ON SCHEDULE | | | | | | | | | FBC EXISTING812.5 ACCESSIBILITY. | | | EXISTING BUILDINGS OR PORTIONS THEREOF THAT UNDERGO A | | | CHANGE OF GROUP OR OCCUPANCY CLASSIFICATION SHALL | | | COMPLY WITH CHAPTER 11 OF THE FLORIDA BUILDING CODE, | | | BUILDING. | | | | | | 14 FBC ACCESSIBILITY 11-4.10 ELEVATORS | | | COMMENTPLEASE PROVIDE NOTE ON PLAN ELEVATOR MUST | | | COMPLY WITH THIS SECTION | | | | | | | | | | | | 15 FBC11-4.10.9 FLOOR PLAN OF ELEVATOR CARS. | | | THE FLOOR AREA OF ELEVATOR CARS SHALL PROVIDE SPACE FOR | | | WHEELCHAIR USERS TO ENTER THE CAR, MANEUVER WITHIN | | | REACH OF CONTROLS, AND EXIT FROM THE CAR. ACCEPTABLE | | | DOOR OPENING AND INSIDE DIMENSIONS | | | THE CLEARANCE BETWEEN THE CAR PLATFORM SILL AND THE | | | EDGE OF ANY HOIST WAY LANDING SHALL BE NO GREATER THAN | | | 1 1 / 4 INCHES (32 MM). | | | | | | 16 ELEVATOR PIT | | | COMMENTIDENTIFY THE DEPTH OF THE PIT FROM FINISHED | | | FLOOR AND ALL OTHER REQUIRED MEASUREMENTS | | | | | | 17 FBC3006.2 VENTING. | | | ELEVATOR MACHINE ROOMS THAT CONTAIN SOLID-STATE | | | EQUIPMENT FOR ELEVATOR OPERATION SHALL BE PROVIDED WITH | | | AN INDEPENDENT VENTILATION OR AIR-CONDITIONING SYSTEM | | | TO PROTECT AGAINST THE OVERHEATING OF THE ELECTRICAL | | | EQUIPMENT. THE SYSTEM SHALL BE CAPABLE OF MAINTAINING | | | TEMPERATURES WITHIN THE RANGE ESTABLISHED FOR THE | | | ELEVATOR EQUIPMENT. | | | COMMENT -WILL THIS SECTION APPLY? | | | | | | | | | 18 FBC1807.3.2 WALLS. ELEVATOR SHAFT WALLS | | | WALLS REQUIRED TO BE WATERPROOFED SHALL BE OF CONCRETE | | | OR MASONRY AND SHALL BE DESIGNED AND CONSTRUCTED TO | | | WITHSTAND THE HYDROSTATIC PRESSURES AND OTHER LATERAL | | | LOADS TO WHICH THE WALLS WILL BE SUBJECTED. | | | COMMENTTHE WALLS OF THE ELEVATOR PIT ARE SUBJECT TO | | | GROUND WATER/MOISTURE INTRUSION. PLEASE DEFINE A | | | WATERPROOFING SYSTEM (NEGATIVE SIDE) OR IF NOT | | | REQUIRED, A SOIL TEST REPORT ON THE GROUND WATER | | | CONDITION | | | | | | | | | FBCRESIDENTIALENERGY CALCULATIONS13-6 | | | | | | PERFORMANCE METHOD ABASE / AS-BUILT | | | | | | 19 GLASS TYPES | | | EAST WALLAREA WITHOUT DEDUCTING FRAME 52.17 S.F. | | | YOUR CALCULATIONS WITH FRAME DEDUCTION 38.5 S.F. | | | PLEASE EXPLAINTHIS. | | | | | | 20 DOOR TYPES | | | EXTERIOR DOOR STEEL.YOUR CALCULATIONS BASED ON WOOD. | | | PLEASE EXPLAIN THIS | | | | | | 21 CEILING TYPES | | | AREA UNDER ATTIC HAS NO INSULATION. THERE IS A | | | CONDITIONED SECOND FLOOR ABOVE THIS RESIDENCE.YOUR | | | CALCULATIONS STATE R 19. PLEASE EXPLAIN THIS. | | | | | | | | | FBCENERGY CALCULATIONS13-6METHOD A WHOLE | | | BUILDING PERFORMANCE | | | | | | SIGNATURE PAGE 3 | | | 22 SIGNATURES ARE MISSING FOR THE ARCHITECT AND | | | ELECTRICAL DESIGNER |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2008-12-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-12-15 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-12-15 |
Time |
14:17 |
Sent To |
M |
|
| Notes |
| 2008-12-15 14:18:10 | NEW FORM B UNDER CORRECT VERSION 2.5 BROUGHT IN. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2008-12-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-12-05 |
Time |
14:43 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-12-05 |
Time |
14:43 |
Sent To |
|
|
| Notes |
| 2008-12-05 14:44:04 | | | | ** FAILED REVIEW 5TH TIME. ** | | | | | | ** A CALL WAS PLACED TO THE ELECTRICAL ENGINEER AND | | | LEFT MESSAGE ON VOICE-MAIL TO RETURN CALL AS SOON AS | | | POSSIBLE TO GO OVER NOTE BELOW. | | | | | | 1) NOTE: THE SUBMITTED FLA-COM CALCULATIONS ARE NOW | | | METHOD*B* WHICH IS DIFFERENT FROM PREVIOUS SUBMITTED | | | CALCULATIONS. PLEASE SEE SECTION 13-400.B.3 OF THE | | | FLORIDA BUILDING CODE. THE VERSION SUBMITTED IS NOT | | | ADOPTED BY THE STATE OF FLORIDA. THIS HAS BEEN | | | DISCUSSED AND CONFIRMED ON MORE THAN ONE OCCASION WITH | | | MO MADANI WITH DEPARTMENT OF COMMUNITY AFFAIRS. THE | | | ADOPTED VERSION IS 2.5. | | | PLEASE SEE THE FOLLOWING WORDING WHICH IS TAKEN | | | DIRECTLY FROM THE ENERGY GAUGE WEBSITE. PLEASE BE SURE | | | TO READ THE LAST LINE IN PARENTHESIS. YOU WILL SEE IT | | | STATES **VERSION 2.5**. | | | IT IS IMPORTANT TO KNOW THAT IT IS THE UNDERSTANDING TO | | | THIS OFFICE THAT THERE IS A FREE PATCH ON THEIR WEBSITE | | | IN ORDER TO OBTAIN CORRECT VERSION. IT IS ALSO THE | | | UNDERSTANDING OF THIS REVIEWER/OFFICE FROM NUMEROUS | | | OTHER DESIGNERS WHO HAVE HAD TO DO THIS IS THERE IS NO | | | FEE ASSOCIATED WITH PATCH. | | | | | | ***BUILDING OFFICIALS: ENERGYGAUGE SUMMIT VERSION 3.00 | | | THROUGH 3.14 SATISFIES THE REQUIREMENTS IN 13-400.3.A | | | AND 13-400.3.B (GENERATED BY FLA/COM-2004 COMPUTER | | | PROGRAM, VERSION 2.5).*** | | | | | | | | | | | | | | | THERE WILL BE COMMENTS FROM OTHER TRADES WITH RESPECT | | | TO OTHER COMPONENTS ON THE INPUT DATA REPORT OF THE | | | SUBMITTED CALCULATIONS. AS A *HEADS-UP* TO OTHER | | | POSSIBLE CONFLICTS PLEASE SEE THE OTHER | | | ITEMS/COMPONENTS WHICH ARE NOT PLACED IN THE IDR AS | | | REQUIRED. | | | METHOD *B* IS FOR ENVELOP TRADE-OFF COMPLIANCE. | | | | | | A) TYPE OF ROOF IS NOT CALLED OUT IT SIMPLY STATES | | | *ROOF* UNDER TYPE OF ROOF. | | | B) NO FLOORS IN THE IDR. | | | C) NO INFORMATION ON HOT WATER PIPE INSULATION. | | | ETC. | | | | | | | | | | | | **IMPORTANT** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2008-10-03 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-10-03 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-10-03 |
Time |
15:50 |
Sent To |
|
|
| Notes |
| 2008-10-03 15:50:43 | | | | ** DENIED 4TH REVIEW ** | | | 3RD REVIEW UNDER PERMIT APPLICATION. | | | | | | 1) NOTE: PLEASE SEE THE SUBMITTED FORM *C* IS NOT IN | | | COMPLIANCE WITH FBC 13-415.2,13-415.2.ABC.1.1,.1.2, | | | .1.3. | | | THE FORM *C* NOW NOTES THREE SEPARATE SPACES WHICH MAY | | | NOT BE USED AS FORM *C* IS FOR A SPECIFIC USE OR | | | OCCUPANCY. IF USING A SPACE BY SPACE THEN TABLE *B* IS | | | REQUIRED TO BE USED. PLEASE SEE THE SECTIONS ABOVE | | | ALONG WITH SECTION 202 OF CHAPTER 13 FOR THE | | | DEFINITIONS OF A RENOVATION. THE FORM *C* DOES NOT SHOW | | | COMPLIANCE FOR EXTERIOR LIGHTING AS NOTED IN | | | 13-415.2.ABC.1.3 NOTED INALL REVIEWS. | | | COMPLIANCE WITH THE SPECIFIC CODES ABOVE HAS NOT BEEN | | | DEMONSTRATED. THE RESPONSE LETTER MENTIONS THIS IS NOT | | | AN ELECTRICAL COMMENT. HOWEVER PLEASE SEE STATEMENTS | | | ISSUED BY THE FLORIDA BUILDING COMMISSION WHICH ARE | | | AVAILABLE ON-LINE WHICH STATE: * THE INTENT FOR REVIEW | | | OF THE CALCULATIONS AND CHAPTER 13 IS FOR EACH TRADE | | | REVIEWER TO REVIEW THAT PARTICULAR TRADE. | | | A CALLED WAS PLACED TO THE ELECTRICAL ENGINEER AS OF | | | THIS REVIEW AND A MESSAGE WAS LEFT ON VOICEMAIL TO | | | RETURN CALL. | | | THE CALCULATIONS ON FORM *C* AS SUBMITTED ALONG WITH | | | ELECTRICAL PLANS WILL BE RETAINED BY THIS OFFICE. | | | BASED ON THE *C* SUBMITTED AND OCCUPANCY DESIGN WATTAGE | | | IS OVER THE ALLOWANCES PERMITTED. THIS IS NOT | | | LODGE/HOTEL/TRANSIENT LODGING. THIS IS A ASSEMBLY | | | OCCUPANCY BASED ON ARCHITECTURAL PLANS OCCUPANCY | | | DESIGNATION. PLEASE CONTACT THIS OFFICE/REVIEW TO GO | | | OVER HOWEVER THE CODE COMPLIANCE CAN BE SHOWN. | | | | | | | | | 2) NOTE: PLEASE SEE THE FS 553.80(2)(B) WITH RESPECT TO | | | REPEAT COMMENT FOR CODE COMPLIANCES. THE SPECIFIC | | | SECTIONS OF THE CODE HAVE BEEN GIVEN NOW FOR FOUR | | | REVIEWS THREE OF WHICH ARE UNDER PERMIT APPLICATION. | | | THE STATUTORY REQUIREMENT IS THAT A FEE BE ASSESSED. | | | THIS IS NOT A LOCAL ORDINANCE, REGULATION, OR | | | ADMINISTRATIVE AMENDMENT. THIS IS A FLORIDA STATUTE | | | REQUIRED FEE. THIS OFFICE HAS PLACED THE CONTACT | | | INFORMATION FOR ANY QUESTIONS OR COMMENTS ON ALL | | | REVIEWS TO GO OVER PLANS HOWEVER CONTACT HAS NOT YET | | | BEEN MADE. | | | | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2008-04-03 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-04-03 |
Time |
18:43 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-04-03 |
Time |
18:43 |
Sent To |
|
|
| Notes |
| 2008-04-03 18:43:28 | ** DENIED 3RD REVIEW ** | | | ** ONLY 2ND REVIEW UNDER ACTUAL PERMIT APPLICATION. | | | | | | ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE | | | STILL IN NEED OF ADDRESSING ALONG WITH SOME NEW | | | COMMENTS BASED ON CHANGES MADE TO PLANS AND/OR | | | DOCUMENTS SUBMITTED. | | | | | | 1) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS | | | FOR COMMERCIAL PORTION OF BUILDING NEEDS TO MEET CODE | | | AND COORDINATE WITH PLANS. PLEASE BE SURE TO SEE | | | 13-415.2, 13-415.2.ABC.1.1, .1.2 AND .1.3. | | | FOR EXAMPLE: | | | PLEASE BE SURE TO SEE THE CALCULATIONS STATED ON SHEET | | | E-3 STATES THIS BUILDING AS A "LODGE". HOW IS THIS | | | POSSIBLE? THE SUBMITTED ENERGY CALCULATIONS CLEARLY | | | STATE "OFFICE". | | | FOR EXAMPLE: | | | PLEASE SEE THE INPUT DATA REPORT WHICH DOES NOT SHOW | | | ANY EXTERIOR LIGHT FIXTURES YET THE PLANS CLEARLY SHOW | | | EXTERIOR LIGHTING. HOW IS THIS POSSIBLE? | | | FOR EXAMPLE: | | | PLEASE SEE ONLY TWO TYPES OF FIXTURES ARE SHOWN FOR | | | FIRST FLOOR ZONE HOWEVER THE PLANS CONTAINS A MINIMUM | | | OF FOUR DIFFERENT TYPES OF FIXTURES. (THIS IS NOT | | | NOTING THE SEPARATE ELEVATOR ZONE) | | | FOR EXAMPLE: | | | PLEASE SEE UPPER FLOOR ZONE FOR AHU3. WHERE ARE K | | | FIXTURES, WHERE ARE THE FIXTURES IN BATHROOMS SHOWN FOR | | | SHOWERS? WHERE ARE THE WALL SCONCES? | | | | | | ** PLEASE ALSO BE SURE THE OWNER AGENT IS SIGNED ON THE | | | CERTIFICATION SHEET WHEN RESUBMITTING. FBC 13-103.1 | | | | | | 2) NOTE: PLEASE SEE THE TAPPED CONDUCTORS FROM THE | | | 320AMP METER CAN SHALL TERMINATE IN OVER CURRENT | | | PROTECTION HOWEVER THE RISER ONLY SHOWS A 30AMP 2-POLE | | | DISCONNECT AT BOTH THE SERVICE MAIN LOCATION AND THE | | | ELEVATOR DISCONNECT. | | | PLEASE KNOW THE FIRST ITEM IS THIS 30AMP DISCONNECT IS | | | ONE OF THE SERVICE MAINS YET NO LABELING OF THIS IS | | | SHOWN. 230.2E (ALL) | | | PLEASE SEE THE SECOND ITEM IS THAT THIS 30AMP | | | DISCONNECT SHALL BE SERVICE EQUIPMENT RATED AND SERVICE | | | ENTRANCE RATED FOR A MAIN. 230.70, 230.71, 110.7, 90.7 | | | PLEASE VERIFY THIS. | | | PLEASE SEE FOR THE THIRD ITEM; PLEASE SEE 240.21, | | | 310.16 AND 240.4 AS THE TAPPED CONDUCTORS SHALL | | | TERMINATE IN OVER CURRENT PROTECTION. | | | | | | 3) NOTE: PLEASE SEE THE OVER CURRENT PROTECTION SHOWN | | | ON ELECTRICAL PANEL SCHEDULES AND MECHANICAL PLANS ARE | | | NOT CODE COMPLIANT. | | | PLEASE SEE THE CODE REQUIRES MINIMUM OVER CURRENT | | | PROTECTION OF 125% PER 424.3B. PLEASE SEE ONE OF THE | | | 5KW AH UNITS STATES 60AMP OCP. | | | PLEASE SEE THE AC SHEETS AS THESE STATES THE MINIMUM | | | CIRCUIT AMPACITY OF THE 5KW UNITS IS 13AMPS AND THE MAX | | | OCP ID 20AMPS. THIS CAN NOT BE POSSIBLE AS THE LOAD OF | | | 5KW AT 240V IS OVER 20AMPS. THIS IS BEFORE THE MINIMUM | | | 125% WHICH IS REQUIRED BY CODE. | | | PLEASE SEE THE UNIT WHICH SHOWS A 12.9 KW HEAT STRIP | | | SHOWS MINIMUM CIRCUIT LOAD OF 20AMPS AND THE MAXIMUM | | | OCP AT 40AMPS. THIS IS ALSO NOT POSSIBLE AS THE LOAD ON | | | THIS UNIT BEFORE 125% IS SUBSTANTIALLY HIGHER THAN THE | | | 40AMP BREAKER OR CIRCUIT. | | | PLEASE SEE 424.3B, 240.4, 310.16 ETC. | | | | | | ** PLEASE SEE THE ARCHITECTURAL PLANS STATE AND SHOW A | | | AHU #4, WHEREAS THE MECHANICAL PLANS SHOWS THE AHU#3 IN | | | THE SAME LOCATION. | | | | | | 4) NOTE: PLEASE SEE THE MINIMUM PHOTO-METRIC LEVELS ON | | | THE OUTSIDE STAIRS DO NOT MEET THE LIFE SAFETY CODE FOR | | | COMPLIANCE. | | | PLEASE SEE 7.8.1.3 AS THIS REQUIRES A *MINIMUM* OF | | | 10FOOT CANDLES. THE PLANS SHOWS ABOUT HALF OF THE | | | NEEDED FOR NORMAL LIGHTING LEVELS. | | | | | | 5) NOTE: PLEASE SEE A NOTICE TO FS 553.80(2)(B) IS NOW | | | BEING GIVEN. THERE ARE REPEAT COMMENTS FOR CODE | | | COMPLIANCE WHICH HAS BEEN MADE ON THE LAST TWO REVIEWS | | | WHICH ARE BEING REPEATED ONCE AGAIN. THE INITIAL REVIEW | | | DOES NOT APPLY AS PLANS WERE ONLY SUBMITTED FOR *PLAN | | | REVIEW* AND WERE NOT SUBMITTED FOR PERMIT APPLICATION. | | | | | | PLEASE BE SURE ALL COMMENTS ARE ADDRESSED ON THE THIRD | | | REVIEW UNDER PERMIT AND FORTH REVIEW FOR PROJECT. ONCE | | | AGAIN AS STATED ON PREVIOUS REVIEWS IF THERE ARE | | | QUESTIONS OR COMMENTS PLEASE CONTACT THIS REVIEWER. | | | PLANS AND CALCULATIONS MAY BE RETAINED BY THIS OFFICE | | | DUE TO THE REPEAT COMMENTS FOR CODE COMPLIANCE. | | | | | | | | | | | | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | | DELAYS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2008-01-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-01-22 |
Time |
12:04 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-01-18 |
Time |
16:46 |
Sent To |
|
|
| Notes |
| 2008-01-22 12:05:11 | | | | | | | ** DENIED 2NDREVIEW ** | | | | | | ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL | | | IN NEED OF ADDRESSING. | | | | | | 1) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENTS WITH | | | RESPECT TO FBC CHAPTER 13 FOR LIGHTING PERFORMANCE | | | CALCULATIONS/ENERGY CALCULATIONS. | | | PLEASE SEE ONCE AGAIN THE SUBMITTED ENERGY CALCULATIONS | | | MAY NOT BE USED AS SHOW. PLEASE SEE IN FACT THESE ARE | | | THE SAME AS PREVIOUSLY SUBMITTED. ONE SET IS FORM 600 | | | FOR WHOLE BUILDING RESIDENTIAL WHICH THIS IS NOT A | | | WHOLE RESIDENTIAL BUILDING BY DEFINITION. THIS 600A | | | FORM ALSO STATES AN ADDRESS OF 2037 SPRUCE WHICH IS NOT | | | THE BUILDING ADDRESSING OF THIS APPLIED SCOPE OF WORK. | | | PLEASE SEE THE OTHER METHOD SUBMITTED IS THE SAME | | | METHOD *A* FROM PREVIOUS REVIEW. THIS MAY ALSO NOT BE | | | USED AS SUBMITTED. | | | PLEASE SEE THE INFORMATION ON THE COVER SHEET, SUMMARY | | | SHEETS AND THE INPUT DATA REPORTS DO NOT CORRELATE WITH | | | PLANS. | | | THE AMOUNT OF LIGHT FIXTURES, THE WATTAGE, THE TYPES | | | AND THE METHOD OF CONTROLS ALL NEED TO MEET 13-415.2. | | | PLEASE SEE 13-415.1.ABC.1.1, .1.2 AS THE SQ FT ON | | | CALCULATIONS IS STATING THE BUILDING IS 8K PLUS SQ FT. | | | PLEASE KNOW IF A/C IS BEING ADDED, PLEASE SEE | | | MECHANICAL REVIEW COMMENTS. | | | PLEASE SUBMIT THE ABOVE INFORMATION. | | | | | | 2) NOTE: PLEASE SEE PREVIOUS REVIEW REQUESTED | | | COORDINATION OF ALL SERVICE ENTRANCE CONDUCTORS AND | | | FEEDERS WITH THAT OF WHICH IS SINGLE PHASE AND THREE | | | PHASE. MOST OF THESE WERE DONE BUT PLEASE SEE THERE IS | | | NO NEUTRAL CONDUCTOR BEING SHOWN TO THE ELEVATOR | | | SERVICE DISCONNECT WHICH IS REQUIRED. | | | PLEASE ADJUST THE SERVICE ENTRANCE CONDUCTORS TO THIS | | | FIRST MEANS OF DISCONNECT. | | | 230.42C, 250.24C, 250.6 ETC | | | | | | 3) NOTE: PLEASE SEE PREVIOUS REVIEW REQUEST TO CLEARLY | | | DESIGNATE THE SMOKE DETECTION DEVICES. SYMBOL LEGEND | | | STILL CALLS FOR SMOKE DETECTORS AND THEN ALSO NOTES | | | SMOKE ALARMS. | | | PLEASE SHOW WHICH ONE AS THESE ARE DIFFERENT BY | | | DEFINITION. | | | PLEASE SEE NFPA-72 | | | | | | 4) NOTE: PLEASE SEE PREVIOUS REQUEST FOR PHOTO-METRIC | | | LEVELS UNDER NORMAL AND EMERGENCY CONDITIONS. | | | LS 101 7.8.1.3, 7.9.2.2 | | | PLANS SEEM TO INDICATE LEVEL UNDER EMERGENCY ONLY. | | | | | | 5) NOTE: PLEASE SEE PREVIOUS REVIEW WITH RESPECT TO | | | SEAL NO BEING CLEAR AND VISIBLE WITH ALL INFORMATION ON | | | SAID SEAL. | | | PLEASE SEE THE LICENSE NUMBER ON SEAL IS MISSING THE | | | LAST DIGIT AND CAN NOT CLEARLY SEE THIS. | | | A LEAD RUB WAS USED AND INFORMATION WAS STILL NOT CLEAR | | | AND VISIBLE. | | | PLEASE SEE FS 471.025 AND ADJUST. | | | | | | 6) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO | | | REPEAT COMMENTS FOR CODE COMPLIANCE. | | | THIS IS ONLY A NOTICE GIVEN AT THIS TIME. | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | | DELAYS. | | | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-09-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-09-13 |
Time |
11:20 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-09-13 |
Time |
08:52 |
Sent To |
|
|
| Notes |
| 2007-09-13 11:20:40 | | | | ** DENIED ** | | | | | | *** IMPORTANT** | | | PLANS HAVE ONLY BEEN SUBMITTED FOR PLAN REVIEW AND HAVE | | | NOT BEEN SUBMITTED FOR PERMIT APPLICATION. | | | PLEASE KNOW EVEN ONCE ALL CODE COMMENTS ARE ADDRESSED | | | AND PERMIT HAS NOT BEEN APPLIED FOR BY A LICENSED | | | CONTRACTOR, THE REVIEW WILL STILL REMAIN INA *F* | | | STATUS UNTIL APPLICATION IS MADE. ALL LICENSING FOR | | | CONTRACTORS, DESIGNERS WILL BE VERIFIED AT THAT TIME | | | BEFORE PERMIT ISSUANCE. | | | | | | | | | 1) NOTE: PLEASE CLARIFY EXISTING OCCUPANCY. | | | | | | 2) NOTE: PLEASE SEE CERTIFICATE OF AUTHORIZATION NUMBER | | | SHOWN ON TITLE BLOCKS FOR ARCHITECTURAL FIRM IS NOT | | | THAT AS LISTED WITH THE DEPARTMENT OF BUSINESS AND | | | PROFESSIONAL REGULATION. PLEASE SEE THE ATTACHED PRINT | | | OUT AS OF THIS REVIEW. | | | PLEASE SEE FAC 61G1-16.004 AND FLORIDA STATUTES | | | 481.219 | | | | | | 3) NOTE: PLEASE BE SURE THE RAISED/EMBOSSED SEAL ON THE | | | ELECTRICAL SHEETS IS CLEAR AND VISIBLE WITH ALL | | | INFORMATION ON SAID SEAL. SOMEARE VERY FAINT AND NOT | | | EASILY READ. | | | FS 471.025, FAC 61G15-23.001 | | | | | | 4) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH | | | ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS | | | UNDER THE NEW CODES ADOPTED BY THE STATE. | | | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO | | | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. | | | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY | | | AFFECT DESIGNS FOR ALL TRADES. | | | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS | | | REVIEWER AT A MINIMUM. | | | 2004 FBC W/ 2006 REVISIONS | | | 2005 NFPA-70 | | | 2002 NFPA-72 | | | 2003 NFPA-101 | | | | | | 5) NOTE: PLEASE SEE MECHANICAL REVIEW COMMENTS AS THE | | | ADDITIONAL A/C BEING ADDED TO SPACE MAY REQUIRED ENERGY | | | CALCULATIONS BY METHOD AS SPECIFIED IN 13-415.1.B, | | | 13-415.1.C. | | | PLEASE SEE THE LIGHTING ON THE INPUT DATA REPORT DO NOT | | | CORRELATE WITH PLANS AND FIXTURE LEGEND. THE IDR ONLY | | | INDICATES 3 FIXTURES TOTAL? | | | PLEASE ALSO SEE METHOD A BEING SUBMITTED. | | | PLEASE KNOW THAT LIGHTING PERFORMANCE CALCULATIONS ARE | | | STILL REQUIRED PER 13-415.2. PLEASE SEE TABLES | | | 415.2.C.1, 415.2.B.1. | | | PLEASE BE SURE TO COORDINATE ALL OF THESE ITEMS. | | | FBC 106.1.2, 106.3.5.1.2 | | | | | | 6) NOTE: PLEASE INDICATE THE AIC RATINGS FOR NEW MAINS | | | AND SERVICE EQUIPMENT AS SHOWN ON RISER. | | | 110.9. SOME ARE SHOWN BUT NOT ALL. | | | FBC 106.3.5.1.2, 106.1.2 | | | | | | 7) NOTE: PLEASE SEE THE RISER IS SHOWING *EQUIPMENT | | | GROUNDING CONDUCTORS* AHEAD OF MAINS WHICH IS NOT | | | PERMITTED. AS THE NEUTRAL/GROUNDED CONDUCTOR IS BONED | | | AT THE FIRST MEANS OF DISCONNECT, IF AN *EQUIPMENT | | | GROUNDING CONDUCTOR * WAS INSTALLED AHEAD OF MAINS, | | | THIS WOULD CREATE OBJECTIONABLE CURRENTS PER 250.6, | | | 250.24 | | | PLEASE REMOVE. | | | | | | 8) NOTE: PLEASE SEE 310.16, 110.14, 240.4 AS THE 1/0 | | | CONDUCTORS ARE NOT RATED FOR THE 175AMP BREAKER/OVER | | | CURRENT PROTECTION TO PANEL *B*. | | | | | | 9) NOTE: PLEASE SEE LS 200 WHICH MENTIONS THE EMERGENCY | | | FIXTURES ON AN EMERGENCY CIRCUIT, YET THERE IS NO | | | GENERATOR BACK UP ON PLANS? | | | PLEASE VERIFY AS THE ELECTRICAL PLANS INDICATES THE | | | CIRCUITING CORRECTLY PER 700.12F. | | | | | | 10) NOTE: PLEASE CORRELATE PLANS WITH RISER FOR ALL | | | FEEDERS. PLEASE SEE THE RISER SHOWS SERVICE ENTRANCE | | | CONDUCTORS AND FEEDERS FOR THREE PHASE TO PANEL *A* YET | | | PANEL *A* IS SHOWN AS SINGLE PAHSE. PLEASE CORRELATE | | | AND ADJUST. | | | FBC 106.1.2 FOR COORDINATION. | | | | | | 11) NOTE: PLEASE CORRELATE FEEDERS ON RISER AND PANEL | | | SCHEDULE FOR PANEL *B* AS PANEL INDICATES 2/0 AND THE | | | RISER SHOWS 1/0. PLEASE SEE PREVIOUS NOTE ABOVE #7 AS | | | THE 1/0 CONDUCTORS ARE NOT RATED FOR THE 175AMPS. | | | PLEASE CORRELATE AND ADJUST. | | | FBC 106.1.2, 106.3.5.1.2, ETC | | | | | | 12) NOTE: PLEASE SEE THE RISER WHICH INDICATES BUILDING | | | STEEL AS PART OF THE GROUNDING ELECTRODE SYSTEM. THIS | | | IS BEING ASSUMED THIS IS ACTUALLY *FOOTER STEEL*? IN | | | EITHER CASE PLEASE KNOW AS THIS IS AN EXISTING BUILDING | | | THE FOOTER STEEL WOULD NOT REQUIRE AN ATTACHMENT AS | | | THIS MAY CREATE AN ADVERSE AFFECT ON THE STRUCTURAL | | | INTEGRITY OF THE FOUNDATION. | | | (IF SHOWN ON RISER, THEN THIS WOULD BE REQUIRED AS THIS | | | IS BEING SPECIFIED.) | | | PLEASE SEE MISSING GAS LINE BOND AS REQUIRED. 250.50, | | | 250.104. | | | | | | 13) NOTE: PLEASE SEE NEC 422.13 AS THE WATER HEATER IS | | | REQUIRED TO BE FIGURED AT 125% FOR LOAD. PLEASE KNOW | | | THIS WAS A CHANGE IN THE 2005 NEC. | | | 230.42, 215.3, 422.13 ETC | | | | | | 14) NOTE: PLEASE SUBMIT PHOTO-METRICS FOR THE MINIMUM | | | LIGHTING LEVELS UNDER NORMAL AND EMERGENCY CONDITIONS | | | PER NFPA-101 7.8.1.3, 7.9.2.2 FOR STAIRS/DESIGNATED | | | EGRESS PATHS. | | | FLORIDA ADMINISTRATIVE CODE 61G15-33.004 | | | | | | 15) NOTE: PLEASE INDICATE THE SIZE/AMPERAGE OF METER | | | CANS. | | | PLEASE VERIFY RISER AS SHOWN WITH AN ADDITIONAL GUTTER | | | ON THE SECONDARY SIDE OF THE METER. | | | FBC106.1.2 | | | | | | 16) NOTE: PLEASE SEE PANEL SCHEDULES NEED TO BE | | | SPECIFIC TO THE ROOMS AND AREAS IN WHICH THEY FEED. | | | PLEASE SEE THE FOLLOWING TEXT WHICH IS TAKEN DIRECTLY | | | FROM THE NEC. | | | *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE | | | THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A | | | PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE | | | THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. | | | CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED | | | AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE | | | BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, | | | DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE | | | CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT | | | ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS | | | ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR | | | RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT | | | OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE | | | ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT | | | PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS | | | SECTION.* | | | 408.4, 310.16, 240.4 ETC | | | FBC 106.3.5.4 | | | | | | 17) NOTE: PLEASE VERIFY THE SMOKE DETECTION DEVICES, | | | TYPES AND DESIGNATIONS ON PLANS. | | | PLEASE SEE NFPA-72 AS SMOKE DETECTORS ARE ONLY DEVICES | | | WHICH DETECT AND DO NOT SOUND AN ALARM AND SMOKE ALARMS | | | DETECT AND SOUND AN ALARM. | | | IF TWO DIFFERENT TYPES OF DEVICES ARE BEING USED AS IT | | | SEEMS, PLEASE ADJUST DESIGNATIONS. | | | | | | 18) NOTE: PLEASE SEE 210.12 AS ALL *OUTLETS* IN | | | SLEEPING ROOMS REQUIRE ARC FAULT PROTECTION. | | | PLEASE KNOW THIS INCLUDES RECEPTACLES, LIGHTS, SMOKE | | | ALARMS, FANS ETC. | | | | | | 19) NOTE: PLEASE SEE MISSING CIRCUITS/LIGHTS/GFI PER | | | 620.24. | | | PLEASE ALSO SEE HANDBOOK REFERENCES THE ANSI/ASME 2004 | | | ELEVATOR SAFETY CODE FOR MINIMUM LIGHTING LEVELS IN PIT | | | AREA. (5FT CANDLES) PLEASE ALSO SEE ANY MINIMUM | | | REQUIREMENTS FROM THE STATE OF FLORIDA AND STATE | | | ELEVATOR CODE WHICH MAY BE MORE RESTRICTIVE. | | | | | | 20) NOTE: PLEASE SPECIFY ALL LIGHTING FOR | | | CLOSETS/LOCKERS AS THEY ARE REQUIRED TO MEET 410.8. | | | PLEASE KNOW THIS IS ALSO REQUIRED OF THE DWELLING UNIT | | | CLOSET. *(PLANS NOTE LIGHT FIXTURES TO BE OWNER CHOSEN, | | | HOWEVER NEED TO MEET MINIMUM LIFE SAFETY CODE AT THIS | | | TIME.) | | | | | | 21) NOTE: PLEASE SEE ANY COMMENTS FROM OTHER TRADES | | | WHICH MAY AFFECT THE ELECTRICAL PLANS AND/OR DESIGN FOR | | | BUILDING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2008-12-15 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-12-15 |
Time |
13:58 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-12-15 |
Time |
13:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
F |
Date |
2008-10-20 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-10-20 |
Time |
15:32 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-10-20 |
Time |
15:01 |
Sent To |
|
|
| Notes |
| 2008-10-20 15:32:25 | *****UNSAT***** | | | | | | "THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE | | | PLAN REVIEW STILL NEED TO BE ADDRESSED:" | | | | | | 9. KNOX LOCKING CAPS WILL BE REQUIRED FOR THE FIRE | | | DEPARTMENT CONNECTIONS. FOR APPLICATIONS, CONTACT WEST | | | PALM BEACH FIRE PREVENTION BUREAU AT 561-804-4724. ADD | | | COMMENT TO SHEET FS-2 | | | | | | "THE FOLLOWING NEW COMMENT STILL NEEDS TO BE | | | ADDRESSED:" | | | | | | C. ON SHEET FS-2, REFERENCES ARE MADE TO MIAMI DADE | | | FIRE RESCUE DEPARTMENT AND MIAMI AND MIAMI-DADE WATER & | | | SEWER. PLEASE PROVIDE FLOW TEST DATA AS PER WEST PALM | | | BEACH FIRE PREVENTION AND WATER SUPPLY CHARACTERISTICS | | | AS PER CITY OF WEST PALM BEACH WATER UTILITIES | | | DEPARTMENT. | | | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS | | | ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2008-05-01 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-05-01 |
Time |
13:56 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-05-01 |
Time |
13:56 |
Sent To |
|
|
| Notes |
| 2008-05-01 14:08:03 | ***DENIED*** | | | | | | MOST OF THE COMMENTS HAVE BEEN ADDRESSED. PLEASE SEE | | | THE FOLLOWING PAST COMMENTS AND A NEW COMMENT: | | | | | | 9) KNOX LOCKING CAPS WILL BE REQUIRED FOR THE FIRE | | | DEPARTMENT CONNECTIONS. FOR APPLICATIONS, CONTACT WEST | | | PALM BEACH FIRE PREVENTION BURAEU AT (561) 804-4724. | | | ADD COMMENT TO SHEET FS-2. | | | | | | B) PLEASE EXPLAIN THE ADDITION OF APT. 101 IN THE | | | PROJECT SITE ADDRESS SHOWN IN THE TITLE BLOCK OF EACH | | | SUBMITTED PLAN SHEET. | | | | | | C) ON SHEET FS-2, REFERENCES ARE MADE TO MIAMI DADE | | | FIRE RESCUE DEPARTMENT AND MIAMI AND MIAMI-DADE WATER | | | AND SEWER. PLEASE PROVIDE FLOW TEST DATA AS PER WEST | | | PALM BEACH FIRE PREVENTION AND WATER SUPPLY | | | CHARACTERISTICS AS PER CITY OF WEST PALM BEACH WATER | | | UTILITIES DEPARTMENT. | | | | | | NEW COMMENT: | | | | | | 1) SHEET CS 100 REFERENCES SPRINKLER SYSTEM TO COMPLY | | | WITH 2004 NFPA 101, SECTION 9.7. NOTE SHOULD REFERENCE | | | 2003 EDITION. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS | | | ADDRESSED. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2008-02-19 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-02-19 |
Time |
12:12 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-02-19 |
Time |
11:10 |
Sent To |
|
|
| Notes |
| 2008-02-19 12:11:46 | *****DENIED***** | | | | | | "THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE | | | PLAN REVIEW STILL NEED TO BE ADDRESSED:" | | | | | | 3. OUTSIDE STAIRS AND LANDINGS SHALL BE OF SLIP | | | RESISTANT SURFACES AND DESIGNED TO MINIMIZE WATER | | | ACCUMULATION ON THEIR SURFACES. ADD COMMENT TO AN | | | APPROPIATE PLAN SHEET | | | | | | 4. THE NEW ELEVATOR SHALL BE IN ACCORDANCE WITH ASME | | | A17.1, SAFETY CODE FOR ELEVATORS AND ESCALATORS. ADD | | | COMMENT TO AN APPROPIATE PLAN SHEET | | | | | | 5. BUILDING ELEMENTS SHALL BE USED TO RESTRICT WATER | | | EXPOSURE OF ELEVATOR EQUIPMENT. ADD COMMENT TO AN | | | APPROPIATE PLAN SHEET | | | | | | 6. IN REFERENCE TO THE DWELLING UNIT ON SHEET E-1, | | | AMEND ELECTRICAL LEGEND ON SHEET E-3 TO REFLECT SMOKE | | | ALARMS INSTEAD OF SMOKE DETECTORS. SMOKE DETECTORS ARE | | | TIED INTO THE BUILDING FIRE ALARM SYSTEM, WHEREAS SMOKE | | | ALARMS ALERT THE OCCUPANTS OF THE SAID UNIT. TO PREVENT | | | CONFUSION, DELETE SMOKE DETECTOR REFERENCE | | | | | | 9. KNOX LOCKING CAPS WILL BE REQUIRED FOR THE FIRE | | | DEPARTMENT CONNECTIONS. FOR APPLICATIONS, CONTACT WEST | | | PALM BEACH FIRE PREVENTION BUREAU AT 561-804-4724. ADD | | | COMMENT TO SHEET FS-2 | | | | | | "THE FOLLOWING NEW COMMENTS ARE TO BE ADDRESSED:" | | | | | | A. THE UPPER LEFT HAND CORNER OF SHEET CS100 LIST THE | | | ADDRESS AS 2027 SPRUCE AVENUE. | | | | | | B. PLEASE EXPLAIN THE ADDITION OF APT. 101 IN THE | | | PROJECT SITE ADDRESS SHOWN IN THE TITLE BLOCK OF EACH | | | SUBMITTED PLAN SHEET. | | | | | | C. ON SHEET FS-2, REFERENCES ARE MADE TO MIAMI DADE | | | FIRE RESCUE DEPARTMENT AND MIAMI AND MIAMI-DADE WATER & | | | SEWER. PLEASE PROVIDE FLOW TEST DATA AS PER WEST PALM | | | BEACH FIRE PREVENTION AND WATER SUPPLY CHARACTERISTICS | | | AS PER CITY OF WEST PALM BEACH WATER UTILITIES | | | DEPARTMENT. | | | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS | | | ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2007-10-22 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-10-22 |
Time |
16:55 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-10-22 |
Time |
15:04 |
Sent To |
|
|
| Notes |
| 2007-10-22 15:19:32 | *****DENIED***** | | | | | | | | | 01.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED.I.E. ON SHEET LSP200 LISTS 2004 | | | | | | 02.POST/SHOW THE NUMERICAL ADDRESS OF THE BUILDING ON | | | THE APPROPIATE EXTERIOR ELEVATION WHICH FRONTS SPRUCE | | | AVENUE.AS PER WEST PALM BEACH CODE, THE NUMBERS SHALL | | | BE NO LESS THAN SIX INCHES IN HEIGHT AND NO LESS THAN | | | ONE INCH IN WIDTH. | | | | | | 03.OUTSIDE STAIRS AND LANDINGS SHALL BE OF SLIP | | | RESISTANT SURFACES AND DESIGNED TO MINIMIZE WATER | | | ACCUMULATION ON THEIR SURFACES. | | | | | | 04.THE NEW ELEVATOR SHALL BE IN ACCORDANCE WITH ASME | | | A17.1, SAFETY CODE FOR ELEVATORS AND ESCALATORS. | | | | | | 05.BUILDING ELEMENTS SHALL BE USED TO RESTRICT WATER | | | EXPOSURE OF ELEVATOR EQUIPMENT. | | | | | | 06.IN REFERENCE TO THE DWELLING UNIT ON SHEET E-1, | | | AMEND ELECTRICAL LEGEND ON SHEET E-3 TO REFLECT SMOKE | | | ALARMS INSTEAD OF SMOKE DETECTORS.SMOKE DETECTORS ARE | | | TIED INTO THE BUILDING FIRE ALARM SYSTEM, WHEREAS SMOKE | | | ALARMS ALERT THE OCCUPANTS OF THE SAID UNIT. | | | | | | 07.IN NEW CONSTRUCTION, WHERE TWO OR MORE SMOKE | | | ALARMS ARE REQUIRED WITHIN A DWELLING UNIT, THEY SHALL | | | BE ARRANGED SO THAT OPERATION OF ANY SMOKE ALARM SHALL | | | CAUSE THE ALARM IN ALL THE OTHER SMOKE ALARMS TO | | | SOUND. | | | | | | 08.AMEND ON SHEET FA-02 UNDER DUCT DETECTOR, DUCT | | | SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE ALARM (AS | | | PER LOCAL CODE). | | | | | | 09. KNOX LOCKING CAPS WILL BE REQUIRED FOR THE FIRE | | | DEPARTMENT CONNECTIONS.FOR APPLICATIONS, CONTACT WEST | | | PALM BEACH FIRE PREVENTION BUREAU AT 561-804-4724. | | | | | | 10.ELECTRONIC SWITCHES, CHAIN AND LOCK SHALL BE | | | REQUIRED ON THE FIRE LINE BAK FLOW DEVICE. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE ON THE PLANEACH COMMENT WAS | | | ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2008-11-24 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-11-24 |
Time |
08:31 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-11-24 |
Time |
08:31 |
Sent To |
|
|
| Notes |
| 2008-11-24 08:31:31 | TO "COMM" BD#63 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2008-09-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-09-19 |
Time |
14:24 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-09-19 |
Time |
14:21 |
Sent To |
|
|
| Notes |
| 2008-10-14 15:10:09 | 10/14/08--TAKEN FROM BD AND ROUTED TO MIKE WILLIAMS | | | DESK | | 2008-09-19 14:29:05 | TO "COMM" BD#39 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2008-04-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-04-02 |
Time |
16:39 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-04-02 |
Time |
16:39 |
Sent To |
|
|
| Notes |
| 2008-04-02 16:43:48 | TO "COMM" BD#9 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-01-14 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-01-14 |
Time |
14:36 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-01-14 |
Time |
14:36 |
Sent To |
|
|
| Notes |
| 2008-01-14 14:38:40 | TO "COMM" BD#56 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-10-22 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-10-22 |
Time |
15:04 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-08-15 |
Time |
10:40 |
Sent To |
|
|
| Notes |
| 2007-09-10 16:59:15 | TO "COMM" BD#12 | | 2007-08-15 10:40:34 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
P |
Date |
2008-12-16 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-12-16 |
Time |
20:54 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-12-16 |
Time |
20:54 |
Sent To |
PC |
|
| Notes |
| 2008-12-16 20:55:09 | CORRECTED ENERGY CALCS SUBMITTED. REVIEW NOW IN PASSED | | | STATUS. PLANS SENT FOR PROCESSING/PERMIT ISSUANCE |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
F |
Date |
2008-12-13 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-12-13 |
Time |
11:02 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-12-13 |
Time |
10:54 |
Sent To |
|
|
| Notes |
| 2008-12-13 11:01:46 | **NOTE** | | | MECHANICAL REVIEW WAS PREVIOUSLY PASSED, BUT NOW THE | | | ENERGY CALCULATIONS HAVE BEEN REDONE WITH SEVERAL | | | DEFICIENCIES. PLEASE SEE ELECTRICAL PLAN REVIEW DATED | | | 12/5/08 FOR A MOR DETAILED DESCRIPTION. MECHANICAL | | | REVIEW WILL BE PASSED ONCE CORRECT ENERGY CODE | | | COMPLIANCE DATA IS SUBMITTED. | | | THE PREVIOUSLY PASSED MECHANICAL REVIEW STATUS WILL BE | | | CHANGED TO FAIL PENDING SATISFACTIRY RESOLUTION. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2008-12-13 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-10-01 |
Time |
14:50 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-10-01 |
Time |
14:17 |
Sent To |
|
|
| Notes |
| 2008-12-13 11:04:06 | **NOTE** | | | THIS MECHANICAL REVIEW WAS PREVIOUSLY PASSED, BUT NOW | | | (12/13/08) THE ENERGY CALCULATIONS HAVE BEEN REDONE | | | WITH SEVERAL DEFICIENCIES. PLEASE SEE ELECTRICAL PLAN | | | REVIEW DATED 12/5/08 FOR A MORE DETAILED DESCRIPTION. | | | MECHANICAL REVIEW WILL BE PASSED ONCE CORRECT ENERGY | | | CODE COMPLIANCE DATA IS SUBMITTED. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2008-04-25 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-04-25 |
Time |
10:00 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-04-24 |
Time |
17:29 |
Sent To |
|
|
| Notes |
| 2008-04-25 10:00:24 | REVIEW #: 3RD | | | ACTION: DENIED | | | | | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH | | | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN | | | RESPONSES FOR THE PURPOSE OF CONTINUITY. | | | | | | COMMENTS 1-4 OK | | | | | | 5. FRC SECTION M1501.1 EXCEPTION 1: "WHERE A CLOTHES | | | DRYER BOOSTER FAN IS INSTALLED AND LISTED AND LABELED | | | FOR THE APPLICATION, THE MAXIMUM LENGTH OF THE EXHAUST | | | DUCT, INCLUDING ANY TRANSITION DUCT, SHALL BE PERMITTED | | | TO BE IN ACCORDANCE WITH THE BOOSTER FAN MANUFACTURER?S | | | INSTALLATION INSTRUCTIONS." | | | NO DRYER BOOSTER FAN LISTING OR INSTALLATION | | | INSTRUCTIONS HAVE BEEN PROVIDED. NOTE THAT THIS SECTION | | | REQUIRES THE BOOSTER FAN TO BE LISTED FOR USE IN A | | | DOMESTIC CLOTHES DRYER APPLICATION. IF THIS EXCEPTION | | | IS TO BE USED, PROVIDE ALL REQUIRED INFORMATION TO BE | | | INCLUDED IN THE PERMIT DOCUMENTATION PRIOR TO PERMIT | | | ISSUANCE. | | | FRC SECTION M1501.1 EXCEPTION 2: "WHERE THE MAKE AND | | | MODEL OF THE CLOTHES DRYER TO BE INSTALLED IS KNOWN AND | | | THE MANUFACTURER?S INSTALLATION INSTRUCTIONS FOR SUCH | | | DRYER ARE PROVIDED TO THE BUILDING OFFICIAL, THE | | | MAXIMUM LENGTH OF THE EXHAUST DUCT, INCLUDING ANY | | | TRANSITION DUCT, SHALL BE PERMITTED TO BE IN ACCORDANCE | | | WITH THE DRYER MANUFACTURER?S INSTALLATION | | | INSTRUCTIONS." | | | NO DRYER MODEL OR INSTALLATION INSTRUCTIONS HAVE BEEN | | | PROVIDED. IF THIS EXCEPTION IS TO BE USED, PROVIDE ALL | | | REQUIRED INFORMATION TO BE INCLUDED IN THE PERMIT | | | DOCUMENTATION PRIOR TO PERMIT ISSUANCE. | | | | | | NOTE: THE CLOTHES DRYER SHALL BE INSTALLED AND | | | TRANSITION DUCT CONNECTED FOR FINAL MECHANICAL | | | INSPECTION. | | | | | | NOTE: PLEASE ADDRESS ELECTRICAL REVIEW COMMENTS RELATED | | | TO ELECTRICAL RATINGS OF A/C APPLIANCES, SHOWING | | | COORDINATION BETWEEN MANUFACTURER'S REQUIREMENTS, | | | ELECTRICAL PLANS AND A/C UNIT SCHEDULE ON PG AC-2. | | | | | | ALL OTHER MECHANICAL COMMENTS HAVE BEEN ADEQUATELY | | | ADDRESSED. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2008-02-11 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-02-11 |
Time |
15:29 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-02-11 |
Time |
14:31 |
Sent To |
|
|
| Notes |
| 2008-02-11 15:28:54 | REVIEW #: 2ND | | | ACTION: DENIED | | | | | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH | | | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN | | | RESPONSES FOR THE PURPOSE OF CONTINUITY. | | | | | | 1 THROUGH 4: OK | | | | | | 5. BOOSTER FAN HAS BEEN ADDED TO ACCOMMODATE NEW DRYER | | | EXHAUST OUTLET LOCATION. CLOTHES DRYERS SHALL BE | | | EXHAUSTED IN ACCORDANCE WITH THE MANUFACTURER?S | | | INSTRUCTIONS PER FBC, M 504.1. A BOOSTER FAN MAY ONLY | | | BE USED IF ALLOWED BY DRYER MANUFACTURER?S INSTALLATION | | | INSTRUCTIONS. | | | NOTE: WHERE THE MAKE AND MODEL OF THE CLOTHES DRYER TO | | | BE INSTALLED IS KNOWN AND THE MANUFACTURER?S | | | INSTALLATION INSTRUCTIONS FOR SUCH DRYER ARE PROVIDED | | | TO THE CODE OFFICIAL, THE MAXIMUM LENGTH OF THE EXHAUST | | | DUCT, INCLUDING ANY TRANSITION DUCT, SHALL BE PERMITTED | | | TO BE IN ACCORDANCE WITH THE DRYER MANUFACTURER?S | | | INSTALLATION INSTRUCTIONS PER FBC 504.6.1 EXCEPTION. | | | THE DRYER MANUFACTURER MAY ALLOW DRYER DUCT LENGTHS | | | WHICH WILL MAKE A BOOSTER FAN UNNECESSARY. PROVIDE | | | MANUFACTURER?S INSTRUCTIONS. | | | | | | 6 AND 7: OK | | | | | | 8. VENTILATION RATE FOR DWELLING UNIT TO BE DETERMINED | | | PER THE RATIO OF OPENABLE WINDOW AND DOOR AREA TO FLOOR | | | AREA IN ACCORDANCE WITH FRC 303.1. PROVIDE CALCULATIONS | | | CONTAINING THIS DATA SHOWING COMPLIANCE WITH THIS | | | SECTION. ASHRAE 62-89 IS NOT APPLICABLE IN THIS | | | SITUATION UNDER THIS CODE AS IT IS NOT A REFERENCE | | | STANDARD FOR THE FRC ACCORDING TO FRC CHAPTER 43. | | | | | | 9. NO INFORMATION COULD BE FOUND ON PLANS REGARDING | | | THIS COMMENT. THIS ISSUE CAN BE ADDRESSED BY FIELD | | | INSPECTION. HOWEVER, ADDRESSING THIS NOW WITH DETAILED | | | INFORMATION COULD AVOID DELAYS AND FAILED INSPECTIONS | | | IN THE FUTURE. | | | | | | 10. WIND LOAD CALCULATIONS SUBJECT TO BUILDING PLAN | | | REVIEW. | | | | | | 11. OK | | | | | | 12. FIRESTOP DETAIL FOR REFRIGERANT PIPES SHOWN ON | | | PLANS, CAJ 1047, DOES NOT MAKE PROVISIONS FOR PIPE | | | INSULATION AND THEREFORE IS NOT APPROPRIATE FOR A | | | REFRIGERANT PIPE APPLICATION. PROVIDE A | | | THROUGH-PENETRATION FIRESTOP SYSTEM WHICH IS | | | APPROPRIATE FOR THE PIPING SYSTEM BEING USED PER FBC | | | 712.3. | | | | | | NOTE: PLEASE PROVIDE WRITTEN RESPONSE TO REVIEW | | | COMMENTS TO ASSIST IN SUBSEQUENT REVIEWS. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2007-09-18 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-09-18 |
Time |
15:48 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-09-17 |
Time |
19:58 |
Sent To |
|
|
| Notes |
| 2007-09-18 15:48:53 | REVIEW #: 1 | | | ACTION: DENIED | | | | | | FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. THE DESIGNER OR OWNER MUST SELECT THE LEVEL OF | | | ALTERATION BEING PROPOSED PER FBC,EB 301.5. | | | | | | 2. IS THIS A CHANGE OF OCCUPANCY? SEE FBC,EB 301.4 AND | | | 306.1. | | | | | | 3. VALUE OF WORK HAS NOT BEEN DECLARED. FOR PURPOSE OF | | | FBC CH,13 COMPLIANCE, IT IS ASSUMED THAT THE WORK | | | QUALIFIES AS A RENOVATION AS DEFINED IN FBC 13-202. | | | | | | 4. AC-1: LOCATION OF CU-2 APPEARS TO BE IN CONFLICT | | | WITH STAIR LANDING ON WEST ELEVATION. VERIFY REQUIRED | | | CLEARANCES FOR CU PER FBC,M 304.1. | | | | | | 5. AC-1: BATH AND DRYER EXHAUST FROM RESIDENCE WILL BE | | | DISCHARGING ONTO THE STAIR SHOWN ON WEST ELEVATION. | | | EXHAUST AIR SHALL NOT BE DIRECTED ONTO WALKWAYS PER | | | FBC,M 401.5.2. | | | | | | 6. AC-1: REFRIGERANT LINES FOR CU-2/AHU-2, IF THEY ARE | | | TO RUN ABOVE CEILING, THEY MAY BE IN CONFLICT WITJ | | | STAIR ON WEST ELEVATION WHEN THEY LEAVE THE BUILDING. | | | PLEASE VERIFY THERE IS NO CONFLICT. FBC 106.1.2. | | | | | | 7. PG LSP200 SHOWS AHU IN CLOSET ON 2ND FL NEXT TO | | | JANITOR'S CLOSET. PG AC-1 DOES NOT. PLEASE COORDINATE | | | PLANS. FBC 106.1.1 AND 106.1.3. | | | | | | 8. AC-1: PLEASE PROVIDE CALCULATIONS SHOWING HOW THE | | | VENTILATION REQUIREMENTS OF FRC 303.1 ARE BEING MET FOR | | | THE RESIDENCE. | | | | | | 9. AC-1: ALL A/C CLOSETS SHALL BE LINED WITH A | | | CONTINUOUS, NON-POPOUS, APPROVED AIR BARRIER AND | | | EXTERIOR WALLS USED AS A PLENUM SHALL BE INSULATED TO | | | MIN. R-8 PER FBC,M 603.8 AND 603.9. | | | | | | 10. PG AC-1: CONDENSER MOUNTING DETAIL, FBC,M 301.13.1 | | | ONLY APPLIES TO R-3 OCCUPANCIES AND 5 TONS OR LESS. THE | | | PRESCRIPTIVE METHOD OF 301.13.1 ONLY APPLIES TO CU-2. | | | PROVIDE ENGINEERING FOR WIND LOADS AND ATTACHMNENTS FOR | | | OTHER CU'S PER FBC,M 301.13 AND FBC CH.16. | | | | | | 11. AC-1: NOTE #14, CONDENSATE DRAIN LINES SHALL BE OF | | | NON COMBUSTIBLE MATERIALS PER FBC,M 602.2.1. | | | | | | 12. AC-1: PROVIDE DETAIL AND LISTING OF | | | THROUGH-PENETRATION FIRESTOP SYSTEM FOR LINES | | | PENETRATING THE RATED STORAGE ROOM PER FBC 712.3. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2008-09-23 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-09-23 |
Time |
10:59 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-09-23 |
Time |
10:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2008-04-14 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-04-14 |
Time |
07:52 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-04-14 |
Time |
07:52 |
Sent To |
|
|
| Notes |
| 2008-04-14 07:53:05 | PASSED/PROVISO--RPZV BACKFLOW REQUIRE ON THE WATER | | | SERVICE. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2008-02-08 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-02-08 |
Time |
09:17 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-02-07 |
Time |
15:50 |
Sent To |
|
|
| Notes |
| 2008-02-08 09:36:43 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | ****FROM PREVIOUS REVIEW: | | | | | | 1. OK | | | 2. OK | | | 3. OK | | | | | | 4. SHT A700 WOMENS TOILET ROOM STALL SHALL BE | | | ACCESSIBLE AND SHALL MEET THE REQUIREMENTS OF FIGURE | | | 11-30E.--EACH WATER CLOSET UTILIZED BY THE PUBLIC | | | OR EMPLOYEES SHALL OCCUPY A SEPARATE COMPARTMENT WITH | | | WALLS OR PARTITIIONS AND A DOOR ENCLOSING THE FIXTURES | | | TO ENSURE PRIVACY. SECTION 310.4. SHOW THE ACCESSIBLE | | | TOILET AND LAV IN THE STALL/COMPARTMENT. | | | ****RESPONSE NOTED, BUT THE ACCESSIBLE STALL DOES NOT | | | COMPLY WITH FIG 11-30E. THE CLEAR FLOOR SPACE FOR THE | | | W/C IS NOT INDICATED ON THE FLOOR PLAN, AND THE SIDE OF | | | THE LAV IS LESS THAN 5' OFF THE WALL ADJACENT TO THE OF | | | THE W/C AS REQUIRED IN FIG 11-30E. | | | | | | 5. OK | | | | | | 6. SHT A700 MENS TOILET ROOM SHALL BE ACCESSIBLE AND | | | SHALL MEET THE REQUIREMENTS OF FIGURE 11-30E.-- EACH | | | WATER CLOSET UTILIZED BY THE PUBLIC OR EMPLOYEES SHALL | | | OCCUPY A SEPARATE COMPARTMENT WITH WALLS OR PARTITIIONS | | | AND A DOOR ENCLOSING THE FIXTURES TO ENSURE PRIVACY. | | | SECTION 310.4. SHOW THE ACCESSIBLE TOILET AND LAV IN | | | THE STALL/COMPARTMENT. | | | ****RESPONSE NOTED, BUT THE ACCESSIBLE STALL DOES NOT | | | COMPLY WITH FIG 11-30E. THE CLEAR FLOOR SPACE FOR THE | | | W/C IS NOT INDICATED ON THE FLOOR PLAN, AND THE SIDE OF | | | THE LAV IS LESS THAN 5' OFF THE WALL ADJACENT TO THE OF | | | THE W/C AS REQUIRED IN FIG 11-30E. | | | | | | 7. OK | | | | | | 8. SHT A700 PLEASE SHOW COMPLIANCE FOR THE FOLLOWING: | | | ___W/C'S | | | A. 11-4.16.5 FLUSH CONTROLS | | | ****NOT ADDRESSED | | | ___URINAL | | | A. 11-4.18.2 HEIGHT | | | ****NOT ADDRESSED | | | B. 11-4.18.3 CLEAR FLOOR SPACE | | | ****NOT ADDRESSED | | | C. 11-4.18.4 FLUSH CONTROLS | | | ****NOT ADDRESSED | | | ___ FOR LAVS | | | A. 11-4.19.5 FAUCETS | | | ___SHOWERS | | | A. 11-4.21.2 SIZE & CLEARANCES | | | ****NOT ADDRESSED, SHOWS 3'-10-5/8" | | | B. OK | | | C. OK | | | D. OK | | | C. OK | | | E. OK | | | | | | 9. OK | | | 10. OK | | | 11. OK | | | 12. OK | | | | | | 13. SHT P-2 WATER RISER DIAGRAM. AN RPZV BACKFLOW IS | | | REQUIRED ON THE WATER SERVICE TO THE COMMERCIAL | | | OCCUPANCY. SECTION 608.13.2. PLEASE INDICATE ON THE | | | RISER DIAGRAM. | | | ****RESPONSE NOTED, BUT THE CIVIL PLANS HAVE NOT BEEN | | | SUBMITTED. | | | | | | 14. OK | | | | | | 15. THE ENERGY EFFICIENCY CODE SYSTEM COMPLIANCE REPORT | | | DOES NOT REFLECT WHAT IS SHOWN ON SHT P-3. REPORT | | | INDICATES NONE FOR THE WATER HEATER, BUT SHT P-3 | | | INDICATES TYPICAL WATER HEATER 80 GAL, 4.5KW, 208V. | | | PLEASE CORRELATE.--INPUT DATA REPORT ALSO SHOWS NO | | | INFORMATION FOR THE WATER HEATER.--THE RESIDENTIAL | | | WHOLE BUILDING PERFORMANCE METHOD A INDICATES A 50 GAL | | | CAP. WATER HEATER WHICH DOES NOT RELFECT THE 80 GAL | | | SHOWN ON SHT P-3. PLEASE CORRELATE INFORMATION. SECTION | | | 13-103. | | | ****NO RESPONSE, NOT ADDRESSED. (ALSO SEE COMMENT | | | NUMBER ONE OF THE ELECTRICAL PLAN REVIEW). | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | | FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-09-27 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-09-27 |
Time |
10:44 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-09-26 |
Time |
18:57 |
Sent To |
|
|
| Notes |
| 2007-09-27 16:26:37 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. ALL SHEETS WITH DALIMA STUDIO TITLE BLOCK. THE FIRMS | | | LICENSE NUMBER, (CERTIFICATE OF AUTHORIZATION), IS | | | REQUIRED ON EACH SHEET. FAC 61G1-16.004(2) & FS | | | 481.219, 481.2055. PLEASE INDICATE FIRM LICENSE NUMBER | | | IN THE TITLE BLOCK ON EACH SHEET. | | | | | | 2. SHT A200. THE A-3 OCCUPANCY REQUIRES A DRINKING | | | FOUNTAIN, BUT A BOTTLED WATER COOLER IS SHOWN. THIS IS | | | NOT APPROVED. BOTTLED WATER DISPENSERS SHALL BE | | | PERMITTED TO BE SUBSTITUTED FOR NOT MORE THAN 50% OF | | | THE REQUIRED DRINKING FOUNTAINS. SINCE ONLY ONE | | | DRINKING FOUNTAIN IS REQUIRED, THE BOTTLED WATER | | | DISPENSER IS BEING SUBSTITUTED FOR 100% OF THE REQUIRED | | | FIXTURES. TABLE 403.1 AND SECTION 410.1. PLEASE | | | INDICATE THE LOCATION OF THE DRINKING FOUNTAIN. | | | | | | 3. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN SHOWING | | | COMPLIANCE WITH SECTION 11-4.15 AND ALL SUBSECTIONS AS | | | WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE | | | WHO HAVE DIFFICULTY BENDING OR STOOPING. | | | | | | 4. SHT A700 WOMENS TOILET ROOM STALL SHALL BE | | | ACCESSIBLE AND SHALL MEET THE REQUIREMENTS OF FIGURE | | | 11-30E.--EACH WATER CLOSET UTILIZED BY THE PUBLIC | | | OR EMPLOYEES SHALL OCCUPY A SEPARATE COMPARTMENT WITH | | | WALLS OR PARTITIIONS AND A DOOR ENCLOSING THE FIXTURES | | | TO ENSURE PRIVACY. SECTION 310.4. SHOW THE ACCESSIBLE | | | TOILET AND LAV IN THE STALL/COMPARTMENT. | | | | | | 5. SHT A700 WOMENS TOILET ROOM WILL REQUIRE ANOTHER LAV | | | FOR THE W/C OUTSIDE THE ACCESSIBLE STALL. SECTION | | | 405.3.2.. PLEASE SHOW THE LOCATION OF THE LAV OUTSIDE | | | THE ACCESSIBLE STALL. | | | | | | 6. SHT A700 MENS TOILET ROOM SHALL BE ACCESSIBLE AND | | | SHALL MEET THE REQUIREMENTS OF FIGURE 11-30E.-- EACH | | | WATER CLOSET UTILIZED BY THE PUBLIC OR EMPLOYEES SHALL | | | OCCUPY A SEPARATE COMPARTMENT WITH WALLS OR PARTITIIONS | | | AND A DOOR ENCLOSING THE FIXTURES TO ENSURE PRIVACY. | | | SECTION 310.4. SHOW THE ACCESSIBLE TOILET AND LAV IN | | | THE STALL/COMPARTMENT. | | | | | | 7. SHT A700 WOMENS TOILET ROOM WILL REQUIRE ANOTHER LAV | | | FOR THE URINAL OUTSIDE THE ACCESSIBLE STALL. SECTION | | | 405.3.2.. PLEASE SHOW THE LOCATION OF THE LAV OUTSIDE | | | THE ACCESSIBLE STALL. | | | | | | 8. SHT A700 PLEASE SHOW COMPLIANCE FOR THE FOLLOWING: | | | ___W/C'S | | | A. 11-4.16.5 FLUSH CONTROLS | | | ___URINAL | | | A. 11-4.18.2 HEIGHT | | | B. 11-4.18.3 CLEAR FLOOR SPACE | | | C. 11-4.18.4 FLUSH CONTROLS | | | ___ FOR LAVS | | | A. 11-4.19.5 FAUCETS | | | ___SHOWERS | | | A. 11-4.21.2 SIZE & CLEARANCES | | | B. 11-4.21.3 SEATS | | | C. 11-4.21.4 GRAB BARS | | | D. 11-4.21.5 CONTROLS | | | C. 11-4.21.6 SHOWER UNITS | | | E. 11-4.21.7 CURBS | | | PLEASE SUBMIT DETAILS OR ELEVATIONS AND ADJUST DETAILS | | | ALREADY SUBMITTED. SEE SECTION 11-4.23AND ALL | | | SUBSECTIONS. | | | | | | 9. SHT P-1 DETAIL 1 THE SHOWER IN BATHROOM #2. PER | | | TABLE 906.1 THE MAXIMUM DISTANCE FROM THE TRAP TO THE | | | VENT FOR 2" IS 6FT. PER THE FLOOR PLAN, THIS SCALES OUT | | | TO 8FT. PLEASE CHECK DISTANCE FROM TRAP TO VENT FOR THE | | | SHOWER. | | | | | | 10. SHT P-1 DETAIL 1 APPLIANCE P-6 IS NOT INDICATED ON | | | THE PLUMBING FIXTURE SCHEDULE FOUND ON SHT P-3. PLEASE | | | INDICATE WHAT TYPE OF FIXTURE THIS IS. SECTION | | | 106.1.1. | | | | | | 11. SHT P-1 DETAIL 1 BATHROOM 3 IS INDICATED AS CLOSET | | | NO.3. PLEASE CLARIFY. (ALSO SEE OTHER SHEETS). SECTION | | | 106.1.1. | | | | | | 12. SHT P-2 SANITARY RISER DIAGRAM. ITEM P-6. IF THE | | | ITEM IS A WASH MACHINE, THEN 3" IS REQUIRED FOR THE | | | BRANCH DRAIN AND STACK SECTION 406.3--ALSO A | | | STANDPIPE IS REQUIRED FOR THE W/M PER SECTIONS 1002.1 & | | | 802.4.--A CLEANOUT SHALL BE INSTALLED AT LEAST 4FT | | | ABOVE THE FLOOR PER SECTION 708.9. PLEASE SHOW ON THE | | | ISOMETRIC IF P-6 IS THE WASH MACHINE. | | | | | | 13. SHT P-2 WATER RISER DIAGRAM. AN RPZV BACKFLOW IS | | | REQUIRED ON THE WATER SERVICE TO THE COMMERCIAL | | | OCCUPANCY. SECTION 608.13.2. PLEASE INDICATE ON THE | | | RISER DIAGRAM. | | | | | | 14. SHT P-3 PLEASE SUBMIT THE CALCULATIONS FOR THE | | | EXPANSION TANK. PLEASE SUBMIT THE MANUF. SPECIFICATION | | | SHEETS FOR THE EXPANSION TANK AND INDICATE THE MODEL | | | NUMBER. SECTION 607.3.2. | | | | | | 15. THE ENERGY EFFICIENCY CODE SYSTEM COMPLIANCE REPORT | | | DOES NOT REFLECT WHAT IS SHOWN ON SHT P-3. REPORT | | | INDICATES NONE FOR THE WATER HEATER, BUT SHT P-3 | | | INDICATES TYPICAL WATER HEATER 80 GAL, 4.5KW, 208V. | | | PLEASE CORRELATE.--INPUT DATA REPORT ALSO SHOWS NO | | | INFORMATION FOR THE WATER HEATER.--THE RESIDENTIAL | | | WHOLE BUILDING PERFORMANCE METHOD A INDICATES A 50 GAL | | | CAP. WATER HEATER WHICH DOES NOT RELFECT THE 80 GAL | | | SHOWN ON SHT P-3. PLEASE CORRELATE INFORMATION. SECTION | | | 13-103. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | | FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2008-10-03 |
|
|
Cont ID |
|
| Sent By |
kdfreema |
Date |
2008-10-03 |
Time |
11:54 |
Rev Time |
0.00 |
| Received By |
kdfreema |
Date |
2008-10-03 |
Time |
11:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2008-04-04 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2008-04-04 |
Time |
10:27 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2008-04-04 |
Time |
10:27 |
Sent To |
|
|
| Notes |
| 2008-04-04 10:27:59 | ***APPROVAL PER AJV*** |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2008-01-17 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2008-01-17 |
Time |
15:28 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2008-01-17 |
Time |
15:28 |
Sent To |
|
|
| Notes |
| 2008-01-17 15:29:09 | ***APPROVAL PER AJV*** |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2007-09-18 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-09-18 |
Time |
16:32 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-09-18 |
Time |
16:32 |
Sent To |
|
|
| Notes |
| 2007-09-18 16:32:54 | PLAN REVIEW - NO COMMENTS AT THIS TIME PER AJV.FINAL | | | APPROVAL SHALL BE MADE UPON SUBMITTAL FOR PERMIT. |
|
|